FIRE ALARM WIRE LEGEND
DESIG.
DESCRIPTION
A
16/2 FPLR INITIATING CIRCUIT WIRING
B
14/2 FPLR INDICATING CIRCUIT WIRING
C
16/4 FPLR ANNUNCIATOR CIRCUIT WIRING
D
14/2 FPLP DUCT DETECTOR OR DOOR HOLDER POWER WIRING
E
AWG-16-THHW FOR DIRECT BURY/WET LOCATION
-
KEY LEGENDCOMPONENT AND CO O NT LIST
SYMBOL
DESCRIPTION
QTY
PART #
MANUFACTOR
MOUNTING SPEC
FIRE ALARM CONTROL PANEL
1
FX -2001-6
MIRCOM
WALL TOP @ 66'
EMI
FIRE SIGNAL EXPANDER
WALL TOP @ 66'
I FSE I
ANNUNCIATOR
1
RAX -LCD
MIRCOM
WALL TOP @ 66'
LIME
TRANSMnTER
FIELD VERIFY
I TRAN I
SUBSCRIBER TERMINAL UNIT
FIELD VERIFY
®
HORN
WALL @ 80"-96"
MINI -HORN
WALL @ 80'-96"
all
BELL
1
MB -G10 -24R
WHEELOCK
OUTSIDE WALL @ 10'
CJ
BELL -STROBE
WEATHER PROOF ON WALL @ 1d
STROBE
2
ZRS-MCW-FW
WHEELOCK
WALL @ 80"-96"
E2
III
HORN -STROBE
1
ZNS-MCW-FW
WHEELOCK
WALL @ 80"-96°
0
CEILING MOUNTED HORN/STROBE
3
ZNS-MCC-FW
WHEELOCK
CEILING
0
CEILING MOUNTED STROBE
CEILING
C
CHIME
FIELD VERIFY
! s�
SPEAKER
WALL @ 90'
OJ
JUNCTION BOX
FIELD VERIFY
DOOR HOLDER
FIELD VERIFY
m
DOOR STRIKE
FIELD VERIFY
Ea
F
MANUAL PULL STATION
3
MS-701ADU
MIRCOM
WALL @ 48"
® AB
SMOKE DETECTOR ABOVE CEILING
ABOVE CEILING OR IN DUCT
®
SMOKE DETECTOR
12
MIX -2251B
MIRCOM
CEILING - 3' FROM AIR DEFUSER
® BL
SMOKE DETECTOR BELOW FLOOR
BELOW FLOOR
®
135° FIXED TEMP HEAT DETECTOR
2
MIX -5251
MIRCOM
CEILING
194'®R
194° RATE OF RISE HEAT DETECTOR
-
CEILING
OR
135° RATE OF RISE HEAT DETECTOR
CEILING
19ea)AB
194° FIXED TEMP ABOVE CEILING
7
5604
SYSTEM SENSOR
ABOVE CEILING
LINE TYPE HEAT DETECTOR
FIELD VERIFY
WF
WATERFLOW SWITCH
RISER PIPE
PS
PRESSURE SWITCH
RISER PIPE
TS
TAMPER SWITCH
GATE VALVE
JB
JUNCTION BOX ALONGSIDE DEVICE
FIELD VERIFY
M
MONITOR MODULE
7
MIX-M500M
MIRCOM
FIELD VERIFY
R
ADDRESSABLE RELAY
FIELD VERIFY
TO CENTRAL
STATION
REMOTE
ANNUNCIATOR
MODEL RAX -LCD
I�1
TP
#16/4
PHONE UNE f1
FACP
SLC
Ott OM'
Advanced life Safely Soluyo e -
FX -2001-6
UNE
PHONE UNE #2 t
120 VAC S
(DEDICATED CKT.)
NAC -1
H
J
K
M
..................................................
'ELECTRICAL ROOM
FX -2000 CTRL Panel
Addrsbl SLC Devices
LCD Remote Annunc
0.009 ;0.009
.100 0.150
0.000 0.000
.................................
0.000
0.000.;:
0,000
RELAY
.000
0.000
4A INDICATING
Notification Appl Circuit
0.000
0.00
0.000
Notification Appl Circuit
£7.000
0.175
#14 Solid
100
IsJ1-11
Notification Appl Circuit
0.000
0.000 t #14 Solid
PQM 1t
4 Notification Appl Circuit
0.000
0.000 #14 Solid
4.45%
0.44%
0.00%
0.00%
# of NAC's Used
Command Shortcuts
Configure Circuits J Print Page J
Reject Information
Project Name: AT&T WIRELESS
Prepared By: ROBERT
Project ID: 88375
Date: 5/20/2008
Notification Appl Circuit
2
2
ZNS-MCC-FW 95cd
ZNSMCC-FW 30cd
ZRS-MCW-FW 15cd
ZNS-MCW-FW 30cd
MB -G10 -24R
Totals
0000 ,
a 901
Notification Appl Circuit
RS SW P -2475 -FR
Unused
Unused
i0
Totals
X1.000
17
aav a
/g�tngi,�l��i➢l��r�/i b �tii:/Ur}i
'IX el
,/;11'
/, % :,;:�:rs,:,:�rriririrr,.�rfrrrrr.✓rrriiiaiiifirrrr r;
u, �
"'."://"/
#16/2
NAC -2
NAC -3
95cd 30cd 15cd
.275amp
75cd
15cd
30cd
1 EOL
.275arnp .12 .060arnp .060amp .107amp
.138amp .040amp
NAC -4
�h - �w
BATTERY I BATTERY
12V-12AH 12V-1211
#14/2
RISER DIAGRAM
SPARE
SPARE
F
10
MAP OF LOCATION
NOTICE
A completed, signed, Tukwila
Fire Department Pre=test
Certificate must be presented
to the Inspector prior to
commencement of Acceptance
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
termination of the testing.
Because of increased demand our
inspectors' schedules are booked
3-7 days ahead. Therefore,youu
will need to call 205-575-4407 to
schedule your inspections a
minimum of 43 hours in advance
of the date you want an
ins; eo on,
Fc/,V, I ,g-cc_e p7'' A S c).6
Id- r
I
ACCEPTED
O Without Comments
As Noted In Red
Per The Attached Letter
z
0
w
cc
J
0
o_
0
w
0
0
U
z
W
Z
0
ELECT. FIREOI*O99KW
206-575-0311
107 WASHINGTON BLVD. ALGONA WA, 98001
I nese plans have been reviewed by The Tukwila Fre
Prevention Bureau for conformance with current ci
standards. Acceptance is suhiect to errors and
omissions which do not authorize violations of adopted
stanoaras and oratnances. The responsibility for the
adequacy of design rests totally with the designer.
Additions, deletions or revisions to these drawings tter
this date will void thisacceptance and will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to field test and Inspection )y
The Tukwila Fire, Prevention Bureau.
[Date: 72--2/47c4:5 By: 6700
cc co
Lu
Z
W
I—
O
rA
N
CO
GENERAL NOTES:
TUKWILA I -IRE DEPARTr+ 1t
Please call: 575.4407
and give this job
No.
and exact address for shut.
iown or restoration approval.
PA D
2 2008
Tukwila Fire
4(05
A. THE DOOR TO THE CONTROL PANEL SHALL HAVE 1' LETTERS, WHICH READS
'FIRE AMC OR 'FIRE ALARM CONTROL'.
B. DEDICATED ARE ALARM CIRCUIT BREAKERS SHALL BE EQUIPPED WITH LOCK
OUT DEVICES.
C. ME RESET CODE SHALL BE 1-2-3-4-5.
D. CONTACT 1UKWILA ARE DEPARTMENT FOR KNOX BOX INFORMATION 0
206-575-4407.
cc
LII
LL
QZ
0_
CC
cc
U-
m
CC
C,)
o�
APPROVED BY :
ER
DRAWN BY:
RG
DATE:
5-20-08
JOB#
88375
DWG. NO. :
FA -01
A
B
C
H
2
3
4
5
6
7
8
10
General Notes N,P,PA, 72-2002 Edition
5,1,,,heal-sensing fire detectors shall be located on the
■ ceiling not less than lOOmm (4 in) from the sidewall or on the
sidewalls between iOOnm and 5OOmm (4in and IZin) from the
ceiling, See figure P,5,63/
�2 -5ec 5,7.5,2,1.,,snoke defectors shall be located on the ceiling not
/ ■• \ less than 100mm (4 in) from a sidewalf fo the near edge or if on a
sidewall, between lOOmm and 5OOmm (4in. and i2in) down from the
ceiling fo the fop of the defector. See figure 1=,5,73.2.1
n3 'Sec. /1,5,7,4,1 Defectors should not be located in a direct airflow or
closer Phan lm (( ft.) from an air supply diffuser or return air opening.
Supply or return sources larger than those commonly found in
residential and small commercial establishments can require greater
clearance fo smoke detectors, 5inilariy, smoke detectors should be
located farther away from high velocity air supplies,
/4 -see. 5.12.4 The operable pad of each manual fire alarn box shall be
■ not less Phan IJn (54 ft) and not more than 1.37m (4 %Z f1.) above
floor levet See figure r,5,12,4
4\5 -sec 75,4 Wall mounted appliances shall be mounted ouch that the
/ •■ entire lens is not less than 2m (80 in) and not greater than 2,4m (96
in) above the finished floor, See figure F.7.5,4
t 6 -sec, 4,4,1,4,1 Dedicated branch circuit, A dedicated branch circuit of
■ one of the following shall supply primary power;
(I) Gonmercial light and power.
(2) An engine -driven generator or equivalent in accordance with
4,4,1,9.2, where a person specifically trained in its operation is on
duly at all fires,
(3) An engine -driven generator or equivalent arranged for cogeneration
with corurcial light and power in accordance with 4,4,1,9,2, where a
person specifically trained in ifs operation is on duty of all fines,
Ceiling
Acceptable her*
Note: Measurements shown are to
the closest edge of the detector.
100 mm (4 in.)
100 mm
(4 in.)
minimum
Never here
Top of detector
acceptable here
300 mm
(12 in.)
maximum
Sidewall
Sidewall
4A]l4-1
2.4 m
(96 in.)
maximum
207n.) (8m
n.)
minimum
i
i
i
Lens
Finished floor
S/.,///////////1
INVENTORY/MDF ROOM
G.B. CEIUNG @ 10'-O AFF.
5009
004
WOMEN'S
G.B. CEILING @ B-0" AFF.
Ops -A
MEN'S
G.B. CEILING @ e-0' AFF.
LS -R
11571
002
MANAGER OFFICE
ACT -2 CEIUNG @ 10'-0' AFF.
14007
14-0" SOFFIT RADIUS
ACT -3 CEILING
S 9'-4" AFF, TYP.
003
OPEN OFFICE
ACT -2 CEIUNG @ 10-G AFF.
$013
Al5007
14.—On SOFFIT RADIUS
ACT -3 CEILING D 9'-4" AFF, TYP-
14'-0' SOFFIT RADIUS
ACT -3 CEILING 0 9'-4' AFF, FTP.
A
95cd
WI
SALES AREA
ACT -1 CEILING @ 1G-0' AFF
14010
$014
AT&T FIRE ALARM PLAN
1/8"=11-0"
SYSTEM INPUT /
OUTPUT MATRIX
YSTEM INPUTS
SYSTEM OUTPUTS
CONTROL UNIT ANNUNCIATION
NOTIFICATION
I
B
REQUIRED FIRE SAFETY CONTROL
SUPPLEMENTARY
ABCDEFGHI
:®
141
I
I
J
KL
•
--Operable
PacfR
-
O
,
P
1.1
(3)4
minimum
1.37
(4X
maximum
m
f.)
�y
I
m
ft.)
,x,12, /J
Finished floor
.1—Sidewall
U
/7/./././/77/////
W
X
Sidewall
4A]l4-1
2.4 m
(96 in.)
maximum
207n.) (8m
n.)
minimum
i
i
i
Lens
Finished floor
S/.,///////////1
INVENTORY/MDF ROOM
G.B. CEIUNG @ 10'-O AFF.
5009
004
WOMEN'S
G.B. CEILING @ B-0" AFF.
Ops -A
MEN'S
G.B. CEILING @ e-0' AFF.
LS -R
11571
002
MANAGER OFFICE
ACT -2 CEIUNG @ 10'-0' AFF.
14007
14-0" SOFFIT RADIUS
ACT -3 CEILING
S 9'-4" AFF, TYP.
003
OPEN OFFICE
ACT -2 CEIUNG @ 10-G AFF.
$013
Al5007
14.—On SOFFIT RADIUS
ACT -3 CEILING D 9'-4" AFF, TYP-
14'-0' SOFFIT RADIUS
ACT -3 CEILING 0 9'-4' AFF, FTP.
A
95cd
WI
SALES AREA
ACT -1 CEILING @ 1G-0' AFF
14010
$014
AT&T FIRE ALARM PLAN
1/8"=11-0"
SYSTEM INPUT /
OUTPUT MATRIX
YSTEM INPUTS
SYSTEM OUTPUTS
CONTROL UNIT ANNUNCIATION
NOTIFICATION
I
B
REQUIRED FIRE SAFETY CONTROL
SUPPLEMENTARY
ABCDEFGHI
JKL
MNOPQRSTUVWXYZIAABBCCODEEFFG
I
I
47
66 ' GP
sy.' 4.
8° 4-
o eY
a•
CoJA.
0 2 O=4.0
.� 0 4'
O
�Jr �e �J BJP 0 J Jsr
�G, P G G QG
st-
9-
Gv
P
Q
5
Descdplion
.
A
I
B
I
CDE
/
I
I
F
I
GNI
I
I
J
KL
•
/
M
I
N
-
O
,
P
QRS
♦
I
T
U
V
W
X
Y
Z
AABBCCJDEEFFGG
SMOKE DETECTORS
-
®
000
-',
0000
0
PULL STATIONS
0
0
0000400
MONITOR MODULES
®
000
•
0
HEAT DETECTORS
®
0
®
0
0000
-0
GENERAL NOTES:
A. THE DOOR TO THE CONTROL PANEL SHALL HAVE 1'
7IRE ALARM OR 'FRE ALARA CONTROL'.
B. DEDICATED FIRE ALARM CIRCUIT BREAKERS SHALL BE
OUT DEVICES.
C.
D.
LETTERS, MN READS
EQUIPPED WITH LOCK
THE RESET CODE SHALL BE 1-2-3-4-5.
CONTACT TUKWLA FIRE DEPARTMENT FOR KNOX BOX INFORMATION 0
206-575-4407.
z
0
w
cc
ISSUED FOR APPROVAL
ci
z
0
w
0
0
C)
Z
UJ
0z
W
li
ELECT. FIREOI*099KW
206-575-0311
107 WASHINGTON BLVD. ALGONA WA, 98001
AT&T WIRELESS
2
CC co
Q co
EL
LL W
W �
Z
W
H
`0
VJ
N
Co
.4-
T—
ME ME
w
ac
U—
RISER/BOM - FIRE ALARM PLAN
APPROVED BY :
ER
DRAWN BY:
RG
DATE:
5-20-08
JOB#
88375
DWG. NO. :
FA -02 2