FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: Batteries Plus
17065 Southcenter Py
Permit No.: 09-S-197
Date: November 30, 2009
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ' of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2'/z inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-05, section 13.5.6.2.2.
• Provide sprinkler protection beneath all obstructions greater than 4 ft in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
f
• Comply with obstructed/non-obstructed construction rules for sprinkler head
placement.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
• Modifications involving 30 or more heads require hydrostatic test and system
isolation if necessary.
• For dry pipe and double interlock preaction systems, in addition to the standard
hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24
hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the
24 hours shall be corrected.
• These conditions apply to all sprinkler piping exposed as necessary to
accomplish the permitted scope of work.
All code references are NFPA 13, 2007 Edition.
A. Reflected Ceiling Plan
Scale: 1/8"----V-0"
DL, 6rTV
Pay NF'A )3 R Ni ..R. '
/ f ie1 e./ rcw
V, 4
To.. be t) c;'t , V'. L / ► 5 "e .
I
A,va;►abie in IL
I Ctr'le=
172072
ti
❑
ACCEPTED
Without Comments
As Noted In Red
Per The Attached Letter
F1R
N
PRo7EGTION) + -t<t )
These plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformcnca with current city
standards. Acceptance is subject to errors and
omissions which do not authorize violations of adopted
standards and ordinances. The responsibillty for the
adequacy of design rests totally with the 6.l i ner. •
Additions, deletions or revisior y to these dr wirsgs after
this date will void this acceptc:r.ee and will require a
resubmittal of revised drawings for.subsequent approval.
Final acceptance is subject to field test and inspection by
The Tukwila Fire Prevention Bureau.
r 9 By:• -•
Date: 3� � •�
TUKWILA FIRE DEPARTMENT, i'
Please call: 575.4407,
and give this job
No, 9/-5-0
and exact address for shuts
clown nr restoration annroval:
SCALE
FILE
a
, ADO 4 SKLER5 I E Nt5T4
RDori T1'RINN UL,
To Accom.sNoortTE IJeya
'T-151442.. cEiLt'at>, UPRw iT3Tp (Zr.Hrt
1
2 Exts.roJ6 U&..L
O%J , �$ r>9EAOy
Spito4mtfeb
TENANT
THIS, PROJECT dS A TE
ALREADY BEEN PROTEC
FIRE SYSTEMS WEST I�
HEADS TO ACCOMMODA
LIGHTING AND HVAC LA
WITHOUT AFFECTING TH'
IMPROVEMENT,
' 1NT IMPROVEMENT, THIS FACILITY HAS,
��''D BY A,' FIRE "SPRINKLER. SYSTEM. •
ADDING ANO/OR RELOCATING SPRINKLER
THE NEW TENANT WALL;` CEILING;,
)UT. ALL WORK WILL BE DONE
CAPABILITY OF ;THE EXISTING SYSTEM.
SYMHOL LEGEND
DENOTES ° 1 SPRINKLER HEAD TO BE
RELOCATE ).
DENOTES'IA SPRINKLER HEAD TO BE ADDED
REPR SENTS EXISTING SPRINKLER, PIPE.
REPRESENTS NEW SPRINKLER PIPE.
1,
3148th St
S 950th St
al y
A
S 156th St
S 60th St
TukwIla
Eat 1
SIN 21st $t
Iia
S 1 6th St
5 168th St
S 170th St
va
m
S 172nd St
`rl S 173rd St
S 175th St
S 176th St
cry
Vi
i
-
S 1.72.nd P11
St
S 188th St 1-
1/3
,Jo@SIT
;
L; V
1st Q Minkler B. Ivo..
vo.
Qf
Poland 9r
S 180th`St
1JTS
pLoT PLA$J
NT,S
•
CONTRACT NAME:
NATIONAL BEDROOMS
17065 SOUTHCENTER PARKWAY
TUKWILLA,WA
CONTRACT WITH:
NATIONAL BEDROOMS
17065 SOUTHCENTER PARKWAY
TUKWILLA,WA
FFB26i a
HANQER LEQEND
SPRINKLER HEADS
REVISIONS
QENERAL NOTES
"tf HOOK
L
"L" ROD
SYMBOL
TYPE
MFG
MODEL
SIZE
TEMP.
FINISH
CANOPY
QUANTITY
MK
DATE
BY
DESCRIPTION
B
COACH SCREW ROD
M
MACHINE THREADED ROD
PEt4bENr
GCM
A
\S5
Rt)ti
SEMI
RECESSED
4
C
"C" CLAMP
N
TOGGLE .NUT
D
TOP BEAM CLAMP
P
POWDER DRIVEN STUD
0
E
EYE ROD
R
WEDGE ANCHOR
F
FLUSH SHELL
T
APPROVALS REOUIRED
G
CEIUNG FLANGE
U
Ccry o F "1"..0r-vo %kl A
SIDE BEAM BRACKET
W
J
"f BOLT
X
SHORT CUP
TOTAL THIS SHEET
1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UNDERWRITERS APPROVED.
2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS
SHOWN THUSLY (1-6) WHICH ARE END TO END.
3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA
SET tie. L5
4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH
NFPA PAMPHLET NO. 13.
5. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13.
6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN
ACCORDANCE WITH NFPA PAMPHLET NO. 13.
7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM
FREEZING IN AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM.
8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER
PIPING IS THE RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL
REPRESENTATNE.
Fire Systems. West
219 FRONTAGE ROAD N., SUITE B
PACIFIC, WA 98047
(253) 833-1248
FAX (253) 735-0113
WA CL #FIRESWI 140B1
WA ECL #FIRESWI 055LW
Q.C, FAB BY:
/
Q.C. INSTALL BY:
/
DESIGNER
DATE
JOB NO.
SHEET
J TugK
2 - 24-y9
A 3410 A
ort