HomeMy WebLinkAboutPP - 17065 SOUTHCENTER PKWY - BATTERIES PLUS - PERMITS AND PLANS17065 SOUTHCENTER PKWY ASSOCIATED PERMITS 99-5-059 09-S-197 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Batteries Plus 17065 Southcenter Py Permit No.: 09-S-197 Date: November 30, 2009 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/z inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. f • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2007 Edition. A. Reflected Ceiling Plan Scale: 1/8"----V-0" DL, 6rTV Pay NF'A )3 R Ni ..R. ' / f ie1 e./ rcw V, 4 To.. be t) c;'t , V'. L / ► 5 "e . I A,va;►abie in IL I Ctr'le= 172072 ti ❑ ACCEPTED Without Comments As Noted In Red Per The Attached Letter F1R N PRo7EGTION) + -t<t ) These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformcnca with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibillty for the adequacy of design rests totally with the 6.l i ner. • Additions, deletions or revisior y to these dr wirsgs after this date will void this acceptc:r.ee and will require a resubmittal of revised drawings for.subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. r 9 By:• -• Date: 3� � •� TUKWILA FIRE DEPARTMENT, i' Please call: 575.4407, and give this job No, 9/-5-0 and exact address for shuts clown nr restoration annroval: SCALE FILE a , ADO 4 SKLER5 I E Nt5T4 RDori T1'RINN UL, To Accom.sNoortTE IJeya 'T-151442.. cEiLt'at>, UPRw iT3Tp (Zr.Hrt 1 2 Exts.roJ6 U&..L O%J , �$ r>9EAOy Spito4mtfeb TENANT THIS, PROJECT dS A TE ALREADY BEEN PROTEC FIRE SYSTEMS WEST I� HEADS TO ACCOMMODA LIGHTING AND HVAC LA WITHOUT AFFECTING TH' IMPROVEMENT, ' 1NT IMPROVEMENT, THIS FACILITY HAS, ��''D BY A,' FIRE "SPRINKLER. SYSTEM. • ADDING ANO/OR RELOCATING SPRINKLER THE NEW TENANT WALL;` CEILING;, )UT. ALL WORK WILL BE DONE CAPABILITY OF ;THE EXISTING SYSTEM. SYMHOL LEGEND DENOTES ° 1 SPRINKLER HEAD TO BE RELOCATE ). DENOTES'IA SPRINKLER HEAD TO BE ADDED REPR SENTS EXISTING SPRINKLER, PIPE. REPRESENTS NEW SPRINKLER PIPE. 1, 3148th St S 950th St al y A S 156th St S 60th St TukwIla Eat 1 SIN 21st $t Iia S 1 6th St 5 168th St S 170th St va m S 172nd St `rl S 173rd St S 175th St S 176th St cry Vi i - S 1.72.nd P11 St S 188th St 1- 1/3 ,Jo@SIT ; L; V 1st Q Minkler B. Ivo.. vo. Qf Poland 9r S 180th`St 1JTS pLoT PLA$J NT,S • CONTRACT NAME: NATIONAL BEDROOMS 17065 SOUTHCENTER PARKWAY TUKWILLA,WA CONTRACT WITH: NATIONAL BEDROOMS 17065 SOUTHCENTER PARKWAY TUKWILLA,WA FFB26i a HANQER LEQEND SPRINKLER HEADS REVISIONS QENERAL NOTES "tf HOOK L "L" ROD SYMBOL TYPE MFG MODEL SIZE TEMP. FINISH CANOPY QUANTITY MK DATE BY DESCRIPTION B COACH SCREW ROD M MACHINE THREADED ROD PEt4bENr GCM A \S5 Rt)ti SEMI RECESSED 4 C "C" CLAMP N TOGGLE .NUT D TOP BEAM CLAMP P POWDER DRIVEN STUD 0 E EYE ROD R WEDGE ANCHOR F FLUSH SHELL T APPROVALS REOUIRED G CEIUNG FLANGE U Ccry o F "1"..0r-vo %kl A SIDE BEAM BRACKET W J "f BOLT X SHORT CUP TOTAL THIS SHEET 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UNDERWRITERS APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1-6) WHICH ARE END TO END. 3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA SET tie. L5 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. 5. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL REPRESENTATNE. Fire Systems. West 219 FRONTAGE ROAD N., SUITE B PACIFIC, WA 98047 (253) 833-1248 FAX (253) 735-0113 WA CL #FIRESWI 140B1 WA ECL #FIRESWI 055LW Q.C, FAB BY: / Q.C. INSTALL BY: / DESIGNER DATE JOB NO. SHEET J TugK 2 - 24-y9 A 3410 A ort