Loading...
HomeMy WebLinkAboutPP - 12870 INTERURBAN AVE S - GATEWAY CORPORATE CENTER BUILDING #1 - PERMITS AND PLANS12870 INTERURBAN AVE S ASSOCIATED PERMITS 14-S-115 99-5-241 13-5-274 889161 12-S-166 888153 11-S-225 866134 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Clear Sign Combustion 12870 Interurban Ave S Permit No.: 11-S-225 Date: October 4, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. 05/28/2014 WED 11:09 FAX 2538261033 Fire Sprinklers Inc. frill I firrinkle WA CO FIRESI988R1 12001/001 1 524 45th Street E, Suite 102, Sumner, WA 98390.253-826-0099 • Fax 253-826-1033 • www.firesprinklersinc.com 5/28/14 Tukwila Fire Department Al Metzler, Address: Clearsign 12870 Interurban Ave S Tukwila, WA 98168 I am requesting a shutdown number for replacing (14) existing 155° sprinkler heads with 286° sprinkler heads. The tenant has concerns that the equipment being used in the lab gernerates enough heat will generate enough heat to fuse a 155° sprinkler. Please let me know of any other questions or concerns you may have. Sincerely, • Scott Seibert, Project Manager scott@firesprinklersinc.com TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No. and exact address for shut- down hutdown or restoration approval. , 11/15/2013 FRI 14:49 FAX 2538261033 Fire Sprinklers Inc. ire 9'�` °en ri Fire Sprinklers WA CL# FIRESI"988RJ 0002/002 1524 45th Street E, Suite 102, Sumner, WA 98390.253-826-0099 • Fax 253-826-1033 • www.firesprinklersinc.com 11/15/13 Tukwila Fire Department Al Metzler, Address: Clearsign 12870 Interurban Ave S Tukwila, WA 98168 I am requesting a shutdown number for replacing (9) existing 155° sprinkler heads with 286° sprinkler heads. The tenant has concerns that the equipment being used in the lab gernerates enough heat will generate enough heat to fuse a 155° sprinkler. Please let me know of any other questions or concerns you may have. Sincerely, ---tt Seibert, Project Manager scott@firesprinklersinc.com TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No. -S- 274 and exact address for shut- down or restoration approval. 07/27/2012 FRI 13:28 FAX 2538261033 Fire Sprinklers Inc. cram - Fire Sprinklers WA CLN FIRESI*988RJ 0001/001 1524 45th Street 13, Suite 102, Sumner, WA 98390.253-826-0099 • Fax 253-826-1033 • www.firesprinklersinc.com 07/27/2012 Tukwila Fire Department Al Metzler, I am requesting a shutdown number for the Sprinkler System for ClearSign Combustion Corporation, located at 12870 Interurban Avenue South. ClearSign installed new equipment in a room that produces excessive heat, and we have been asked to change the existing 155° Sprinkler Heads out for new 286° Sprinkler heads. Please let me know of any other questions or concerns you may have. Sincerely, Jay Kolbe, Project Manager TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No. and 7-- and exact address for shut- down hindown or restoration approval. Q r-/ t 1 r 9fiti; C SY-b- scrAE: _ - _ — - - - t or Th 6' Z-1-7— frit- .‘ rifb Limit/ Ir /FaNti 1UE 1/1,1441Z 4,tf (21.1 eati 0 - 1 4. 4- 4 \-,115[Etturb c.t3 I 14 I i -g;414Er_ t1W I lxiCP triPti titrja 11111 -\co lu, Th HL Kea% - • , _ rwr :Rxt t‘ito IS 7 5.g.ttif 1 I= 1: _1 APPROVED BY WASHINGTON SURVEYING & RAIN BUREAa SEATTLE. WASH. %LS 2 c5 19E C. As meeting requirements of tnis Bureau for cclassiefincctearidoncnasthseprairttacklerheclea however, sestem changes or additions as recmm sheet(s) will result in improved rates. Acceptancesoapplies to submitted and for construction and occupancy h plans shaeds mstallation subiect to irspection for final acceptance. wn thereon. MI comment = -no ac..plautes relate exclusively to retains effect of Yr, -I - ,i1 in insurance rates. They are not te be constru.. - - _ coi W. upon tre qutstioo of ,,r4 :ether "du* cue" has be,r c sed with respect to possible liahlity for persond Inpiry or damage to property. ft rs reagacir.d that hazards which mew mutt m toss still evict i 7777,10 - tiiIr.p."1,xcz ;° e fr vk2 . 1 -4- - L.P121 nIyir 41 AP. elok t — et it ,t;„ r_ Cs tit f, 44 11.4'2 kily,f, r 7.171F.mitg FE ia:t4E 4!• '4:01. cyff!}46, t_it. W67-4 -.L. 6xzi. 9 1- - _ t .- ... i t.t - - -a- - - — - _ ACCEPTED WITHOUT COMMENTS.- AS NOTED IN RED o PER THE ATTACHED LETTER _ The drawings affixed hereto have been reviewed and accepted by the City of Tukwila Fire Dept. Additions, deletions or revisions to these drawings after this date will void this acceptance and wilt require a resubmittal of revised drawfngs. Final acceptance is subject to field= inspection by a representative of this department - - BY: .71 CITY OF TUKWILA /-\_ _66 575-4407 - _ = 12870 INTERURBAN AVE S 86—S-134 revisions 1 @WYII1tb 5Yffr1 6141 f&tFPi _ = 31 sErmiler;- u4,55,,Y; Th rX& TUKWILA FIRE DEPARTMEn - - - Please call: 5754407 - and give this Iola 866134 — and exact address for shut- - down or restoration aproval. - RECE1yED - BY TUKWILA FIRE ........ - RC tcli-e/A,t) /gr70 -114 IfTRIANGLE FIRE PROTECTION INC. PO. Box 264 = _ Woodinville,Wa. 9807Z _ _AUG U1986 = scale: date: SCD by: V1-ftr__ NAV LAATOK S __ GATEWAY CORPORATE CENTEP Job: imt 1303 contract with: e -- 411 OF HYDRAULIC INFORMATION ? O 4 1- n i\IEW J?AC; r ',..101 `.Aid, /AFO GENERAL NOTES T HANGER LEGEND SPRINKLER HEAD SYMBOLS STATIC FLOWING G.P. RESIDUAL P.S.I. THIS SYSTEM DESIGNED G.P.M. OVER THE HYDR RE ' : E SQ. FT. WHEN SUP • D WITH WATER A ATA RATE S - G.P.M. AT 0 E BASE OF RISER P.S.I. E HOSE INSIDE HOSE RACK SPRK. 1) INSTALLATION TO CONFORM TO_3 N.F.P.A. # 1 AND � �./ IF-TEK:WI a�a -' � \, 2) ALL MATEIRIALS NEW AND J. -- APPROVED. 3) ALL WELDING PERFORMED IN SHOP AND IN ACCORD- ANCE WITH A.W.S. D-10.9. 4) PAINTING OF PIPE NOT IN CONTRACT. 5) ELECTRICAL WIRING NOT IN CONTRACT. 6) EARTHQUAKE BRACING PER CODE. 7) USE FIG. # 401 POLISHED ALUM. CANOPY, U.N.O. #1 #2 #3 #4 #5 #6 #7 #8 #9 - EXP. SHELL, ROD & RING - C -CLAMP, ROD & RING - POWDER STUD, ROD & RING - ANGLE CLIP, ROD & RING - L -ROD & RING - EYEROD & RING - COACH SCREW. ROD & RING - CEIL. FLG., ROD & RING - U HOOK - UPRIGHT ON LINE - UPRIGHT ON 1' SPRIG UP - PENDENT ON LINE - PENDENT ON 1- DROP - UPRIGHT & PENDENT DROP - UPRIGHT SPRIG & PENDENT DROP - SIDEWALL - DRY SIDEWALL - DRY PENDENT DROP ALARM: SPRINKLERS REVISIONS ruxwitA FIRE DEPARTMENT Please call: 575.4402 and give this job and'exact address for shut. down or restoration approval; ACCEPTED " HOUT COMMENTS. o AS NOTED IN RED Q PER THE ATTACHED LETTER 4 The drawings affixed hereto have been reviewed and accepted by the City of Tukwila Fire Dept. Additions, deletions or revisions to these dr::swings after this date will void this accee,i+: n-::: art.: will requirea resubmittal revue ings. Final acceptance is subject 5 i,,1.1- inspection by a representative o,f •" department DATE: CITY OF 575-440i ILA WIT DgP11147--r 4.4Z.LIZAT, p T �� MAX IIP' ✓�i` 4, 40 TELL— PPE 4% REP g E TEp }r4.t":.TAG 5 --To F..Yet.��1'v~+ •-�I,-��ty'.r �� n' `�'A'i.R• E _ i �-/ ,1/Y Y' -•I lv t7 X it/1 ji�ij 1�1LC:.V� ORIF: TYPE DEGREE 1 1, 0 Y2 .: t-== rte; FINISH rt QTY 1/ Z 12830 INTERURBAN AVE S 88-S-153 NORTH re 74 LI D BY ,S...;ln I SUN » RATING K R:ail SEATTLE. MASH. ._ 1 _ �I:j� r.s meeting requirements of this oi.reau for classification as spr!akiered; t: ra: dr, spstsm changes or additions as recommended on the attached ;4_` +� 1 resaka it improved rates. Accept r e apples to pians as �.- „a. y - t •--- •h-t,a� a:.❑ tJ Ecn�=ru�a.un 6nJ GCiu - : S ��:: approvals and acceptances relate exclusively a inn affect comments, pp on the Gm.stiog of whether "duel �tfect of various conditions aeon hoe insurance rates. They ta be construed a- bearing i't any way upon care" has be axercis l rty. It respect recognized that liability vend% rot ve auor dames, o p! Injury It in toss ' Y1 . t ,--- 2.5 70 KITE. 12 L ,8v 1 TRIANGLE FIRE PROTECTION P.O. BOX 264 WOODINVILLE, WA 98072 527-5211 483-5211 TOTAL SPRINKLERS CONTRACT WITH: WA. STATE CONT. LIC. NO. TR - IA - NF - P2740P SCALE: ; 5 Ni OTE, DATE: P) - BY: .OB #: Pa- I OF T%E COMPLETE LIssiE± 104012 it 0 1 E K /y 3 - f* ----1 • E , E m R s 4'10vi eel• /+ ` . -+ , ' I \ ta I.(11 Y.S 1b4:l r.)— 1 I _ 1 R11_ Fy ; V z,1- 1 j _-- _� I 01 T i / t • - en *, tib i I• I iiE R 0 r E i f ? /15 hi 1 n i\IEW J?AC; r ',..101 `.Aid, /AFO GENERAL NOTES T HANGER LEGEND SPRINKLER HEAD SYMBOLS STATIC FLOWING G.P. RESIDUAL P.S.I. THIS SYSTEM DESIGNED G.P.M. OVER THE HYDR RE ' : E SQ. FT. WHEN SUP • D WITH WATER A ATA RATE S - G.P.M. AT 0 E BASE OF RISER P.S.I. E HOSE INSIDE HOSE RACK SPRK. 1) INSTALLATION TO CONFORM TO_3 N.F.P.A. # 1 AND � �./ IF-TEK:WI a�a -' � \, 2) ALL MATEIRIALS NEW AND J. -- APPROVED. 3) ALL WELDING PERFORMED IN SHOP AND IN ACCORD- ANCE WITH A.W.S. D-10.9. 4) PAINTING OF PIPE NOT IN CONTRACT. 5) ELECTRICAL WIRING NOT IN CONTRACT. 6) EARTHQUAKE BRACING PER CODE. 7) USE FIG. # 401 POLISHED ALUM. CANOPY, U.N.O. #1 #2 #3 #4 #5 #6 #7 #8 #9 - EXP. SHELL, ROD & RING - C -CLAMP, ROD & RING - POWDER STUD, ROD & RING - ANGLE CLIP, ROD & RING - L -ROD & RING - EYEROD & RING - COACH SCREW. ROD & RING - CEIL. FLG., ROD & RING - U HOOK - UPRIGHT ON LINE - UPRIGHT ON 1' SPRIG UP - PENDENT ON LINE - PENDENT ON 1- DROP - UPRIGHT & PENDENT DROP - UPRIGHT SPRIG & PENDENT DROP - SIDEWALL - DRY SIDEWALL - DRY PENDENT DROP ALARM: SPRINKLERS REVISIONS ruxwitA FIRE DEPARTMENT Please call: 575.4402 and give this job and'exact address for shut. down or restoration approval; ACCEPTED " HOUT COMMENTS. o AS NOTED IN RED Q PER THE ATTACHED LETTER 4 The drawings affixed hereto have been reviewed and accepted by the City of Tukwila Fire Dept. Additions, deletions or revisions to these dr::swings after this date will void this accee,i+: n-::: art.: will requirea resubmittal revue ings. Final acceptance is subject 5 i,,1.1- inspection by a representative o,f •" department DATE: CITY OF 575-440i ILA WIT DgP11147--r 4.4Z.LIZAT, p T �� MAX IIP' ✓�i` 4, 40 TELL— PPE 4% REP g E TEp }r4.t":.TAG 5 --To F..Yet.��1'v~+ •-�I,-��ty'.r �� n' `�'A'i.R• E _ i �-/ ,1/Y Y' -•I lv t7 X it/1 ji�ij 1�1LC:.V� ORIF: TYPE DEGREE 1 1, 0 Y2 .: t-== rte; FINISH rt QTY 1/ Z 12830 INTERURBAN AVE S 88-S-153 NORTH re 74 LI D BY ,S...;ln I SUN » RATING K R:ail SEATTLE. MASH. ._ 1 _ �I:j� r.s meeting requirements of this oi.reau for classification as spr!akiered; t: ra: dr, spstsm changes or additions as recommended on the attached ;4_` +� 1 resaka it improved rates. Accept r e apples to pians as �.- „a. y - t •--- •h-t,a� a:.❑ tJ Ecn�=ru�a.un 6nJ GCiu - : S ��:: approvals and acceptances relate exclusively a inn affect comments, pp on the Gm.stiog of whether "duel �tfect of various conditions aeon hoe insurance rates. They ta be construed a- bearing i't any way upon care" has be axercis l rty. It respect recognized that liability vend% rot ve auor dames, o p! Injury It in toss ' Y1 . t ,--- 2.5 70 KITE. 12 L ,8v 1 TRIANGLE FIRE PROTECTION P.O. BOX 264 WOODINVILLE, WA 98072 527-5211 483-5211 TOTAL SPRINKLERS CONTRACT WITH: WA. STATE CONT. LIC. NO. TR - IA - NF - P2740P SCALE: ; 5 Ni OTE, DATE: P) - BY: .OB #: Pa- I OF T%E COMPLETE LIssiE± 104012 HYDRAULIC INFORMATION STAT I C FLOWING G.P. RESIDUAL P.S.I. THIS SYSTEM DESIGNED G.P.M. OVER THE HYDRRU RE' : E SQ. FT, WHEN SUP 1 t D WITH WATER A . E BASE OF RISER ATARATE G.P.M. AT PSI OIIT E HOSE INSIDE HOSE RACK SPR 1 HE COOKE Ei 1 E LINE ! 104012 I r it 5-811. - _ 3340 tE OE. IrKX iml .II,E F,E,FLEC- E►7 I L.I � T/ I AF nI (� ENN PIPNC.; L: GENERA NOTES 0 aavEw c, P#f' SPI2I h I- 'S 0 't,14J U I'Ji ii I'Ia it. pratN V4Lv5 C,kl`T�►`'� t,14Ir �t ✓.4 (04 t3><.i. M:+t Ten (rawer") aAlk1 11 II E ^�.►- I 2) • txwar. ,x2,41.1c 1 urIt:- (vr E. „1.17 F1,n o -Tae -s i� P; 4IZE' Ili ACcoR[741.1(.,E- vim] DczPIr Iris N-4Z4F7 P1 E. e.:tEHEDLJI_i. 'PES P= 2� LLL E,RA Cq L.:1,15(7 Fix�,r^I-�, !-p ,:TEE L- PIPE - WI T -1i.2. C.I. 5,I-TTIrI4S '3) g;--111201-1 Epp L - .T1or"l AKE 6IVAI-1I t. -L -`i ' At, por "I0T Ir1F'L( C E tl.E, . _ — =E/.ISi'It e. PIPI 1 --ro LEIL11,4-1 FLAq6„15-. R.111( , I•Jo , IRn ll4 Airrop '361-zE.uY (z) -� t7F cox 4 ' sIt.c efri:ErAlkagt1 A7r R;i d?T,14 N �c, 14.m4 se Zi L4zi 46)251,4 'tom PU21.t l 1'S , RE -P E.r J TE,p C CE PT ED WITHOUT COMMENTS. I AS NOTED IN RED II 0 PER THE ATTACHED LETTER The drawings affixed hereto have been reviewed and accepted by the Cityf Tukwila Fire Dept. Additions, deleti ns or revisions to these drawings after his date will void this acceptance and will require a resubmittal of revised draJvings. Final acceptance is subject to field - inspection by a representative of this department DATE: ?Uf CITY OF TUKWILA 575.4407 l INSTALLATION TO CONFCjRMTO N.F.P �A. # 13 AND c it Ir ret..,2°PT. i V), t . 2) ALL MATERIALS NEW ANC LJ.I APPROVED. 3) ALL WELDING PERFORM:in IN SHOP AND IN ACCORD- ANCE WITH A.W.S. D-10.9. 4) PAINTING OF PIPE NOT IV CONTRACT. 5) ELECTRICAL WIRING NOT IN CONTRACT. 6) EARTHQUAKE BRACING PER CODE. 7) USE FIG. # 401 POLISHED ALUM. CANOPY, U.N.O. #1 #2 #3 #4 #5 #6 #7 #8 #9 HANGER LEGEND - EXP. SHELL, ROD & RING - C -CLAMP, ROD & RING - POWDER STUD, ROD & RING - ANGLE CLIP, ROD & RING - L -ROD & RING - EYEROD & RING - COACH SCREW, ROD & RING - CEIL. FLG., ROD & RING -U HOOK SPRINKLER HEAD SYMBOLS 0 0 - UPRIGHT ON LINE - UPRIGHT ON 1" SPRIG UP - PENDENT ON LINE • PENDENT ON 1" DROP - UPRIGHT & PENDENT DROP - UPRIGHT SPRIG & PENDENT DROP • SIDEWALL - DRY SIDEWALL - DRY PENDENT DROP ALARM: IFj`lez.;..1- I144-1, SPRINKLERS ORIF. TYPE DEGREE FINISH Irl 3,4w r'j3tie, t QTY I`� Z IT , L 1? I! I 'h1 k' r 41-1'1191 REVISIONS 400 b ra or -r TUK ACCEPTED EY WASVIIVIVORIX a &huuwi sF.ATTI_E:, WA$M. SEP 1 1939 MI meeting requirements of Sirs tiuiteu rut mastication as sprinktered, however, system themes or additions as recommended on the attached sheets) will result In improved rates. Acceptance Minis to Owls is rttor construction and occupancy utrwrn. 41r04 Mrtatleinand wiet lslnapectionur et 101rii�trli All comments and acceptances relate exclusively to relative effect of various conditions upon fire insurance rates. They are not to be con- strued as bearing in any way upon the question of whether "due me" has been exercised with respect to possible liability for personal in• ury or damage to property. It is recognized that halarilS wh'Gh may t1.44Il, ill gall exist. WILA FIRE DEPARTMEITI• • 646 Please call: 575.4407 and give this job and exact address for shut. down or restoration approval. NORTH UJ 1IVFt? ,L- 005Prr4,L, ' 5lfl L.'"Ti — (: -� ,VL u�c +4' I Z- 570 r I'TF.L) Z.., j..1 #6,`w' U k -r ,/ I I ....,C: , \e",/.6- TRIANGLE b"'v/,L` TRIANGLE FIRE PROTECTION P.O. BOX 264 WOODINVILLE, WA 98072 527-5211 483-5211 TOTAL SPRINKLERS 1145 1W..15,- kr ^ CONTRACT WITH: `>6.1. (.1) P7 WA. STATE CONT. LIC. NO. TA-IA-NF-P2740P SCALE: a OTS p DATE: r�. BY: ::• `1-'4 ,? . JOB #: OF > z . o Y.th-at: Comments Q Aslot- ed I�tiL _ +.� in ��.� Per The Attached Letter iPr;eFlans have ve en reviewed by T'ne Tukwila Fire a ben _`{ent on Bo . eau f rrla re current City oda. Cs. ACC r#~ to errors or and ---missions tibia bo , _ __ vioi,--Itions of adopted t:ndar ds and rd r -w r •ins b ty for the adequacy of C q,>, deletions n _ rawii Js after "=is date will vo!,d require a esi bmitta _e' ia';d _ .,: ?s :,r aucsequent approval. x -Al acceotc +> su: -'ect to fel' test and Inspection by i t TukwilaF -, Prevencioo urea' j T UKW1LA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No. I1 - S- and exact address for shut Jow l or restoration approval. REFLECTED CEILING PLAN GENERAL NOTES 1. DESIGN AND INSTALLATION SHALL CONFORM TO NEPA PAMPHLET 13 AND CiTY OF TUKWILA REQUIREMENTS. 2. ALL MATERIALS SHALL BE NEW AND U.L. APPROVED. 3. PIPE: ALL PIPE 2' AND SMALLER TO BE SCHEDULE 40 BLACK STEEL AU. PiPE 2' AND LARGER TO BE SCHEDULE 10 BLACK STEEL_ 4. FITTINGS: ALL FITTINGS (SCREWED AND GROOVED) AND GROOVED COUPLINGS TO BE DUCTILE IRON. 5. PAINTING OF PiPE AND PROTECTION OF SPRINKLER HEADS FROM PAiNT IS BY OTHERS. G. AIL ELECTRICAL WIRING AND CONDIUT TO BE PROVIDED AND INSTALLED BY OTHERS. 7. NOT USED 8. OWNER IS RESPONSIBLE TO ASSURE THAT STRUCTURE AS IT IS SHOWN ON THE CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS. NO AUXIWARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPUMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER PIPING LOADS. 9. CASCADE ALARM ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED. FOR THE CONDITION. PERFORMANCE OR CURRENT CODE COMPUANCE OF THE EXISTING 51'5TEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY CASCADE ALARM. 10. NOT USED 1 I . ALL DIMENSIONS ARE TO CENTERLINE OF PIPE. 12. DOTTED UNES DENOTE EXISTING PiPE. 13. SYMBOLS/ABREVIATIONS: CX' -X']- DENOTES CENTER UNE OF SPRINKLER FIFE AFF. X' -X' DENOTES CEILING HBGHT. AFF - CENTERLINE Of PiPE ABOVE FINISHED FLOOR. BDK - CENTERLINE OF PIPE BELOW BOTTOM OF DECK. (=r- FLEXIBLE GROOVED COUPUNG. MT - MECHANICAL TEE I`D - PL.EXABL E DROP NIPPLE. SEE PLAN FOR LEGNTH. 7-- THREAD END PWG En_ HYDRAULIC REFERENCE NODE. \OTES • = (E) HEADS AT CEILING A Q = (N) HEADS R © = (E) HEADS RELOCATED P c = (E) PLUG HEADS '1 • VI a 1 1 IMPORTANT In localities subject to freezing conditions. it is the owner's responsibility to provide heat throughout wet pipe sprinkler systems areas and in enclosures for dry pipe deluge and other types of valves controlling water supplies to sprinkler systems. This drawing and the information and design application herein contained is the property of Cascade Alarm. and is loaned upon express conditions that the sane be returned to Cascade Alarm upon request; all information herein contained shall be treated as secret, and confidential; no reproduction of this drawing or any part thereof shall be mode without written consent of Cascade Alarm. CONTRACT RESPONSIBILITIES SPRINKLERS ITEM CASCADE OTHERS TYPE ORIFICE I TEMP. FINISH I CANOPY SYMBOL OTY. TY -FRB 1/2" I 155 CHROME I SEMI RECESSED CH • SYSTEM TYPE WET ® _D ❑ ❑ Cascade Alarm CONTRACT NAME: Clear Sign Combustion 12870 Interurban Ave. So. (GCC BLDG 1) Tukwila, WA. CONTRACT WITH: SCALE: 1/8"=r-0" DRAWN .BY: RC DESCRIPTION: REFLECTED CEILING PLAN CHECKED BY: NO. CU DATE BY REVISIONS - SEE FLAGGED AREA ON PLAN ELTA TOTAL THIS SHEET APPROVALS. OUT OUT OUT OUT IN IN IN IN FIRE PROTECTION DIVISION Post Office Box 7459, Kent, WA. 206-767-5800, Ext 2 SYSTEM DESIGN DATA DATE: 9/27/11 HAZARD rJ AGdFICATION• - O IE © I HYDRAULIC DENSITY DESIGN DATA: AREA OF APPUCATION: TOTAL SYSTEM RFOIIIREMENTS: WATER SUPPLY fNFORMATION: SYSTEM AREA: GPM/SQ. FT. HOSE ALIOWANGFS PSI. AT SQ. FT. GPM. AT SQ. FT./HD. GPM STATIC PRESSURE 80 RESIDUAL PRESSURE TEST TAKEN AT PST. WITH BY PSL GPM FLOWING DRAWING NO. FP 1 DATE 12870 INTERURBAN AVE S 11-S-225 PAD SET' 29 2011 V I IL.i- FIRE /f/ 9/• S `, 7 °: _ 1111 IF II lik L.. ��1T" ,,..} -I� O R OR kVA{ %-- Al `� - 1 __ .__fId ■ IIIIIIIIia ► % ���► E ii. EiIMEM OR 11111 1111_'muippzil OEM AIM • • pli r • >< 'AISE THESEHEADS • S •• 101 • FOR EW CILING Millw • • - • • ❑1 0 el • • • 0 • • mt •• >< ><, 0 �r.• • • OR - • • 0., A >< ► • >C X I ,1 • • _23><: • •p • !. / � /• /\ . • OR • • >< / •P n �\ AREA OF WORK \\ • •P OR >< 4 \ \ \\ REFLECTED CEILING PLAN GENERAL NOTES 1. DESIGN AND INSTALLATION SHALL CONFORM TO NEPA PAMPHLET 13 AND CiTY OF TUKWILA REQUIREMENTS. 2. ALL MATERIALS SHALL BE NEW AND U.L. APPROVED. 3. PIPE: ALL PIPE 2' AND SMALLER TO BE SCHEDULE 40 BLACK STEEL AU. PiPE 2' AND LARGER TO BE SCHEDULE 10 BLACK STEEL_ 4. FITTINGS: ALL FITTINGS (SCREWED AND GROOVED) AND GROOVED COUPLINGS TO BE DUCTILE IRON. 5. PAINTING OF PiPE AND PROTECTION OF SPRINKLER HEADS FROM PAiNT IS BY OTHERS. G. AIL ELECTRICAL WIRING AND CONDIUT TO BE PROVIDED AND INSTALLED BY OTHERS. 7. NOT USED 8. OWNER IS RESPONSIBLE TO ASSURE THAT STRUCTURE AS IT IS SHOWN ON THE CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS. NO AUXIWARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPUMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER PIPING LOADS. 9. CASCADE ALARM ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED. FOR THE CONDITION. PERFORMANCE OR CURRENT CODE COMPUANCE OF THE EXISTING 51'5TEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY CASCADE ALARM. 10. NOT USED 1 I . ALL DIMENSIONS ARE TO CENTERLINE OF PIPE. 12. DOTTED UNES DENOTE EXISTING PiPE. 13. SYMBOLS/ABREVIATIONS: CX' -X']- DENOTES CENTER UNE OF SPRINKLER FIFE AFF. X' -X' DENOTES CEILING HBGHT. AFF - CENTERLINE Of PiPE ABOVE FINISHED FLOOR. BDK - CENTERLINE OF PIPE BELOW BOTTOM OF DECK. (=r- FLEXIBLE GROOVED COUPUNG. MT - MECHANICAL TEE I`D - PL.EXABL E DROP NIPPLE. SEE PLAN FOR LEGNTH. 7-- THREAD END PWG En_ HYDRAULIC REFERENCE NODE. \OTES • = (E) HEADS AT CEILING A Q = (N) HEADS R © = (E) HEADS RELOCATED P c = (E) PLUG HEADS '1 • VI a 1 1 IMPORTANT In localities subject to freezing conditions. it is the owner's responsibility to provide heat throughout wet pipe sprinkler systems areas and in enclosures for dry pipe deluge and other types of valves controlling water supplies to sprinkler systems. This drawing and the information and design application herein contained is the property of Cascade Alarm. and is loaned upon express conditions that the sane be returned to Cascade Alarm upon request; all information herein contained shall be treated as secret, and confidential; no reproduction of this drawing or any part thereof shall be mode without written consent of Cascade Alarm. CONTRACT RESPONSIBILITIES SPRINKLERS ITEM CASCADE OTHERS TYPE ORIFICE I TEMP. FINISH I CANOPY SYMBOL OTY. TY -FRB 1/2" I 155 CHROME I SEMI RECESSED CH • SYSTEM TYPE WET ® _D ❑ ❑ Cascade Alarm CONTRACT NAME: Clear Sign Combustion 12870 Interurban Ave. So. (GCC BLDG 1) Tukwila, WA. CONTRACT WITH: SCALE: 1/8"=r-0" DRAWN .BY: RC DESCRIPTION: REFLECTED CEILING PLAN CHECKED BY: NO. CU DATE BY REVISIONS - SEE FLAGGED AREA ON PLAN ELTA TOTAL THIS SHEET APPROVALS. OUT OUT OUT OUT IN IN IN IN FIRE PROTECTION DIVISION Post Office Box 7459, Kent, WA. 206-767-5800, Ext 2 SYSTEM DESIGN DATA DATE: 9/27/11 HAZARD rJ AGdFICATION• - O IE © I HYDRAULIC DENSITY DESIGN DATA: AREA OF APPUCATION: TOTAL SYSTEM RFOIIIREMENTS: WATER SUPPLY fNFORMATION: SYSTEM AREA: GPM/SQ. FT. HOSE ALIOWANGFS PSI. AT SQ. FT. GPM. AT SQ. FT./HD. GPM STATIC PRESSURE 80 RESIDUAL PRESSURE TEST TAKEN AT PST. WITH BY PSL GPM FLOWING DRAWING NO. FP 1 DATE 12870 INTERURBAN AVE S 11-S-225 PAD SET' 29 2011 V I IL.i- FIRE /f/ 9/• S `, 7 °: Without Comments As Noted In Red Per The Attached Letter 9 These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted 'standards and ordinances. The responsibility for the 1:. adequacy of design rests totally with the designe ii Additions, deletions or revisions to these drawing this date will void this acceptance and will require f resubmittal of revised drawings forsubsequent ap t Final acceptance is subject to field test and inspe The Tukwila Fire Prevention Bureau. IDate: 7)-7(f 9 By: 1 TUKWILA FIRE DEPARTME 1 Please call: 575.440 and give this job / No. 7-- 9--�1 and exact address for shut. down or restoration approvci. 24'- 0 " 0 ©F=1 ce B' -D" SOO q= 0" 0 Ex- S' MA)N Fl RE PROTECTION PLAN 0 •t 4 o,_ 9" _ SCALE: l/ = l' -O" 12870 INTERURBAN AVE S 99-S-241 CROSS SECTION GDx1T2ncf NAME: ORTI-4OPEDIC PARTS 12.870 INTERURBANi AVE .S SEATTLE I WA. ci81(0. IGF LEC JD sPrz.1Nk.Ler-s usep APPEoVALS ;ZEQuleEP laENE7-AL NQS Fire Systems West SYM. 0 0 TYPE MFL' ./ MODEL SIJ-�_ = � k / A SIZE '/2 '_ TEMP_ 155'.WASS FINISH NIA ou 4. (✓ I TY OF Tv K'AJ I LA 2- O+niN /ARCt; FSW VTA1. 1, TOTAL-- i.� L ls__ r•_I ...l -WS BEE- t OEsi&NFP NSA i3 oia0INAeY t4A2A2o C.TeP I oc.cvPANCY, 2.) At.L HEW PlPtNCE TO Be ALLIED W/%2sIP SCI tail"�f.��. 219 Frontage Road, North • Suite B • Pacific, WA 98047 PHONE: 206-833-1248 • FAX: 206-735-0113 PLI BY 1CV_RA DATE 7=-14.' qq Joe, 'Jo. 44(7 A SHEET' ( OF ./.