HomeMy WebLinkAboutPP - 14800 STARFIRE WAY - STARFIRE SPORTS INDOOR SOCCER - PERMITS AND PLANS14800 STARFIRE WAY ASSOCIATED PERMITS 58-19 30-19 02-19 11-18 D18-0231 19-F-119 17-F-086 16-F-160 08-F-518 04-F-143 19-S-075 09-S-139 08-S-470 07-S-269 05-S-033 04-S-029 SITE LOCATION CITY OF TUKWILA FIRE MARSHAL'S OFFICE 206-575-4407 FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: 23230tfiao/ Site Address: /11900 . (.Y,(/rG LC2 t( Tt'kw,/ct. G(JA l/a3lEia3 Suite Number: Floor: Tenant Name: 5$0-Ctre. Spot -kir, Cde,,,p\P y. 1.1 New Tenant? ❑ - Yes Eg - No Property Owner's Name: Slay Jrie, Sone r ex,rr1a/e44 Forkbe..v► f P & Mailing Address: lei7-La4A3t /G.. 1.4)79 City State Zip CONTACT PERSON -if there are questions about the submittal. Name: Act -we Aleisa, Day Telephone: 253-872-7222 cx+• 2114 Company Name: RY'G4lt1/ e;Yl Mailing Address: 18 S 21****► St Lie City State Zip E-mail Address: kIl P .!'At .YChert" rrx+fcor; .rtwrn Fax Number: Contractor's City of Tukwila Business License number: BUS CY:V12(, �S4 Total number of new/relocated devices or sprinlder heads: 9q Valuation of Project (contractor's bid price): $ 25,`715 Scope of Work (please provide detailed information): AV hew e-tk 1L>set/ ewe -rage. S1 rJ i id arNP raq e In >th-t ntc...$ a. r - PERMIT APPLICATION NOTES Value of Construction - In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE 0113,ArIGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING 0 R OR THORIZED AGENT: Signature: APR 10 2011 TUKWILA FIRE Date: y//d/2019 Print Name: 12.61 fi e �ca'l Day Telephone: 25?, -$72 ''72ZZ Plan Permit App.doc 8/22/14 -vel TFD FP Form 8 SITE LOCATION o.: �'j p pG Site Address: King Co. Assessor's Tax N l � � a © J/ f\� Suite Number:_________ Tenant Name: 'J �- Property Owner's Name: Mailing Address: 1 L\ CONTACT PERSON -if there are questions about the submittal. Name: (_ v Company Name: = l Mailing Address: ? G' E-mail Address: CA" t' • NICET III number: ity Day Telephone:_ Fax Number: Contractor's City of Tukwila Business License number:�' Total number of new/relocated devices or sprinkler heads: i ` 1 Vaz Valuation of Project (contractor's bid price): $G Scope of Work (please provide detailed information):_,- rA PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Eve ry is commenced within 180 days after its iss it Tuan e, orssued a if the work authorized on the site by sll become invalid unless the work onuch site permitis suspended by suchr permit abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to writing, one or more extensions of time, for periods not more than 180 days each. The extension shall ended or and justifiable cause demonstrated.grant, in be requested in writing I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME T O UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZ TRUE FOR THIS PERMIT. ED TO APPLY BUILDING OWNE Plan Permit Ann dor Date: 5 7 Day Telephone: L`' 6 -- 7 L31'Z `i TP11 FP Pnrm R Date: 9/22/19 CITY OF TUKWILA TEMPORARY SPECIAL EVENT PERMIT Permit # 58-19 By virtue of The Provisions of the International Fire Code adopted by City of Tukwila Ordinance, Rave Green 5K Fun Run located at Baker Blvd./Christensen Rd. having made application in due form, and as the conditions, surrounding, and arrangements are, in my opinion, such that the intent of the Ordinance can be observed, authority is hereby given and the PERMIT is granted *To temporarily use a Right -of -Way per 11.08.010 and 11.08.020 of the Tukwila Municipal Code 11.08.020 Right -Of -Way Use Permits, A. Type A — Short -Term Nonprofit. 1. Type A permits may be issued for use of a right-of-way for 72 or less continuous hours for nonprofit purposes, which do not involve any physical disturbance of the right-of-way. 2. This type of use may involve disruption of pedestrian and vehicular traffic or access to private property, and may require inspections, cleanup and police surveillance. For periods longer than 72 hours, these uses will be considered Type D, long-term. If any of these uses are for profit, they are considered Type B. 3. Type A permits include but are not limited to the following, when for nonprofit purposes: a. Assemblies. b. Bike races. c. Block parties. d. Parades. e. Parking. f. Processions. g. Nonmotorized vehicle races. h. Street dances. i. Street runs. *To use temporary signs per 19.24.050 of the Tukwila Municipal Code. Temporary Sign condition Temporary signs allowed only for the duration of the event (but in no case more than 30 days) shall comply with the following requirements: Temporary Signs Up to two temporary signs per permit. The total area of all temporary signs displayed may not exceed 64 square feet in sign face area. Also refer to TMC 19.24 for additional requirements for placement and setback of temporary signs. Additionally, per TMC 19.12.020, the City does not regulate signs that are not discernable from adjacent properties or public right-of-way. 19.24.050 General Provisions for all Temporary Signs A. Placement. Temporary signs may only be placed on the wall fronting the tenant space of the applicant that has been issued the temporary sign permit or on the associated premises. The sign must be securely attached, either to the wall if located on the building, or securely tied to stakes located in a landscaped area. Display of temporary signs in any other manner, except as outlined by this code, is strictly forbidden. B. Setbacks. All temporary signs not attached to buildings shall be placed a minimum of five feet from all property lines. No temporary sign more than three feet in height shall be placed within the sight distance triangle of a vehicular access point, unless it can be demonstrated the sign will not pose a safety issue by reducing visibility. TMC 8.22 and 19.24 — DCD *To comply with noise regulations per 8.22.050 and 8.22.120 of the Tukwila Municipal Code. Noise Code Condition The maximum noise levels when measured at or within the boundary of a receiving property shall not exceed the following levels: District of Sound Producing Source District of Receiving Property Residential Daytime Residential, Nighttime Commercial Industrial Residential 55 dB(A) 45 dB(A) 57 dB(A) 60 dB(A) Commercial 57 dB(A) 47 dB(A) 60 dB(A) 65 dB(A) Industrial 60 dB(A) 50 dB(A) 65 dB(A) 70 dB(A) "Daytime" means 7AM-10PM, Monday through Friday and 8AM-10PM, Saturday, Sunday and State - recognized holidays. At any hour of the day or night, the applicable noise limitations above may be exceeded for any receiving property by no more than: a. 5 dB (A) for a total of 15 minutes in any one-hour period; b. 10 dB (A) for a total of 5 minutes in any one-hour period; or c. 15 dB (A) for a total of 1.5 minutes in any one-hour period. If noise levels will be exceeded beyond those noted above, then the applicant shall provide written notice to all residents within 500 feet of where the party or project is being held. Per TMC 8.22.020 "Residence" means a building regularly or intermittently occupied by a person for dwelling, lodging or sleeping purposes. Therefore, notice to hotels is required. When the 500 -foot radius includes multi- family complexes, all residents of the complex shall be notified. Written notice shall be provided between 10 and 30 days of the onset of activity and shall enumerate the anticipated party hours or work schedule for the length of the project. An affidavit of distribution shall be provided to the City. Maintain emergency vehicle access around property as submitted with application. A 20ft clear access path is needed for the Fire Lane. For questions about Fire Code items, please contact: Aaron Johnson Deputy Fire Marshal Fire Department Aaron.Johnson@tukwilawa.gov 206-575-4407 For questions about Police Department items, please contact: Kraig Boyd Police Commander K. BoydPTukwilaWA.gov City of Tukwila Temporary Special Event Permit Application You May Email Application To: TempSpecialEvents@TukwilaWA.clov Or You May Deliver Application to: City of Tukwila, Fire Marshal Office, 6300 Southcenter Blvd, Ste 209, PH# 206-575-4407 No Fee for Event Application. A permit fee may apply depending on event. Please allow 10 -15 business days for issuance of permit. ASSIGNED PERMIT Date of Application: # 7/16/19 Event Contact Information Name of Organization Sponsoring Event: Seattle Sounders RAVE Foundation City of Tukwila Business License:NA UBI# Event Contact Name:Ashley Fosberg (Race Director) Phone #206-512-1200 Email Address:ashleyf@soundersfc.com Mailing Address:159 S Jackston Street, Seattle WA 98104 Event Back Up Contact Name:Jared Loranger (Course Manager) Phone #360-220-4548 Email Address:Jared@fizzeventsnw.com Type of Event —Ex: Sidewalk/Parking lot sale, Live Musical Performance, Type of Event:5K Fun Run Carnival, Block Party, organizel walk, run, bike ride, etc. SCALED SITE PLAN OF EVENT IS REQUIRED ATTACH BROCHURES / FLYERS / POSTERS OR MAILING ADVERTISEMENT / ANNOUNCEMENT OF EVENT Dates of Event: 9/22/19 Hours of Operation: 9 - 12PM Number of Event Volunteers: 50 Address / location of event:Intersection of Baker Blvd & Christiansen Will the event be held at any time during non -day light hours: NO Private Security provided: NO Will the event be held indoors or outdoors:Outdoors In Parking lot: On Sidewalk: Streets, Trails and Parking - Attach Trail route, Parking Plan and location maps, written narrative of traffic Will streets need to be closed: YES Will any portion of a City trail need to be closed: YES What trail? Green River If Yes, what streets and for how long: On Map When and how long: During Race Trail route/site plan required Parking; On street: 1 Off street: ✓ If yes, what streets will be used:Multiple in Legal Parking Only How will parking be directed / controlled:Pre-Race Emails will be sent with parking information Live Music or Amplified Sound or Voice - TMC Noise Code 8.22 - Refer to Code for Complete Information TMC Noise Code; allowable times 7am - lOpm Monday through Friday 8am -10pm Saturday and Sunday Use of PA System?Yes between 9am - 12pm If DJ; Name of DJ: NO If live music event / performance - Name of performer / group: Start Time: gam Stop Time:l 2pm City of Tukwila Temporary Special Event Permit Application - page 2 SCALED SITE PLAN REQUIRED TO SHOW LAYOUT OF EVENT ASSIGNED PERMIT # Restroom / Washing Facilities Permanent Restroom Available: YES NO F, and Garbage Collection and Disposal Portable Restroom: YESZNO Hand Washing Station: YES NO F, Garbage Receptacles: YES FA NO E Qnty: 15 Garbage Collection and Disposal PIan:15 - Will collect Electrical / Propane / Gas Usage — location must be included in scaled site plan Using liquid propane gas / open flame: YES II NO F, For cooking: For heating: Portable generators used: YES NO❑Type: Cord & Plug FA Hardwire Electrical Service for / at the Tot, includin use of power / �I extension cords: YES NO fl Temporary Structures — location must be included on scaled site plan Tents: YES r, NO Qnty:8 Dimensions, including height:1 OX1 0 tents only, 7 feet tall Trailers / Cargo Containers: YES II NO F, Qnty: Dimensions, including height: Temporary Stages: YES CI NO Qnty: 1 Dimensions, including height:16'x8'X1' Scaffolding: YES II NO FA Temporary Water Meter needed: YESE NO FA Selling / Serving - Food / Alcohol Selling / Serving Alcohol: YES NO FJ WA State Liquor Lic. # Selling / Serving Food: YES NO FA King County Food Permit # RCW 69.50.445(1) STATES INFUSED PRODUCTS Event Entertainment Motorized vehicles: YES: NO THAT IT IS UNLAWFUL TO OPEN A PACKAGE CONTAINING, OR CONSUME, MARIJUANA, MARIJUANA - OR MARIJUANA CONCENTRATES IN VIEW OF THE GENERAL PUBLIC OR IN A PUBLIC PLACE Carnival Inflatable Floats: YES NO FI FI Rides: YES NO FI Bouncers: YES NO F, Fireworks: YES NO F Animals: YES E NO F, Types: Booths/ Vendors: YES FA NO Signage — criteria for temporary signage to be followed — max 2 signs, up to 64sqft total, shown on site plan Temporary Signs / Wind Animated Banners: YES F, NO ■ Qnty:2 Dimensions:3 X1 O Objects: YES NO F, Searchlights: YES�NO�� CHECKLIST Completed Application Scaled Site Plan Event Fivers / Brochures Insurance - If Required The applicant may be required to procure and maintain proof of minimum insurance 1 full business day prior to the event and for the duration of the event naming the City of Tukwila as Primary and Non-contributory Additional insured. Applicant also agrees to defend, indemnify and hold the City, its officers, officials, employees, representative and volunteers harmless from any and all claims, injuries, damages, losses or suits including attorney fees, arising out of or In connection with activities or operations performed by the Applicant or on Applicant's behalf out of issuance of this Permit, except for injuries and damages caused by the sole negligence of the City. Signature certifies acceptance of terms and information provided is accurate: Signature Date7/16/19 ACORO® CERTIFICATE OF LIABILITY INSURANCE L.------- 3/1/2020 DATE(MM/DD/YYYY) 7/17/2019 THIS CERTIFICATE IS ISSUED AS A MATTER OF INFORMATION ONLY AND CONFERS NO RIGHTS UPON THE CERTIFICATE HOLDER. THIS CERTIFICATE DOES NOT AFFIRMATIVELY OR NEGATIVELY AMEND, EXTEND OR ALTER THE COVERAGE AFFORDED BY THE POLICIES BELOW. THIS CERTIFICATE OF INSURANCE DOES NOT CONSTITUTE A CONTRACT BETWEEN THE ISSUING INSURER(S), AUTHORIZED REPRESENTATIVE OR PRODUCER, AND THE CERTIFICATE HOLDER. IMPORTANT: If the certificate holder is an ADDITIONAL INSURED, the policy(ies) must have ADDITIONAL INSURED provisions or be endorsed. If SUBROGATION IS WAIVED, subject to the terms and conditions of the policy, certain policies may require an endorsement. A statement on this certificate does not confer rights to the certificate holder in lieu of such endorsement(s). PRODUCER Lockton Companies, LLC 601 108th Avenue NE, Suite 1969 Bellevue WA 98004 CONT NAMEACT PHO(NCNE. Ext): FAX . No): E-MAIL ADDRESS: INSURER(S) AFFORDING COVERAGE NAIC 8 INSURER A : National Casualty Company 11991 INSURED Seattle Soccer, LLC 1442818 dba Seattle Sounders FC 159 S. Jackson St., Suite 200 Seattle WA 98107 INSURER B : KK00000007840100 INSURER C : 3/1/2020 INSURER D : $ 1,000,000 $ 1,000,000 INSURER E : INSURER F : }{ COVERAGES SEASO01 CERTIFICATE NUMBER: 16200523 REVISION NUMBER: XXXXXXX THIS IS TO CERTIFY THAT THE POLICIES OF INSURANCE LISTED BELOW HAVE BEEN ISSUED TO THE INSURED NAMED ABOVE FOR THE POLICY PERIOD INDICATED. NOTWITHSTANDING ANY REQUIREMENT, TERM OR CONDITION OF ANY CONTRACT OR OTHER DOCUMENT WITH RESPECT TO WHICH THIS CERTIFICATE MAY BE ISSUED OR MAY PERTAIN, THE INSURANCE AFFORDED BY THE POLICIES DESCRIBED HEREIN IS SUBJECT TO ALL THE TERMS, EXCLUSIONS AND CONDITIONS OF SUCH POLICIES. LIMITS SHOWN MAY HAVE BEEN REDUCED BY PAID CLAIMS. INSR LTRJNSf1 TYPE OF INSURANCE ADDL SUBR WVD POLICY NUMBER POLICY EFF (MM/DD/YYYY) POLICY EXP (MM/DD/YYYY) LIMITS A X COMMERCIAL GENERAL LIABILITY y N KK00000007840100 3/1/2019 3/1/2020 EACH OCCURRENCE $ 1,000,000 $ 1,000,000 CLAIMS -MADE }{ OCCUR DAMAGE TO RENTED PREMISES (Ea occurrence) X Part Lgl Liab $1M MED EXP (Any one person) $ Excluded PERSONAL & ADV INJURY $ 1,000,000 $ Not Applicable $ 2,000,000 $ GEN'L AGGREGATE POLICY OTHER: LIMIT APPLIES PRO- JECT PER: LOC GENERAL AGGREGATE PRODUCTS - COMP/OP AGG AUTOMOBILE LIABILITY ANY AUTO OWNED AUTOS ONLY HIRED AUTOS ONLY AUTOSULED NON -OWNED AUTOS ONLY NOT APPLICABLE COMBINED SINGLE LIMIT (Ea accident) $ XXXXXXX BODILY INJURY (Per person) $XXXXXXX BODILY INJURY (Per accident) $XXXXXXX PROPERTY DAMAGE (Per accident) $ XXXXXXX $ XXXXXXX UMBRELLA LIAB EXCESS LIAB _ OCCUR CLAIMS -MADE NOT APPLICABLE EACH OCCURRENCE $ XXXXXXX AGGREGATE $ XXXXXXX DED RETENTION $ $ XXXXXXX WORKERS COMPENSATION AND EMPLOYERS' LIABILITY ANY PROPRIETOR/PARTNER/EXECUTIVE OFFICER/MEMBER EXCLUDED? (Mandatory In NH) If yes, describe under DESCRIPTION OF OPERATIONS below Y / N N / A NOT APPLICABLE PER STATUTE OTH- ER E.L. EACH ACCIDENT $ XXXXXXX E.L. DISEASE - EA EMPLOYEE $ XXXXXXX E.L. DISEASE - POLICY LIMIT $ XXXXXXX DESCRIPTION OF OPERATIONS / LOCATIONS / VEHICLES (ACORD 101, Additional Remarks Schedule, may be attached if more space is required) RE: RAVE Green Run September 22, 2019. City of Tukwila is an Additional Insured to the extent provided by the policy language or endorsement issued or approved by the insurance carrier. CERTIFICATE HOLDER CANCELLATION See Attachment 16200523 City of Tukwila 6200 Southcenter Blvd. Tukwila WA 98188 I SHOULD ANY OF THE ABOVE DESCRIBED POLICIES BE CANCELLED BEFORE THE EXPIRATION DATE THEREOF, NOTICE WILL BE DELIVERED IN ACCORDANCE WITH THE POLICY PROVISIONS. AUTHORIZED REPR f` //41"-m--- ACORD 25 (2016/03) ©1988-2015'ACORD CORPORATION. All rights reserved. The ACORD name and logo are registered marks of ACORD COMMUNICATIONS LIST (ICS 205A 1. Incident Name: 2019 Rave Green 5K 2. Operational Period: Date From: 0700 Date To: 09/22/19 Time From: 1200 Time To:09/22/19 3. Basic Local Communications Information: Incident Assigned Position Name (Alphabetized) Method(s) of Contact (phone, pager, cell, etc.) Incident Commander PD OPS Boyd, Kraig (206) 391-8059 Operations Section FD OPS Flores, Chris (206) 571-3429 Logistics Section/Traffic Control Mitchell, Scott (206) 571-6299 Starfire Sports Zach Zielinski (206) 714-6451 Sounders FC/RAVE Foundation Ashley Fosberg (206) 234-3729 City of Tukwila Sponsor REP Brandon Miles (206) 731-9071 FIZZ Events NW, Course MGMT Jared Loranger (360) 220-4548 4. Prepared by: Name: Chris Flores Position/Title: Date/Time: Asst. Fire Chief Signature: 09/19/19 1000 ICS 205A IAP Page Date: 6/11/19 Tukwila Fire Department OPERATIONAL PERMIT By virtue of the provisions of the International Fire Code adopted by City of Tukwila Ordinance, Seattle Soccer LLC located at 14800 Starfire Way 30-19 having made application in due form, and as the conditions, surrounding, and arrangements are, in my opinion, such that the intent of the Ordinance can be observed, authority is hereby given and the PERMIT is granted to operate an air -supported temporary membrane structure or a tent having an area in excess of 400 square feet (37 m2), or a canopy in excess of 700 square feet (65 m2) per section 105.6.43 of the International Fire Code. This PERMIT is issued and accepted on condition that all Ordinance provisions now adopted, or that may hereafter be adopted, shall be complied with. THIS PERMIT IS VALID FOR -June 15 thru November 30, 2019 - This permit does not take the place of any License required by law and is not transferable. Any change in use or occupancy of premises shall require a new permit. Fire Marshal THIS PERMIT MUST BE POSTED ON THE PREMISES MENTIONED ABOVE. T.F.D./F.P. #2 CiAti) 11 1 5-67 Date: 1/29/19 Tukwila Fire Department OPERATIONAL PERMIT By virtue of the provisions of the International Fire Code adopted by City of Tukwila Ordinance, Pyro and Fire Fx, LLC located at 14800 Starfire Way 2-19 having made application in due form, and as the conditions, surrounding, and arrangements are, in my opinion, such that the intent of the Ordinance can be observed, authority is hereby given and the PERMIT is granted for the manufacture, storage, handling, sale or use of any quantity of explosive, explosive material, fireworks or pyrotechnic special effects within the scope of Chapter 56 of the International Fire Code section 105.6.14* This PERMIT is issued and accepted on condition that all Ordinance provisions now adopted, or that may hereafter be adopted, shall be complied with. THIS PERMIT IS VALID FOR -Seawolves 2019 Season - This permit does not take the place of any License required by law and is not transferable. Any change in use or occupancy of premises shall require a new permit. Fire Marshal THIS PERMIT MUST BE POSTED ON THE PREMISES MENTIONED ABOVE. T.F.D./F.P. #2 CtUNCIL A GENA SYNOPSIS Initials STAFF SPONSOR: DON TOMASO ITEM NO. Meeting Date Prepared by Mayor's review Council review 04/16/18 DT ❑ Ordinance Mtg Date ❑ Bid Award Mtg Date ❑ Public Hearing Mtg Date ❑ Other Mtg Date Mtg Date Mtg SPONSOR ❑ Council ❑ Mayor ❑ HR ❑ DCD ❑ TS ❑ P&R ❑ Police ❑ PW ❑ Finance ►1 Fire SPONSOR'S PYRO & FIRE FX, LLC on behalf of Seawolves Rugby team has applied for a season long SUMMARY fireworks permit to utilize speciality fire works during their home games at Starfire Sports complex. The fireworks will consist of Galaxis Flame Units, Smoke units, (1) artillery plate, Mine 75's and Mine 100's these are all proximity fireworks and do not produce any fallout debris. REVIEWED BY ❑ COW Mtg. ❑ CA&P Cmte ❑ F&S Cmte ❑ Transportation Cmte ❑ Utilities Cmte ❑ Arts Comm. ❑ Parks Comm. ❑ Planning Comm. DATE: N/A COMMII"1'EE CHAIR: RECOMMENDATIONS: SPONSOR/ADMIN. COMMITTEE Fire Department ITEM INFORMATION STAFF SPONSOR: DON TOMASO ORIGINAL AGENDA DATE: 04/16/18 AGENDA ITEM TITLE Fireworks permit for Seawolves Rugby Season at Starfire Sports Complex CA 1 EGORY II Discussion 04/16/18 Motion Date 04/16/18 ❑ Resolution Mtg Date ❑ Ordinance Mtg Date ❑ Bid Award Mtg Date ❑ Public Hearing Mtg Date ❑ Other Mtg Date Mtg Date Mtg SPONSOR ❑ Council ❑ Mayor ❑ HR ❑ DCD ❑ TS ❑ P&R ❑ Police ❑ PW ❑ Finance ►1 Fire SPONSOR'S PYRO & FIRE FX, LLC on behalf of Seawolves Rugby team has applied for a season long SUMMARY fireworks permit to utilize speciality fire works during their home games at Starfire Sports complex. The fireworks will consist of Galaxis Flame Units, Smoke units, (1) artillery plate, Mine 75's and Mine 100's these are all proximity fireworks and do not produce any fallout debris. REVIEWED BY ❑ COW Mtg. ❑ CA&P Cmte ❑ F&S Cmte ❑ Transportation Cmte ❑ Utilities Cmte ❑ Arts Comm. ❑ Parks Comm. ❑ Planning Comm. DATE: N/A COMMII"1'EE CHAIR: RECOMMENDATIONS: SPONSOR/ADMIN. COMMITTEE Fire Department COST IMPACT / FUND SOURCE EXPENDITURE REQUIRED AMOUNT BUDGETED APPROPRIATION REQUIRED $0 $0 $0 Fund Source: Comments: MTG. DATE RECORD OF COUNCIL ACTION MTG. DATE ATTACHMENTS 04/16/18 Informational Memorandum dated 04/13/18 Firework Permit Application Packet City of Tukwila Allan Ekberg, Mayor INFORMATIONAL MEMORANDUM TO: Public Safety Committee FROM: Chief Wittwer BY: Don Tomaso, Fire Marshal CC: Mayor Ekberg DATE: April 13, 2018 SUBJECT: Seawolves Rugby Team Fireworks Permit \ ISSUE The Seawolves Rugby Team has applied for fireworks permit for their 2018 Rugby season home games. BACKGROUND The Seawolves Rugby Team has requested fireworks permit for their 2018 season home games, pursuant to RCW 70.77 and TMC 8.12.020(3). They will be using proximity type fireworks, Galaxis Flame Units, Smoke Units, (1) artillery plate, Mine 75's and Mine 100's these are all proximity fireworks and do not produce any fallout debris. DISCUSSION The Seawolves Rugby Team will be using the fireworks during the opening ceremonies. Starfire Sports is supportive of this request and has provided a letter of support. Staff has reviewed the submitted documents and noted that they make provisions to ensure the smoke from the smoke units does not impede the exit paths. FINANCIAL IMPACT None RECOMMENDATION Staff recommends that the application be approved at the April 16, 2018 council meeting. ATTACHMENTS Memo to Chief Wittwer dated April 13, 2018 Washington State Public Fireworks Display Permit Packet Tukwila Fire Department InterOffice Memo DATE: April 13, 2018 TO: Chief Wittwer FROM: Don Tomaso, Fire Marshal SUBJECT: Seawolves Rugby Team Fireworks Permit Application The Seawolves has applied for a firework permit to utilize proximity fireworks as listed for select home games this season at Starfire Sports stadium. There are 4 scheduled home games and an undetermined number of potential post season games. Starfire Sports has also provided a letter of support for this permit at their stadium. The Galaxis Flame Units emit a vertical column of flame up to 20' in height and will be used during the player introductions (players will run between two units). The Smoke units produce colored smoke that will reflect the team colors. (1) artillery plate, Mine 75's and Mine 100's these are all proximity fireworks and do not produce any fallout debris. All these items are commonly used at sporting and concert events. The company preforming the show is PYRO & FIRE FX, LLC. The firm has supplied the required application and certificate of insurance as required by RCW 70.77 and TMC 8.12 and provided the current copy of the pyro technician's license. I conducted research on PYRO & FIRE FX, LLC. They conduct special effects for a variety of public sporting and concert venues within the State. I have scheduled this firework permit for the Council Meeting Monday April 23, 2018. I have contacted the City Clerks' Office to let them know of the short time frame for this approval. If you have any questions, please let me know. COUNCIL AGENDA SYNOPSIS Initials Aleeting Date Prepared by Mayors review Council review 06/26/17 DT // Motion Date 6/26/17 ❑ Resolution 'Wig Date Ct ❑ Bid Award Altg Date :❑ Public Nearing Mtg Date ❑ Other :11tg Date Mtq Date A1tg SPONSOR ❑ Council ❑ Major ❑ 1!R ❑ DCD ❑ Finance /1 Fire ❑ IT ❑ P&R ❑ Police ❑ PW' SPONSOR'S Authorize the approval of a fireworks permit submitted by Zakuani and Friends Charity SUMMARY Match to be used on July 2, 2017 at Starfire Sports. The fireworks will consist of GERBS which are a proximity firework. This is identical to what is used at Century Link Field for the Sounders home games. This request came in on Thursday, June 22, within the legally required 10 -day period for submitting a Fireworks permit application, but past the agenda deadline; some documentation will be provided at the meeting. Rr.\'n•;vvlu BY ❑ COW Mtg. ❑ CA&P Cmte ❑ F&S Crate ❑ Utilities Cmte ❑ Arts Comm. ❑ Parks Comm. DATE: COMMITTEE CHAIR: • Transportation Crate • Planning Comm. ITEM INFORMATION ITEM NO. 3.E. & Spec 2.D. 91 S'I':\H; SPONSOR: DON TOMASO, FIRE MARSHAL ORIGIN;AI. AGENDA DA'll:: 06/26/17 AGENDA I m:M TITLE Fireworks Permit for July 2, 2017 at Starfire Sports. C\'FNGORY 1 Discussion 6/26/17 // Motion Date 6/26/17 ❑ Resolution 'Wig Date ❑ Ordinance Altg Date ❑ Bid Award Altg Date :❑ Public Nearing Mtg Date ❑ Other :11tg Date Mtq Date A1tg SPONSOR ❑ Council ❑ Major ❑ 1!R ❑ DCD ❑ Finance /1 Fire ❑ IT ❑ P&R ❑ Police ❑ PW' SPONSOR'S Authorize the approval of a fireworks permit submitted by Zakuani and Friends Charity SUMMARY Match to be used on July 2, 2017 at Starfire Sports. The fireworks will consist of GERBS which are a proximity firework. This is identical to what is used at Century Link Field for the Sounders home games. This request came in on Thursday, June 22, within the legally required 10 -day period for submitting a Fireworks permit application, but past the agenda deadline; some documentation will be provided at the meeting. Rr.\'n•;vvlu BY ❑ COW Mtg. ❑ CA&P Cmte ❑ F&S Crate ❑ Utilities Cmte ❑ Arts Comm. ❑ Parks Comm. DATE: COMMITTEE CHAIR: • Transportation Crate • Planning Comm. RECOMMENDATIONS: SPoNsoR/ADMIN. C(.)M MI'I'I'E Fire Marshal Office, Fire Department l COST IMPACT / FUND SOURCE EXPINDrru1u. REQUIRED AMOUNT BUDGETED APPROPRIATION REQUIRED $0 $0 $0 Fund Source: Comments: MTG. DATE RECORD OF COUNCIL ACTION MTG. DATE ATTACHMENTS 06/26/17 Permit documentation 91 City of Tukwila Allan Ekberg, Mayor INFORMATIONAL MEMORANDUM TO: Public Safety Committee FROM: Chief Wittwer BY: Don Tomaso, Fire Marshal CC: Mayor Ekberg DATE: June 22, 2017 SUBJECT: Zakuani & Friends Charity Fireworks Permit ISSUE The Zakuani & Friends Charity has applied for a fireworks permit for the July 2, 2017 charity soccer match. BACKGROUND The Zakuani & Friends Charity has requested a fireworks permit pursuant to RCW 70.77 and TMC 8.12.020(3). They will be using proximity type fireworks called "GERBS": these specialty fireworks emit a shower of sparks that quickly extinguish before they fall to the ground or turf. The Sounders S2 used the same style of GERBS at Starfire Sports Complex for the 2016 Season. DISCUSSION The Zakuani & Friends Charity will be using the fireworks during the opening ceremonies. Starfire Sports is supportive of this request and has provided a letter of support. FINANCIAL IMPACT None RECOMMENDATION Staff recommends that the application be approved and placed on the June 26, 2017 Committee of the Whole and Special Meeting Consent Agenda to follow that same evening. ATTACHMENTS Memo to Chief Wittwer dated June 22, 2017 Washington State Public Fireworks Display Permit Packet 93 Date: 4/20/18 Tukwila Fire Department OPERATIONAL PERMIT By virtue of The Provisions of the Uniform Fire Code adopted by City of Tukwila Ordinance, Pyro and Fire FX, LLC located at 14800 Starfire Way 11-18 having made application in due form, and as the conditions, surrounding, and arrangements are, in my opinion, such that the intent of the Ordinance can be observed, authority is hereby given and the PERMIT is granted for the manufacture, storage, handling, sale or use of any quantity of explosive, explosive material, fireworks, or pyrotechnic special effects within the scope of Chapter 56 of the International Fire Code section 105.6.14* This PERMIT is issued and accepted on condition that all Ordinance provisions now adopted, or that may hereafter be adopted, shall be complied with. THIS PERMIT IS VALID FOR -For the 2018 Seawolves Season - This permit does not take the place of any License required by law and is not transferable. Any change in use or occupancy of premises shall require a new permit Fire Marshal THIS PERMIT MUST BE POSTED ON THE PREMISES MENTIONED ABOVE T.F.D./F.P. #2 11,11),)1 6V:A 9R3 S / I AS1164.1 1.1 -A wF S PYRO I I GIINI(S (�ONt t 1,111.01M (,)LI,NI S ,1\14starftra Rfs April 15, 2018 Don Tomaso Battalion Chief Fire Marshall City of Tukwila Dear Don, I am writing to confirm Starfire Sports grants Seattle Seawolves Rugby permission to use fireworks during the Seawolves games inside the Starfire Sports Stadium for the 2018 season. Sean Engl Director Starfire Sports Stafflre Sports 14800 Starfire Way Tukwila, WA 98188 Phone: 206.431.3232 Fax: 206.431.6811 www.starfiresports.com info@starfiresports.com Seawolves Fireworks Map at Starfire Stadium Prevailing wind direction at site is from the SW to the NE. Instructed that player intros will be from NW corner and any smoke will blow away from crowd. National Anthem Pyrotechnics E Galaxis Flame Units Smoke Units 0 *Revised 4/20/2018 *Subject to Change/Revisions Seawoives Fireworks Map at Starfire Stadium National Anthem Pyrotechnics Galaxis Flame Units Smoke Units As of 4/13/2018 *Subject to Change/Revisions Below are the pyrotechn,cs being used in the national anthem pyro. - (1) artillery plate - Mine 75s - Mine 100s x • Washington State Patrol Fire Protection Bureau Office of the State Fire Marshal Pyrotechnic Operator License Licensee Data Jesse Miller 4100 Foster Street Apt. 208 Gig Harbor, WA 98335 License Number: P-04480 (474 State Fire Marshal 3000-420-043 (10118) oa s 'PF 44R9HAvsc, Licensee Data Jesse Miller 4100 Foster Street Apt. 208 Gig Harbor, WA 98335 License Number: P-04480 Phone Number: (253) 227-8905 Email Address: thefenex@outlook.com Date of Issue: January 30, 2019 Date of Expiration: January 31, 2020 Licensee Signature Licensee Wall Mount Card Washington State Patrol Fire Protection Bureau Office of the State Fire Marshal Pyrotechnic Operator License State Fire Marshal 3000-420-043 (10/18) Phone Number: (253) 227-8905 Email Address: thefenex@outlook.com Date of Issue: January 30, 2019 Date of Expiration: January 31, 2020 General Display Employer Portion 1) Cut along dotted lines to release the four license cards. 2) All four license cards are individually legal and valid evidence of licensing. 3) All four cards constitute an entire license for a single operator. 4) The Licensee must sign all four portions of the license. 5) ALL four license cards are legal and valid evidence of licensing. 6) The Licensee must carry either the wallet (landscape) or the lanyard card (portrait). License Number: P-04480 Pyrotechnic Operator License Washington State Patrol Fire Protection Bureau 10089P January 31, 2020 Jesse Miller Current/Valid Until Pyrotechnic Operator State Fire Marshal Licensee Signature 3000-420-043 (10/18) 10089P Licensee Signature 10089P License Number: P-04480 Washington State Patrol Fire Protection Bureau Pyrotechnic Operator Licensing Type January 31, 2020 Current and Valid Until Jesse Miller Pyrotechnic Operator Li nsee Signature State Fire Marshal 3000-420-043 (10/18) r CAUTION: This email originated from outside the City of Tukwila network. Please DO NOT open attachments or click links from an unknown or suspicious origin. 2 r \ 7 '\ .w_,_,__._,_,_._,_,_,_,_,_,..,w__.1V_.11W_,_,_,_, Certificate of Flame Resistance Registered # F98301 Issued By Tacoma Tent & Awning Tacoma, WA 98403 (253) 627-4128 Manufactured Date 04/10/2019 This is to certify that the material listed below has been flame retardant treated or is inherently non-flammable, and meets both NFPA-701 and CAN/ULC-S109-14 standards. Company City Starfire Sports Seattle Certification is hereby made that: (Check "A" or "B") Address 14800 Starfire Way State, Zip WA, 98188 ❑ (A) The articles described below have been treated with a flame resistant chemical approved and registered by the State Fire Marshal and the application of said chemical was done in conformance with the laws of the State of California and the rules and regulations of the State Fire Marshal. Name of Chemical Method of Application ® (B) The articles described below are made from a flame resistant fabric or material registered and approved by the State Fire Marshal for such use. Chemical Registered Trade name of flame resistant fabric Showtime S-83 DBO Registered # F98301 The flame retardant process used will not be removed by washing. Darrel Brown By Chris Pace Production Superintendent Description of Articles: (2) 40x b/o gable — catenary (4) 40 x 15 b/o mid — catenary (8) 8 x 15 b/o 2pc keder j -hook sidewall (4) 8 x 20 b/o 2pc keder j -hook sidewall Washington State Patrol Fire Protectior Bureau Office of:.the-State Fire Marshal Pyrotechnic Operator Licens Licensee Data. Richard J. Olsen Post Office Box 193 Gig Harbor, WA 98335 License Number:. P-02940 Phone Number: -(253) 307-5118 Email Address: pyro2940@aol.corn Date of Issue: January 23 2019 Date of Expiration: January 31,e2020 State Fire Marsha( 3000.420-041-.(10/18) Licensee Signature= y.. Licensee •Wall Mount Card ashington.;State Patrol Fire Protection Burea Office of the State Fire Marshal yrotechn c Operator License Licensee Data Richard J. Olsen Post::. Office Box 193 Gig Harbor, WA 98335 License Number: P-02940 PhoneNumber-253 307 ti Email Address. piro2940( Date of Issue January 2 ke .of Expiration~ January .State Fire Marshal' 3000420-041, (10/ 8); • General Display Employer Portion :,471.44/0.60 1 sieti4te_ cietk 6)? 8404, Wa>;. ,ngton State Patrol Fire Prootectiok..3ureau Office of the State Fire Marshal Pyrotechnic Operator License Licensee Data Steven Russell Gardner 819 Buena Vista Drive Othello, WA 99344 License Number: P-04408 State Fire Marshal 18-1341 Phone Number: (509) 989-2615 Email Address: biggreen50 1 0@gmail.com Date of Issue: January 26, 2018 Date of Expiration: January 31, 2019 Licensee Wall Mount Card Licensee Signature 'fir Licensee Data Steven Russell Gardner 819 Buena Vista Drive Othello, WA 99344 License Number: P-04408 Washington State Patrol Fire Protection Bureau Office of the State Fire Marshal Pyrotechnic Operator License State Fire Marshal 18-1341 Phone Number: (509) 989-2615 Email Address: biggreen5010@gmaii.com Date of Issue: January 26, 2018 Date of Expiration: January 31, 2019 General Display Employer Portion Licensee Signature 1) Cut along dotted lines to release the four license cards. 2) All four license cards are individually legal and valid evidence of licensing. 3) All four cards constitute an entire license for a single operator. 4) The Licensee must sign all four portions of the license. 5) ALL four license cards are legal and valid evidence of licensing. 6) The Licensee must carry either the wallet (landscape) or the lanyard card (portrait). License Number: P-04408 Pyrotechnic Operator License Washington State Patrol 1$-1341 Fire Protection Bureau January 31, 2019 Current/Valid Until Pyrotechnic Operator Steven Russell Gardner 8-1341 License Number: P-04408 Washington State Patrol Fire Protection Bureau Pyrotechnic Operator Licensing Type January 31, 2019 Current and Valid Until Steven Russell Gardner Pyro : hnic Oeerator State Fire Marshal w FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Starfire Sports 14800 Starfire Way Permit No.: 19-S-075 Date: April 23, 2019 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • All valves controlling the water supply for automatic sprinkler systems and waterflow switches on all sprinkler systems shall be electrically supervised. • All interior control valves shall be readily accessible, labeled and located not more than 6 ft. above the floor. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2019 Edition. INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit DA' —0Z3 I PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project:_ Type of ection: Fire Alarm: Address: Suite #: )t-fcx S . \kti3lt Contac Person: & I - Special Instructions: Phone No.: Approved per applicable codes. Corrections required prior to approval. COMMENTS: A-Edde-ei Pa 1 / <27p=th,r-1-1 171-„s Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: , 1i Date: ¶h 9 i(4: Hrs.: I , t $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 6/11/10 T.F.D. Form F.P. 113 INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit _b_t_S- o z3( PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 206-575-4407 Project: Type of Inspection: ''t €A Fire Alarm: Address: / Suite #: / CraCX) cpsrr-K✓tL, 0-/ Contact Person: Special Instructions: 1 Phone No.: Approved per applicable codes. COMMENTS: Corrections required prior to approval. /S /AlS 4, LA,0 )t aLo'S U. i . re_21 Lit/ Crri-741e- Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: L y7-711 S�,.. Date: A)/2.1 //I Hrs.: O $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. CaII to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 3/14/14 T.F.D. Form F.P. 113 3 INSPECTION NUMBER INSPECTION RECORt Retain a copy with permit Deb— OZ�/ PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 206-575-4407 Project: 5-Thrhiq. Sprinklers: Type of Inspection: ipzoa //.4 Address: Suite #: /V600 s7 Occupancy Type: r,e toot -t/ Contact/Person: Special Instructions: Phone No.: riApproved per applicable codes. COMMENTS: Corrections required prior to approval. � g&ics %''7 Eyd4a /7i94 tuQat- ukele4�Sr,� - �*L 2 char ieo� — ,G,en QST 06Gtea Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: f ,-Ai ? Date: A5/74// 1 Hrs.: J 1 $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. CaII to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 3/14/14 T.F.D. Form F.P. 113 INSPECTION RECORD Retain a copy with permit INSPECTION NUMBER PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 206-575-4407 Project: Type of Inspection: -fftu_Nto,,t, Address:Contact '',...5)--h-r-a, Person: T' Suite #: / oo V v tcl Special Instructions: Phone No.: pproved per applicable codes. Corrections required prior to approval. COMMENTS: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: 4-C,G6/ / i4 _ � s — Mar ' ,1€54, g - c L -2-1 --' ®i/ID WI l/ s7/111 1 S A - ere_. /t/,Pct 72_ c 'kA /yew e'ki -. /a — G'i91/ %r /rirreerl wl(4 / fir /4 - mgr /<" k, Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: , f v7 S^'2.1 Date: g)Zo) f (4 Hrs.: (. 0 $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. CaII to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 3/14/14 T.F.D. Form F.P. 113 INSPECTION RECORD Retain a copy with permit INSPECTION NUMBER PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 206-575-4407 Project: Sprinklers: Fire Alarm: Type of Insp ion: Address: Suite #: /7�,� � / e l/ Contact Per n: Special Instructions: Phone No.: K Approved per applicable codes. Corrections required prior to approval. COMMENTS: ---Thi Aim& e) Ivi;k0 /� l ii&AdAdf twid �,ae Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector:'(. 11%1 ` j Date: WO/ Hrs.: Z 4 $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspecton. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 3/14/14 T„F.D. Form F.P. 113 v `�, CORRECTION NOTICE/REINSPECTION FEE Inspector: / , r ` c`'/, Permit number: TUKWILA FIRE MARSHAL'S OFFICE Office: 206-575-4407 Fax: 206-575-4439 Email: Fire Marshal na tukwilawa.sov Business Name:hi/PM-it-L' Jo) re- Type of Inspection: 5f4 T-- Location �idres OD 6 RN- F/ z Date : (Wf Contact Person :?\______.101.e.,,, izzdPhone ez-- o.: 60A) ACTION REQUIRED iY19�i� ONl 3b" ce,C-'h2_ /•\J F(1-oDJ?—�� ez-- PA90\16--5, p,09-1/4-7 57)21/9(A/67 60A) pL6d cz___ 70 Pevxfl f7z,fZ GIc-iiN t 6K1/17AJ Gylr&)lYe'2-s Ui\J OeYZ Sv„�!� 6e7/1/Vi l'`''(---7 filv\q'( / r CORRECTION OF THE ABOVE ITEMS ARE REQUIRED BY : FAILURE TO COMPLY MAY RESULT IN THE ISSUANCE OF A CRIMINAL CITATION/TICKET. Signature: Billing/Mailing Address : Attn: Company Name: Address: City: State: Zip: ❑ A $100.00 Reinspection Fee is required. You will receive an invoice from the City of Tukwila Finance Department. ❑ Ticket Issued. Citation # Correction Notice Reinsp Fee2.doc Revised 6/17/14 T.F.D. Form F.P. 100 ign. 0/(1) (rte-�-�� • Ogg S(3-red4 ru INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 206-575-4407 Project: �� Fire Alarm: Type of Ins ectioR: Type Ou Address:Contact Suite #: /4 d 6 ST4.12,6/!, " erson: Special Instructions: .k,ZM Phone No.: d/r Approved per applicable codes. Corrections required prior to approval. COMMENTS: F-0 `lam 119 TO by sp 42_ S SA/ ` Fit9- f71 -c Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: 4 E l7 '-,4,--- Date: "7/s/ jq_ Hrs.: i $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 3/14/14 T.. F.D. Form F.P. 113 INSPECTION NUMBER INSPECTION RECORD h i permit a copy with pe t j 7 — 0 S PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 206-575-4407 ZtlittleerProject:/�Type S d ?"-a.� of Ins ection: a.70 f& 3-- Address:> Suite #: ! r,e3G ,574)i- i- ei ✓"t" Willi Contact Person: Special Instructions: .7(--2,0. Phone No.: Approved per applicable codes. nCorrections required prior to approval. COMMENTS: Pcssex.d ckr� C irrge,1-v.-, N t74 ( / SSvt-e-g'( 11 Garr /SSS h y / /Z / 7 Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: ;yyl S 3) Date: W57/ 7 Hrs.: /.. d / $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 3/14/14 T.F.D. Form F.P. 113 INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 206-575-4407 Projept : vb «C-:5 A. C. . Type of I spection: tea.Tr< Ti* Address: j 44 80 ?kcrct*." \),-.)c.: Suite #: Contact Person: Special Instructions: Phone No.: Approved per applicable codes. Corrections required prior to approval. C Needs Shift Inspection: /COMMENTS: • \-4 ft ✓t c k L... n ik ' M A cAk.a 4 P oU.- Ott" & 01N`� w\\\ "+`\b\.+4 J 10k -s► c.t , r1.4 (S' "64- Prov t A uvLttb PY1oyw...1_, DEs_Q% s a.c-G-„,... k-u,A 31.,,-. &Owr Q d„\ sds , A CV,�.�Zo r.. \--\A_...., \c.4\64 A c %c` So ynNake, pv.� IA ,.r 4' 's s. D.A.€ Lo . k A.c GJvk�tKv-C.1 h 1/4.,,,N Pre -Fire: ,r-). Com\\ 4r ""-si W4r� It PL . Permits: -Qv 0► caw. .44 R -VD g g.L \\ L<.'. v, IA. o L 5..rksr co., " c Occupancy Type: 'ncrn @ Nsuz COI AA -e- /vt R,br.+~Y, cs1/4(. — as 3 - 3 e 0 -5 2-( 0 C Needs Shift Inspection: Sprinklers: t j �S Fire Alarm: PY1oyw...1_, Hood & Duct: Y cot Monitor: Pre -Fire: Permits: , p , Occupancy Type: A - Inspector:. �crv151 Date: $1 Z`1 \ vi... Hrs.: \ O $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 3/14/14 T.F.D. Form F.P. 113 INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 206-575-4407 Project: 9..... -- Type of Inspection: F-7 Address: Suite #: 1 �d salt., 1A -M1 Contact Person: Special Instructions: Phone No.: Approved per applicable codes. Corrections required prior to approval. COMMENTS: Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: *K. 5-4—A-2.---- Date: t thii 4,. Hrs.: $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 3/14/14 T.F.D. Form F.P. 113 i -S-07C REVIEWED THE FPI CONSORTIUM, INC. XNo Comments/No Exceptions Taken Make Corrections As Noted Revise and Resubmit Reviewed for general conformance with the Design Basis. This review is not inten to uthorize•any workpiyt' jpw 1papia with Code. ARCHER CONSTRUCTION, INC. By: Date ti_V/.V! y 7855 S. 206th STREET KENT,WA 98032 HYDRAULIC CALCULATIONS FOR STARFIRE Sports Complex 14800 Starfire Way Tukwila, WA. 98188 REVISED 4-5-19 Carl Anderson PE DRAWING NUMBER: FP -1 DATE: APR 5, 2019 -DESIGN DATA - REMOTE AREA LOCATION:LOWER LVL NW CORNER REMOTE AREA NUMBER:1 Digitally signed by Carl Anderson, PE 019.04.09 14:4': 7-07'00' OCCUPANCY CLASSIFICATION: OHG I DENSITY:.15 gpm/sq. ft. AREA OF APPLICATION: 1740 sq. ft. COVERAGE PER SPRINKLER:324 sq. ft. TYPE OF SPRINKLERS CALCULATED:K-11.2 EC NUMBER OF SPRINKLERS CALCULATED: 7 *IN -RACK SPRINKLER DEMAND: NA gpm HOSE -STREAM DEMAND:250 gpm TOTAL WATER REQUIRED (INCLUDING HOSE): 605.3 gpm FLOW AND PRESSURE (AT CITY): 605.3 gpm @ 125.2 psi TYPE OF SYSTEM:WET *VOLUME OF DRY OR PREACTION SYSTEM: *DETAILS: WATER SUPPLY Source: CITY Test Date: Test By: Location: Static: 142 psi Residual: 20 psi Flow: 5000.0 gpm Source Elevation Relative to Finished Flow Level: INSTALLING CONTRACTOR Name: Address: Phone: Certification number: NAME OF DESIGNER:MIKE AUTHORITY HAVING JURISDICTION:CITY OF TUKWILA NOTES:Per NFPA 13 13.1 Miscellaneous Storage to 12' Class I Calculations performed by HASS under license # 16031162 granted by HRS SYSTEMS, INC. (Notes continue after pipe calculations results.) ft. SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 4/5/2019 F:\MIKEPC\HASS DATA\STARFIRE TI EC.SDF JOB TITLE: STARFIRE GROUND LEVEL TI WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) CITY 142.0 20.0 5000.0 139.5 605.3 125.2 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 605.3 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 250.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 355.3 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) CITY 0.0 SOURCE 125.2 355.3 1 8.0 K=11.20 19.1 49.0 2 8.0 K=11.20 19.5 49.4 3 8.0 K=11.20 20.3 50.4 4 8.0 K=11.20 20.0 50.1 5 8.0 K=11.20 20.4 50.5 6 8.0 K=11.20 21.2 51.6 7 8.0 K=11.20 23.4 54.2 100 8.0 - - - - 20.8 - - - 101 8.0 21.7 101A 8.0 24.3 102 8.0 60.5 103 8.0 71.5 104 8.0 110.4 105 8.0 113.7 TOR 8.0 115.5 HDR 4.0 118.2 BF1 3.0 123.7 BF2 3.0 118.7 UG 1.0 124.6 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 4/5/2019 F:\MIKEPC\HASS DATA\STARFIRE TI EC.SDF JOB TITLE: STARFIRE GROUND LEVEL TI PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -49.0 2.229 PL 18.00 PF 0.3 1 8.0 11.2 19.1 49.0 4.0 120 FTG ---- PE 0.0 2 8.0 11.2 19.5 49.4 0.017 TL 18.00 PV Pipe: 2 -98.4 2.229 PL 6.25 PF 1.3 2 8.0 11.2 19.5 49.4 8.1 120 FTG T PE 0.0 100 8.0 0.0 20.8 0.0 0.063 TL 20.69 PV Pipe: 3 -50.4 2.229 PL 11.75 PF 0.5 3 8.0 11.2 20.3 50.4 4.1 120 FTG T PE 0.0 100 8.0 0.0 20.8 0.0 0.018 TL 26.19 PV Pipe: 4 -50.1 2.229 PL 18.00 PF 0.3 4 8.0 11.2 20.0 50.1 4.1 120 FTG ---- PE 0.0 5 8.0 11.2 20.4 50.5 0.018 TL 18.00 PV Pipe: 5 -100.6 2.229 PL 6.25 PF 1.4 5 8.0 11.2 20.4 50.5 8.3 120 FTG T PE 0.0 101 8.0 0.0 21.7 0.0 0.066 TL 20.69 PV Pipe: 5A -51.6 2.229 PL 11.75 PF 0.5 6 8.0 11.2 21.2 51.6 4.2 120 FTG T PE 0.0 101 8.0 0.0 21.7 0.0 0.019 TL 26.19 PV Pipe: 5B -54.2 2.229 PL 24.25 PF 0.8 7 8.0 11.2 23.4 54.2 4.5 120 FTG T PE 0.0 101A 8.0 0.0 24.3 0.0 0.021 TL 38.69 PV Pipe: 6 -148.8 2.703 PL 18.00 PF 1.0 100 8.0 0.0 20.8 0.0 8.3 120 FTG ---- PE 0.0 101 8.0 0.0 21.7 0.0 0.053 TL 18.00 PV Pipe: 7 -301.1 2.703 PL 13.00 PF 2.5 101 8.0 0.0 21.7 0.0 16.8 120 FTG ---- PE 0.0 101A 8.0 0.0 24.3 0.0 0.195 TL 13.00 PV Pipe: 7A -355.3 2.703 PL 118.00 PF 36.3 101A 8.0 0.0 24.3 0.0 19.9 120 FTG T PE 0.0 102 8.0 0.0 60.5 0.0 0.266 TL 136.65 PV Pipe: 8 -355.3 2.703 PL 35.00 PF 10.9 102 8.0 0.0 60.5 0.0 19.9 120 FTG L PE 0.0 103 8.0 0.0 71.5 0.0 0.266 TL 41.22 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 4/5/2019 F:\MIKEPC\HASS DATA\STARFIRE TI EC.SDF JOB TITLE: STARFIRE GROUND LEVEL TI PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 9 -355.3 2.703 PL 128.00 PF 38.9 103 8.0 0.0 71.5 0.0 19.9 120 FTG T PE 0.0 104 8.0 0.0 110.4 0.0 0.266 TL 146.65 PV Pipe: 10 -355.3 2.703 PL 6.00 PF 3.2 104 8.0 0.0 110.4 0.0 19.9 120 FTG L PE 0.0 105 8.0 0.0 113.7 0.0 0.266 TL 12.22 PV Pipe: 11 -355.3 4.310 PL 41.00 PF 1.8 105 8.0 0.0 113.7 0.0 7.8 120 FTG 3L PE 0.0 TOR 8.0 0.0 115.5 0.0 0.027 TL 66.09 PV Pipe: 12 -355.3 4.310 PL 9.00 PF 1.0 TOR 8.0 0.0 115.5 0.0 7.8 120 FTG T PE 1.7 HDR 4.0 0.0 118.2 0.0 0.027 TL 36.87 PV Pipe: 13 -355.3 4.310 PL 1.00 PF 0.0 HDR 4.0 0.0 118.2 0.0 7.8 120 FTG ---- PE 0.4 BF2 3.0 0.0 118.7 0.0 0.027 TL 1.00 PV Pipe: 14 FIXED PRESSURE LOSS DEVICE BF1 3.0 0.0 123.7 0.0 5.0 psi, 355.3 gpm BF2 3.0 0.0 118.7 0.0 Pipe: 15 -355.3 4.310 PL 2.00 PF 0.1 BF1 3.0 0.0 123.7 0.0 7.8 120 FTG ---- PE 0.9 UG 1.0 0.0 124.6 0.0 0.027 TL 2.00 PV Pipe: 16 -355.3 6.280 PL 10.00 PF 0.2 UG 1.0 0.0 124.6 0.0 3.7 140 FTG TG PE 0.4 CITY 0.0 SRCE 125.2 (N/A) 0.003 TL 62.00 PV NOTES (HASS): (1) Calculations were performed by the HASS 8.8 computer program in accordance with NFPA13 (2016) under license no. 16031162 granted by HRS Systems, Inc. 208 Southside Square Petersburg, TN 37144 (931) 659-9760 (2) The system has been calculated to provide an average imbalance at each node of 0.005 gpm and a maximum imbalance at any node of 0.096 gpm. SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 4/5/2019 F:\MIKEPC\HASS DATA\STARFIRE TI EC.SDF JOB TITLE: STARFIRE GROUND LEVEL TI (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 19.9 ft/sec at pipe 10. (4) Items listed in bold print on the cover sheet are automatically transferred from the calculation report. (5) Available pressure at source node CITY under full flow conditions is 139.38 psi with a flow of 627.61 gpm. (6) PIPE FITTINGS TABLE HASS Pipe Table Name: standard.pip PAGE: * MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N E11 Tee LngEll ChkVly BfyVly GatVly AlmChk DPVly NPTee 2.229 7.22 14.44 4.33 15.88 8.66 1.44 14.44 14.44 14.44 2.703 9.33 18.65 6.22 21.76 10.88 1.55 15.54 15.54 18.65 4.310 13.94 27.87 8.36 30.66 16.72 2.79 27.87 27.87 27.87 PAGE: D MATERIAL: DIRON HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G N Ell Tee LngEll ChkVly BfyVly GatVly NPTee 6.280 22.00 47.00 14.00 51.00 16.00 5.00 47.00 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 4/5/2019 F:\MIKEPC\HASS DATA\STARFIRE TI EC.SDF JOB TITLE: STARFIRE GROUND LEVEL TI WATER SUPPLY ANALYSIS 160.0 140 1AL 2A? G120.0 A U G100.0 E P 80.0 R E 60.0 S S U 40.0 R E 20.0 p 1 0.0 -14.7 Static: 142.00 psi Resid: 20.00 psi Flow: 5000.0 gpm LEGEND 1111 Available pressure 139.55 psi @ 605.3 gpm 2 II Required pressure 125.24 psi @ 605.3 gpm 1A1110 Avail. OnSite Demand Press. 139.55 psi @ 355.3 gpm Req. OnSite Demand Press. 125.24 psi @ 355.3 gpm A. Source Supply Curve B. System Demand Curve C. Available at Source 2A 1111011. 111.M111.1111111111 I000E1 IMO, tall,,, ll huM1 •NMal IMNI aO11ISI hall hal 1 1 1 1 1 1 1 1 10C150C2000 2500 3000 3500 4000 4500 5000 FLOW (GPM) Note: (1) Dashed Lines indicate extrapolated values from Test Results (2) On Site pressures are based on hose stream deduction at the source SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 4/5/2019 F:\MIKEPC\HASS DATA\STARFIRE TI EC.SDF JOB TITLE: STARFIRE GROUND LEVEL TI WATER SUPPLY CURVE 144+ *0 I\ 132+ \ I \ IX \ I \ 120+ \ I \ I \ 1 108+ \ 1 1 1 P 96+ \ R I \ E I S I \ S 84+ \ u 1 \ R I \ E I \ 72+ \ ( I P 1 \ s 1 \ 160+ 1 1 1 48+ \ 1 1 1 36+ 1 1 1 24+ LEGEND \ " * <-20.0 psi @ 5000 gpm 1 X = Required Water Supply "Flow Test Point 1 125.24 psi @ 605.3 gpm " 12+ I 0 = Available Water Supply I 139.55 psi @ 605.3 gpm SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 4/5/2019 F:\MIKEPC\HASS DATA\STARFIRE TI EC.SDF JOB TITLE: STARFIRE GROUND LEVEL TI 0++-+---+----+ + + + + + + 16002400 3200 4000 4800 5600 6400 7200 8000 FLOW (GPM) Size and Type of Pipe TOLBraceTM Seismic Calculations Project Address: Starfire 14800 Starfire Way Tukwila, WA 98188 Job # S19-24 Archer Construction,Inc. 7855 So 206th St Kent, WA 98032 Carl Anderson, 253-872-7222 ARCHEI-219*DR Calculations based on 2013 NFPA Pamphlet #13_ de INC s Takrn lly Dg:And r,ne +TioN Can Anderson. - PE Date: 2019 04 09 q 14:454607'00' Powth1t&%ars REVIEWED EFCONSORTIUM, XTNEcP _ epn',r __ Moire Corrections As Noted Revise and Resubmit .. ey 'A-- agate:` 472d19- Brace Information 2" Sch.7 Steel Pipe (50.8 mm) TOLCOTM Brace Components Maximum Spacing 25' 0" (7.62 m) Maximum Brace Length T 0" (2.13 m) Bracing Material 1" Sch.40 Angle from Vertical 60° Min. Least Rad. of Gyration 0.42" (11 mm) L/R Value 200 Max Horizontal Load 1604 lbs (728 kg) Force Factor (Cp) 0.68 — TOLCOTM Component Fig. Number Adjusted Load Fig. 1001 Clamp 1386 lbs (629 kg) Fig.980 Universal Swivel 1745 lbs (792 kg) 'Calculation Based on CONCENTRIC Loading *Please Note: These calculations are for TOLCOTM components only. Use of any other components voids these calculations and the listing of the assembly. Assembly Detail TOLCO FIG. 981 UNIVERSAL SWAY BRACE ATTACHMENT STEEL PIPE 0 Fastener Information 15% "`4• / Fastener Orientation Maximum Load Diameter Length Type NFPA Type C 970 lbs (440 kg) 1/2" 3-1/4" Embed Wedge Anchor TOLCO FIG. 1001f/f. FAST CLAMP �♦' / / e Brace Identification on Plans 1 (alt) Orientation of Brace Lateral Size and Type of Pipe 1 Total Length 1 Total Calculated Load 2.5" Sch.7 Steel Pipe (63.5 mm) 25ft (7.6 m) 87 lbs (39 kg) 2" Sch.7 Steel Pipe (50.8 mm) 164ft (50 m) 423 lbs (192 kg) Percentage added for Fittings and Sprinklers 15% 76 lbs (34.48 kg) Total Adjusted Load of all pipe within Zone of Influence 586 lbs (266 kg) {TOLBraceT'" Version 8) Use of TOLBrace-m is subject to terms and conditions per the end user license agreement TOLBrac&' Seismic Calculations Starfire 14800 Starfire Way Brace Identification Brace Type (Per NFPA#13) Braced Pipe Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # 519-24 1 (alt) NFPA Type C 2.5" Sch.7 Steel Pipe 25' 0" (7.62 m) Lateral 1" Sch.40 7'0"(2.13m) 200 60° Wedge Anchor 3-1/4" Embed Summary of Pipe within Zone of Influence Er AT N 2.5" Sch.7 Steel Pipe (63.5 mm) 25ft (7.6 m) T Sch.7 Steel Pipe (50.8 mm) 1648 (50 m) G -Factor Used 0.68 Allowance for Heads and Fittings Conclusions Total Adjusted Load of Pipe in Zone of Influence Material Capacity Fastener Capacity Fig. 1001 Clamp Fig.980 Universal Swivel Structural Member 15% 586 lbs (266 kg) 1604 lbs (728 kg) 970 lbs (440 kg) 1386 lbs (629 kg) 1745 lbs (792 kg) Concrete Deck Calculations prepared by Queen * The description of the Structural Member is for informational purposes only. TOLBrace" software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBrace'" 8 Visit us at www.tolco.com Size and Type of Pipe Total Length Total Calculated Load TOLBraceTM Seismic Calculations Project Address: Starfire 14800 Archer Construction,lnc. 7855 So 206th St Kent, WA 98032 253-872-7222 8 imsst?d� e ARCHEI-219*DR on 2013 NFPA Pamphlet #13 Starfire Way Tukwila, WA 98188 Job # S19-24 Calculations based Brace Information TOLCOTM Brace Components Maximum Spacing Maximum Brace Length Bracing Material Angle from Vertical Least Rad. of Gyration L/R Value Max Horizontal Load Force Factor (Cp) 25' 0" (7.62 m) TOLCOTM Component Fig. Number Adjusted Load Fig. 1001 Clamp 866 lbs (393 kg) Fig.980 Universal Swivel 1745 lbs (792 kg) *Calculation Based on CONCENTRIC Loading *Please Note: These calculations are for TOLCOT'" components only. Use of any other components voids these calculations and the listing of the assembly. T 0" (2.13 m) 1" Sch.40 60° Min. 0.42'1(11 mm) 200 Assembly TOLCO UNIVERSAL SWAY ATTACHMENT STEEL Detail FIG. 981 BRACE 1604 lbs 728 k• 0.68 PIPE ',I ' - 4 Fastener Information '°it Fastener Orientation` Maximum Load Diameter Length Type NFPAType C 970 lbs 440 k. TOLCO FIG. 10013' FAST CLAMP 4 /4'. '. ;' `, +i 1/2" 3-1/4 Embed Wedge Anchor Brace Identification on Plans 1 Orientation of Brace Lateral Size and Type of Pipe Total Length Total Calculated Load 2" Sch.7 Steel Pipe (50.8 mm) 25ft (7.6 m) 64 lbs (29 kg) 2" Sch.7 Steel Pipe (50.8 mm) 98ft (29.9 m) 253 lbs (115 kg) Percentage added for Fittings and Sprinklers 15% 48 lbs (21.78 kg) Total Adjusted Load of all pipe within Zone of Influence 365 Ibs (166 kg) {TOLBraceT" Version 8} Use of TOLBracem is subject to terms and conditions per the end user license agreement TOLBrace' Seismic Calculations Starfire 14800 Starfire Way Brace Identification Brace Type (Per NFPA#13) Braced Pipe Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # S19-24 1 NFPA Type C 2" Sch.7 Steel Pipe 25' 0" (7.62 m) Lateral 1" Sch.40 7'0"(2.13 m) 200 60° Wedge Anchor 3-1/4 Embed Summary of Pipe within Zone of Influence Pow;flog Saslow:S? 2" Sch.7 Steel Pipe (50.8 mm) 25ft (7.6 m) 2" Sch.7 Steel Pipe (50.8 mm) 98ft (29.9 m) G -Factor Used 0.68 Allowance for Heads and Fittings Conclusions Total Adjusted Load of Pipe in Zone of Influence Material Capacity Fastener Capacity Fig. 1001 Clamp Fig.980 Universal Swivel Structural Member 15% 365 lbs (166 kg) 1604 lbs (728 kg) 970 lbs (440 kg) 866 lbs (393 kg) 1745 lbs (792 kg) Concrete Deck Calculations prepared by Queen * The description of the Structural Member is for informational purposes only. TOLBraceTM software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBraceTM 8 Visit us at www.tolco.com Size and Type of Pipe TOLBraceTM Seismic Calculations Project Address: Starfire Archer Construction,Inc. 7855 So 206th St Kent, WA 98032 Ei oN 253-872-7222 ttow� a+ r e ARCHEI-219*DR on 2013 NFPA Pamphlet #13 14800 Starfire Wa Tukwila, WA 98188 Job # S19-24 Calculations based Brace Information TOLCOTM Brace Components Maximum Spacing Maximum Brace Length Bracing Material Angle from Vertical Least Rad. of Gyration UR Value Max Horizontal Load Force Factor (Cp) 80' 0" (24.38 m) TOLCOTM Component Fig. Number Adjusted Load Fig. 4A Clamp 707 lbs (321 kg) Fig.980 Universal Swivel 1425 lbs (646 kg) *Calculation Based on CONCENTRIC Loading *Please Note: These calculations are for TOLCOT" components only. Use of any other components voids these calculations and the listing of the assembly. 7' 0" (2.13 m) 1" Sch.40 45° Min. 0.42"111 mm) Assembly TOLCO SWAY ATTACHMENT STEEL TOLCO FIG. 4A PIPE CLAMP FOR SWAY BRACING r- — i FIG. Detail 981 BRACE TYP. PIPE *I I 4.` 200 1310 lbs(594 kg)UNIVERSAL 8 0.68 Fastener Information Fastener Orientation Maximum Load Diameter Length Type NFPAT •e B 467 lbs(212 k g) 1/2" 3-1/4" Embed Wedge Anchor Brace Identification on Plans 2 Orientation of Brace Longitudinal Size and Type of Pipe Total Length Total Calculated Load 2.5" Sch.10 Steel Pipe (63.5 mm) 80ft (24.4 m) 320 lbs (145 kg) Percentage added for Fittings and Sprinklers 15% 48 lbs (21.78 kg) Total Adjusted Load of all pipe within Zone of Influence 368 lbs (167 kg) {TOLBracen, Version 8} Use of TOLBracen, is subject to terms and conditions per the end user license agreement TOLBraceTM Seismic Calculations Starfire 14800 Starfire Way Brace Identification Brace Type (Per NFPA#13) Braced Pipe Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # S19-24 2 NFPA Type B 2.5" Sch.10 Steel Pipe 80' 0" (24.38 m) Longitudinal 1" Sch.40 7'0"(2.13m) 200 45° Wedge Anchor 3-1/4" Embed Summary of Pipe within Zone of Influence Po wrmq &dints tilt:4 Ode 2.5" Sch.10 Steel Pipe (63.5 mm) 80ft (24.4 m) G -Factor Used 0.68 Allowance for Heads and Fittings Conclusions Total Adjusted Load of Pipe in Zone of Influence Material Capacity Fastener Capacity Fig. 4A Clamp Fig.980 Universal Swivel Structural Member 15% 368 lbs (167 kg) 1310 lbs (594 kg) 467 lbs (212 kg) 707 lbs (321 kg) 1425 lbs (646 kg) Concrete Deck Calculations prepared by Queen • The description of the Structural Member is for informational purposes only. TOLBrace"" software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBraceTM 8 Visit us at www.tolco.com ACE FIRE & SECURITY SYSTEMS A division of Alarm Center Inc. 4500 3rd Ave Lacey, WA 98503 TUKWILA FIRE DEPARTMENT Date: 08/04/2016 News ,call 236-5754407 and CITY OF TUKWILA give thi5 Fire Permit No. Fire Marshal's Office ic -1--/(00 6300 Southcenter Blvd and exact address for shut - Tukwila, WA 98188 down or restoration approval. RE: STARFIRE SPORTS MAINTENANCE 14800 Starfire Way Tukwila, WA. 98188 Parcel #2323049001 Ace Fire and Security Systems, a UL listed fire and secu Without Comments ❑ As Noted in Red ❑ Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which co nor authorize violations of adopted standards and ordinances The responsibility for the adequacy of design 'ests totally with the designer. Additions, deletions ,,..•evisions to these drawings after this date will void trtiS acceptance and will require a resubmittal of revises' drawings fa subsequent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: g ' / By: company, submits the following description of work to be done at the above listed location. Scope of Work We will be adding an AES 7788F fire alarm communicator to the existing FACP. Product is UL Fire and NFPA-72 compliant, and has built-in power supply and charger. Thank you for this opportunity. Point of Contact: Kara Morrow CAD/Permit Lead Ace Fire and Security 1 800 354 1555 x 6338 (360)481-4969 karat alarmcenterinc.com NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure. nf test will result in a Re -inspection Fee and termination of the testing This proposal is not a contract nor binding until our standard form agreement is executed and which will incorporate this proposal. ACE Fire & Security Systems • www.reachone.com/ace Street Address: 4500 Third Ave SE, Lacey, WA 98503 Mail Address: PO Box 3407, Lacey, WA 98509-3407 E-mail: acereachone.com • Fax: (360)438-4244 • Phone: 1 -800 -354 -MD Ai d+ —4 201b r UKWILAFRE 14800 STARFIRE WAY 16-F-160 _ Symbol Legend FIRE ALARM CONTROL PANEL FIRE ALARM POWER SUPPLY ANALOG/ADDRESSABLE CONTROL/NOTIFICATION MODULE s ANALOG/ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR ANALOG/ADDRESSABLE SINGLE ACTION MANUAL PULL STATION wall mount 0 48' A.F.F. to bottom of back box TOILE A,B&C;, 110cd 177 140cd A,B&C 8. SPEAKER/STROBE COMBINATION wall mount 0 80" A.F.F. to bottom of back box cd = candela rating of strobe light >orcd SPEAKER/STROBE COMBINATION ceiling mounted cd — candela rating of strobe light xrr:d STROBE UGHT wall mount 0 80" A.F.F. to bottom of back box cd = candela rating of strobe light WP xcd WEATHERPROOF HORN/STROBE COMBINATION �•� woll mount 0 80" A.F.F. to bottom of back box cd candela rating of strobe light -YAMEOLR END OF UNE DEVICE )TOR. SHOWER o INDICATES EXISTING DEVICE Flag Notes A,B&C 1 KITCHEN 101 RELOCATE EXISTING DEVICES, BACK BOX AND ASSOCIATED WIRE AS SHOWN. INSTALL NEW DEVICE, EXTEND EXISTING CIRCUITS AS SHOWN. ;EXISTING) SOCCER ARENA Wire Legend New Addition Fire Alarm Plan SIGNAL UNE CIRCUIT SPEAKER CIRCUIT STROBE CIRCUIT STROBE CIRCUIT (FEED/RETURN) (2) #18AWG. FPLR (FIRE RATED CABLE) (2) #12AWG. FPLR (FIRE RATED CABLE) (2) #12AWG. FPLR (FIRE RATED CABLE) (4) #12AWG. FPLR (FIRE RATED CABLE) Key Plan General Not SCALE: 1/8" = 1 — 0' AREA UNDER THIS PERMIT NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. 1. VERIFY ON SITE THAT THE EXISTNIG BACK UP BATTERIES AND CIRUITS HAVE THE CAPACITY TO ACCOMADATE THE ADDITIONAL DEVICE. EXISTING BUILDING Vicinity Map Without Comments As Noted In Red Per The Attached Letter FiLE CO 1 nese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and Ordinances. The responsibility for the �iequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter : thil datei�lill void thi .acceptance Rnd will require a resubmittal of revised drawings for subsequent approval. Final acceptance is -subject to field test and inspection b\ The Tukwila Fire Prevention Bureau. loate: /.)-// a-� 6 g By:.. SI f 1 GUKvP11.A FiRE DEPART:A t Please call: 575-440Z and give this job - .a3 -E -Sts and exact address for shut. PAID NOV 2 5 [U08 Tukwila Fire _.i/2& 33/. PROJECT NAME: Starfire Sports Complex 14800 Starfire Way Tukwila, WA 98188 'ATE: 11/19/08 .CALE: AS SHOWN SYSTEM TYPE: FIRE ALARM & DETECTION CONTRACTORSINALARPIICI055CW REVISION DRAWN BY: J.F. APPROVED BY: REVISION SHEET NO. A DIVISION OF ALARM CENTER, INC. PO BOX 3363 - LACEY WA 98509-3363 14800 STARFIRE WAY 08-F-518 Flag Notes (EXISTING) OFFICE 220 (EXISTING')( FFICE 210 (EXISTING) OFFICE (EXISTING) OFFICE 217 RELOCATE EXISTING DEVICES, BACK BOX AND ASSOCIATED WIRE AS SHOWN. INSTALL NEW DEVICE, EXTEND EXISTING CIRCUITS AS SHOWN. General Notes 1. VERIFY ON SITE THAT THE EXISTNIG BACK UP BATTERIES AND CIRUITS HAVE THE CAPACITY TO ACCOMADATE THE ADDITIONAL DEVICE. (E) J :110cd LOCKER RM. 216 (EXISTING) OFFICE 221 (E:.XISUNG) OPEN OFFICE 105 OFHCE 212 (EX: TING) OFFICE NICHE' ' COPY 110cd (E) OFFICE 212 KITCHEN / COPY 211 (EXISTING) OFFICE s>2s CONFERENCE RM. 205 CONFERENCE RM. 210 (EXISTING) OPEN OFFICE (EYIST;NG) SERVER RM. (EXISTING) RECEPTION 201 (EXISTING) CONFERENCE RM. SCALE: 1/8" = Key Plan PROJECT NAME: Starfire Sports Complex 14800 Starfire Way Tukwila, WA 98188 ATE: 11/19/08 'CALE: AS SHOWN DATE SYSTEM TYPE: FIRE ALARM & DETECTION CONTRACTORS ALARIVICI055CW REVISION A DMSION OF ALARM CENTER, INC. DATE DRAWN BY: J.F. APPROVED BY: REVISION PO BOX 3363 - LACEY WA 98509-3363 SHEET NO. FA2 NSF Farenhyt Model SD500-PS and SD500-PSDA Addressable Pull Station The SD500-PS is a single action addressable fire pull station, and the SD500--PSDA is a dual action addressable fire pull station. The SD500-PS/PSDA feature rugged metal construction. A term nal strip on back of the pull station allows interconnection of the pull station to the SLC loop of a Silent Knight analog/addressable fire alarm control panel. The SD500-PS/PSDA is designed for indoor use in non -explosive environments. The normally open initiating point contacts are gold-plated to avoid risk of corrosion. The SD500-PS/PSDA has been tested by UL for compliance to the requirements of the Americans with Disabilities ACT (ADA). Features • UL Listed • CSFM listed • ADA compliant • Key reset (Same key as Silent Knight enclosures) • Surface mount back box available • Terminals - accept up to 14 gauge wire • Extremely easy to operate • Corrosion -resistant gold-plated contacts. • Reflective label makes it easier to locate in low light Operation The SD500-PS single action pull stations are operated by a pull on the front pull cover of the station. The SD500-PSDA dual action pull stations are operated by lifting up an access plate and then pulling forward on the front cover of the pull station. A plunger switch, wired to a self contained addressable module, is released as the pull station opens to initiate the alarm. Once operated, the cover hangs down and can be seen up to 100 feet away. The pull station is reset by returning the front cover to the normal upright position and relocking the station with a reset key. The reset keys are the same keys used on Silent Knight enclosures. The SD500-PS/PSDA includes a status LED which blinks, indicating that the addressable module is communicating with the loop. The status LED lights continuously during an alarm. A dip switch on the addressable module is used to set the unique address. SILENT KNIGHT 7550 Meridian Circle Maple Grove. Mn 55369-4927 763-493-6455 1-500-325-0103 Fax: 763-493-7475 http://www.farenhyt.com Addressable Pull Station MEA 429-92-E Vol. 9 SD500-PS Spa WHIMS Operating Voltage: Standby Current: Alarm Current: Ambient Temperature: Mounting: 24VDC .55mA .55mA 32°F to 120°F (0°C to 49°C) Single gang box Optional Red Surface Mount Box PS-SMBB Dual Action Conversion Kit SD500-LK Included with SD500- PSDA or it can be ordered separately and used to convert SD500-PS to SD500-PSDAs (See illustration on back page.) P/N 350254, 09/02 Copyright © 2002 Silent Knight Dimensions .. s; , -• -.. .... ,..4:1;:. . A. ,i_.4 -11,-,-. r.,-.7:1-..' in- - t_C•77:5/.11..v.r.r men) r:g: I.. .1- .1 SLC Wiring ,Perr,117,42' SILENT KNIGHT SD500-LK Installation 7550 Meridian Circle, Maple Grove, MN 55369-4927 1-800-446-6444 or in Minnesota 763-493-6435 FAX: 763-493-6475 World Wide Web: http://www.farenhyt.com • Made in the U.S.A. MEA S"7114 53074; HIGH WATTAGE FIRE ALARM SPEAKER/ SELECT A -STROBE COMBINATION Designed to meet or exceed NFPA/ANSI Standards and ADA accessibility guidelines UL Listed for fire protective service • Field selectable taps from 2, 4, and 8 Watts UL Listed for wall or ceiling mount Available in 25V RMS and 70.7V RMS • Screw terminals capacity up to AWG12 • Frequency range 400 Hz - 4000 Hz • Two field selectable settings: 15 or 30 cd • Polarized strobes with wide listed voltage ranges using filtered or unfiltered FWR input voltage • Synchronization requires the SMD 10-3A Sync Module Amseco's high quality fire alarm speakers are designed to generate attention grabbing tones and voice commands for emergency signaling evacuation applications. These highly efficient speakers are available with field selectable taps from 2 - 8 Watts. The speakers are available in two input voltage models, 25V RMS and 70.7V RMS and can be installed on a standard 4" electrical back box with an extension ring. The SFH45-153075 Series features a new and exclusive select -a -strobe. The strobe utilized a unique candela intensity field selector switch for alternating the candela output from 15 to 30. The strobe housing is clearly labeled with "FIRE" lettering and is polarized for connecting to supervised fire alarm circuits. The strobe is designed with a xenon flash tube and provides a candela intensity field selector switch for maximum performance. They are available in red or white housing. The strobe can be synchronized by using the SMD10-3A Sync Module to comply with NFPA recommendations concerning photosensitive epilepsy when installing two or more visual appliances within the field of view. The strobe signals are listed for indoor use. ceiling and wall mount, under UL 1971 Standard. Ordering Information Model Number Stock Number Speaker Voltage (VAC) Strobe Voltage (VDC) Strobe Candela (Selectable) Selectable Wattage Flash Rate (Per Minute) Grille Type Grille Color SFH45-153075R-25S 4650006 25 24 15 or 30 2,4,8 60 Square Red SFH45-153075W-25S 4650010 25 24 15 or 30 2,4,8 60 Square White SFH45-153075R-25R 4650005 25 24 15 or 30 2,4,8 60 Round Red SFH45-153075W-25R 4650009 25 24 15 or 30 2,4,8 60 Round White SFH45-153075R-70S 4650008 70.7 24 15 or 30 2.4.8 60 Square Red SFH45-153075W-70S 4650012 70.7 24 15 or 30 2,4,8 60 Square White SF1-145-153075R-70R 4650007 70.7 24 15 or 30 2,4,8 60 Round Red SFF145-153075W-70R 4650011 70.7 24 15 or 30 2,4,8 60 Round White Engineering Specifications The fire alarm speaker shall be capable of reproducing alarm tones or voice commands on 25V RMS or 70.7V RMS. Speakers shall provide incremental tap settings of 2, 4, or 8 Watts and shall be selected by means of a jumper wire. The speaker shall have a frequency range of 400 - 4000 Hz and shall have an operating temperature between 14°F and 140°F. The speaker shall produce a UL sound pressure level at 10 feet up to 84dB. The speaker shall be approved for fire alarm signaling use. The strobe shall be listed under UL 1971 standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The candela ouput shall be field selectable, having a dual setting of 15/75cd or 30/120cd output. The signaling strobe shall operate on 24V DC from a non -coded regulated DC supply or full -wave rectified, unfiltered supply. It shall be designed to produce one signal flash per second with continuously applied minimim voltage. The SFH45-153075 shall be capable of wall or ceiling mounting. The visual signaling devices are to be installed in all non-sleeping/corridor areas as per plans and specifications. Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MKT. #8850032 - REV A PAGE 1 OF 2 5/06 A ®POTTER Brand Dimensions: inches (mm) 7-114 (1841 ; 45 w (1 75 HIGH WATTAGE FIRE ALARM SPEAKER/ SELECT A -STROBE COMBINATION 0 °. 0.0 1 CJ 5-1/2(141)) Mounting 118-32 SFFI-45-153075 SFI145-75110 Round SFN-45-153075 SF1145-75110 Square 4" Square Backbox 2 1/8" Deep Extension Ring 1 1/2" Deep Wiring Diagram SPEAKER STROBE TO NGKT DEVICE OIL END -OF -LINE RESISTOR 7 Multiple Tap Setting To select desired wattage (Fig. 1) using the change lead wire, set the desired output level (2, 4, and 8 Watt). * The unit is set at the factory to the 2 Watt position. Fig.1. SMD10-3A IN OUT + - - - TO NEXT DEVICE OR END -OF -LINO RESISTOR i ONe Multiple taps are provided for field wattage selection. To avoid electric shock, do not attempt to install wires when power is on. Rated Input Voltage (V RMS) 25V 70.7V Input Power (Watts) 2W 4W 8W 2W 4W 8W Impedance (Ohms) 310 156 78 2500 1250 620 Sound Pressure (dB/1 Oft) 90 93 96 90 93 96 Frequency Response (Hz) 400-4000 Low Frequency Cut-off (Hz) 200 Operating Temperature Range 32°F - 120°F (0°C - 49°C) Strobe Light Maximum RMS Current (mA) Regulated 24V DC (Typical) Regulated 24V DC/FWR (Typical) 1Scd 115 (S3) 162(117) 3Ocd 172(112) 232(155) PRINTED IN USA MKT. 48050032 - REV A 5/06 PAGE 2 OF 2 SL24W-75110 SELECT A -STROBE MEA Meets or exceeds NFPA/ANSI Standards and ADA Accessibility Guidelines • UL Listed for wall mounting • Screw terminal capacity up to AWG12 • Universal mounting plate included 24V DC strobe with two field selectable settings: 75cd or 110cd • Polarized strobes with wide operating voltage range using filtered DC or unfiltered FWR input voltage • Mounts to 4" square, single gang. double gang, or octagonal back box • Tamper -proof candela selector switch • Synchronization requires Sync Module (SMD10-3A) • Available in red or white housing Amseco's Select -A -Strobe Series is designed to comply with the Americans with Disabilities Act (ADA) and meet UL standard 1971 requirements for emergency signaling devices for the hearing impaired. The Select -A -Strobe SL24W series features a unique candela intensity field selector switch for alternating the candela output 75cd to 110cd. The strobe housing is clearly labeled with vertical "FIRE" lettering. The strobe is polarized for connecting to supervised fire alarm circuits and is designed with a xenon flashtube to provide maximum performance with a candela intensity field selector switch. The SL24W-75110 can be synchronized by using the SMD10-3A Sync Module to comply with NFPA recommendations concerning photosensitive epilepsy when installing two or more visual appliances within the field of view. The strobe signals are listed for indoor use, wall mount, under UL 1971 standard. Ordering Information Model Number Stock Number Housing Color Input Voltage Operating Voltage Range Selectable Strobe Output Flash Rate Wiring Type Mounting Type Operating Temperature Range SL24W-75110R 4560019 Red Regulated 24V DC/FWR 16 - 33V DC 16 33V FWR 75cd or 110cd 60 times' min. emu Tnals Wall Mount 32°F - 120°F (0°C - 49°C) SL24W-75110W 4560020 White Engineering Specifications The visual alarm indicating appliance shall be Amseco model SL24W-75110 or equivalent device. The strobe shall be listed under UL 1971 standard for signaling devices for the hearing impaired and shall be approved for fire protective service. For outdoor applications and in UL NEMA -4X rated or UL Haz Dust Tight condition, use Amseco UL/ULC ESH1229/1229HTR polycarbonate covers. The candela output shall be field selectable, having a dual setting of 75cd or 110cd output. The signaling strobe shall operate on 24V DC from a non -coded regulated DC supply or full -wave rectified, unfiltered supply. The strobe shall be designed to produce one signal flash per second with continuously applied minimum voltage. The strobe shall have a universal back mounting plate, capable of wall mounting to a back box. When strobe synchronization is required. the strobe shall be compatible with Amseco SMD 10-3A (daisy chain) or other source of Amseco sync protocol. Visual signaling devices shall be installed in accordance with current NFPA guidelines. Strobes must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted circuits in which the applied voltage is interrupted ON and OFF as the strobe may fail to flash. The applied voltage must be within its rated input voltage range. Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits. Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersienal.com PRINTED IN USA MKT. 08850014 - REV 6 PAGE 1 OF 2 9107 A L) POTTER Brand SL24F 7- 51110 SELECT A -STROBE Installation Single Gang Box SL24W Ur ivcrsal Mounting Plate 4" Square Back Box SL.24W Universal )Mounting Plate Double Gang Boz SL24W Universa] Mounting Plate ABX -1 SL24N Dimensions: inches (mm) 5 (127) J//(\r1P 7L \i 2 I/4 (5(.9) \� WALL ffS Cornpouod 46 Wiring Diagram lu Near Device or Ind-of-Liuo Resistor Wiring 2 Wiring Diagram using are Sync Module lS .1D10 -3A) F.A.C.P. sin..! relent + - SYNC MODULE SMD10-3A DIPtTT I I 1 I OUTPUT LI+ 1-1- + - + - "1111111Mommorr 10 Next Uc 0e or End, f -Lac kesislor -MN Strobe Light Specifications Max. RMS Operating Current Regulated. 24V DC Regulated 24V FWR 75cd 137 (typical 90) 190 (typical 135) 110cd 189 (typical 120) 256 (typical 172) Sound Output Dispersion Horizontal dB Vertical dB 24V DC (mA) +90 -6 -3 120 +60 -2 -2 ../L] +30 -1 -1 67.50 0 0 0 30 -30 -1 -3 99.00 -60 -2 -5 48.75 -90 -6 -6 Under ULC ULC Current at 525/526 24V DC (mA) 75cd 93 ll0cd 120 UL Required Minimum Light Output Horizontal Vertical cri N ". 75 cd 1lOcd 75cd 110cd 0 75.00 110.00 75.00 110.00 5-25 67.50 99.00 67.50 99.00 30 56.25 82.50 67.50 99.00 35 56.25 82.50 48.75 71.50 40 56.25 82.50 34.50 50.60 45 56.25 82.50 25.50 37.40 50 41.25 60.50 20.25 29.70 55 33.75 49.50 16.50 24.20 60 30.00 44.00 13.50 19.80 65 26.25 38.50 12.00 17.60 70 26.25 38.50 11.25 16.50 75 22.50 33.00 9.75 14.30 80 22.50 33.00 9.00 13.20 85-90 18.75 27.50 9.00 13.20 Compound 45 18.00 26.40 - - PRINTED IN USA MKT. #8850014 - REV B 9/07 PAGE 2 OF 2 Farenhyt Model SD500-PS and SD500-PSDA Addressable Pull Station The SD500-PS is a single action addressable fire pull station, and the SD500--PSDA is a dual action addressable fire pull station. The SD500-PS/PSDA feature rugged metal construction. A terminal strip on back of the pull station allows interconnection of the pull station to the SLC loop of a Silent Knight analog/addressable fire alarm control panel. The SD500-PS/PSDA is designed for indoor use in non -explosive environments. The normally open initiating point contacts are gold-plated to avoid risk of corrosion. Tie SD500-PS/PSDA has been tested by UL for compliance to the requirements of the Americans with Disabilities ACT (ADA). Features • UL Listed • CSFM listed • ADA compliant • Key reset (Same key as Silent Knight enclosures) • Surface mount back box available • Terminals - accept up to 14 gauge wire • Extremely easy to operate • Corrosion -resistant gold-plated contacts. • Reflective label makes it easier to locate in low light Operation The SD500-PS single action pull stations are operated by a pull on the front pull cover of the station. The SD500-PSDA dual action pull stations are operated by lifting up an access plate and then pulling forward on the front cover of the pull station. A plunger switch, wired to a self contained addressable module, is released as the pull station opens to initiate the alarm. Once operated, the cover hangs down and can be seen up to 100 feet away. The pull station is reset by returning the front cover to the normal upright position and relocking the station with a reset key. The reset keys are the same keys used on Silent Knight enclosures. The SD500-PS/PSDA includes a status LED which blinks, indicating that the addressable module is communicating with the loop. The status LED lights continuously during an alarm. A dip switch on the addressable module is used to set the unique address. ElSILENT KNIGHT a,. 7550 Meridian Circle Maple Grove, Mn 55369-4927 763-493-6455 1-800-326-0103 Fax: 763-493-7475 http://www.farenhyt.com Addressable Pull Station MEA 429-92-E Vol. 9 SD500-PS Sp cifications Operating Voltage: Standby Current: Alarm Current: Ambient Temperature: Mounting: 24VDC .55mA .55mA 32°F to 120°F (0°C to 49°C) Single gang box Optional Red Surface Mount Box PS-SMBB Dual Action Conversion Kit SD500-LK Included with SD500- PSDA or it can be ordered separately and used to convert SD500-PS to SD500-PSDAs (See illustration on back page.) P/N 350254, 09/02 Copyright © 2002 Silent Knight Dimensions r_Ctttax taw n rrmeekeguinsamennius i. SLC Wiring p • SILENT KNIGHT SD500-LK Installation 7550 Meridian Circle, Maple Grove, MN 55369-4927 1-800-446-€444 or in Minnesota 763-493-6435 FAX: 763-493-6475 World Wide Web: http://www.farenhyt.com Made in the U.S.A. SF 45 4. 3 75 HIGH WATTAGE FIRE ALARM SPEAKER/ SELECT A -STROBE COMBINATION • Designed to meet or exceed NFPA/ANSI Standards and ADA accessibility guidelines • UL Listed for fire protective service • Field selectable taps from 2, 4, and 8 Watts • UL Listed for wall or ceiling mount • Available in 25V RMS and 70.7V RMS • Screw terminals capacity up to AWG12 • Frequency range 400 Hz - 4000 Hz • Two field selectable settings: 15 or 30 cd • Polarized strobes with wide listed voltage ranges using filtered or unfiltered FWR input voltage • Synchronization requires the SMDI 0-3A Sync Module Amseco's high quality fire alarm speakers are designed to generate attention grabbing tones and voice commands for emergency signaling evacuation applications. These highly efficient speakers are available with field selectable taps from 2 - 8 Watts. The speakers are available in two input voltage models, 25V RMS and 70.7V RMS and can be installed on a standard 4" electrical back box with an extension ring. The SFH45-153075 Series features a new and exclusive select -a -strobe. The strobe utilized a unique candela intensity field selector switch for alternating the candela output from 15 to 30. The strobe housing is clearly labeled with "FIRE" lettering and is polarized for connecting to supervised fire alarm circuits. The strobe is designed with a xenon flash tube and provides a candela intensity field selector switch for maximum performance. They are available in red or white housing. The strobe can be synchronized by using the SMD 10-3A Sync Module to comply with NFPA recommendations concerning photosensitive epilepsy when installing two or more visual appliances within the field of view. The strobe signals are listed for indoor use, ceiling and wall mount, under UL 1971 Standard. Ordering Information Model Number Stock Number Speaker Voltage (VAC) Strobe Voltage (VDC) Strobe Candela (Selectable) Selectable Wattage Flash Rate (Per Minute) Grille Type Grille Color SFH45-153075R-25S 4650006 25 24 15 or 30 2,4,8 - 60 Square Red SFH45-153075W-25S 4650010 25 24 15 or 30 2,4,8 60 Square White SFH45-153075R-25R 4650005 25 24 15 or 30 2,4,8 60 Round Red SFH45-153075W-25R 4650009 25 24 15 or 30 2,4,8 60 Round White SFH45-153075R-70S 4650008 70.7 24 15 or 30 2,4,8 60 Square Red SFH45-153075W-70S 4650012 70.7 24 15or30 2,4,8 60 Square White SFH45-153075R-70R 4650007 70.7 24 15 or 30 2,4,8 60 Round Red SFH45-153075W-70R 4650011 70.7 24 15 or 30 2,4,8 60 Round White Engineering Specifications The fire alarm speaker shall be capable of reproducing alarm tones or voice commands on 25V RMS or 70.7V RMS. Speakers shall provide incremental tap settings of 2, 4, or 8 Watts and shall be selected by means of a jumper wire. The speaker shall have a frequency range of 400 - 4000 Hz and shall have an operating temperature between 14°F and 140°F. The speaker shall produce a UL sound pressure level at 10 feet up to 84dB. The speaker shall be approved for fire alarm signaling use. The strobe shall be listed under UL 1971 standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The candela ouput shall be field selectable, having a dual setting of 15/75cd or 30/120cd output. The signaling strobe shall operate on 24V DC from a non -coded regulated DC supply or full -wave rectified, unfiltered supply. It shall be designed to produce one signal flash per second with continuously applied minimim voltage. The SFH45-153075 shall be capable of wall or ceiling mounting. The visual signaling devices are to be installed in all non-sleeping/corridor areas as per plans and specifications. Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 631464161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MKT. #8850032 - REV A 506 PAGE IOF2 F 4 -153075 HIGH WATTAGE FIRE ALARM SPEAKER/ SELECT A -STROBE COMBINATION Dimensions: inches (mm) m 7-1/4 (184) 2-9/32 (58 1-19/32(15) 3-3/18(81) ' q, 5-1/2(140) 2-9/32 (58 1-19/32 (15) Mounting SF11-45.153075 SFH45-75110 Round SFII-45-153075 SFA45-75110 Squarc 4" Squarc Backbox 2 1/8" Deep Extension Ring 1 1/2" Deep Wiring Diagram SPEAKER STROEE Multiple Tap Setting To select desired wattage (Fig. 1) using the change lead wire, set the desired output level. (2, 4, and 8 Watt). * The unit is set at the factory to the 2 Watt position. CONTROL PANEL - S- S - TO NEXT DEVICE OR END -OF -LINE RESISTOR 7 Fig.1. SYNC MODULE LSM0l03 A IN OUT + - + TO NEXT DEVICE OR END -OF -LINE RESISTOR Multiple taps are provided for field wattage selection. Rated Input Voltage (V RMS) 25V 70.7V Input Power (Watts) 2W 4W 8W 2W 4W 8W Impedance (Ohms) 310 156 78 2500 1250 620 Sound Pressure (dB/loft) 90 93 96 90 93 96 Frequency Response (Hz) 400-4000 Low Frequency Cut-off (Hz) 200 Operating Temperature Range 32°F - 120°F (0°C - 49°C) To avoid electric shock, do not attempt to install wires when power is on. Strobe Light Maximum RMS Current (mA) Regulated 24V DC (Typical) Regulated 24V DC/FWR (Typical) 15cd 11.5(83) 162 (117) 30cd 172 (112) 232 (155) PRINTED IN USA MKT, 98850032 - REV A 5/06 PAGE 2 OF 2 SL24W-75110 SELECT A -STROBE MEAS • Meets or exceeds NFPA/ANSI Standards and ADA Accessibility Guidelines • UL Listed for wall mounting • Screw terminal capacity up to AWG12 • Universal mounting plate included • 24V DC strobe with two field selectable settings: 75cd or 110cd • Polarized strobes with wide operating voltage range using filtered DC or unfiltered FWR input voltage • Mounts to 4" square, single gang, double gang, or octagonal back box • Tamper -proof candela selector switch • Synchronization requires Sync Module (SMDI 0-3A) • Available in red or white housing Amseco's Select -A -Strobe Series is designed to comply with the Americans with Disabilities Act (ADA) and meet UL standard 1971 requirements for emergency signaling devices for the hearing impaired. The Select -A -Strobe SL24W series features a unique candela intensity field selector switch for alternating the candela output 75cd to 110cd. The strobe housing is clearly labeled with vertical "FIRE" lettering. The strobe is polarized for connecting to supervised fire alarm circuits and is designed with a xenon flashtube to provide maximum performance with a candela intensity field selector switch. The SL24W-75110 can be synchronized by using the SMD10-3A Sync Module to comply with NFPA recommendations concerning photosensitive epilepsy when installing two or more visual appliances within the field of view. The strobe signals are listed for indoor use, wall mount, under UL 1971 standard. Ordering Information Model Number Stock Number Housing Color Input Voltage Operating Voltage Range Selectable Strobe Output Flash Rate Wiring Type Mounting Type Operating Temperature Range SL24W-75110R 4560019 Red Regulated 24V DC/FWR l6 - 33V DC 16 - 33V FWR 75cd or 110cd 60 times/ min. Terrrtinals Wall Mount 32°F - 120°F ( 49°C) 0°C - 49°C 51.24W -75110W 4560020 White Engineering Specifications The visual alarm indicating appliance shall be Amseco model SL24W-75110 or equivalent device. The strobe shall be listed under UL 1971 standard for signaling devices for the hearing impaired and shall be approved for fire protective service. For outdoor applications and in UL NEMA -4X rated or UL Haz Dust Tight condition, use Aniseco UL/ULC ESH1229/1229HTR polycarbonate covers. The candela output shall be field selectable, having a dual setting of 75cd or 110cd output. The signaling strobe shall operate on 24V DC from a non -coded regulated DC supply or full -wave rectified, unfiltered supply. The strobe shall be designed to produce one signal flash per second with continuously applied minimum voltage. The strobe shall have a universal back mounting plate, capable of wall mounting to a back box. When strobe synchronization is required. the strobe shall be compatible with Amseco SMD 10-3A (daisy chain) or other source of Amseco sync protocol. Visual signaling devices shall be installed in accordance with current NFPA guidelines. Strobes must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted circuits in which the applied voltage is interrupted ON and OFF as the strobe may fail to flash. The applied voltage must be within its rated input voltage range. Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits. Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersienal.com PRINTED IN USA MKT. 118850014 - REVD c/07 PAGE 1OF2 A () POTTER Brand SL24W-75110 SELECT A -STROBE Installation Single Gang Box SL24W UI ivcrsal Mounting Plate 4" Square Back Box SL24W Universal Mounting Plate Double Gang Box SL24W Universal Mot n(ing Plate 4BX-1 SL24W Dimensions: inches (mm) 5 (127) 2 1/4 (56.9) compmmd45 =--%-.41144. f�/M gS Compound 46 WALL Wiring Diagram 7o Nat Device or Ind-uf-Line Resistor Wiring 2 Wiring Diagram wing the Syne Module (SMDI0-3A) F.A.C.P. SYNC MODULE SMDID-3A Signal ('imnt INPUT + I -F- 1 I OUTPUT 7 H+ 1-1 + t T Strobe Light Specifications Max. RMS Operating Current Regulated. 24V DC Regulated 24V FWR 75cd 137 (typical 90) 190 (typical 135) ]lOcd 189 (typical 120) 256 (typical 172) Sound Output Dispersion Horizontal dB Vertical dB 24V DC (rA) +90 -6 -3 120 +60 -2 -2 w I-) +30 -1 -1 0 0 0 99.00 ljj a -30 -1 -3 99.00 -60 -2 -5 48.75 -90 -6 -6 Under ULC ULC Current at 525/526 24V DC (rA) 75cd 93 110cd 120 UL Required Minimum Light Output Horizontal Vertical DEGREES 75 cd 110cd 75cd 110cd 0 75.00 110.00 75.00 110.00 5-25 67.50 99.00 67.50 99.00 30 56.25 82.50 67.50 99.00 35 56.25 82.50 48.75 71.50 40 56.25 82.50 34.50 50.60 45 56.25 82.50 25.50 37.40 50 41.25 60.50 20.25 29.70 55 33.75 49.50 16.50 24.20 60 30.00 44.00 13.50 19.80 65 26.25 38.50 12.00 17.60 70 26.25 38.50 11.25 16.50 75 22.50 33.00 9.75 14.30 80 22.50 33.00 9.00 13.20 85-90 18.75 27.50 9.00 13.20 Compound 45 18.00 26.40 - - PRINTED IN USA MKT. (:8850014 - REV B 9/07 PAGE 2OF2_ AC' EPT Without Comments As Noted In Red Per The Attached Letter 'These plans have been reviewed by The Tukwila Fire PreVention Bureau for conformance with current city Istartdards. AC:WV:tam*. is subject to errors and omissions which do not authorize violations of adopted 1 standards and ortheances. The responsibility for the 1adequacy of design rests totally with the designer. '.Additions, deletions or revisions to these drawings after this date will void this,acceptance and will require si resubmittal of revised drawings for subsequent approval. Final acceptance Pi subject to field test and inspection by 1 The Tukwila Fire Prevention Bureau. 62/30/0L1 Date: By: TUKWILA FIRE DEPARTIVIallt Please call: 575-4401 and give this job 1\10.0 1113 and exact address for shut. down or restoration approval, 1:1 LINE OF FLOOR ABOVE LINE OF EDGE OF CONCRETE SLAB P z z STAIR x 5 T1/4I 111,4B,2S STAI #1 STORAGE 110 0 (6) 110 OL Voltage 2.582VDC 110 8 (9) STAIR I #9 I 110 SOCCER FIELDS STORAGE 004 110 110 LINE OF BALCONY ABOVE 110 A,2B,S- 1 1 0 C J. C9 0 C.J. 2B STAIR #5 C.J. EOL Voltage 23.604VDC , 110 PORTAL FRAME E0 B, 110 EOL joltagew 22.2 VDC UP 15 CONCRItTE SLAB ED LINE OF EDGE OF CONCRETE SLAB ED CONCRETE SLAB STAIR I #6 2A,4,2S IIUTDOOR STORAGE 002 INDOOR STORAGE 003 C.J. io. CONCRETE SLAB UP STAIR #7 IgtrATEN:5) rileArticinh in kia$'' . 9 12045 31st Ave NE Seattle, WA 98125 V1)t) 440,6763 or (800) 6811125 FAX (206) 417-805.1------ go. LEGEND SYMBOL PART NO. DESCRFRON MOUNTING 4..v EST212,110 FIRE ALARM CONTROL PANEL SURFACE WALL MOUNT FACP BPS -6 EXTENDS) SIGNAL PANEL SURFACE WAU. MOUNT 1 ESP 1 SCA -PS SGA -S0 PHOTCELECIRIC DETECTOR BASE FOR ABOVE 4" OCT. 1-1/2" DP. COMO MOUNT 0 I r21612111 DUCT SMOKE DETECTOR SAMPLING 'TUBE DUCT MOUNT (EDS SIGA-SB HEAT oramoR BASE FOR ABOVE 4" OCT. 1-1/2" DP. CSUNG MOUNT SOA -C12 DUAL REMOTE MONITOR MODULE S.0 2-1/2" DP. WALL OR =NG III A NA SPRINKLER FLOWINSWITCH CONFECTION ONLY 8 NA SPRINKLER TAMPER SWITCH CONFECTION ONLY Ca SIGA-278 MANUAL PULL STATION S.O. 2 1/2" OP 48" AFT Elni et -HV__. SPEAKER/STROBE 4 SQ. 2 1/2" DP • Irli WP 787 -8A -SS SPEAKER/STROBE 767A-03 BACK Eic SIGA-CR REMOTE CONTROL MODULE 3.0 2-1/2" DP. WALL OR CIIIING MR101\C REMOTE AUXIUARY RELAY SURFACE MOUNT Ili WIRE LEGEND A - DATA LOOP TOWED SHIELDED PAIR #18 GAUGE ME B so INDICATING CIRCUIT PAIR # 12 GAUGE WIRE c is MYER / CONTROL CIRCUIT PAIR #I6 GAUGE UNE 5 - SPEAKER CIRCUIT WASTED PAR #I2 ME * SHALL BE LOCATED NOT LESS THAN 80 INCHES ABOVE FLOOR LEVEL. o IL, C16 hoes BELOW THE CEILING. HEVER IS LOWER. * OF kt ,:;%4 Of A 44, ida Fire Pr tech* Inc. 12045 31st AVE NE SEATTLE, WA 00125 DRAWN BY CONT#FIREPI*021N11... EXP. 06/04 LI # CATS'Ilt.022CG SEATTLE FRE DEPT( SCP -C-0055 NICET#4 # 007337 CEPS #1473 FIRE PROTECTION, INC. DATE EXR 06/04 EXP. 07/03 EXP. 10/04 EXP. 05/04 ESERVED *SCOPE. OF WORK!' INSTALL AN AUTOMATIC FIRE ALApil "*\ ALL *IRE TO DE • PLR -MIN 18AWG, 16AWG FOR NAC CIRCUITS. 1‘ OBES TO BE AT 111,1" ON BOTTC.41, 75D B MINIM IRA THROUGHOUT. ALL PW,.,% S .4vr 48" ON I11101'41T 0 RliNG ,C;,:.7.0d‘rn. STATION, ALARM C, ENTER INC,, LAC.; F.'? .4),GRFFIVENT pui.‘GE To ,A,,,,:,:ftztNt.1.1 PHR NFPA, PE.RFORIVED SHALL MEET NFif.'A Ag -y LocAL AHJ CODES. A FULL P -T E AND CO E TEST NEPA ACCEETANCE FORM' SHALL BE COMPLETED PRIOR TO CALLING AHJ FOR E ACCEPTANCE 'TEST #=Indicates Candela Rating FIELD PERIMETER SPEAKERS TAPED AT 2 WATTS ALL LEVELS. ROOM 15 CANDEJ.A DEVICES 1/2 WATT ALL OTHER DEVICES 1 WATT 0 A,C R ESP A,C,S U 0 FACILITY PA SHUTDOWN FACP I ESP RRAC M S STV IN A A,2S 1 E6p F FIRE ALARM SYSTEM RISER DIAGRAM G AL \OTES 1. Installation shall be accomplished in strict compliance with NFPA, Local & State Authorities and Contract Drawings. 2. All conduit sizing and routing by Electrical contractor per NEC or AHJ. 3. .Verify all locations of devices with electrical/architectural plans. Scale and place all devices per electrical plans/architectural plans. 4. Prior to installing any wire, review of system requirements shall be confirmed with Electronic Systems field technician. Wire routing is diagrammatic in nature only, and not intended for actual conduit routing. 5. Confirmation of field device mounting, termination and quantities will be completed prior to any installation of devices. 6. Smoke Detectors shall not be located within 4'—O" of air diffusers. 7. Smoke detectors will not be installed until final construction cleanup is completed. 8. A set of installation as --built drawings showing actual conduit and conductor routes shall be kept by project foreman for use by Electronic Systems field technician. 9. All circuits will be properly tagged and rang out for opens, grounds, shorts, and proper end of line resistance. Each circuit's meter reading must be documented and presented to Electronic Systems field technician upon his initial arrival on site for checkout and other field services. 10. _FACP shall not be energized without the presence of ESC technician. 11. Electronic Systems services include programing, central control term— ination, installation supervision assistance and checkout assistance. Notification for these services must be made ten working days in advance. 12. A contractor provided Electrician familiar with the installation wilL assist continously ESC field technician until project is complete. 13. Heat Detectors shown in elev. pit and machine room are for shunt trip purpose only, not connect to FA system. FOR CONSTRUCTION L-2).. It JUN 2 2 200444AA VD1Y-1.u=' t:4 C:Z z er) 14800 STARFIRE WAY 04-F-143 E) C.3 B.6 EDGE OF FLOOR SLAB cp STAIR #10 C6) C8) Of 9F ROOF ABOVE J/1\61Arat/f STAIR LEI 2A,28,2S 2B,2 TO FIELD LEVEL TO FIELD LEVEL STAIR 1111 311111111N 0.11111'.11111111111111 #B1 LA,B,2S EOL Voltage 2.3 11VDC OFFICES LWAY 03 STUDY 11-0-1 60 2A,2:,2 ikammitrr (34 31111111 7115 2A,2:23SB:21011 D 111 ENTRY IIIIIiIIIUhIIIh LOBBY =1,1 15 1101 PRO SHOP VATCR H. R. STAIR HALLWAY STAIR 60 A,313,2S COURT 60 GAME 30 ROOM EN'S LOCKER R00 EN'S LOCKER RO 30 TRAINER'S MEETING ROOM AINER'S EFICES TAIR 1, 6 EOL Voltage WOMEN EXT. DECK GUARDRAIL EOL 22.6 Vo 113111111111111 a1ll111111111 LINE OF BALCONY ABOVE STAIR F 11 Pr tecti "11 inc. 12045 31st Ave NE Seattle, WA 98125 (Oe) 440-5763 or (800) 681-1125 FAX (206).417-8051. R CONSTRUCTION /vivo 5hrik7e aktt Or C:4 0 z STAR #10 I Fh 110 x ROOM 1 202 —2B,2S ROOF ACCESS 207 1 LJ STAIR ri El El EOL Voltage 23.043VDC /—LINE OF BALCONY BELOW OL Voltage .032VDC F <kW- EOL DN STAIR #2 DN ROOM 203 I 11 F wp —WALL WASH - WE ASSUME FLOOR WILL BE LIT ADEQUATLY BY ARENA LIGHTS DECK 1 206 1 ,213,2S 7 -LINE OF BALCONY BELOW FOR CONSTRUCTION t410 r (action, Inc 12045 31st Ave NE Seattle, WA 98125 (206) 440-5763 or (800) 681-112z FAX (206) 417061 /WO Az41re c-eit rx1 z CN1 ffl FOR CONSTRUCTION Fire 3r.tect on, (i " cp. 12045 31st Ave NE Seattle, WA 98125 (206) 440-5763 or (800) 881-1125 FAX (206) 417-8051 MOO 5k1 CSL/ Ott —F—H3 P4 z r-1 N M Star Fire Soccer Facility, Tukwila Standby Battery Calculations Project: Starfire Soccer Facility Standby Power Required Quiescent (Ts) Alarm (Ta) 24 Hours 5 Minutes Edwards EST2 Series Control Panel 11/24/2003 Qty Module Type Current (Amps) Quiescent Alarm Total Load Quiescent Alarm 1 2 -MCD Common Control 0.1500A 0.2750A 0.1500A 0.2750A o 2-LSRA R. Annunciator 0.0080A 0.0080A 0.0000A 0.0000A o SAN -4 Interface Assy. 0.0035A 0.0070A 0.0000A 0.0000A 1 DL2 Dual Line Dialer 0.0100A 0.0200A 0.0100A 0.0200A 21 SIGA-PS Photo Detector 0.0003A 0.0003A 0.0066A 0.0066A o SIGA-HRS Heat Detector 0.00005A 0.00005A 0.00000A 0.00000A 16 SIGA-278 Manual Pull Station 0.0003A 0.0004A 0.0048A 0.0064A o SIGA-CT1 Input Module 0.0003A 0.0004A 0.0000A 0.0000A 1 SIGA-CT2 Input Module 0.0004A 0.0007A 0.0004A 0.0007A 10 SIGA-CC1 Riser Module 0.0002A 0.0001A 0.0022A 0.0010A 4 SIGA-CR Control Module 0.00003A 0.00003A 0.0001A 0.0001A 0 SIGA-REL Releasing Module 0.02500A 0.17000A 0.0000A 0.0000A 1 2 -MIC Master Microphone 0.08000A 0.09000A 0.0800A 0.0900A 30 SIGA-AA50 50 Watt Amplifier 0.00010A 1.90000A 0.0030A 57.0000A 0 SIGA-AA30 Amplifier 0.0010A 1.5000A 0.0000A 0.0000A 1 SIGA-MDM Message Module 0.0080A 0.0200A 0.0080A 0.0200A 0 External Load 0.0000A 0.0300A 0.0000A 0.0000A 0 Horn 0.0000A 0.0400A 0.0000A 0.0000A 0 Horn/Strobe 15 Cd 0.0000A 0.0890A 0.0000A 0.0000A 0 Horn/Strobe 30 Cd 0.0000A 0.1450A 0.0000A 0.0000A 0 Horn/Strobe 75 Cd 0.0000A 0.1730A 0.0000A 0.0000A 0 Horn/Strobe 110 Cd 0.0000A 0.2590A 0.0000A 0.0000A 0 Mini -Horn 0.0000A 0.0100A 0.0000A 0.0000A 0 Mini-Horn/Strobe 15 Cd 0.0000A 0.0800A 0.0000A 0.0000A 0 Mini -Horn . / Strobe 30 Cd 0.0000A 0.1150A 0.0000A 0.0000A 0 Mini -Horn / Strobe 110 Cd 0.0000A 0.2290A 0.0000A 0.0000A 0 Strobe 15 Cd 0.0000A 0.0490A 0.0000A 0.0000A 1 Strobe 30 Cd 0.0000A 0.1050A 0.0000A 0.1050A 0 Strobe 60 Cd 0.0000A 0.1550A 0.0000A 0.0000A 0 Strobe 75 Cd 0.0000A 0.1330A 0.0000A 0.0000A 0 Strobe 110 Cd 0.0000A 0.2190A 0.0000A 0.0000A 0 Bell 0.0000A 0.0300A 0.0000A 0.0000A Is: TOTAL SYSTEM STANDBY QUIESCENT CURRENT la: TOTAL SYSTEM ALARM CURRENT (5A Max) Amp Hour rating of system Battery Size to be used C = [Ts * Is + Ta(la+Is)] * K Where ... C = Battery Capacity Ts = Time duration in standby (Hours) Ta = Time duration in alarm (Hours) Ls--- 0.265A K = 1.2 (reserve factor) Is = standby current la = Alarm Current la= 57.525A C= 13.4 AH 15.0 AH Standby Battery Calculations BPS 6 Remote Power Supply Project: Starfire Soccer Facility - Field Level Standby Power Required Quiescent (Ts) Alarm (Ta) 24 Hours 5 Minutes 1 Qty Module Type Current (Amps) Quiescent Alarm Total Load Quiescent Alarm 1 BPS 6 Power Supply 0.0750A 0.1000A 0.0750A 0.1000A 0.1000A External Load External Load 0 Horn 0.0000A 0.0400A 0.0000A 0.0000A 0 Horn/Strobe 15 Cd 0.0000A 0.0890A 0.0000A 0.0000A 0 Horn/Strobe 30 Cd 0.0000A 0.1450A 0.0000A 0,0000A 0 Horn/Strobe 75 Cd 0.0000A 0.1730A 0.0000A 0.0000A 0 Horn/Strobe 110 Cd 0.0000A 0.2590A 0.0000A 0.0000A 0 E/P Horn 0.0000A 0.1600A 0.0000A 0.0000A 0 E/P Strobe 0.0000A 1.4000A 0.0000A 0.0000A 0 Mini -Horn / Strobe 30 Cd 0.0000A 0.1150A 0.0000A 0.0000A 0 Mini -Horn / Strobe 110 Cd 0.0000A 0.2290A 0.0000A 0.0000A 3 Strobe 15 Cd 0.0000A 0.1050A 0.0000A 0.3150A 0 Strobe 30 Cd 0.0000A 0.1050A 0.0000A 0.0000A 0 Strobe 60 Cd 0.0000A 0.1550A 0.0000A 0.0000A 0 Strobe 75 Cd 0.0000A 0.1330A 0,0000A 0.0000A 23 Strobe 110 Cd 0.0000A 0.2190A 0.0000A 5.0370A 0 Bell 0.0000A 0.0300A 0.0000A 0.0000A Is: TOTAL SYSTEM STANDBY QUIESCENT CURRENT la: TOTAL SYSTEM ALARM CURRENT (6A Max) Amp Hour rating of system Is= 0.075A la= 5.452A Battery Size to be used C = [Ts * Is + Ta(Ia+Is)] * K Where ... C = Battery Capacity K = 1.5 (reserve factor) Ts = Time duration in standby (Hours) Is = standby current Ta = Time duration in alarm (Hours) la = Alarm Current Standby Battery Calculations BPS 6 Remote Power Supply Project: Starfire Soccer Facility - Upper Level 3 Standby Power Required Quiescent (Ts) Alarm (Ta) 24 Hours 5 Minutes C= 3.4 AH 7.5 AH Qty Module Type Current (Amps) Quiescent Alarm Total Load Quiescent Alarm 1 BPS 6 Power Supply 0.0750A 0.1000A 0.0750A 0.1000A 0.1000A External Load External Load 0 Horn 0.0000A 0.0400A 0.0000A 0.0000A 0 Horn/Strobe 15 Cd 0.0000A 0.0890A 0.0000A 0.0000A 0 Horn/Strobe 30 Cd 0.0000A 0.1450A 0.0000A 0.0000A 0 Horn/Strobe 75 Cd 0.0000A 0.1730A 0.0000A 0.0000A 0 Horn/Strobe 110 Cd 0.0000A 0.2590A 0.0000A 0.0000A 0 E/P Horn 0.0000A 0.1600A 0.0000A 0.0000A 0 E/P Strobe 0.0000A 1.4000A 0.0000A 0.0000A 0 Mini -Horn / Strobe 30 Cd 0.0000A 0.1150A 0.0000A 0.0000A 0 Mini -Horn / Strobe 110 Cd 0.0000A 0.2290A 0.0000A 0.0000A 5 Strobe 15 Cd 0.0000A 0.1050A 0.0000A 0.5250A 0 Strobe 30 Cd 0.0000A 0.1050A 0.0000A 0.0000A 4 Strobe 60 Cd 0.0000A 0.1550A 0.0000A 0.6200A 1 Strobe 75 Cd 0.0000A 0.1330A 0.0000A 0.1330A 6 Strobe 110 Cd 0.0000A 0.2190A 0.0000A 1.3140A 0 Bell 0.0000A 0.0300A 0.0000A 0.0000A Is: TOTAL SYSTEM STANDBY QUIESCENT CURRENT la: TOTAL SYSTEM ALARM CURRENT (6A Max) Amp Hour rating of system Is= 0.075A la= • 2.692A Battery Size to be used C = [Ts * Is + Ta(Ia+Is)] * K Where ... C = Battery Capacity K = 1.5 (reserve factor) Ts = Time duration in standby (Hours) Is = standby current Ta = Time duration in alarm (Hours) la = Alarm Current C= 3.0 AH 7.5 AH Standby Battery Calculations Fire Prot ationt Ince 12040 31 of Ave NE Seattle, WA 98103- (20W 810'3(,206) 440.6703 or (NO i 1-11 FAX (200) 41741 BPS 6 Remote Power Supply Project: Starfire Soccer Facility - Main Level 2 Standby Power Required Quiescent (Ts) Alarm (Ta) 24 Hours 5 Minutes Qty Module Type Current (Amps) Quiescent Alarm Total Load Quiescent Alarm 1 BPS 6 Power Supply 0.0750A 0.1000A 0.0750A 0.1000A External Load 0 Horn 0.0000A 0.0400A 0.0000A 0.0000A 0 Horn/Strobe 15 Cd 0.0000A 0.0890A 0.0000A 0.0000A 0 Horn/Strobe 30 Cd 0.0000A 0.1450A 0.0000A 0.0000A 0 Horn/Strobe 75 Cd 0.0000A 0.1730A 0.0000A 0.0000A 0 Horn/Strobe 110 Cd 0.0000A 0.2590A ' 0.0000A 0.0000A 0 E/P Horn 0.0000A • 0.1600A 0.0000A 0.0000A 0 E/P Strobe 0.0000A 1.4000A 0.0000A 0.0000A 0 Mini -Horn / Strobe 30 Cd 0.0000A 0.1150A 0.0000A 0.0000A 0 Mini -Horn / Strobe 110 Cd 0.0000A 0.2290A 0.0000A 0.0000A 14 Strobe 15 Cd 0.0000A 0.1050A 0.0000A 1.4700A 9 Strobe 30 Cd 0.0000A 0.1050A 0.0000A 0.9450A 10 Strobe 60 Cd 0.0000A 0.1550A 0.0000A 1.5500A 2 Strobe 75 Cd 0.0000A 0.1330A 0.0000A 0.2660A 2 Strobe 110 Cd 0.0000A 0.2190A 0.0000A 0.4380A 0 Bell 0.0000A 0.0300A 0.0000A 0.0000A Is: TOTAL SYSTEM STANDBY QUIESCENT CURRENT la: TOTAL SYSTEM ALARM CURRENT (6A Max) Amp Hour rating of system Is= 0.075A la= 4.769A Battery Size to be used C = [Ts * Is + Ta(la+Is)] * K Where ... C = Battery Capacity K = 1.5 (reserve factor) Ts = Time duration in standby (Hours) Is = standby current Ta = Time duration in alarm (Hours) la = Alarm Current C= 3.3 AH 7.5 AH /fV s t v -�i`re La/ by. -F -/y3 0 rt Q z Kul Star Fire Soccer Facility, Tukwila WA 0 Without Comments a AsNoted in Red EKP per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for c .niormance with current City standards. Acceptance is subject to errors and which do rot r;� ':i :f i = �,loladons of adopted omissions wh_I_ _, lr;S't:f,t��•;ihiiltl` for the standards and orutrta ,Y design t l: 1ti,, wit the designer. adequacy of de.�.,1 ;`, .`...` ot_ ra o,,r�, drawings after Additions, deletions , ,t `..w ;�T�t:�` _{'� , ', will requirea this date will void tari., s ` ``..' ,.... resubmlttai of revised drawirtc;; `o :,, ,,;egUent approval. Final acceptance is subject to field tit and Inspection by The Tukwila Fire. Prevention Bureau. Date:! RattilitA E DEPART : 4ffi1 Please call: 575-44W and give this job to.Oq S 1 'xact address for shuti or Yetstoration approval, FIRE SPRINKLER TI PLAN SCALE:1/8" =1'-0" PRE -DRILLED HOLE DROP IN ANCHOR HANGER RING HDI -P HANGER TYPE P NTS MECHANICAL TEE J -1" ARM -OVER (VARIES) 48" FLEX DROP \- 1/2" SSP FLEX DROP NTS / AREA OF / 7 SCOPE OF WORK: 1. ADD NEW PENDENT SPRINKLERS IN GYM AREA FOR NEW WALLS AND CEILINGS. 2. SYSTEM DESIGNED IN ACCORDANCE WITH NFPA #13 ORDINARY HAZARD GROUP 1. 3. PLAN SUBMITTAL TO AND APPROVAL BY CITY OF TUKWILA. 4. MATERIALS PER NFPA #13 STANDARDS AS SELECTED BY FSI. 5. TESTING PER NFPA #13 AND THE CITY OF TUKWILA. GENERAL NOTES: 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UL LISTED OR FM APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1-6), WHICH IS END TO END. 3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA PAMPHLET #13. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA PAMPHLET #13. 5. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET #13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET #13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL. 9. ALL FIRE ALARMS, WIRING AND MONITORING ARE TO BE INSTALLED BY OTHERS. RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL. CONSTRUCTION NOTES: 1. ALL PIPING TO BE SCHD 40 AND DYNAFLOW. 2. ALL NEW FITTINGS TO BE THREADED DUCTILE IRON AND GROOVED FITTINGS. 3. ARMOVERS LONGER THAN 2'-0" SHALL HAVE A HANGER. 4. TYPICAL HANGER TO BE A HDI-P(UNO). 5. MAX SPACING TO BE 130 SQ FT. 5113rdSt S 1.13r<i PI - np01�Sr� S 1111th 51 S lS thSt 5 153rd St 200+9 t � a�C7uc st lr VICINITY MAP SCALE: NTS tvlapData /12009t4'V1rQ Tr9leAtiroi - ALARM VALVE RISER - FLOW SWTICH RISER • - DRY PIPE RISER 0 - DELUGE/P.A. RISER - FIRE DEPARTMENT CONNECTION /6. - WATER MOTOR GONG - ELECTRIC BELL DRAWING SYMBOLS RIGID GROOVED COUPLING - THREADED PIPE COUPLING - CONTROL VALVE —1>•— - CHECK VALVE ( A-1 ) - WELDED PIPE TAG O- BRANCHLINE NUMBER 1 9-0 • 1 (8-10) - PIPE SIZE & LENGTH HYDRAULIC DESIGN INFO. ❑ THIS SYSTEM IS HYDRAULICALLY DESIGNED HANGER LEGEND HEAD LEGEND gTHIS SYSTEM IS NOT II HYDRAULICALLY DESIGNED FLOW TEST SPRINKLER TYPE MFG MODEL SYMBOL ORIFICE FINISH CANOPY TEMP K— FAC QTY RECESSED PENDENT TYCO TY -FRB 1/2" WHITE WHITE 155° 5.6 6 STATIC RESIDUAL GPM FLOWING 100 PSI 20 PSI P HDI—P UPRIGHT TYCO TY -FRB 0 1/2" BRASS 155° 5.6 1000 GPM PIPE SIZE & LENGTH(CUT) DATE •& TIME Fire S • rinklers SYSTEM DESIGN WA CL# FIRESI*988RJ - HYDRAULIC NODE REMOTE AREA xx PIPE HANGER (SEE CHART) �-f - PIPE HANGER (SEE CHART) dik 10'-0" AFF ELEVATION DATUM 0'-10" BOD DENSITY xx MAX, AREA/HEAD xx - CENTERLINE OF PIPE TO DECK K—FACTOR xx xx 1014 North Street Sumner, WA 98390 (253) 826-0099 TOTAL THIS SHEET 7 PROJECT: MVP - Katz Gym (Starfire Sports) 14800 Starfire Way Tukwila, Wa 98188 CONTRACT WITH: Starfire Sports 14800 Starfire Way Tukwila, Wa 98188 Phone: Fax: PAI 2009 Tukwila Fire 2C&7f'— DESIGNER: Chance Gallant DATE: August 31, 2009 SCALE: As Noted HAZARD: As Noted AHJ: City of Tukwila JOB # 2386 SHEET # FP1 OF 1 14800 STARFIRE WAY 09-S-139 10'-10" SECTION 1 trt t:i r HYDRAULIC REMOTE AREA NFPA 13 2007 OHG I THIS SYSTEM DESIGNED TO DISCHARGE -0r]5 G,P OVER 900SF USING QR HEAL S WHEN SUPPLIED WITH WATER AT THE FITY CONN. AT A RATE OF 474.6 G.P.M. AT OUTSIDE HOSE ALLOWANCE: 250 GPM �et `meg) 5c473 Q,1 �C. 30'-0" \O°r 0 OPEN TO ABOVE rn STOR. 3,-7" 11 6'1" 30'-0" 6'-0," 10 30'-0" •__. RIMY -61 _RIM _4J O179F�C � m Elm e :WB CLiv( ro 9'-0" A1F.Fy Q Mali! 0 5A II =WV, CL,' @ 9'-0' c ALL I SHO'4VER 1 I 11101 1 5-01*e 0 0 1 HA- M ifs 8-941 - N 1G 11� nA. 0 0 VB SOFF T @ a'-0" A.F.F. ICE 0 l7( it ! min I�„rum �� FPI 1 1 - -. v �- • .� �� / ` ii�10. "TIJIERA Y 'ACO ING-e STIC = G OPEN T ABOVE JA 10 1 GYtl CLG c 9'- " A.F.F. TOILET E1 0 4-0 4 GWB CLG @ 10'-0" A.F.F 0 4°3 v ±ET 1 3-10 - 0-1114 10,_ GROOMIN HMI • m GWB CLG @ 9'-0" A.FI r It Ani TAY JI BA _ OJI NO - 0 -1114 II hid 0 MI =au amommi IMPINE min ivi. I1 ■0■ CEIL @ 9' a■ ar_1 M: NMI 111110. . I 10-2 0 N N N 4 10-2 0 N 4 10-2 0 N N cJ C4 N N e N N N N e N N N N e N N N N N e L 4 10-2 ®° 10-2 0 N N N N N N 10-2 0 N N N N e N N N N N 10 0 N N 1 N 4 0 F 4 10-2 0 10-2 N N N N N N N N N e N N N N N N 9-8 0 N N N 1-4 O E 6- '1 11i i II111.11 2-414 - .� GWEDCLG % 1 MiNgl lilleAMINI c@9'-0"A.F.F IR III III nil MININI a U -■ -1u' IN C) 5 mop, Erl Ju "til I • eta - 4 4 10-2 0 N N 1- 10-2 @CD 3-5 n N N N N f N N N N N N N N N N N sY N 0 O G SOFFIT m A.F.F. COI Tf G -G1 0- A.I u u mo 0 GWB@ Cr A.F.F C11 Cr :""e, O m 0 O 0 KITCHEN 4 ® m 0 11011 Y GWB SOFFIT 1 @ 11'-0" A.F.F. II 9-4 1 6-2 N N 4 10-2 • 0 4 0 10-2 0 N N N N N N N st N N N sy N N N N N N c-1 1 CV J® AREA OF WORK B c wg of increased demand our i! ,spa;or schedules are booked 3-7 days ahead. Therefore; you will need to call 206-575-4407 to schedule your inspections a minimum of 48 hours in advance of the date you want an inspection. XISTING BUILDING NO WORK Without CommentS As Noted In Red Per The Attached Letter hese plans have been revim,ved by The Tukwila Fire Prevention Elureau for cionfCii-t.:1;C,E,'• with current city standards. ArGootnda to errors and omission's; do vir_lations Of adopted 3tario;:lco-,i; for the edNuacy 01 designer. drawings alter this date wiil void itii,:.:,.;:recepr:ificu va require a resubmittal of revised drawing.' for subsequent approval. Final -acceptance is subject to field test and inspection SThe Tukwila Fire Prevention Bure u. SECTION 2 CE Wek! stamps must be 1 inspected before pipe is hung. Do not paint piping - prior to hydrostatic test RAW' LA FIRE DEPART -Won Please call: 575-440Z and give this job ,xact address for shut. A SCOPE OF WORK: 1. REVISE EXISTING WET SYSTEM FOR NEW TENANT . 2. IMPROVEMENT TO BE DESIGNED PER NFPA #13. 3. PLAN SUBMITTAL TO AND APPROVAL BY CITY OF TUKWILA. 4. MATERIALS PER NFPA #13 STANDARDS AS SELECTED BY FSI. 5. TESTING PER NFPA #13 AND CITY OF TUICWILA. GENERAL NOTES: 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UL LISTED OR FM APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1-6), WHICH IS END TO END. 3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA PAMPHLET #13. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA PAMPHLET #13. 5. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET #13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET #13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL. 9. ALL FIRE ALARMS, WIRING AND MONITORING ARE TO BE INSTALLED BY OTHERS. RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL. CONSTRUCTION NOTES. • 1. ALL NEW PIPING TO BE DYNA FLO, SCHD 10 AND SCHD 40. 2. ALL NEW FITTINGS TO BE THREADED DUCTILE IRON AND GROOVED FITTINGS. 3. ARMO'VERS LONGER THAN t6(+"/ SHALL HAVE A HANGER. 4. HEADS SHOWN ARE ON 24" F EX DROPS UNO. 5. HEADS SHOWN ARE NOT AT NTERLINE OF CEILING TILE. 0.4 SAMMY SUPER SCREW SWDR 516 HANGER RING SAMMY SUPER SCREW SWDR 516 Z-PURLIN HANGER TYPE S FIG. 980 SWIVEL SWAY BRACE FITTING NTS BRACE PIPE r,IG, 1000 FAST CLAMP'e SWAY BRACE ATTACHMENT LATERAL EARTHQUAKE BRACE 701d1 NON -THREADED BRACE PIPE REVISIONS CHANGES PER CITY certIficat 4s) _6., r/ __/,400#44,1,0„..aire,.... ,4,..4.,,,,,e4. 1,...0 YANOW N. 10/1/08 PARCEL # - 2323049001 PERMIT# -xxxx DRAWING SYMBOLS HYDRAULIC DESIGN INFO. HANGER LEGEND HEAD LECGfiltr' A_ ALARM VALVE RISER A_ FLOW SWTICH RISER • - DRY PIPE RISER - DELUGE/P.A. RISER 0 - FIRE DEPARTMENT CONNECTION - WATER MOTOR GONG - ELECTRIC BELL 0 FLEXIBLE GROOVED COUPLING - RIGID GROOVED COUPLING THREADED PIPE COUPLING - CONTROL VALVE - CHECK VALVE PIPE HANGER (SEE CHART) - PIPE HANGER (SEE CHART) ( A-1 ) - WELDED PIPE TAG 9-0 (8-10) PIPE SIZE & LENGTH PIPE SIZE 8c LENGTH(CUT) - HYDRAULIC NODE ELEVATION DATUM - CENTERLINE OF PIPE TO DECK gTHIS SYSTEM IS ri THIS SYSTEM IS NOT HYDRAULICALLY DESIGNED HYDRAULICALLY DESIGNED A U -HOOK "L" ROD SPRINKLER TYPE MFG MODEL SYMBOL ORIFICE FINISH CANOPY TEMP K -FAC QTY FLOW TEST STATIC 1 00 RESIDUAL 20 GPM FLOWING 1000 DATE & TIME City 9/23/08 COACH SCREW ROD TOGGLE NUT "C" CLAMP RECESSED PENDENT UPRIGHT TYCO TYCO TY -FRB CD 1/2" CHROME TY -FRB 0 1/2" BRASS CHROME NA 5.6 44 5.6 3 TOP BEAM CLAMP W/ STRAP WEDGE ANCHOR RECESSED PENDENT TYCO TY -FRB • 1/2" CHROME CHROME 5.6 EYE ROD SYSTEM DESIGN FLUSH SHELL S20 SAMMY SUPER SCREW (GST20) REMOTE AREA 900 DENSITY .15 MAX. AREA/HEAD 130 K -FACTOR 5.6 XX CEILING FLANGE SX SAMMY X -PRESS SIDE BEAM BRACKET TRAPEZE "J" BOLT UNISTRUT POST SHORT CLIP TOTAL THIS SHEET 50 Fire Sprinklers t nc WA CL# FIRESI*988RJ 1014 North Street Sumner, WA 98390 (253) 826-0099 Seattle Sounders FC 14800 Starfire Way Tukwila, WA. 98188 CONTRACT WITH: Dutchess Construction DESIGNER: Mike DATE: September 22, 2008 SCALE: As Noted " HAZARD: As Noted AHJ: City of Tukwila JOB # 2102 SHEET # FP 14800 STARFIRE WAY - ALARM VALVE RISER - FLOW SWTICH RISER • - DRY PIPE RISER 01 - DELUGE/P.A. RISER - FIRE DEPARTMENT CONNECTION .6. - WATER MOTOR GONG - ELECTRIC BELL r HYDRAULIC REMOTE AREA NFU 152007 0110I THIS SYSTEM DESIGNED TO DISCHAR OYE0.900SP MHO QRH WHEN SUPPLIED WITH WATER ATTR' AT A RATE OF 474.6OPM AT 65, OUTSIDE HOSE ALLOWANCE: 25 OASUPAL- CHY CONN. S1 SPM CG GGGCLG 1OI V AFF SECTION 1 0 O 41101 0 1 O 13'-0" 1 AREA OF WORK 10-2 43 10.2 10-2 10-2 a 16.2 10-2 16.2 2 10.2 4a 16.2 O 16-2 O U t) DIs:10 SYSIII DRAWING SYMBOLS —G— FLEXIBLE GROOVED COUPLING --g— RIGID GROOVED COUPLING THREADED PIPE COUPLING - CONTROL VALVE —Ij— - CHECK VALVE PIPE HANGER (SEE CHART) -�- f - PIPE HANGER (SEE CHART) ( A-1 ) - WELDED PIPE TAG 09 - BRANCHLINE NUMBER 9-0 PIPE SIZE & LENGTH 1 (8-10) PIPE SIZE & LENGTH(CUT) - HYDRAULIC NODE azik 101-011 AFF ELEVATION DATUM 01-1011 BOD - CENTERLINE OF PIPE TO DECK PIPING PLAN 1/16"=1'-0" HYDRAULIC DESIGN INFO. LLIIg THIS SYSTEM IS ❑ THIS SYSTEM IS NOT HYDRAULICALLY DESIGNED HYDRAULICALLY DESIGNED FLOW TEST STATIC xx RESIDUAL xx GPM FLOWING xx DATE & TIME REMOTE AREA xx SYSTEM DESIGN xx DENSITY xx MAX. AREA/HEAD xx K—FACTOR xx xx A B C U—HOOK COACH SCREW ROD "C" CLAMP HANGER LEGEND L N P "L" ROD TOGGLE NUT HDI—P D E F G H J K TOP BEAM CLAMP W/ STRAP EYE ROD FLUSH SHELL CEILING FLANGE SIDE BEAM BRACKET "J" BOLT SHORT CLIP R S S20 SX T U W WEDGE ANCHOR SAMMY SIDEWINDER (SWG20) SAMMY SUPER SCREW (GST20) SAMMY X—PRESS TRAPEZE UNISTRUT POST SPRINKLER TYPE SECTION 2 0 EXISTING BUILDING NO WORK MFG HEAD LEGEND MODEL SYMBOL ORIFICE FINISH CANOPY TEMP K—FAC QTY (5 tileorporafea c c�\0 ale certificate o /p Level fc Fs� t1 Michael Ma. uire r'..hav �y ti REVISIONS athrou A CHANGES PER CITY PROJECT: Seattle Sounders FC 14800 Starfire Way Tukwila, WA. 98188 Fire Sprinklers WA CL# FIRESI*988RJ CONTRACT WITH: Dutchess Construction TOTAL THIS SHEET 1014 North Street Sumner, WA 98390 (253) 826-0099 email:mike@firesprinklersinc.com 10/1/08 5 1( O h SprinK\E ,S^• Decefe' DESIGNER: Mike PARCEL # - 2323049001 PERMIT# -xxxx DATE: September 22, 2008 SCALE: As Noted HAZARD: As Noted AHJ: City of Tukwila JOB # 2102 SHEET # FP 2 B.2 B.1 PRO SHOP 1111111111111 1 1 1 1 1 11 1 1 1 1 1 1 1 1 1 1 1 1'1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 EX. F.D. i DECK LiQ9] EXIST. OVERHEAD GLASS DOOR OVERHEAD GLASS DOOR L a '• INOPERABntE� I I I I FOOD COURT SERVING 0102 1—— C//J,.,1�/l I ///LC /J/L/J./ LK/1Tl'/7JJ „M YLP G1BSS.D.(Li,!` r -n-1 JIII 1I_„ L. s A OY,,,O PLUG HEAD ( NEW -TEE a IN WIALLS " HSSW—UNDER —frtr' Rt'it'. NEII�/� OH DOOR ��i'• Him lT ARE! 0021 SERVING AREA V� I I 110LLI A ,A , _�O? 0 Gi _ CUT IN If J ,`\\PLU•G HEAD NEW TEE IN WALL DREP. D02Ei KcfP Papp r 0 a0 te4/ ' 0 4o .1171 LZ7727777,,zl//// :Q727'//"i<Z/Z77L7Z.i/ .,rr.. — I L_ r i r EXIST. OVERHEAD CLASS DOOR I EXIST. OVERHEAD GLASS DOOR EXIST. OVERHEAD GLASS DOOR INOPERABLE W/ GUARD RAILING W/ GUARD RAILING INOPERABLE 2.5 FIRE SPRINKLER TI PLAN SCALE: 1/8" =1'-011 SYMBOL LEGEND 0 _ MT QA OA i iyel" 1 C (j �.rl p PI cirm • - EXISTING UPTIGHT SPRINKLER - MECHANICAL (CLAMP) TEE. FIRE SPRINKLER TO BE ADDED. NEW FIRE SFRINKLER PIPE (SOLID LINE). - EXISTING FIRE SPRINKLER PIPE (DASHED LINE). VICINITY MAP SCALE: NONE SCOPE: 1. PLUG TWO UPRIGHTS IN WALL, ADD 4 UPRIGHTS ON THE BRANCHLINES, ADD ONE NEW SIDEWALL UNDER NEW OH DOOR, AND CHANGE ONE UPRIGHT TO 286* FOR STOVE. GENERAL NOTES: 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UL LISTED OR FM APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1-6), WHICH IS END TO END. 3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 2002 EDITION. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 1999 EDITION. 5. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 2002 EDITION. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 2002 EDITION. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL 9. ALL FIRE ALARMS, WIRING AND MONITORING ARE TO BE INSTALLED BY OTHERS. 10. EXISTING BUILDING PROTECTED BY EXISTING OVERHEAD WET SYSTEM. CONSTRUCTION NOTES: 1. ALL HEADS TO BE SPACED 130 SQ FT. 2. DESIGN CRITERIA TO BE OH—II (RETAIL). I ACCEPTED n Without Comments As Noted In Red 0 Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and k omissions which do not authorize violations of adopted stanaaras and ordinances. The responsibility for the . adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void this -acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: 1'L 5 Cq- By: 1 1 AREA OF WORK IMPORTANT NOTICE Because of increased demand our Inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4407 to schedule your Inspections a minimum of 48 hours in advance of the date you want an inspection. 1 UKWILA FIRE DEPARTNIkAit Please call: 575-440Z -nd give this job ,o. O -S_2,9 • end exact address for shut: ' Owen or restoration appr0 PROJECT # -XXXX PERMIT # -XXXXX LU 0 Lu w Lu CONTRACTOR: DRAWING SYMBOLS HYDRAULIC DESIGN INFORMATION HANGER LEGEND HEAD LEGEND • ALARM VALVE RISER DRY PIPE RISER FLOW SWTICH RISER DELUGE/PA. RISER 0 PIPE 'RISE' c PIPE 'DROP' PIPE HANGER (SEE CHART) - f , SEISMIC BRACING FLEXIBLE GROOVED COUPLING RIGID GROOVED COUPLING THREADED PIPE COUPLING CONTROL VALVE CHECK VALVE FDC WATER MOTOR GONG ELECTRIC BELL 1A 6x21-0 WELDED PIPE TAG 9-0 PIPE LENGTH BRANCHLINE NUMBER HYDRAULIC NODE CENTERLINE OF PIPE TO DECK @9'-0' CEILING ELEVATION S9 -0 ELEVATION DATUM A.F.F. 1-1 THIS SYSTEM IS SI THIS SYSTEM IS NOT I I I HYDRAULICALLY DESIGNED ' I HYDRAULICALLY DESIGNED FLOW TEST STATIC xxx RESIDUAL xxx GPM FLOWING xxx DATE & TIME xxx SPRINKLER TYPE ADDED UPRIGHT ADDED' Pet 6fr- REPLACEE UPRIGHT MFG. MODEL TYCO TY -B TYCO TYCO TY -B SYMBOL OA A ORIFICE FINISH 1/2" BRASS 1/2" TY -B 4 1/2" BRASS BRASS CANOPY N/A N/A N/A TEMP. K—FAC. 155°F 155°F 286°F 5.6 5.6 5.6 QTY. 4 1 1 SYSTEM DESIGN REMOTE AREA xxx DENSITY xxx MAX. AREA/HEAD xxx K -FACTOR xxx WATER INFO TUKWILA WATER TOTAL THIS SHEET 6 Fire Sprinklers Inc; WA CL# FIRESI*988RJ 1014 North St, #200 Sumner, WA 98390 (253) 826-0099 PROJECT: Siena Coffee TI 14800 Starfire Way Tukwila, WA PAID CEC - 4 2007 i,e CONTRACT WITH: Aptus Construction XXX Sumner, WA DESIGNER: KYLE BARROW DATE: November 30th, 2007 SCALE: VARIES HAZARD: SEE NOTES AHJ TUKWILA FIRE JOB # 1859 SHEET # FP -1 OF 1 14800 STARFIRE WAY #140 SCOPE: FSI TO INSTALL THREE NEW DRY SSP IN NEW COOLER GENERAL NOTES: 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UL LISTED OR FM APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1-6), WHICH IS END TO END. 3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 1999 EDITION. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 1999 EDITION. 5. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 1999 EDITION. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 1999 EDITION. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL 9. ALL FIRE ALARMS, WIRING AND MONITORING ARE TO BE INSTALLED BY OTHERS. 10. EXISTING BUILDING IS PROTECTED BY EXISTING OVERHEAD WET SYSTEM. 11. ALL ARMOVERS OVER 1'-0" TO BE HUNG FROM STRUCTURE ( EXCESS OF 100 PSI). NEW 212 x 1 MECH. TEE 1 MAIN— //:41) .AIN— T •F 13 _ 0 •' u, 2,-0' NEW 112 X t MECH. EE"' 1-9 3'-3' , SYMBOL LEGEND 9-6 I *— COOLER CEILING HEIGHT TO BE 9'-2" rt `OOorporate e� a re Gertihc; .4. r Level °� Q a 111 c° 4 • 9 i x` Kyle Barrow 0 `4OO, -2655 I. 396 mul tPV Signa ure • •at7F Ar i D 14 rcK` ,.5.4 �%.• I4:ii h Dece� S FIRE SPRINKLER COOLER TI - PLAN VIEW SCALE: 1/8" = - EXISTING FIRE SPRINKLER NEW FIRE SPRINKLER PIPE (SOLID LINE). — -- — - EXISTING FIRE SPRINKLER PIPE (DASHED LINE). HEAD LEGEND SPRINKLER TYPE NEW DRY PENDENT MFG. VIK MODEL SYM. ORIFICE FINISH CANOPY TEMP. K -FAC. QTY M • 1/2" CHR CHR 200°F 5.6 3 avrivnvn Fire Sprinklers WA CL# FIRESI*988RJ 14115 16th Street East Sumner, WA 98390 (253) 826-0099 PROJECT: MAD PIZZA COOLER TI 14800 STARFIRE WAY TUKWILA, WA 98188 DESIGNER: KYLE BARROW DATE: 2-24-05 SCALE: 1/8" =1'-0" CONTRACT WITH: CLEMENTS CONSTRUCTION 15805 SE 264th StJOB N 1316 Y/rl kIT IAIA AriAll �'� HAZARD: OHI AHJ TUKWILA 14800 STARFIRE WAY #240 05-S-033 SHEET # FP1 OF 1 -42 35- .011111.111111=1.011.11MM.11.1•110.11.0111.1111.011011 0 AnCEPTED Wlthout Comments As Noted In Red Par The 'Attached Letter These plans have brl.!..,r re:vi.fs.'d by The Tulwiln Fire Prevention BO 't",!,,.:,:,1 i-r:r Cr.:i'?•;11;Ltilt:,•6 Vitti CU vrt-:;11: ciq standards k.':::::;.11..?,.--i7:-.i':: ''..' ,:l.:rnIssiorlF '',,v;:1,...::', ;:•;1,:,i rt:)! ;...111".f,,i;;.i v;!...:',..ic'rt,:-.:i of :i::,:.':r.rptc:ti rcis lcizi c ,...li7s1",4.1(4,-,.. "I itU i'.:':pi:s.'il.:',1",,ii,7.V t*.i!:' ''... ';'•., t,;dly \i:ItC; Oqi.V:g1Sow...; or vz:.;v1si.int, n i;,.,:e ,:lra,.;.in;.-..: .-'.: d5te will vola tnisaccepia',-;e :i.,.rid will ireclo::e a I. .,'. '.submittal of revised drawings for subsequent ar.4';i•ov.I. .. Final acceptance is subject to field test and inspection by IThe Tukwila Fire Prevention Bureau. Date?/2-67'os" By:i.--41-141 11.IKWILA FIRE (APAR Mt.1111 Please call: 575.4407 and give this job No --C-03 and exact address for shut- down or restoration approval., ces to\a z cat2s �:ret`'e itkti petson� �aY R Wel t\'i2 �+ t . o \tab t a�aC�S h\G CO'mo cc ttbn ° et., �:l ati ` o t to `: 6 tt''t \ aciac s c° ‘a.0 , `y\th te5 \ts tec % sttUeaPett exQtc' �eaPe�. bas b - t kEe eats` ISM 3`. , - to ei,,.. they t .- \ ttt' cce0ta- ,,,sUcorc u.•,stion o - • f , a. -.o!. '\j, {c\\ • ar .a ai d.,-,1:14A: ad - - St1\1 UNDERGROUND NOTES':' 1) ALL UNDERGROUND TO BE BY OTHERS. CONTRACTOR TO BE STATE LICENSED AND CERTIFIED TO INSTALL UNDERGROUND PIPING PER WAC 212-80. 2) PIPE TYPE AND CLASS TO MEET LOCAL JURISDICTION APPROVAL 3) ALL UNDERGROUND PIPING SHALL HAVE 3 FEET MINIMUM BURY (TO TOP OF PIPE). 4) ALL UNDERGROUND PIPING SHALL BE UL LISTED AND/OR FM APPROVED FOR FIRE PROTECTION. 5) ALL UNDERGROUND PIPING SHALL 6E RESTRAINED IN ACCORDANCE WITH THE SPECIFICATIONS AND NFPA 24 ( LATEST EDITION ). 6) ALL UNDERGROUND PIPING SHALL BE HYDRO- STATICALLY TESTED AT NOT LESS THAN 200 PSI OR 50 PSI ABOVE STATIC PRESSURE IN EXCESS OF 150 PSI FOR TWO HOURS IN ACCORDANCE WITH NFPA 24 ( LATEST EDITION). 7) ALL UNDERGROUND PIPING SHALL BE FLUSHED IN ACCORDANCE WITH NFPA 24 ( LATEST EDITION ). FLOW THE REQUIRED RATE UNTIL WATER IS CLEAR AS INDICATED BY NO COLLECTION OF FOREIGN MATERIAL IN BURLAP BAGS AT OUTLETS. 4" - 390 GPM 6" - 880 GPM 8" - 1,560 GPM 10" - 2,400 GPM 12" - 3,520 GPM 8) ALL UNDERGROUND PIPING SHALL BE STERIUZED PER LOCAL JURISDICTION REQUIREMENTS. STARFIRE SOCCER COMPLEX TOTAL SQUARE FEET: 84,074 BUILDING TYPE: TYPE II FIRE RESISTIVE OCCUPANCY: ASSEMBLY OFFICE, B MERCANTILE, M UNASSIGNED ARCHER START POINT AT 6" SUPPLY FLANGE AT 1'-0" AFF (SEE RISER DETAIL THIS SHEET) SITE PLAN 4" FDC UNE 6"CL52DJ. SUPPLY 0 15 30 45 60 75 MI a MI .1114 1111 1111Wk, 1.1 -a SEM Mileg II 61.2, 16 le El SCALE 1" = 30' SITE PLAN SYMBOL3 1 ® ® I® NEW UNDERGROUND BY OTHERS 4- -D4- EXISTING UNDERGROUND NEW FIRE HYDRANT EXISTING FIRE HYDRANT NEW YARD POST INDICATOR NEW VALVE WITH ROADWAY BOX EXISTING VALVE WITH ROADWAY BOX NEW TWO WAY FIRE DEPARTMENT CONNECTION WATER SUPPLY INFORMATION STATIC PRESSURE: RESIDUAL PRESSURE: FLOWING: LOCATION: BY: 142 PSI 20 PSI 5000 GPM SITE TUKWILA PUBLIC WORKS STANDING SEAM MTL ROOF 0/ STL ZEE PURLINS 1.9 12 STANDING SEAM MTL O/ STL ZEE PURLINS 12 0.5 6" BATT IN LATION COLUMN WITH SP- -ON FIREPROOFING & G : COVER -t 1- f- TO OUR ' •TING TYPICAL FLOOR CONSTRUCTION �II CONCRETE SLAB SPRAY -ON FIRE PROOFING TO 2 -HR RATING 6" R-19 BATT INSULATION POLYETHEYLENE FACING SHEETING STEEL BEAM ACCEPTED 5 =:.: - Yom.~ -4 TYPICAL WALL C '®UCTIO A ------LAYER 5/8" TYPE X GW; BOTH SIDES OF W LL 3(172 S@ 0.C. _ ---BERG. BATT IL. �-2.- �-_�NMIEN Pire a` ., n:.$i_....11,......../s= � 0 E1�'-_ �,�_� -rte- N -�:� __�__�_r,,�- ----_-__ -- -- •lam= 1 ....O.. 11"." I ''''''''.."'.. l'411:1.4111:MaL•1••••••••••=•••••:1,T m."..."....." iinl mom ••••• ••••• immuiml!!I�FnI+uuu)11l!nII;; 111111111111111111111' 1111Ii111111111111111 ••••• ••••• 111111111111111111111111111111111 II1l1!111 I1u111IIH 1U111ll1 ••••• ••••• ••••• muo 1111111 11111 11011114111 IlIIIill - UPPER LEVEL AREA AREA � NUMBER OF DESCRIPTION SQ. FOOTAGE SPRINKLERS OFFICE 17,156 SQ. FT155 HYDRAULIC CALCULATION MOST DEMANDING AREA DATA SQUARE FEET OVER 1504 SQ. FT. HOSE ALLOWANCE) HOSE ALLOWANCE) i DESIGN DENSITY : .15 GPM / 1500 ACTUAL DENSITY : .15 GPM/SQ. FT DEMAND AT BASE OF RISER : 207.3 GPM AT 63.6 PSI (0 GPM INSIDp DEMAND AT CITY CONNECTION : 457.3 GPM AT 71.1 PSI (250 GPM TOTAL TYPICAL WALL CONSTRUCTION PREFINISHED METAL WALL PANEL STRUCTURAL GIRT R-11 BATT INSULATION FIRE RATED POLYETHYLENE - FACING SHEET CAL SLAB CONSTRUCTION C4 NC. SLAB W/ REINFORCEMENT P ' STRUCT. Without Comments As Noted In Red 0 Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and or-dinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will void this.accep tance and will require a resubmittal of revised drawings for subsequent approval. Finalacceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: 1 -I l''®i`I .8y:,Y- 0 TUKWILA FIRE DEPART MEi i Please call: 575-440Z and give this job No. 0 5 ®2 BUILDING SECTION and exact address for shut' (FACING WEST) do-rvn or restoration approval: NTS 5 �u Jf ovf .e,xeeed p per se -con 190/ (Rm©F f ' / pips << 9 \` 1' STORAGE ROOM AREA AREA NUMBER OF DESCRIPTION SQ. FOOTAGE SPRINKLERS STORAGE 2,371 SQ. FT. 24 HYDRAULIC CALCULATION DATA MOST DEMANDING AREA DESIGN DENSITY : .15 GPM / 1500 SQUARE FEET ACTUAL DENSITY : .15 GPM/SQ. FT OVER 1573 SQ. FT. DEMAND AT BASE OF RISER : 258.4 GPM AT 77.2 PSI (0 GPM INSIDE HOSE ALLOWANCE) DEMAND AT CITY CONNECTION : 508.4 GPM AT 84.9 PSI (250 GPM TOTAL HOSE ALLOWANCE) 2'-3" 1'-9" 11.5' 1'-5" MAIN LEVEL in 79 6'-9" AFF AFF Zo Zo 0 :o 4(1^0) . AFF 6" x 4" CONCENTRIC REDUCER GxG 6" FLANGE ADAPTER QTY. SIZE 1 4" 1 4" 2 1 2" 1 1/2" 1 1" 1 4" 1 10" 1 1" 1 6HEAD (0-6) 1 1/2" PIPESTAND 1" BALL VALVE (AUX DRAIN) RISER SECTION 'B' (FACING SOUTH) 0 2 4 SCALE 1/2"=1-0" RISER EQUIPMENT LIST DESCRIPTION DOUBLE CHECK DETECTOR ASSEMBLY BUTTERFLY VALVES VALVE SUPERVISORY SWITCH MAIN DRAIN VALVE PRESSURE GAUGE INSPECTOR'S TEST VALVE WATER FLOW SWITCH ELECTRIC BELL RESTRICTED ORIFICE UNION SPARE HEAD CABINET CONTAINING THE FOLLOWING: MANUFACTURER WILKINS VICTAULIC POTTER ELECTRIC POTTER ELECTRIC POTTER ELECTRIC SPARE SPRINKLERS AND WRENCHES MODEL MANUFACTURER TYPE RELIABLE - RELIABLE PEND UPRIGHT F1 FR F1 FR HEAD FINISH CHR BRZ ORIFICE SIZE 1/2" 1/2" THREAD SIZE TEM'. RATING OUANTITY 1/2" 155° 3 - 1/2" 155° 3 ROOF LEVEL AREA AREA NUMBER OF DESCRIPTION SQ. FOOTAGE . SPRINKLERS ASSEMBLY 74,873 SQ. FT. 308 HYDRAULIC CALCULATION DATA MOST DEMANDING AREA DESIGN DENSITY : .15 GPM / 1500 SQUARE FET ACTUAL DENSITY : .15 GPM/SQ. FT OVER 1545 SQ. FT. DEMAND AT BASE OF RISER : 592.9 GPM AT 86.0 PSI (400 GPM INSIDE HOSE ALLDWANCE) DEMAND AT CITY CONNECTION : 842.9 GPM AT 94.3 PSI (250 GPM TOTAL HOSE ALLOWANCE) MODEL # 450DA 708 OSYSU-2 VSR-F PBD 2410 71? SCOPE OF WORK ARCHER CONSTRUCTION INC. WILL PROVIDE (1) WET PIPE AUTOMATIC FIRE PROTECTION SPRINKLER SYSTEM TO PROTECT THE INTERIOR OF THE BUILDING. ARCHER WILL START WORK AT A SIX INCH SUPPLY FLANGE (BY OTHERS) LOCATED INSIDE THE BUILDING NEAR GRIDLINES 9 AND A.3. CLARIFICATIONS - ALL AREAS PROTECTED BY A WET SYSTEM MUST BE MAINTAINED AT A MINIMUM OF 40° F (BY OTHERS) IN ORDER TO PREVENT THE PIPE FROM FREEZING. EXCLUSIONS - PAINTING OR LABELING OF SPRINKLER PIPING AND/OR EQUIPMENT, EXCEPT AS REQUIRED BY NFPA #13. - ELECTRICAL WIRING OF ANY KIND, INCLUDING, BUT NOT UMITED TO, ELECTRIC BELL WATERFLOW SWITCHES, TAMPER SWITCHES, PRESSURE SWITCHES AND AIR COMPRESSOR. -- CENTRAL STATION MONITORING EQUIPMENT, WIRING AND MONITORING SERVICES. - ALL UNDERGROUND WORK - HEAT TRACING AND INSULATION OF 4" WET SUPPLY MAIN RUNNING THROUGH THE PARKING GARAGE. DESIGN CRITERIA OFFICE: HAZARD: DENSITY: ASSEMBLY: A,ARD: DENSITY: MERCANTILE: HAZARD: DENSITY: UNASSIGNED: HAZARD: DENSITY: NOTES PER NFPA #13 (1999 EDITION) AND THE CITY OF TUKWILA. ORDINARY HAZARD GROUP I .15 GPM / 1500 SQUARE FEET PER NFPA #13 (1999 EDITION) AND THE CITY OF TUKWILA. ORDINARY HAZARD GROUP I .15 GPM / 1500 SQUARE FEET PER NFPA #13 (1999 EDITION) AND THE CITY OF TUKWILA. ORDINARY HAZARD GROUP I .15 GPM / 1500 SQUARE FEET PER NFPA #13 (1999 EDITION) AND THE CITY OF TUKWILA. ORDINARY HAZARD GROUP I .15 GPM / 1500 SQUARE FEET 1. MAINTAIN 2" ANNULAR SPACE AROUND ALL PIPING PASSING THROUGH CONCRETE FLOORS. 2. DISCHARGE MAIN DRAIN TO SAFE LOCATION OUTSIDE. 5-0" FLANGE LOCATION PLAN (PLAN VIEW) 0 2 4 SCALE 1/2"=1'-0" 5'-0" Dc\` RISER ROOM DETAIL (PLAN VIEW) 0 2 4 SCALE 1/2"=1'-0" JAN 2 9 2004 �3cDg , 14800 STARFIRE WAY 04-S-029 SPRINKLER SYMBOLS I ABBREVIATIONS 1 REVISIONS 1 HANGERS 1 ATTACHMENT at DESCRIPTION w Q D J 1.17-'2.w2.4"2 OJZ.9 V-'�F--Jtn Le..wSc , LL.OZ=aO coLLLL LLLLLL�ww¢q)ooa =00000=n¢LL 0�_ w o� 000wo �00000 oov)=�mo 0t--3-i-¢w m00000=Lucomo S2 4aocaincoto(LL?0==u..rt. limo-)a.)-u)v)0 i 11-000001-000<ZE Qmmmmmo-u--a-ZOI C 1 ESCUT. TOTAL en Z 2 w I- ORFICE 1 THREAD 1 MODEL w 4 2 STARFIRE SOCCER ARCHER CONSTRUCTION INC .,..:4. ,,....!. :\ AA ..._ 5 TUKWILA, WA 98188 7855 S 206TH ST (gSUcJ s�r-F`� �r KENT, WA 98032 CONTRACTOR: S.D. DEACON PH 253-872-7222 PHONE: 206-243-6604 FX 253-872-7277 FAX: 206-243-3476 28'-0" 28'-0" 28'-0" 30'-0" 30'-0" 294'-0" 30'-0" 0 30'-0" 30'-0" 0'-0" 30'-0" J L -1-1-7 -I rrrrTT11-1-r rrrTTR1-I-rr 11 11 11111111111111111111 IIII 11111111111111111111 1111 1111111111111111111 1.11111 11111111111111111111 LLL1 1 r1 1 J _I LL11 1 1 JJ_L L 1 -.Li x ke SI ! - 1 1 O.�,Ia ;23D /! Ca X :1 C1 V' 'J .0 v7 CU ' ',R Cts tU n 1 io -I. 1 iia • 1 10-0 .J1L UP 23D ca6OD .v o X w s .irn 5- 23D 23D J J i (V a n C'3 CO 7-0 '3- C N 0./ :2-0 23D-/ O c 0.1 N .M 23D 23D 1 Nt4^ • OD 236 / 0 7-9j 1 1¢ 1 N 1 1¢ 11 1 1 3-0 ',3-6 2-0 2-6 5-0 11 a _2_ m ,,•�t23a_-- .N O 1 0 ..-L+4..-L+41 1 1 c IJry‘"\ f ▪ 23B ol 2 ^� 144°717-7-b-0 U' ; 11 1i2 1� \'; 8-\24 -a 1 2- 2-6 5 .o -- -� �' I 9 3-6 2-0 2-6 5-0 1 ; BOD r3�L.L`1.1 m 236. ' .pc/ N O cY r 1 .<6e �N1N � 14 114 1 .14 000_7-O/- - -o 10-0 4-6 2+0 2 4-01 0.m -R+.\ i 4 4 N ' ID 004 1-0 ! tm o m m co 23B 1 D40/ 14 14 14 O1�i.1. -r�H.'- 6-6 10-0 4-6 -2-6 5-0 f„ o 1 4.41 3 3) 2 `S r :0 L 0 0 0 0 N 430 0 \ N A Wi6x2:: 2/ ,1 21 0 0 N 12-0\ 443 7-9 '0 W14x30 W 1:��126 12-0 4-3 t0 N 13 l4 CU cP 15 W14x30 0. O .01 yam 21 .21N W+_=^2A ro N� 1 4l14XQ 0 • ‘N��tx30 o N f! N .2� N 2�1 W16r.26.2� 2� 0 2� 0/ 1 749 11-0 4-3" 7-9 12-0 40747-34-:- -3 7-9 11-1 iln \ 23B Ni 1-0 tris•-^= 0 N W18x35 W16x26 1 4/18x35 n W18x35 2 011 W16x26 W16?c26 W18x35 W18 W16 (35 ;35 w 4-3 7-9 m 4-0 4 m CO • 23B NCOt-a SEECONTSOL-+--;f,' / VALVE DETAIL 7-7' THIS SHEET : {� • ' o N AUX. DRAIN 23B t 5 2-91" 2 1 . :1.141 0�'0 cq2 I . 2 . 2 ,:262 N2 27-9 4 4-6 --7-6 4-3 7-9 4 A^1/ / 24-5 =- 23B It 4-0 CO23W18 ON Z r N 11 ^6 28D 23D O ........ j yCV 1✓ / 236 m BOD - co m 23B 28B / N N W ISx35 eI-1 BOD -13-6 /moi T-4' W16x26 • 6 0:4 6 :m m 2 11 6\4. M m � (...jN i,+12x2eN 1- 1�!;mJr 11-v 4-1 5• ' J' fFDC / t�'�/.9.�i 111��I 1 / 1 1 7 t� 1 I i����y+ 3'1A'. 2 i -F m CDiJ OIS..L L__co rte 24-0 236 m F.. off` tN• .aD 1; m6-0 N 6-0 N /023D V16x 23D-- co Ip� W16x31 1 res. 4' CHECK ea' W16x31 BUB 6'-11' W16 x.'11 1 BOD 23B CO 23D'23D BOD CO W16x 6 Wi6x'6 W16x26 W16x• r+ FIELD LEVEL DETAIL 12 24 N, - - - - - -'- +. - -SNI SCALE 3/32"=1'-O" UP 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 LL 1 1 J_L L1J _L1 1 U1 r �4x21RV 9) 0 10'-6" AFF 0 RISER CLAMP 1. 2" BALL VALVE 2. 1" RESTRICTED ORIFICE UNION 3. 1" BALL VALVE 4. 22 WATERFLOW SWITCH 5. 0-300 PSI WATER GUAGE 6. 22 BUTTERFLY VALVE 7. 1" BALL VALVE (AUX DRAIN) UPPER LEVEL I N 4 (0-6) 4(2-7) 14(1-0), c^; 4(2-10) 4(1-9) 1. 2" BALL VALVE 2. 1" RESTRICTED ORIFICE UNION 3. 1" BALL VALVE 4. 21" WATERFLOW SWITCH 5. 0-300 PSI WATER GUAGE 6. 22 BUTTERFLY VALVE 7. 1" BALL VALVE (AUX DRAIN) MAIN LEVEL 91_9" AFF RISER CLAMP 1 a to i 12 SN (TOWARD) 1. 2" BALL VALVE 2. 1" RESTRICTED ORIFICE UNION 3. 1" BALL VALVE 4. 22" WATERFLOW SWITCH 5. 0-300 PSI WATER GUAGE 6. 22 BUTTERFLY VALVE 7. 1" BALL VALVE (AUX DRAIN) CO 1 cra FIELD LEVEL CONTROL VALVE DETAIL 0 2 4 SCALE 1/2"=1'-0" ROOM SCHEDULE RM # ROOM NAME CEILING HEIGHT CEILING TYPE 002 OUTDOOR STOR. VARIES - 003 INDOOR STOR. VARIES - 004 STORAGE VARIES - 005 STORAGE VARIES - /V8 -b0 /e1()‘/ 4f -s -o4 ATTACHMENT HANGERS co co D_ O 2 0 z . ¢ 0 zz E2 ow 0 0 z aD ¢ c S a - m iz w Z Q w w m H z 0 W 03 DESCRIPTION 0 ,JCn z� ¢� z O<UEert= u_OYw C7 WLWL wp=� Ow_=QZ =mO-3D_1- t' UI- C3LLLL-LLL-11-1-11G°d z 0 0 0 0 0¢ w O o w 0 W 000000OWC:1�Ci�mU 1- 0 0 Cn [q 0 'ooI-F-F-oI-WC0 DoLuWC2 Q mmmmmULi_OZ±LLL0 u m0 -7a -u ��cnOl LL0000OI-Oo2<Z ¢mmmmm0"'-L+--AZO CO 00 LL) 1- n ea W ref Z 1 N 0 4 111 ce 1- N 1 W a 0 2 LL W d 2 w J ww 1.L 1 1- 0 ARCHER CONSTRUCTION INC 7855 S 206TH ST M O co 0) a W PH 253-872-7222 FX 253-872-7277 ran Z V• (.0 co�O0 6 - OTFD 0 0� <(.9 ct? cy) w co cCn < ANN � 1 1 lii • o co 0 co U) N N LI. Ce • i ID D Q CO o I" Q HZ ZOx 01‹ u FIRE PROTECTION PLAN PERMIT NO. PERMIT NUM JOB NO. S03-47 APPROVAL TUKWILA C.D.T. C.D.T. SCALE AS NOTED DATE 116/04 REVISED / / PLATTED P2OF6 294'-0" EXTERIOR ROOF. 28 • -0" 28'-0" ' rn111II N U.nor 28'-0" 30'-0" NATURAL GAS METER /3730 \ABH 2 PSI SUPPLY / PRESSURE" pp�r/, 30'-0" 30'-0" 30'-0" 30' 0" 30' 0 30'-0" !o -23E 0 BOD 0 0 -23E- /-23E X4/18 [DPS 99 10-0 m 98 10-0 ?23E 1 � Q 2 -I 2- , ---J•10 m a -./7-23E CV 1'09� 6-6 !-2 I � 0 BOD -23E 0 c -23E- 0 --o 0 -23E / 23E- O ❑� -.03 m^ M -23E co seg )OQ• 2 ,•J-2 If • 7-62-6 4-0 ▪ .- m N N 1-23E - co �� TITITR1-fT1TI- I' 1 1 1 I 1 I I 1 I I 1 I I 11LU J1111 1� 12-0 0 N '�`Yom` 181 12-0 i 10-6-1 N 14 10-6 1 23B 0 G. N CO O } m 1 1411 0 12-0 oi I 1 BUIg UP 1 12-0 1 0 N En C"%1 14 e 4 11 12-3 12-0 f It 14 • r7,1l Z I 1-6 r1! i t 1 14, 14 ;?12-3 12-0i11 14 0,1CO •1 11-6 2 -S.11 r (!i ,1t.. .14 ,1 I N ( O 11 1 23B !1 2-3 114 -6 -Lit I 10-6 %! 12-0 0 N I1 y i COI f .KV 1 , I`� f /1SL • �1' 11 14 N 1 • TRANSFER DUCT 0 12-0 10-6. z3B / 273 12=0 07 N\� N 0, 14 N . T i Tl � 1 " CI 1-62 �� 'I LiI 14 51..4.1N; � I � c.„,111 RUILT 14 ! 4�9 9-0 1-9' 3-9 8-0 O CO BOD 14 10-6- i co ▪ 23B 1 14 12-0 •, 0 0) 24/14 Y`;3:,:..1 / �1 D'I0,S;. y/ 12-0 ❑ I%<i,1 O 14 12-0 •1 lSk � BUILT UP 1j, .11'1 ! 12-3 12-0 1' 14 o N1 O ` pit -6 11 108 12-0 V 12-0 =i 0 N �t1 NONCOMBUSTIBLE CONSTRUCTION W111 -I NO HANDUNG OF COMBUSTIBLE MATERIALS BELOW. NAS PER NFPA13 (1999) 5-13.8.1 - EXCEPTION. • CV •a) �r �k 11 12-0 1 -Olt 9- 2.---;;;\,--1, 1 1_11-3 •, 1�, 14 -111 • 14 11j • 2,_ 12-0 I` 140--/------0-----/-0 uT �` ❑ 0 0 0 10-0 10-0 + N co 1 N N I N COp ®� 1 j J ;:� 29 Y` 14 / X2361 v tem c. (IR Risol I X BOD 1 ] xiXffao J' {'\�i�1 i6i 4.� fi� �{ 1-3 11 t� �.3 1� `1i 1. 11 1 123B72/ I0 o9 L9_ Ilf3-0 2-3 CO 08-0 6=0 7 -❑3 �—CV "- Ole,—..—...... N 10-0 10-0 I I I o 1 14 114 m 14 /; co f y 14 i .1.1_123 S i 30 3-9 N 10-0 mI N ; 2-0 • 11 I{ li 14 /O , 10-6 10-0 3-3" 0 0 BUILT UP " 1� 10-0 N 1 I 14 10-0 3-311 1. 23B 1-cr ac `, N 1 "II 1 � 2 :�,IO 2 N M 11 1 11 /O ' 10-0 1 3-3 O 23B / CON I 3iUILT UP it ! 114 10-0 m N >jm nt O 1 11 14 10-0 1 (`i .111;70 1 m10-0 10=0 .Q 1 N ^/�236 1.14 N i `pT 1 I Fl 10-0 • 10-0 m 0 N rY ,a i f 14 .14, 3-9 0 co 0 CO L 24-3 5-7 DN ELM DN 23B 1 14 1240 4-9 8-6; T3-6 • ITi. J 4 F CO 6-6 O m N N 41 23B / N 8-s�h ce4 N X ti{ - i 23BN/M f 1 �1 CO N 14 w ru UX. DRAIN 8-0 t f T.1-1— —14-1 i 1"111 I I 1 _ 1-01 4-9 ITill UJ -u= 2 8-6 0 BOD 4141J T 11 3-9 4-9 11 N 11 3-46 O m o 14 8-6 3=6 co • -0, c') 236N/r,! N 17 I -f T1 TI T 17 I -f 111111111111 ILI11111111.1L 0‹— O 0 14 0 N 12-0 14 , I 12-0 fl 1 i4-0 1 24-3 11 , 0 1� 4-3 "7-9 O CL� CUl • 1 x �I 12-0 BUILT 1� . - I5-5 14\ N 11-0 1 0 [9 • 8-9 1i tiN 41 X 1—OX 14' 14 14 1 7-9 12-0 I -2361' rn v 4-3 ❑ CO UP 9-9 CO col xl 21-9 1.14 14 12-0 co 70 0 o 0 O m O ry O O O TO UH -2 O m.-va-a-�cN N I{ 2 4L ff 23E O N4. 2-3 \T )I 4 N BUILT UF N E `" m 0_9, : `Q . 24-7-H4—'-- .".'-'7-.".-.1-7‘;8-3 11-9 J r 7,211tit'3"?0, 8-45_7-,:-:4_10 10-9 -0 0 m • 4!14;:30 0 N 1i - X 1166. ,. __ . ._:1 0 CO N 0 N 30 0 CO 0 N 1� W O O 8-1 10-0A 0 6-3 3-9 10-0 10-0 2313 ,/o O 21 m CO VI ILI vel - CO 0 0 o 14 „4-1 14 1 ...4--C 1 14 1 ,0 c_ j..2.4_____j,.._iA xic .14 14 23°0 ti\F- 2111111611 .01 T AC 230 I I 11 9-0 —Iii9j9-0 Cel 1,3 CO co EE CONTROL VALVE DETAIL SHEET FP2 co 0-9 0 1 12 co co TO UH -1 1 CU 1.14 ii1‘13V1 01 ie. CO 14 6450 1 20 3 -AUXIDRAIrk: j: B OD 8X40 • co 23D-6 23D f< INSULATED VENT GUIDEAAVAES 18/18 UP 6" FLUE PIPE UP TO ROOF MAIN LEVEL 12 24 EXTERIOR ROOF: NONCOMBUSTIBLE CONSTRUCTION WITH NO HANDUNG OF COMBUSTIBLE MATERIALS BELOW. NAS PER NFPA 13 ( 1999 ) 5-13.8.1 - EXCEPTION. 4-4 3-9 8-0 8-0 EEO DN ROOM SCHEDULE RM # ROOM NAME CEILING HEIGHT CEILING TYPE 101 ENTRY LOBBY VARIES - 102 COURT VARIES - 103 HALLWAY VARIES - 104 HALLWAY VARIES - 106 PRO SHOP VARIES - 107 STUDY VARIES - 108 OFFICES VARIES - 109 DECK VARIES - 110 GAME ROOM VARIES - 111 VEST. VARIES - 112 WOMENS VARIES - 113 WOMENS LOCK VARIES - 114 MENS LOCKER VAFilES - 115 ELEC. ROOM VARIES - 116 JANITOR VARIES - 117 VEST. VARIES - 119 MEN VARIES - 120 STORAGE VARIES - 121 MASSG. WAIT VARIES - 122 MASSAGE VARIES - 123 STORAGE VARIES - 124 THERAPY VARIES - 125 TRAINERS ROOM VARIES - 126 DECK VARIES - 127 OFFICES VARIES - 128 ROOM VARIES - 45-0 3/-etegice CO, ATTACHMENT HANGERS 0 0 CI 0 a. cc co LEI 0 cc 0 fo 8,1 -J >- 0 0 CO 0 0 cc 0 co co en 0 DESCRIPTION re <MI:00303030."-ii- ZD 111 CC DO a. 111 11, a. ca T. cg 4 cc cc -J CO LU CC LLI -J CO • ARCHER CONSTRUCTION INC 7855 S 206TH ST op 1-7 to ILI FX 253-872-7277 u. CO CV CV 0 CY L1.1 FIRE PROTECTION PLAN PERMIT NO. PERMIT NUM JOB NO. S03-47 APPROVAL TUKWILA C.D.T. SCALE AS NOTED DATE 04 REVISED / / �4 • • -00 CO I rn • • • 294'-0" 28' 0" 28'-0" 28'-0" 30'-0" 30,-0" 30'-0" 30'-0" 0•- 0' 41 24/20 SL DROPS 18/12 SL DROPS N rr I 1r - 5" HORIZONTAL FLL E 'JEN— TO HORIZONTAL VENT CAP, IV IN. 10' FROM IAC -6, MIN. -' FROM GAS REGULATOR, SEE REZNOR VENT GUIDELINES /J 14 1 w co 12-0 0 CO 14 U1 m N 12-0 1; m uiiiin!!DN 1wiuiI�I�l1!!!! , Uf 1 14I 1 1 ` 7-91 4-3 2-0 f w I Lu(' ✓ f 441 1 BOD r Drr �:� 11� i 7-9` " 4-3 2-0 I w m N f `N 1a, O I 23E 11 .1 1 IFOR1 FUTUR 1.11, 4' 0 1\4MBF 1-0 w N .Q m 46 i10=0' 1 I t;ml`e 1, N 44 1 1 I —014 1-0 0) m Vol ` 4 w m N 12-0 N 7-9 4-3 2-0- w 10=0 1 g 111. 23E .1r 1 14 t flu .14 ' • 1 1 -0 N w N 1 I DUO Nor I i 124/2vDSL 141-11D(I;,r1 I t 12-0 I • 7-9:4-3 2-0 " f I N 23E . / I N I 12-0 L F [11-1 17-91 - 3-2-0 m m 1 co 1 Jol.I I ; 1a 12 A li 4 • 1 • 1 12-0 1 7-9) I-< C.) F4=424 " M 1 m m 23E I ( 1 '1 N N4{ 4 N Q I I I I N Of 14 1 11i ! 13? I 12 112-0 1 1 7-9 1 • • 4-3 I 01 03 N I N I N I I I 1 I I 14 I 1 .14 1 Ili 1 kie 0 112-0th1 7-9 1 4-3 1 N I LLI N IN 'n f I I I m I I Ih i f I F_ 14 . ! �( 14 1 ;1i I 1 12-0 12-0 111 12-0 II I Ili i 7-9 I ' 4=_3.• 12-0 ',TUTU 1 Lb 03 N 1 N \\J K U �!�o2I I 1 , 1 1 "07' I --�' l'--1--'---J-7I i ;1 II 1 1 1r �j.j'�I 14 1� ® 14 14 1 '1i ,--4-111 --=---4--- 1 i`. He,'—',1147..;...'111 �9=0n I 1 (&-0 h 3-0 1 5-9 3-3 : 1— ¢9 T0' •, 4-fi lw ON I I 1 wl illl; :- ,w IN 1 / 23T NIL l Iii\ 1 (N 23 pi [ b m ; ( 23E /a 1 )(1ih 114 3-0 9-0 N—N_M N ® ; N BOD --11 ... 1 01 14 10-0 J 1 -0 li 1/2 UP UP 14 12-0 10 -0 N "ROOF 114 9-0 w N N m UF - fO 1 NI O i O 1'ij' — ; �� I 1 i —1 i �h »� I ii , i 1 G4 NI Fl OO F Its I 1 111 11 ,I 9-0 w. N 9i I 1'4 w N 9r0 14 ® /9-0 w N 5-9 3-3 w N 1C'J 14 11 5-9 1'3-3 1 9-0 4-6 w m 01 9-0 m 3E N I (� 2-9 ! 10 � o N 1 ' � 1 N IBOD 1 11 0 a 23E 0161 14 9-0 14 w I 1 1 14 w9-0 ® 5-9 1 m 1 N • i} I m 1 203 1 tj 1 ? 14® 14 ® 1 9-0 5-9 w m 9-0 N • 1 EXTERIOR ROOF: 9-0 9-0 4311 Rill 0 F 10-0 w m _L IINURE -aJT 14 • 3-4 BOD N 1 4-6 03 23E 1 w m N rret 10-0 04 n O D4 N 1i)N 23E 23T-1eI 6 w 14 1i 1i i,.y N 3-4 10-0 10-0 1 1=1 w crn 1 co 1 gillbfr Ir N 14 C[f)., o° 1 p 231')1 DC0PC /0 ,. to 10-0 4 . w m � *f • 2-1 tt-0 to -0 21 �4" ��' -(4 �J1LE TO RVU T I i X23 " — "—�— _ I � I; � --=,. O / 2� 2 / 'T / 2------fi--��-21 / ;• _;j04J 11-0 1110111 1▪ - ^rI 1 I AS I DN o L— :c7N____=-Ji ED ll 0 0 1\' 1f L T / 1 24/18 SL DROPS il , , r14_—'. , 1`_t_ ii- —O iii 11 3-9 ' v '6-3 10-0 7-9 2-3 ? 3, �_ 1 '-3i/' f 1p1i, / �2k NONCOMBUSTIBLE CONSTRUCTION WITH NO HANDLING OF COMBUSTIBLE MATERIALS BELOW. NAS PER NFPA 13 (1999 ) 5-13.8.1 - EXCEP77ON. —30 — T 0 DLL 11 I>� 26E1-, JT I O • w —• 23E' 1 I 23E 1" CAPI 0 FOR ,UTLORE O -+ 1 V 0 co NI , —rf 5=9 5-0 1,' 1 tr' 1-7\ PAIR UCT To 1100FCAP 1 1� 8-5 2-3 7-9 2" ^ 10�1 6=3 3-9 10-0 "- .-.71.010-/-` ' Ur s Lin OF CFH1 16L-14';12/061 _ / 23- % 1=�12061L�1 :�,yt --3-0 - 11-0 - 10=0 TT 411-0 , , U N 0 64 of 4-0 f _ ® ®m ® w �•w l6L,',..141 ��FUTU�q2-323ED U3E^ 23E— .h „1 =6 3-6 T 8-0 Nj N 4n1 ® -ml o t = J o 23E FLT0URE L^ (T I O 23E-- 01 3Ej01 C (IF BOD O /- 23E Il 1 N ROOF ON 'ROOF i 1 MOUNT @ 2A-' ABOVE FIELD LEVEL U CI<— 14 & GR— '73E 23E BOD VENT ;SES CONTROL /VALVE DETAIL r SHEET FP2 4114. 0 1/ 1 c -Z v1OUNT @ 26' ABOVE Fi ELD LEVEL HORIZ TQ HOPi 10.' FROV GAS REG VENT GUI NTAL FLUE OATA_ VENT LATOR SFE ELINES VE AP, MIN 4' FROM EXTERIOR ROOF: NONCOMBUSTIBLE CONSTRUCTION WITH NO HANDUNG OF COMBUSTIBLE MATERIALS BELOW. NAS PER NFPA 13 ( 1999 ) 5-13.8.1 - EXCEPTION. \_6" FLUE PIPE UP TO ROOF UPPER LEVEL 12 24 ROOM SCHEDULE RM # ROOM NAME CEILING HEIGHT 1411 201 HALLWAY I C9 — ?18 DSR t 10-0 4 jN I N ROOM VARIES — 204 ROOM VARIES N IBOD 1 11 0 a 23E 0161 14 9-0 14 w I 1 1 14 w9-0 ® 5-9 1 m 1 N • i} I m 1 203 1 tj 1 ? 14® 14 ® 1 9-0 5-9 w m 9-0 N • 1 EXTERIOR ROOF: 9-0 9-0 4311 Rill 0 F 10-0 w m _L IINURE -aJT 14 • 3-4 BOD N 1 4-6 03 23E 1 w m N rret 10-0 04 n O D4 N 1i)N 23E 23T-1eI 6 w 14 1i 1i i,.y N 3-4 10-0 10-0 1 1=1 w crn 1 co 1 gillbfr Ir N 14 C[f)., o° 1 p 231')1 DC0PC /0 ,. to 10-0 4 . w m � *f • 2-1 tt-0 to -0 21 �4" ��' -(4 �J1LE TO RVU T I i X23 " — "—�— _ I � I; � --=,. O / 2� 2 / 'T / 2------fi--��-21 / ;• _;j04J 11-0 1110111 1▪ - ^rI 1 I AS I DN o L— :c7N____=-Ji ED ll 0 0 1\' 1f L T / 1 24/18 SL DROPS il , , r14_—'. , 1`_t_ ii- —O iii 11 3-9 ' v '6-3 10-0 7-9 2-3 ? 3, �_ 1 '-3i/' f 1p1i, / �2k NONCOMBUSTIBLE CONSTRUCTION WITH NO HANDLING OF COMBUSTIBLE MATERIALS BELOW. NAS PER NFPA 13 (1999 ) 5-13.8.1 - EXCEP77ON. —30 — T 0 DLL 11 I>� 26E1-, JT I O • w —• 23E' 1 I 23E 1" CAPI 0 FOR ,UTLORE O -+ 1 V 0 co NI , —rf 5=9 5-0 1,' 1 tr' 1-7\ PAIR UCT To 1100FCAP 1 1� 8-5 2-3 7-9 2" ^ 10�1 6=3 3-9 10-0 "- .-.71.010-/-` ' Ur s Lin OF CFH1 16L-14';12/061 _ / 23- % 1=�12061L�1 :�,yt --3-0 - 11-0 - 10=0 TT 411-0 , , U N 0 64 of 4-0 f _ ® ®m ® w �•w l6L,',..141 ��FUTU�q2-323ED U3E^ 23E— .h „1 =6 3-6 T 8-0 Nj N 4n1 ® -ml o t = J o 23E FLT0URE L^ (T I O 23E-- 01 3Ej01 C (IF BOD O /- 23E Il 1 N ROOF ON 'ROOF i 1 MOUNT @ 2A-' ABOVE FIELD LEVEL U CI<— 14 & GR— '73E 23E BOD VENT ;SES CONTROL /VALVE DETAIL r SHEET FP2 4114. 0 1/ 1 c -Z v1OUNT @ 26' ABOVE Fi ELD LEVEL HORIZ TQ HOPi 10.' FROV GAS REG VENT GUI NTAL FLUE OATA_ VENT LATOR SFE ELINES VE AP, MIN 4' FROM EXTERIOR ROOF: NONCOMBUSTIBLE CONSTRUCTION WITH NO HANDUNG OF COMBUSTIBLE MATERIALS BELOW. NAS PER NFPA 13 ( 1999 ) 5-13.8.1 - EXCEPTION. \_6" FLUE PIPE UP TO ROOF UPPER LEVEL 12 24 ROOM SCHEDULE RM # ROOM NAME CEILING HEIGHT CEILING TYPE 201 HALLWAY VARIES — 202 ROOM VARIES 203 ROOM VARIES — 204 ROOM VARIES — 205 ROOM VARIES — 206 WTR. HTR. RM VARIES — ATTACHMENT HANGERS 0 0 cc 0 -J 0 0 CO 0 DESCRIPTION 0 ce a. CO LO LC LC ct 0 ua tn 0 Its 1— LO 4 cc CI 0 -J 4 -J CO -J CO 111 CC 4 ARCHER CONSTRUCTION INC 7855 S 206TH ST Cri FX 253-872-7277 w F 0 u coco z .,,. (c., 0 . N. o- sci 0 CD '4' Cil Cil Wu) (NI c., IL re D 4 0 I— 0 0 CL LL FIRE PROTECTIOIN PLAN PERMIT NO. PERMIT NUM JOB NO. S03-47 APPROVAL TUKWILA C.D.T. C.D.T. SCALE AS NOTED DATE RDA= FP4 OF 6 PLOTTED 1 0 0 -00 M CV N • 294'-0" 10 28 -0" 28'-0" 28'-0" 30'-0" 30'-0" 30'-0" 30'-0" 3 0 30'-0" DN I�1 e i 1 1 I in M .23 • Q 32 .23 —9E-15=0 : m CO 0 -1 CO 4- ti 04 99E - r I co 9E -c4 O I N r -- POD CO /-9E M co 9E m r 9E 411 -a. CO 9 9E 4.441. O 0 9E /-9E CD ®o CO m O O 0000 -03 Qj 9E m /-9E ▪ •E I -▪ 9E • ■ m • iN f I I CC E BOD —9E 23 23�OJe� 23 9E 10=1.L_4 -J._ a? / 9E_15=0 a 44.44. I� (0 9 \Q ® :111- • 23 23 2 cy CO Iss 9E4-11 10=1___ 0 O m x N 2 23 o ,4_ 23 - 23 QJe as 23 9E J3 -L1 03 ▪ �n m 9 9E 9C i 9E 9E 4444. n I m 9E N —9E n m —9E -s. m —9E N 9E 9E N 9E .7_4( js):-7 9E • M ...i. � .- •10 9E m 9E —9E lo m 9E .- • M OM • M 9E -lo a • CO • v -04 CO —9E co ®^ BOD .- ...r CO • E J'' -9E CO • -_.9E •� —9E' m —9E • N —9E n m —9E -s. m —9E T 21 le 2 i,„ 21-9E /0 2, 9E___,/, -,;,F=62, „c-_-)2 v 9E —9E N 9E n m 9E t5-0 1-1 .-r —9E_8_3 ,� 3-a t_ 021 /40 — ▪ 9E 15_0 2-10 23 9E 6=E 8-6 23 -1"0� 15-0 79/-9E m 1 c co M R ---9E M CO 9E BOD .-01 � 9E '....-01 � 9E • M / -.' CO 9E - M 9E v -r —9E lo m .- ..--9E OM a tI • 9E -lo a • CO • v -04 CO —9E co ®^ BOD .- -01 CO --9E 9E M co • -_.9E •� —9E' m —9E • (0 m - co m T 21 le 2 i,„ 21-9E /0 2, 9E___,/, -,;,F=62, „c-_-)2 v 9E —9E N 9E n m 9E t5-0 1-1 .-r —9E_8_3 ,� 3-a t_ 021 /40 — ▪ 9E 15_0 2-10 23 9E 6=E 8-6 23 -1"0� 15-0 79/-9E m 1 c co M R ---9E M CO 9E BOD 9E I u, -sr ccr 9E r —9E -r (0 9E • M / -.' CO 9E - M 9E i L00 • m •M • OM CO 9E tI • 9E m CO • v • ^ • -9E is, 9E -01 0 9E —9E •� —9E' m (0 co —9E - co 9E • • 03 m 9E I u, 01 m E JI N O LO 9 r N 9E 9E 00 m 9E 4 m 1 o... r co 9E • M / -.' CO 9E - M 9E i L00 ^ CO m •M • OM CO 9E m 03 —9E m • _ • ^ • -9E is, ,.-9E _J I —9E -00 —9E' m co 9E co —9E 01 m E JI N O LO 9 r N 9E 9E 00 m 9E 4 m II N �� 9E csr m -CO • 0 CO —9E r a0 —9E 1 o... r co -9E -(9 NI- • -44 N. m 9E i ^, m 9E m cr • CO 9E • 03 —9E CO (0 • - a co II N �� 9E csr m -CO • 0 CO —9E r a0 —9E CO CO BOD 1.1 CO SE CO 1 CN 9E —04 I v co -9E sl- •--E co —9E In In m cr CO • CO 9E 03 03 —9E CO CO CO BOD 1.1 CO SE CO co —9E C.4 CN 9E co co co 9E co —9E In In cr co CO 03 03 CO 17 • • co co BOD co —9E -04 co BOD 03 9 9E CO —9E NC 9E C.4 CN 9E -9E co 9E co —9E In In co co -04 co BOD 03 9 9E CO —9E NC 9E 9E CO c- o co 9E 03 BOD —9E —9E co 9E 03 CO CO CO CO 03 03 CO C▪ O 9E 15-0 kl • 0-21 0-11 14-1 CO cr CO [..._s SEE CONTROL VALVE DETAIL CO .921-9n, .4441. 15-0 kl • ROOF LEVEL 12 24 wr'sJ rzoo110 , ga_J, ATTACHMENT HANGERS 1- - J 0 —J 0 1- 0 0 rn ca DESCRIPTION ca cg UI a. . - - I .7 1.1.7: je . C:C C =L. L I I a . W:11-LJ-U-LLALL:::ffiLlj:,.:5-._ 1::::::°°C11.1..1:1111;:jC;C7) 11:1:1173:13U-201:::: 00 CO ea CC a. 111 IU re 0 4 cc 111 CI LL CD 4 ct 0 ARCHER CONSTRUCTION INC 7855 S 206TH ST csi co 4 PH 253-872-7222 FX 253-872-7277 4 111 • CO CO 0 ct co co FIRE PROTECTION PLAN PERMIT NO. PERMIT NUM JOB NO. S03-47 APPROVAL TUKWILA C.D.T. C.D.T. SCALE AS NOTED DATE 04 C.4 CN 9E -9E co 9E co —9E In In co 03 • -00 CO co 9E co —9E 9E CO c- o co 9E 03 BOD —9E —9E co 9E 03 CO CO CO CO 03 03 CO C▪ O 9E 15-0 kl • 0-21 0-11 14-1 CO cr CO [..._s SEE CONTROL VALVE DETAIL CO .921-9n, .4441. 15-0 kl • ROOF LEVEL 12 24 wr'sJ rzoo110 , ga_J, ATTACHMENT HANGERS 1- - J 0 —J 0 1- 0 0 rn ca DESCRIPTION ca cg UI a. . - - I .7 1.1.7: je . C:C C =L. L I I a . W:11-LJ-U-LLALL:::ffiLlj:,.:5-._ 1::::::°°C11.1..1:1111;:jC;C7) 11:1:1173:13U-201:::: 00 CO ea CC a. 111 IU re 0 4 cc 111 CI LL CD 4 ct 0 ARCHER CONSTRUCTION INC 7855 S 206TH ST csi co 4 PH 253-872-7222 FX 253-872-7277 4 111 • CO CO 0 ct co co FIRE PROTECTION PLAN PERMIT NO. PERMIT NUM JOB NO. S03-47 APPROVAL TUKWILA C.D.T. C.D.T. SCALE AS NOTED DATE 04 10" RETAINER STRAP BOTTOM FLANGE OF BEAM i - 10"Z-PURLINS@5'-0"O.C. 445-1 /2" DIA. x 6" EYE ROD W/ �.„/I ® ROD OUPLING BOLT & 1/2�� x 5�� ATR W/ NUT & WASHER NUT& WASHER -.6-1/2” x 9" ATR W/ NUT & WASHER 4" METAL ROOF/DECK THREAD in Ian CENT#EOOFFDELIN ion LENGTH 11/2" 0.75"j �GRINNELL FIG. 92 TOP FLANGE .. OF STEEL BEAM - '� BEAM CLAMP ATR TO BOAM LENGTH 0'-4" 11° •PIPE 2'-6" ii,,) II SHOP DRILL 9/16" HOLE 1/2" ALL THREAD ROD LENGTH PER PLAN HANGER RING _6„ 0'-4" 2" DIA. SCH. 40 TRAPF7F PIPE 5'-8" LONG `Tfri �'� SEE TABLE FOR I. SEE TABLE FOR SIZE HANGER RING \ ROD SIZE PIPE SIZE ROD SIZE SIZE ROD SIZE 1" - 4" 3/8 „ „ 3/8 5"-8"1/2 5 -8 1/2 FIELD DRILL OR PUNCH HOLE IN BOTTOM OF FLANGE OF BEAM. HANGER DETAIL 'U' HANGER DETAIL 'D' ii HANGER DETAIL 'T' • NTS NTS NTS 3/8" X 3 3/4" KWIK BOLT u (21/2" EMBED) ) CONCRETE DECK 3/8" HILTI QM BOLT 1 ''116' d a ' • • • • o - d ° d a a ° d ' a . • 4 ° ° �- TOLCO FIG. EYELET 58 -- . ATR —.- \ GRINNELL 138R ROD THREAD EXTENSION SPLIT CLAMP HANGER DETAIL 'S' 3/8" PIPE HANGER RING ==PIPE HANGER DETAIL 'E' 3/8" ATR 3/8" HILTI HDI-P ANCHOR HANGER RING HANGER DETAIL 'B' NTS NTS Nig 8" POST TENSION CONCRETE SLAB 3/8" X 3 3/4" HILTI KWIK BOLT (2 1/2" MIN EMBED) (2) 3/8" X 3 3/4" HILTI KWIK BOLT (2 1/2" MIN EMBED) 12" CONCRETE WALL .4 • • 4 • • •° 4 • �• d •. 4• d • • 4. 4 ' •' 4 • 4 .4 4• d d . 4 • . ;• d •. 4 d G, �� 450 TOLCO FIG 980 � 45`��" BRAC) OE ATTACHMENT TOLCO FIG 1000 BRACE ATTACHMENT (2) TOLCO FIG 1000 �� (2) 1(3-0) SCH 40 PIPE FAST CLAMP SPRINKLER (SIZE PER PLAN) LATERAL A)D MAIN . — 1(3-0) SCH 40 PIPE BRACE DETAIL '2' FAST CLAMP 1 SPRINKLER MAIN (SIZE PER PLAN) 4 -WAY BRACE DETAIL NTS NTS j . / A; aRobert Pool3 391-O7-364 '\111 SOO ,L., e, o y- 5 --o9 ATTACHMENT HANGERS 1- cc w 0) z_ w 1- w 0 z O 0 w z w N w CL 1- H z 0 W m DESCRIPTION W a 0 a W ��YI-JCA �LLY�Z LLmJQ�Q=.1�- 0U�p=J LL. LL LLLLLL1-wWLQQ)cpVd z00000��QLL. • wOOOOOOowo=u) C) m000OO�wNOOtt�J_ QmmmmmUti?OZ�Li� u_CCI 0 -)a1 -v) ��u)0 LI- o0000HOoe¢z ¢mmmmm0wu--pZO SPRINKLER SYMBOLS I0 I` C.) W 0 1 z IL 0 N Ir m o. 2 W in L) u� W t3 N�N 0 4 W z J W 0 tr w u- tr w 4 w J m J w w J m J w rn 0 0 4 1- 0 1- ARCHER CONSTRUCTION INC 7855 S 206TH ST PH 253-872-7222 FX 253-872-7277 11 11 ,. co Z co cco O 1 wMCO Q a NN O CO CO fn NN FIRE PROTECTION PLAN PERMIT NO. PERMIT NUM JOB NO. S03-47 APPROVAL TUKWILA C.D.T. C.D.T. SCALE AS NOTED DATE04 �;(0F 6 p ■1 � ���. OF WORK: EXISTING AREA 2. PLAN SUBMITTAL TO & APPROVAL BY THE CI 3. MATERIALS PER NFPA #13 STANDARDS AS S 4. TESTING PER NFPA #13 & THE CITY OF TUK T�CLARIF(CATIONS: D COVERAGE & STANDARD COVERAGE SSU IN THE NEW AREA Y OF TUKWILA LECTED BY ARCHER CONSTRUCTION, INC. ILA. 1. ALL AREAS PROTECTED BY A WET SYSTEM M (BY OTHERS) IN ORDER TO PREVENT THE PIP ORAGE 001 CRITERIA: ST BE MAINTAINED AT A MINIMUM OF 40°F FROM FREEZING. 1. CRITERIA BASED ON NFPA #13.OHG I AND TH 2. MAXIMUM STORAGE HEIGHT 6'-0". FITTER NATES: E CITY OF TUKWILA. ALL PIPE HANGERS TO BE PER NFPA 13 2. AXIMUM HEAD SPACING 196 SQ. FT. 3. NEW PIPING TO BE EDDYFLOW, SCHD 40, 10 & DI FITTINGS. ORAGE in 002 NOTE ;XISTING N0 UD I ICI) l ,8-0 = EXISTING PIPE = NEW PIPE O (E)= EXISTING SSU SPRINKLER ® (N)= NEW 1/2" SSU SPRINKLER ® (N)= NEW K=11.2 EC SSU SPRINKLER Without Comments As Noted in Red Per The Attached Lett- These plans have been reviewed by The Tu Prevention Bureau for conformance with cu standards. Acceptance is subject to errors ,;missions which do not authorize violations Ttandards and ordinances_ The responsibili .:equacy of design rests totally with the -.editions, deletions or revisions to these d this date will void this acceptance and will r resubmittal of revised drawings for subsea Final acceptance is subject to field test and The Tukwila Fire Prevention Bureau. te: -23-/ By: Ila Fire ent City nd of adopted for the .' • ner. wings after • ulre a -nt approval. nspection by This re 2 - 4-3 CL=5" ;BOB REVIEWEDHANGER THE FPI CONSORTIUM, INC. _X No Comments/No Exceptions Taken Make Corrections As Noted Revise and Resubmit Reviewed for general conformance with the Design Basis. iew is not intended to authorize any work not in accordance with Code. By: CPA Date: 4/9/2019 Digitally signed by CarI Carl Anderson, PE Anderson PEIte 20190409 14:38:57 -07'00' 34x30 .416.26. AREA OF WORK """"_'F4":arr—, 1111/1111.11111111111111111111111.10 CONNECT TO (E) N CONNECT TO (E) 18X35= 16X31 i FLEX W1 IILJ lL-LU HANGER #1/20 OD ^ as Bi 289 236 16X31 W18Xf VACINTY MAP i�"T �ii���iD�rt��i• �►�� 11 �A� I -'�•1� [ 11 1I .S��li��t�l��i����� _ a�._!�� >r����Z � �.y, rte.► ARIL`I.....�tl'.i/�.w►' CXM' r lE.~1:xMlirgillIMMI=11h=lir• ' I - - 2'-011 C ' 1-1-__--_1�� ��!� 15' 0" 44' -•10" 11' -11 1/4" 6' 4" 11' - 7 5J8" �� 9 1/8"' i 6"in.mmor, lia 5 i� 202' - 6" tsumsmmmmEpnI Iii.‘111 It... w1 mai =II 0`7amain L. Wrill (1 ii AREA OF WORK 11 •I 1_ I SEE FP -2 FOR.CON1NUATION 0 1 2 4 LiKvVILA FIRE DEEPAP,TIMENT Plea all 205-575-1407 and giy��! ' F� / f's'el'��ct No. -11S15 - 7 tu'd �' and exact address ror shut- down or restoration approval. PAI O LEVEL PIPING PLAN SCALE: 1 /8"------1"— 0" APR 1 n . 1 TUKWILA FIRk HANGERS HYDRAULIC DESIGN INFORMATION ABBREVIATI NS WATERFLOW INFORMATION SPRINKLER SYMBOLS STARF1RE SPORTS COMPLEX REVISIONS —� CONSTRUCTION1 C _ DATE DESCRIPTION BY A BEAM CLAMP W/ RETAINING STRAP AREA NUMBER #1 AREA 1740 sQ FT SQ. FT. CODE NFPA 13 DENSITY 15 GPM/SQ. FT. 'Aran= ALLOWANCE HAZARD rl JA IsysTEM ORDINARY GROUP 1 TYPE OUTSIDE HOSE 250 GPM ALLOWANCE WET AREA PER 324 SPRINKLER AFF BTS BOD BOJ BOP BOT CTS FO IFOW NAS OTS UNO --4— GF ABOVE FINISH' O FLOOR BOTTOMTOST— UCTURE BOTTOM OFD K BOTTOM OFJO= 1ST BOTTOM OFP RLIN BOTTOM OFTR=L..1SS CUT TO SUIT FIELD ORDER INSIDE FACED WALL NOAUTO.SPRI `\KLERS OPEN TO STRIJ =GTURE UNLESS NOTEDD ERWISE RIGID COUPLING FLEXIBLECOURN(== STATIC XX PSI SYM MAKE MODEL SIN# TYPE FINISH K -FAC. THREAD ORIFICE TEMP CANOPY QTY RESIDUAL XX PSI ' ® RELIABLE J112 RA7326 SSU BRASS K=11.2 3/4" 3/4" 155° NA 43 4-5-19 1 Changes per Carl Anderson review MM B SIDE BEAM BRACKET 14800 STARFIRE WAY TU KWI LA WA. 98188 ' PERMIT NO: - C EYE SOCKET ® VICTAULIC V2704 V27 SSU BRASS K=5.6 '/" 1 " 155° NA 51 GPM FLOWING XXXX GPM D NUT &PLATE WASHER JOB NO: S19-32 DATE 8c TIME X)C/X)VXXXX E KWIK-BOLT TOTAL SYSTEM SEE CALCS REQUIREMENTS: F HDI -P AUTHORITY: CITY OF TUKWILA PER: G SAMMYSIDEWINDER HYDRAULIC DESIGN INFORMATION CONTRACTOR: RED HAWK GROUP .. DESIGNER: MIKE LOCATION: H SAMMY SUPERSCREW J COACH SCREW ROD AREA HAZARD SYSTEMCODE SCALE: NOTED K CEILING FLANGE FIRE SPRINKLER DIVISION 7855 S 206TH STREET (ENT WA 98032 SHONE 253-872-7222 FAX 253-872-7277 NOTES: L U -HOOK REMOTE AREAGPM/SQ. DENSITY FT. INSIDE HOSE ALLOWANCE OUTSIDE HOSE ALLOWANCE AREA PER SPRINKLER DATE: 3-26-19 M SHORT STRAP REVISED / / FP WALTRAPEZE RACKET TOTAL SYSTEM REQUIREMENTS: TOTAL PROJECT SPRINKLERS = 94 TOTAL SPRINKLERS THIS SHEET 94 P PLOTTED // 1 OF 1 INPUTS AND ACTIONS sA\ -;1‹4()<(>8% Q`dL�' �9 `OS`sp\ �'9�F�'PTPA, Gyl 4 ,o 9 `s�L�S� `�9��Q4G %��'�,0 C,r� `iOO� 4 05,02 el 'P+ 05, F Gly. ly, `Q>s F� OUTPUTS AND CONTROLS OPERATE ALL AREA EVACUATION SIGNALS 0 SOUND LOCAL PIEZO AT FACP 0 0 0 0 • INDICATE DEVICE AT FACP 0 0 0 • SEND ALARM SIGNAL TO C.S. MONITORING 0 SEND TROUBLE SIGNAL TO C.S. MONITORING • • 0 0 SEND SUPERVISORY SIGNAL TO C.S. MONITORING 0 SEND WATERFLOW SIGNAL TO C.S. MONITORING ILLUMINATE LED ON DETECTOR FIRE ALARM SY'STI�M 14800 STARFIRE ikNeo TU K'- :'I 98188 Symbol Legend SYMBOL DEVICE MOUNTING DETAIL MANUFACTURER PART NUMBER QUANTITY 1 9 AMP NAC POWER SUPPLY W/SYNC (EXISTING) ///, ROOF DECK //////////// ///////// 5499 1 '� MOUNT TO E POTTER ELECTRIC SIGNAL NAC POWER SUPPLY 6 AMP 4 OUTPUT POTTER ELECTRIC SIGNAL PSN -64 1 FAA PSN -64 MB INTELLIGENT 50 WATT AMPLIFIER (EXISTING) FARENHYT STRUCTURE 1 AMP E / BASE HEAD J -BOX ABOVE CEILING DEVICE SUPPORT BRACKET SPEAKER/STROBE, M -C, WHITE, CEILING SYSTEM SENSOR SPSCW 2 / SPEAKER/STROBE, M -C, WHITE, CEILING SYSTEM SENSOR SPSCW l DI SPEAKER/STROBE, M -C, WHITE, CEILING SYSTEM SENSOR SPSCW 2 ,❑".4 SPEAKER/STROBE, M -C, WHITE, CEILING SYSTEM SENSOR SPSCW PLASTER RING o. EOL 4.7Kff \ CEILING SILENT KNIGHT EOL -4.7 2 BASE HEAD SMOKE OR HEAT DETECTOR HORN/STROBE C D MANUAL PULL STATION \it BACK MOUNTED WALL BOX TO FRAMING LIFT FIRE ALAAN0 80" 48" r r INPUTS AND ACTIONS sA\ -;1‹4()<(>8% Q`dL�' �9 `OS`sp\ �'9�F�'PTPA, Gyl 4 ,o 9 `s�L�S� `�9��Q4G %��'�,0 C,r� `iOO� 4 05,02 el 'P+ 05, F Gly. ly, `Q>s F� OUTPUTS AND CONTROLS OPERATE ALL AREA EVACUATION SIGNALS 0 SOUND LOCAL PIEZO AT FACP 0 0 0 0 • INDICATE DEVICE AT FACP 0 0 0 • SEND ALARM SIGNAL TO C.S. MONITORING 0 SEND TROUBLE SIGNAL TO C.S. MONITORING • • 0 0 SEND SUPERVISORY SIGNAL TO C.S. MONITORING 0 SEND WATERFLOW SIGNAL TO C.S. MONITORING ILLUMINATE LED ON DETECTOR FIRE ALARM SY'STI�M 14800 STARFIRE ikNeo TU K'- :'I 98188 Symbol Legend SYMBOL DESCRIPTION MANUFACTURER PART NUMBER QUANTITY 1 9 AMP NAC POWER SUPPLY W/SYNC (EXISTING) SILENT KNIGHT 5499 1 FACP E POTTER ELECTRIC SIGNAL NAC POWER SUPPLY 6 AMP 4 OUTPUT POTTER ELECTRIC SIGNAL PSN -64 1 FAA PSN -64 MB INTELLIGENT 50 WATT AMPLIFIER (EXISTING) FARENHYT VIP -50 1 AMP E 1 SPEAKER/STROBE, M -C, WHITE, CEILING SYSTEM SENSOR SPSCW 2 SPSCW SPEAKER/STROBE, M -C, WHITE, CEILING SYSTEM SENSOR SPSCW 5 DI SPEAKER/STROBE, M -C, WHITE, CEILING SYSTEM SENSOR SPSCW 2 ,❑".4 SPEAKER/STROBE, M -C, WHITE, CEILING SYSTEM SENSOR SPSCW 1 o. EOL 4.7Kff EOL 4.7K SILENT KNIGHT EOL -4.7 2 Bill of Material Qty. Description Manufacturer Model Part No. 1 Panel: FAA RISER, BATTERY & CIRCUIT CALCULATIONS - FIRE ALARM SYSTEM INITIATING DEVICE CIRCUIT BELDEN 1 NAC POWER SUPPLY 6 AMP 4 OUTPUT POTTER ELECTRIC SIGNAL PSN -64 PSN -64 1 6 AMP, 4 NAC PWR SUPPLY MB POTTER ELECTRIC SIGNAL PSN -64 MB PSN -S4 MB AUXILIARY DEVICE CIRCUIT BELDEN 5120UL 14/2 FPLR 10 SPEAKER/STROBE, M -C, WHITE, CEILING SYSTEM SENSOR SPSCW SPSCW 2 EOL 4.7K SILENT KNIGHT EOL -4.7 EOL -4.7 11- F-119 FIRE ALARM CABLING LEGEND CODE CABLE LINETYE CIRCUIT TYPE MANUFACTURER PART NO. CABLE TYPE A RISER, BATTERY & CIRCUIT CALCULATIONS - FIRE ALARM SYSTEM INITIATING DEVICE CIRCUIT BELDEN 5320UL 1812 FPLR B NOTIFICATION APPLIANCE CIRCUIT BELDEN 5120UL 14/2 FPLR C AUXILIARY DEVICE CIRCUIT BELDEN 5120UL 14/2 FPLR D - - -•- - -.- -- - - - - -- REMOTE ANNUNCIATOR CIRCUIT BELDEN 5320UL, 5120UL 18/2 FPLR, 14/2 FPLR i 14 Starf'ire ►t �•. _ -r, Gott Stui9inc s.4' oup Seattie, wA King County_ South T rna rnErii Plant urPrS. rA n@r9I •' Tukwila Farntly. Fun Ce mer &... outh._ ent.e r:S t VICINITY MAP S II DRAWING INDEX SHEET NO. SHEET DESCRIPTION FA0.1 TITLE SHEET FA1.1 FLOOR PLAN - FIRE ALARM SYSTEM FA2.1 RISER, BATTERY & CIRCUIT CALCULATIONS - FIRE ALARM SYSTEM A D 1319 MAY ruk FIRE DRAWING ONLY TO SCALE IF PLOTTED AT 30" X 42" N01 $ N OD 1- O< H N W � Q • I p c H O � It H I m O O Z ' vl O '� �-a co Eh m;. �o o 4) S d CO03 46 may, 03 } • U — O O— •D N rnLi5 03 � v d O a v 3 a3 IF" G P ox 23889 1V III Crek, WA 98082 CA- ) -ei-®5—(z) F_ (8663 -798-9241 W Q 0 W MEM ADRIAN M. STEIK Senior Engineering Technician, Level 4 NICET Certifcation Number. 093706 Authorizing Signature: DRAWN BY: RMV SHEET TITLE: CHECKED BY: Adrian M. Steik PLOT DATE: 5/17/19 N Q\ 4tu 03N I- el D'U Q LTJ 5 ,( • (I) H 0� YO H • I co 0 o 9• Z �0 P'0 EA. 232E1aa. 9 Mill Creek, WA 98082 (4253 X05-07583 1=_ (8663 798-9241 0 > W e. co Vf ADRIAN M. STEIK Senior Engineering Technician, Level 4 NICET Certifcation Number. 093706 Authorizing Signature: A.. >40 ‹c0 sr. Pco tLLi< ;A(•5' OC, c0I.+ DRAWN BY: RMV SHEET TITLE: W H W Z c 0 0 u. CHECKED BY: Adrian M. Steik PLOT DATE: FACP E- FM ALP SPK1-001 FA-NAC1-001 110CD 1W SPK1-002 ,iye FA-NAC1.002 I�FI4 110CD 1W 110CD 2W SPK1-003 FA-NAC1.003 i SPK1-006 FA-NAC1.006__.._.__.._..L. — . 75CD 1W SPK1.004 FA-NAC1-004 110CD 1W SPK1-005 FA-NAC1-005 110CD 1W - ._.._.._..—.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._. _� I SPK1-007 o FA-NAC1.007 ( 110CD 2W 1 I I _ I I I I II VII � 1�1 �.._.._.._.._.. 30CD 0.5W SPK1 -008 FA-NAC1-0081 ' I I I Vis. 1 1 I I I _.r .._.._.._ ._. _..___.._.._.._.._.._.._..- - -.._.._.i SPK1-009 1Ai OCD 1W U9 i I I i L FLOOR PLAN - FIRE ALARM SYSTEM ASCALE -,re„p a 9 II SPK1 EOL 4.7K L I IR. FA-NAC1 EOL 4.7K 11 • SPK1-010 ! FA-NAC1.010 75CD 1W S 14 f�1 PLAN NORTH DRAWING ONLY TO SCALE IF PLOTTED AT 30” X 42" 5/17/19 PROJECT NUMBER: 19-106 DRAWING ONLY TO SCALE IF PLOTTED AT 30" X 42" Battery Calculations for Panel: FAA Part No:PSN-64 - NAC POWER SUPPLY 6 AMP 4 OUTPUT Job number. 1 Part No. Qty. Description Standby Total Standby Alarm Total Alarm Gauge PSN -64 Panel Equipment SPK1 20.4V 515'-5 PSN -64 MB 1 6 AMP, 4 NAC PWR SUPPLY MB 0.060A 0.060A 0.205A 0.205A 002 SPSCW SPEAKER/STROBE, M -C, WHITE, CEILING, 110CD Total Panel Stby 0.060A Total Panel Alarm 0.205A 003 SPSCW Peripheral Devices 39'-10 0.202A 18.868V (0.349V) SPSCW 7 SPEAKER/STROBE, M -C, WHITE, CEILING (Notification) 0.000A 0.000A 0.202A 1.414A SPSCW 2 SPEAKER/STROBE, M -C, WHITE, CEILING (Notification) 0.000A 0.000A 0.158A 0.316A SPSCW 1 SPEAKER/STROBE, M -C, WHITE, CEILING (Notification) 0.000A 0.000A 0.094A 0.094A EOL -4.7 1 EOL 4.7K (Notification) 0.000A 0.000A 0.000A 0.000A 008 SPSCW SPEAKER/STROBE, M -C, WHITE, CEILING, 30CD Total Peripheral Stby 0.000A Total Periph Alarm 1.824A 009 SPSCW SPEAKER/STROBE, M -C, WHITE, CEILING, 110CD 45'-0 0.202A 17.584V (0.099V) 010 SPSCW SPEAKER/STROBE, M -C, WHITE, CEILING, 75CD Total Standby Amps 0.060A Total Alarm Amps 2.029A Standby time: 24 Hrs 1.44Ah Alarm time: 5 Min 0.169Ah Battery requirement: 1.609Ah Compensation Factors - Standby: 1.2 Alarm: 1.2 Re• uirement with corn. ensation: 1.931 Ah FA-NAC1 76CDD I W 110CD I W 30CD0.5W 110CD 2W 75CDD11W 110CD 1 W 11ocD i W 110CD 2W 110CD I W 110CD 1 W Ca. SPKI u, EOL 4.7K f] L•J`i L -=J`• LST L_f'Y LJ�---11 EOL 4.71<1) FA-NAC1.010 FA-NAc1.009 FA-NAC1.008 FA-NAC1.007 FA-NAC1.006 FA-NAC1.005 FA-NAC1.004 FA-NAC1.003 FA-NAC1.002 FA-NAC1.001 SPK1.010 SPK1.009 SPK1.008 SPK1.007 SPK1.006 SPK1.005 SPK1.004 SPKI-003 SPK1.002 SPKI.001 AMP (EXISTING) FACP (EXISTING) FAA Level 1 ARISER DIAGRAM - FIRE ALARM SYSTEM SCALE = NOT TO SCALE Circuit Calculations Panel: FAA Card: 00 Circuit:FA-NAC1 Circuit Name: FA-NACI Circuit Type: Notification Terminal Voltage: 20.4V:DC Amperage: 3.000A Cable: 14/2 SOL JKT FPLR 1M RL RED #14 Calculations based on Running Total Length. Design Criteria: Ambient temperature: 167°F Minimum operating voltage: 16V Device Part No Appliance Desc Distance Current Voltage Voltage Drop Gauge PSN -64 Panel SPK1 20.4V 515'-5 001 SPSCW SPEAKER/STROBE, M -C, WHITE, CEILING, 110CD 78'-6 0.202A 19.515V (0.885V) 002 SPSCW SPEAKER/STROBE, M -C, WHITE, CEILING, 110CD 29'-8 0.202A 19.216V (0.299V) 003 SPSCW SPEAKER/STROBE, M -C, WHITE, CEILING, 110CD 39'-10 0.202A 18.868V (0.349V) 004 SPSCW SPEAKER/STROBE, M -C, WHITE, CEILING, 110CD 46'-8 0.202A 18.516V (0.351V) 005 SPSCW SPEAKER/STROBE, M -C, WHITE, CEILING, 110CD _ 40'-11 0.202A 18.26V (0.256V) 006 SPSCW SPEAKER/STROBE, M -C, WHITE, CEILING, 75CD 51'-9 0.158A 18.001V (0.26V) 007 SPSCW SPEAKER/STROBE, M -C, WHITE, CEILING, 110CD 4T-4 0.202A 17.811V (0.189V) 008 SPSCW SPEAKER/STROBE, M -C, WHITE, CEILING, 30CD 4V-2 0.094A 17.683V (0.128V) 009 SPSCW SPEAKER/STROBE, M -C, WHITE, CEILING, 110CD 45'-0 0.202A 17.584V (0.099V) 010 SPSCW SPEAKER/STROBE, M -C, WHITE, CEILING, 75CD 88'-3_ 0.158A 17.498V (0.085V) EOL -4.7 EOL 4.7K 2'-7 0.000A 17.498V (0V) 516'-8 1.824A Tota (Total VDrop Percent:14.22%) Total Voltage Current: 1.824A Drop : 2.902V Circuit Calculations Panel: AMP Card: 04 Circuit:SPK1 Design Criteria: Ambient temperature: 167°F Maximum dB Drop: 3 dB Circuit Description Type Total Len SPSCW EOL -4.7 Total Watts Gauge dB Loss Max Allowable Len SPK1 Notification/Audio 70v 515'-5 10 1 11.50 Watts #14 -0.06 dB 28628' BATTERY & CIRCUIT CALCULATIONS - FIRE ALARM SYSTEM SCALE = NOT TO SCALE Do N Ql co o it N Lu 03 Ch E 12) a I-3 • SI 74 • HrnLa °N= kI j o v '- o zs3 ectiVQ /> ® EX. 2. 8 8 9 A tiII Crek, WA 98082 (42 3 405-055 F_ (866) X9a-92-4-1 F O z Fn ADRIAN M. STEIK Senior Engineering Technician, Level 4 NICET Certifcation Number. 093705 Authorizing Signature: l4 . JD SHEET TITLE: LU tet 1 t/9 0 .r® LU CCI tei DRAWN BY: RM CHECKED BY: Adrian M. Steik PLOT DATE: 5/17/19 PROJECT NUMBER: OFFICE L215 1 HANGER RING --- C CHANNEL SAMMY SUPER SCREW DSTR 1 3/8" A.T.R. SAMMY SUPER SCREW DSTR 1 HANGER TYPE Sd SCALE: NONE OFFICE 217 OFFICE 218 1 EXISTING OFFICE 214 1 i it LI EXISTING OPEN OFFICE [219 154 1l4 1 i4 rasr EXISTING OFFICE 1213 11:4 O MMI EXISTING OFFICE 212 1 12-0 MUM T 0 1) i 9 1 1 93 154 93 93 93 93 93 +v. cN Wt'-• v A cc —I 4 Z Ct Lu -. to a m. CD A .g..a ..� M. M... M. M M. M. M. M. _ 1 i4 8-0 0 mi.a mass mm a c€.a NEW OFFICE 1 226 1 0-6 NEW OFFICE 225 /Ct1 R 0-101;4 1 ['MU P J. t� 1-0 UM, 0 NEW OFFICE 211 6-0 CD O A .ars ,m rma N LOCKER ROOM_ 11/2 IA 1',4 r'' awn my v.r sr --,. a r va z. va v. v. m= a s ¢= sem e,.e EXISTING OFFICE L219 ] p 5 1 EXISTING RECEPTION 201 *1,, Mrti rtn/;zm ram ,2.2 r�� P TOILET 224 [210 F FIRE SPRINKLER PLAN SCALE: 1/4" = 1'-0" EXISTING LARGE CONFERENCE 2091 SPRINKLER HEAD SPACING IS LIMITED TO 130 SQ. FT. PER TUKWILA ORDINANCE. • AREA OF WORK SCOPE OF WORK 1. RELOCATE (8) EXISTING SPRINKLERS FOR THE NEW WALL OBSTRUCTIONS. 2. PROPOSAL BASED ON THE USE OF THE EXISTING HEAD. EXCLUSIONS 1. OFF HOURS WORK. 2. CITY METER / WATER CONNECTION FEE. 3. ELECTRICAL OR FIRE ALARM WORK OF ANY TYPE. 4. STRUCTURAL VERIFICATION FOR FIRE SPRINLKER SYSTEM PIPING, PENETRATIONS, HANGERS AND BRACING. 5. FIRE CAULKING. 6. WORK ON EXISTING SYSTEM OTHER THAN SPECIFIED ABOVE. 7. WASHINGTON STATE SALES TAX. DESIGN CRITERIA THROUGHOUT: PER NFPA #13 (2007 EDITION) AND THE CITY OF TUKWILA HAZARD: ORDINARY, GROUP I SYMBOL LEGEND - EXISTING SPRINKLER HEAD. • R - SPRINKLER HEAD TO BE RELOCATED. A - SPRINKLER HEAD TO BE ADDE • P - SPRINKLER HEAD TO BE PLUG - SPRINKLER PIPE TO BE DEMOL - EXISTING SPRINKLER PIPE. - NEW SPRINKLER PIPE. - MECHANICAL TEE. r t.m'I'I4LA FIRE DEPARTM NI Please call; 575-4407 and give this job No. / 0 5 $4 and exact address for shub down or restoration approved. 0 5s r• % v- k_ck<c s . 0y' Because of increased demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4407 or email fireinspreoueStnri tukwila t,,a.us td schedule your inspections a minimum of 48 hours in advance of the date yod want an inspection, Tukwila 3ED. ISHED. 13 Without Comments As rioted in Red O Per The Attached Letter These plans have be::x reviewed by The Tukwila Fire Prevention Bt.u-eai.; cc I;onnance with current City standards. is subject to errors and omissions which do lot authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawingsYafter this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval Final acceptance i, subject to field test and inspection bt The Tukwila Fire Prevention Bureau. Date: S( 2.tol`Q By: ,� r AREA OF WORK UPPER/THIRD LEVE INDOOR FIELDS MEZZANINE 1 a Pi KEY PLAN SCALE: NONE 440 s 144th I S:1.17thSt Fan yFtjt CEntet'S t VICINITY MAP SCALE: NONE MAIN LEVEL DRAWING SYMBOLS REVISIONS HYDRAULIC DESIGN INFO HANGER LEGEND SPRINKLER HEAD LEGEND . ALL NEW PIPE TO BE ALLIED DYNA THREAD WITH CAST IRON FITTINGS. ALL SPRINKLERS IN GWB CEILINGS TO HAVE 1" X 1/2" ADJUSTABLE DROP NIPPLES. MK DATE BY DESCRIPTION nTHIS SYSTEM IS THIS SYSTEM IS NOT HYDRAULICALLY DESIGNED Fl HYDRAULICALLY DESIGNED A U -HOOK M SPRINKLER TYPE MFG MODEL SYMBOL K -FAC THREAD TEMP FINISH CANOPY QTY - FLOW TEST - B COACH SCREW N TOGGLE NUT EXISTING UPRIGHT 0 5.6 1/2" 155°F BRASS N/A STATIC: C "C" CLAMP P HDI -P UPRIGHT TYCO TY -B O 5.6 1/2" 155°F BRASS N/A R-3 RESIDUAL: D TOP BEAM CLAMP W/ STRAP R WEDGE ANCHOR A-8 GPM FLOWING: E EYE ROD S SAMMY SIDEWINDER (SWG20) PENDENT TYCO TY -B 0 5.6 1/2" 155°F CHROME REC CHR R-2 DATE & TIME: F FLUSH SHELL Sd SAMMY SUPER SCREW (DSTRT ') A-1 - SYSTEM DESIGN - G CEILING FLANGE REMOTE AREA: - H SIDE BEAM BRACKET SX T SAMMY X -PRESS TRAPEZE DENSITY: J "J" BOLT U MAX AREA/HEAD K SHORT STRAP W K -FACTOR L "L" ROD X TOTAL THIS SHEET 14 riTrir >/ Fire Sprinklers 60 WA CL# FIRESI*988RJ 1524 45th Street East, Suite 102 Sumner, WA 98390 (253) 826-0099 PROJECT: STARFIRE OFFICE 14800 STARFIRE WAY • TUKWILA,WA 98188 PAID AUG S {2p `) TUK MIL r f/0 K 3 /sT DESIGNER: JIM STEWART DATE: AUGUST 18, 2010 SCALE: As Noted CONTRACT WITH: STARFIRE SPORTS RENTON,WA P.M. - BEN OLIVER '"""' '^" "^^^ ''"'' SUPER. - BEN OLIV 14800 10-S-184STARFIRE WAY HAZARD: As Noted AHJ: JOB # 2617 SHEET # I OF I ANALOG/ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR ANALOG/ADDRESSABLE SINGLE ACTION MANUAL PULL STATION HORN/STROBE COMBINATION wall mount ® 80" A.F.F. to bottom of back box cd = candela rating of strobe light STROBE LIGHT wall mount ® 80" A.F.F. to bottom of back box cd = candela rating of strobe light (EXIS INC:) OFFICE (EX!.`;H G) OFF!CL (EX1S HNC) OFFICE (E:XIS It -I O OFFICE INSTALL NEW DEVICE, TIE INTO EXISTING CIRCUIT AS SHOWN. (E> SSING) OPEN OFFICE OFF CE (EXISTING) OFFICE KITCHEN ;COP( cEXIST!,NG) OFF CE CONFERENCE: AM. (NEW) LOCKER! SHOWER RM. TOILET (EXISTING) SLRvER PM (ExisTING) OPEN OFFICE (cXIS PNC; RECEPTION i"E;IJ iii-d(.'C) NOTICE A completed, signed, Tuk Fire Department Pre-te. Certificate must be prese to the Inspector prior commencement of Accept Testing of any Fire Alar and Detection System • Failure of test will resul in a Re -inspection Fee a termination of the testin Without Comments a As Noted in Red C:1 Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally wit% the designer. Additions, deletions or revisions to these drawings;;after this date will void this acceptance and will require "a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. IlatioN4LA FIRE DEPART Arian Please call: 575.4407 and give this job and exact address for shut. Churn or restoration aoarovat PROJECT NAME: Starfire Sports Complex 2nd Floor Office Remodel 14800 Starfire Way Tukwila, WA 98188 LICENSE ALARMCIO55CW ACE FIRE & SECURITY SYSTEMS A DIVISION OF ALARM CENTER, INC. 14800 STARFIRE WAY 10-F-185 Partial Fire Alarm Plan o' SCALE: 1/8" = 1' - 0" North Key Plan ElANALOG/ADDRESSABLE SINGLE ACTION MANUAL PULL STATION xrcd STROBE LIGHT ceiling mounted cd = candela rating of strobe light (E) INDICATES EXISTING DEVICE Flag Notes INSTALL NEW NOTIFICATION DEVICE, TIE INTO EXISTING CIRCUIT AS SHOWN. A. VERIFY ON SITE THAT THE EXISTING BACK UP BATTERIES HAVE THE CAPACITY TO ACCOMMODATE THE ADDITIONAL DEVICES. Wire Legend A SPEAKER CIRCUIT (2) #12AWG. FPLR (FIRE RATED CABLE) SPEAKER CIRCUIT (FEED/RETURN) (4) #12AWG. FPLR (FIRE RATED CABLE) B STROBE CIRCUIT (2) #12AWG. FPLR (FIRE RATED CABLE) STROBE CIRCUIT (FEED/RETURN) (4) #12AWG. FPLR (FIRE RATED CABLE) ruRyfltA FIRE DEF'ARTNIEM PIesse cel: 875- moi, end give this j and exact address for shut, sown or restoration apor 1, U'lithOut, L7 As Noted In Red D Per The Attached Letter These plans have begin reviewed by The Tukwila Fire Prevention Bureau for conformance. >:vith current City 7.-anr ards. Acceptance is subject to errors and .missions which do not authorize violations of adopted 3: ards and ordinances. Tier 'non ibility for the G� ! uacy of design rest_ totally with the designer. Acini ons, deletions or revisions to these drawings after this void khis acceptance and yvl.l reqUiree resui iiiittai of revised drawings for subsequent approval. Final acceptance is subject to ficic► test and inspection by The Tukwila Pile Prevention Bureau. • Date: . o CI By:A`^" NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing.. f'IH 1 `JV 1 2009 _itakwila Fire PROJECT NAME: Starfire Sports Complex �Tz MVP Sports-KATZ Gym it'y� 14800 Starfire Way Tukwila, WA 98188 DATE: 11/10/09 ISYSTEM TYPE: FIRE ALARM & DETECTION DRAWN BY: j F. AS SHOWN LICENSE ALARMCI055CW APPROVED BY: REVISION REVISION ACE FIRE & SECURITY SYSTEMS A DIVISION OF ALARM CENTER, INC. 1-800-354-1555 SHEET NO. VOICE EVAV. SPEAKER/STROBE COMBINATION wall mount ® 80" A.F.F. to bottom of back box cd = candela rating of strobe light �cd VOICE EVAC. SPEAKER/STROBE COMBINATION IN) ceiling mounted cd = candela rating of strobe light xrcd STROBE LIGHT ceiling mounted cd = candela rating of strobe light (E) INDICATES EXISTING DEVICE Flag Notes INSTALL NEW NOTIFICATION DEVICE, TIE INTO EXISTING CIRCUIT AS SHOWN. A. VERIFY ON SITE THAT THE EXISTING BACK UP BATTERIES HAVE THE CAPACITY TO ACCOMMODATE THE ADDITIONAL DEVICES. Wire Legend A SPEAKER CIRCUIT (2) #12AWG. FPLR (FIRE RATED CABLE) SPEAKER CIRCUIT (FEED/RETURN) (4) #12AWG. FPLR (FIRE RATED CABLE) B STROBE CIRCUIT (2) #12AWG. FPLR (FIRE RATED CABLE) STROBE CIRCUIT (FEED/RETURN) (4) #12AWG. FPLR (FIRE RATED CABLE) ruRyfltA FIRE DEF'ARTNIEM PIesse cel: 875- moi, end give this j and exact address for shut, sown or restoration apor 1, U'lithOut, L7 As Noted In Red D Per The Attached Letter These plans have begin reviewed by The Tukwila Fire Prevention Bureau for conformance. >:vith current City 7.-anr ards. Acceptance is subject to errors and .missions which do not authorize violations of adopted 3: ards and ordinances. Tier 'non ibility for the G� ! uacy of design rest_ totally with the designer. Acini ons, deletions or revisions to these drawings after this void khis acceptance and yvl.l reqUiree resui iiiittai of revised drawings for subsequent approval. Final acceptance is subject to ficic► test and inspection by The Tukwila Pile Prevention Bureau. • Date: . o CI By:A`^" NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing.. f'IH 1 `JV 1 2009 _itakwila Fire PROJECT NAME: Starfire Sports Complex �Tz MVP Sports-KATZ Gym it'y� 14800 Starfire Way Tukwila, WA 98188 DATE: 11/10/09 ISYSTEM TYPE: FIRE ALARM & DETECTION DRAWN BY: j F. AS SHOWN LICENSE ALARMCI055CW APPROVED BY: REVISION REVISION ACE FIRE & SECURITY SYSTEMS A DIVISION OF ALARM CENTER, INC. 1-800-354-1555 SHEET NO. Symbol Legend ANALOG/ADDRESSABLE SINGLE ACTION MANUAL PULL STATION VOICE EVAV. SPEAKER/STROBE COMBINATION wall mount 0 80' A.F.F. to bottom of back box cd = candela rating of strobe Tight VOICE EVAC. SPEAKER/STROBE COMBINATION ceiling mounted cd = candela rating of strobe Tight STROBE LIGHT wall mounted 0 80` A.F.F. to bottom of back box cd = candela rating of strobe light STROBE LIGHT ceiling mounted cd = candela rating of strobe Tight INDICATES EXISTING DEVICE Flag Notes Ti Partial Fire Alarm Plan 0' 4' 8' 16' North Key Plan INSTALL NEW NOTIFICATION DEVICE, TIE INTO EXISTING CIRCUIT AS SHOWN. A. VERIFY ON SITE THAT THE EXISTING BACK UP BATTERIES HAVE THE CAPACITY TO ACCOMMODATE THE ADDITIONAL DEVICES. Wire Legend 112 111 1131 SPEAKER CIRCUIT SPEAKER CIRCUIT (FEED/RETURN) STROBE CIRCUIT STROBE CIRCUIT (FEED/RETURN) (2) #12AWG. FPLR (FIRE RATED CABLE) (4) #12AWG. FPLR (FIRE RATED CABLE) (2) #12AWG. FPLR (FIRE RATED CABLE) (4) #12AWG. FPLR (FIRE RATED CABLE) PROJECT NAME: Starfire Sports Complex MVP Sports-KATZ Gym 14800 Starfire Way Tukwila, WA 98188 DATE: 11/10/09 SYSTEM TYPE: FIRE ALARM & DETECTION DRAWN BY: J.F. LLICENSECNOS ALARMCIO55CW APPROVED BY: REVISION 1/30/09 AS - BUILT ACE FIRE & SECURITY SYSTEMS A DIVISION OF ALARM CENTER. INC. SHEET NO. 14800 STARFIRE WAY 09-F-180