FIRE PROTECTION SYSTEMS PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
**PLEASE PRINT**
Site Address: NdS, 7 4 ter <G•[ ( .
Tenant Name: iCtNICA40
King Co. Assessor's Tax No.: 35a3O d/Oy
Suite Number:07"C' ce Floor:
New Tenant? CEI - Yes ❑ - No
Property Owner's Name: S(p IP_ ii(-O?p,ck-t e)
Mailing Address: ?V • box U OPfr
City
CONTACT PERSON-if,there are questions about the submittal.
Name: Mark. MCL l tAG 1.0
Company Name: wd&k ( r\l+o \ A l G rp
Mailing Address: 1 dS 3 J . .CC LK€ r
City
E-mail Address: Mind 1 fr (r. tilSta1('Jr rrfl 1 (DM
\44
State Zip
Day Telephone: Pi% " ' 3
Sec 41 e. W
Fax Number: 966 ' 3e (I y
Valuation of Project (contractor's bid price): $ 596,00
L� �c'aloe5
Scope of Work (please provide detailed information): tQnGnA- 1 e��f Ui(?,�1 nn _G
40 CPAp,C ajc S?c.0 P 1
PERMIT APPLICATION NOTES
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules.
Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit
is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or
abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in
writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE
UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY
FOR THIS PERMIT.
BUILDING OWNER OR AUTHORIZED AGENT:
Signature:
Print Name: L" IGC v MCL (t.11Gt (.
Plan Permit App.doc
Date: 30- D'
Day Telephone: POG- 50'S- - 39-5
cr
5/14/10 TFD FP Form 8
CONFIDENTIAL
A
WASHINGTONALARM
Bldg 733 -Power Supply
FIRE ALARM SYSTEMS
BATTERY CALCULATION CHART
B C DE F
Form: 1/22/01
G
IV&
M
DEVICE/
MODULE
MODEL
NUMBER
QUANTITY
OF
DEVICE/
MODULE
STANDBY
CURRENT
(AMPS)
TOTAL
STANDBY
CURRENT
(CxD)
ALARM
CURRENT
(AMPS)
TOTAL
ALARM
CURRENT
(CxF1
CONTROL PANEL AND MODULES
0
0
0
0
0
Altronix
602ULADA
1
0.075
0.075
0.3
0.3
Existing Strobes
4
0
0.085
0
New Strobes
4
0
0.085
0
Battery 12 VOLTS
NP7-12
1
0
0
0
0
0
0
0
0
0
0
0
0
INITIATING DEVICES
None on this panel
0
0
0
0
0
Existing Horn/Strobes
2
0
0.197
0
Existing Strobes
4
0
0.085
0
New Strobes
4
0
0.085
0
0
0
0
0
0
0
NOTIFICATION APPLIANCES
Existing Horns
17
0.069
1.173
Existing Horn/Strobes
2
0.197
0.394
Existing Strobes
4
0.085
0.34
New Strobes
4
0.085
0.34
0
0
0
0
Sum Column For Standby Load (Amps)
Multiply By Required Standby Time (24 or 60 Hours)
Total Standby AH
0.075
24
1.800
(G)
Sum Column For Alarm Load (Amps)
Multiply By Required Alarm Time (5 min = .083)
Total Alarm AH
2.547
0.083
0.576
TOTAL TOTAL REQUIRED SAFETY TOTAL TOTAL
STANDBY ALARM AH AH (G+H) FACTOR SYSTEM SYSTEM
AH (G) (H) (Multiply) AMPERE- AMPERE -
HOURS HOURS
REQUIRED PROVIDED
1.800 1 0.5756 1 2.376 1 1.3 1 3.088 1 7AH
(H)
NEW DEVICES TAPPED OFF EXISTING CIRCUIT
FACP
/O\
To dedicated 120vac
power supply
FPS
/O\
\/
\
,O\
\O/
�\
`0'
,O\
(w
EOL
221,
To dedicated 120vac
power supply
Ground per NEC Ground per NEC
Standards Standards
FACP
FPS
WIRE TYPE & VOLTAGE DROP LOSS
DMP 1912XR FIRE ALARM
CONTROL PANEL
ALTRONIX 602ULADA
NAC POWER SUPPLY
EDWARDS 270 SERIES MANUAL PULL
EXISITNG WHEELOCK ADJUSTABLE
CANDELA HORN/STROBE 8c STROBE
WHEELOCK EXCEEDER SERIES
ADJUSTABLE CANDELA STROBE
Wire Legend
Type
DESCRIPTION
NOTIFICATION CIRCUITS
16 AWG, 4 CONDUCTOR 'FPLR' JACKETED CABLE1
VOLTAGE DROPS FOR SEGALE BUILDING 733- YAMATO T.I.
CIRCUIT
DEVICE
CURRENT
# OF DEVICES
CURRENT
FORMULA: OHMS PER 1000' X DISTANCE/1000 RESULT X TOTAL CURRENT X 2 =
VOLTAGE DROP
%
LOAD AT EOL
POWER SUPPLY
NUMBER 1
HORN -STROBE
.197
X
2
=
.394
I..
(4.016 x 360)= 1.446 X 1.074 X 2
3.106
12.9
20.89
STROBE
.085
X
8
=
.680
1000
TOTAL CURRENT FOR THIS CIRCUIT
1.074
MEN
30CD
JANITORS
Apporx 63 sq ft
OFFICE
Apporx 128 sq ft
OFFICE
Apporx 130 sq ft
30CD
30CD
OFFICE
Approx 148 sq ft
WOMEN
30CD
BREAK ROOM
30CD
DRAWING SCALED AT 1/8" l'
110CD
CONFERENCE ROOM
30CD
STORAGE OOM
30CD
Approx 145 sq ft
110CD
FS
110CD
V EXISTING WHEELOCK NAC DEVICE
°1
\,
,o\
NEW WHEELOCK NAC DEVICE
Without Comments
O As Noted in Red
Per The Attached Letter
• olans have be fm reviewed by The Tukwila Fire
cion Bureau i,,r -,-iFormance with current City
to errors and
,:Ins which dr: riot ailthorize violations of adopted
.. -rds and ordinances. The responsibility for the
.. acy of de:=frin rests totally with the designer.
,{ cions, deletions ix r: vi cions to these drawings after
_,s aa'te will void this _c:-eptance and will require a
esubmitfal of revised drawings for subsequent approval.
=final acceptance is subject to field test and inspection by
i'ne Tukwila Fire Prevention Bureau.
;,9te;. ' `1- By: l4Vvi .51
TUKWILA FIRE DEPARTMENT
Please call 206-575-4407 and
give this Fire Permit No.
and exact address for shut-
down or restoration approval.
WASH1NGTONALARM
DRAWING SCALED AT 1/16"=1'
AREA OF WORK
THIS PERMIT
NOTICE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate must be presented
to the inspector prior to
commencement of Acceptance
Testing of any. Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
termination of the testing.
WOMEN
JANITORS
APpon63. ft
OPFI®
Apporx 128egf
OFFICE
Approx 148 sq ft
WASHINGTON ALARM INC.
1253 S. Jackson Street
Seattle, WA. 98144
Job # 8735
Designed by: Daniel Eastvold
Drawn by: Mark Mcllwain
Ph: 206-328-3288
Fax: 206-322-7214
REVISIONS
DESCRIPTION
05/30/2012
PERMIT SET
liwAt
FIRE ALARM
PAID
MAY 31 2012
TUKWILA FIRE
.27o' 3 , /D -b —