HomeMy WebLinkAboutPP - 13123 48TH AVE S - HUSKY INTERNATIONAL TRUCKS - PERMITS AND PLANS13123 48TH AVE S
ASSOCIATED PERMITS
08-F-509
08-5-232
Project Name:
two IFire &
Security
Scope Of Work
Husky International
13123 48th Avenue S
Tukwila, WA 98168
FIRE ALARM INSTALLATION
By: ADT Security Services
11824 North Creek Parkway N., Suite 105
Bothell, WA 98011
ADT Representative: Jeff McLaughlin
Telephone: 425-402-3351
FILE
Quantity Model Description
ftJKW1LA FIRE DEPARTbilk.All
Please call: 575-4407
and give this job
F-
J exact address for shut,
A.ol or restoration approval.
NOTICE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate must be presented
to the Inspector prior to
commencement of Acceptance
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
termination of the testing.
1
1
1
1
NOTE:
D7412
D263
(By Others)
(By Others)
Radionics Fire Alarm Control Panel
Smoke Detector
Waterflow Switch
OS&Y Switch
1. Remove existing Radionics 8112
2. Install new Radionics D7412 Fire Alarm Control Panel.
3. Install new Smoke Detector above FACP.
4. Connect to customer owned sprinkler devices.
5. Panel is programmed for monitoring.
1
--- Rise+ code. -10 S< /-..-3-y -s.
adders){s 444vKc
c -e
5#44-.
r h t k lo oA• ot�./,-u o. FA
— 1-654x, a 44.. 0141. iCk0 14 Doi
ACCEPTED
11 Without Commis
Ear As Noted in Red
0 Per The Attached Leber
nese plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current city
standards. Acceptance is subject to errors and
omissions which do not authorize violations of adopted
stanaaras and ordinances. The responsibility for the
adequacy of design rests totally with the designer.
lw Additions, deletions or revisions to these drawings atter
this date will .void thie acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to field test and inspection b‘
The Tukwila Fire Prevention Bureau.
[Date:
// -1 �1 - 03 By: -S l r
L
ar
•
i
two IFire &
Security
Battery Calculation Worksheet
(all currents stated in mA)
11/1412008
PROJECT: HUSKY INTERNATIONAL
Device
Quantity of
Standby mA
Alarm mA
Total Device
Total Device
Description
Devices _
Per Device
Per Device
Standby mA
Alarm mA
System Devices
RADIONICS D7412
1
200
500
200
500
0
0
D263 SMOKE DETECTOR
1
0
0
0.1
0.1
Min. NH Battery
4.84
0
0
33
0
0
0
0
0
0
0
Total System Current
0
0
200
500
Smoke Detectors / Auxiliary Devices
Standby Hrs. Required
24
N/A
5
0
0
D263 SMOKE DETECTOR
1
0.1
0.1
0.1
0.1
Min. NH Battery
4.84
N/A
1.45
33
0
N/A
0
0
N/A
0
0
0
N/A
0
0
0
N/A
0
0
Device Totals
1
33.1
0.1
Notification Appliances (list all)
Standby Hrs. Required
24
N/A
5
N/A
0
Total System Alarm mA
500.1
N/A
4.80
N/A
0
Min. NH Battery
4.84
N/A
1.45
N/A
0
N/A
N/A
0
N/A
N/A
0
0
N/A
N/A
0
0
N/A
N/A
0
Notification Appliance Totals
0
N/A
0
Summary Section
Standby Hrs. Required
24
Alarm Sounding Minutes
5
Total System Standby mA
233.1
Total System Alarm mA
500.1
Total System Standby NH
4.80
Total System Alarm AIH
0.04
Min. NH Battery
4.84
ADD 30% FOR BATTERY DEPLETION
1.45
Required AIH Battery
6.30
A/H BATTERY PROVIDED FOR SYSTEM
7
1
DO NOT EXCEED TOTAL CURRENT DRAW OF 3000mA
MANG a3SIb 3N11 -3N0
0
c_
CD
P
111 I (
I
r
FIRE ALARM SYSTEM - PANEL REPLACEMENT
HUSKY INTERNATIONAL
13123 48TH AVENUE SOUTH
TUKWILA. WA 98168
/
Hydraulics Summary Sheet
SECURITY FIRE PROTECTION
P.O. BOX 487
SOUTH PRAIRIE, WASHINGTON 98385
360 897-6839
Designer: BARR I E D. HAANEN
Calc By: BARR I E 0. HAANEN
Date: MAY 22, 2008
Project Information
HUSKY TRUCK
13123 - 48TH AVENUE SOUTH
TUKWILA, WASHINGTON 98168
Contract No:
Building:
System ID:
Ref. Drawing No:
Construction:
Occupancy:
B-28100
PAINT BOOTH
HUSKY TRUCK B-28100
1 OF 1
Authority: TUKWILA FIRE MARSHALL
System Information
Hydraulics Design Criteria
System Type: WET PIPE
Density: .40 GPM/Sc t
Remote Area: 2 AS Soft
Sprinkler Coverage: 54.96 ScFt
Design Standard: NFPA NO. 13 - 2007 EDITION
Hazard: EXTRA GROUP II
Figure: N/A Curve: N/A
Sprinklers / Nozzles_
Manufacturer: TYCO
Model: TY -FRB
Size: 3/4" I.P.T.
K—Factor: 8.0
Temp. Rating: 286
Hydraulics
Information
Demand...
Spr Req'd Pres:
Spr Req'd Flow:
Add'I Flows:
Hose at Srce:
Total Flow:
Total Pres:
Static Bev:
45.92 PSI
45.56 GPM
0.00 GPM
500.00 GPM
545.56 GPM
45.92 PSI
8.00 Ft
Supply...
Water Flow Test
Static: 160.00 PSI
Residual: 135.00 PSI
Qty Flowing: 1500.00 GPM
Elevation: 0.00 Ft
Date:S/21/08 Time:N/A
By: TUKWILA FIRE DEPARTMENT
Pump Data
Rated: 0.0 PSI! 0.0 GPM
Boost Pres: <NA) PSI
Discharge Pres: (NA) PSI
Discharge Flow: <NA) GPM
Combined
Static:
Residual:
Qty Flowing:
(NA) PSI
(NA) PSI
(NA) GPM
Available...
P) 156.15 PSI! 545.56 GPM
F) 45.92 PSI! 3404.86 GPM
Margin...
Pressure: 110.23 PSI
Flow: 2859.30 GPM
Sigma Dynamics Corporation
7700 Summary Sheet
1
er
oa
a0
a0
e
0E
E
ao
E—
aa
oa
OW
Eo
CO
wti
O
0
.1 -
HUSKY TRUCK
(ISd) eid
t 1500.00
.880
a
8s
xxxz
P0-%%%
(000W
N 0 01
`0 0 8 1
N LA
b
m
Z
_
gin
sure 110.:
2859.:
1
1tf
11
1 1
0
i
RgRg.c-tEssgil)sqsaF-8sse22.317
(ISd) eid
t 1500.00
.880
a
8s
xxxz
P0-%%%
(000W
N 0 01
`0 0 8 1
N LA
SUBMITTAL SERIAL NO:2142HY12
HUSKY TRUCK B-28100
EXTRA HAZARD OCCUPANCY GROUP II
.40 GPM DENSITY / ENTIRE PAINT BOOTH
ADD 500 GPM FOR INSIDE/OUTSIDE HOSE
WET PIPE SYSTEM PAINT BOOTH
CALCULATIONS BY: BARRIE D. HAANEN
FOR: SECURITY FIRE PROTECTION
P.O. BOX 487
SOUTH PRAIRIE, WASHINGTON 98385
360 897-6839
WASHINGTON LICENSE NUMBER SECURFP000BF
LOCATION: HUSKY TRUCK
13123 - 48TH AVENUE SOUTH
TUKWILA, WASHINGTON 98168
TYCO SPRINKLER MODEL TY -FRB
K = 8.0 3/4" I.P.T. 286 DEGREE
WET PIPE SYSTEM PAINT BOOTH
FLOW TEST RESULTS
Water Supply
STATIC 160.00 PSI
RESIDUAL 135.00 PSI @ 1500.00 GPM
CITY PRESSURE AVAILABLE AT
545.6 GPM 156.15 PSI
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K -FACTOR
101 23.58 21.98 8.00
102 21.98 21.98 8.00
TOTAL WATER REQUIRED FOR SYSTEM
OUTSIDE HOSE STREAMS AT 0
TOTAL WATER REQUIREMENT
PRESSURE REQUIRED AT 0
MAXIMUM PRESSURE UNBALANCE IN LOOPS
MAXIMUM VELOCITY FROM 7 TO 8
PRESSURE
8.69
7.55
45.56 GPM
500.00 GPM
545.56 GPM
45.92 PSI
0.10 PSI
16.91 FPS
05-22-2008 PAGE 1
SUBMITTAL SERIAL N0:2142HY12
HUSKY TRUCK B-28100
EXTRA HAZARD OCCUPANCY GROUP II
.40 GPM DENSITY / ENTIRE PAINT BOOTH
ADD 500 GPM FOR INSIDE/OUTSIDE HOSE
WET PIPE SYSTEM PAINT BOOTH
05-22-2008 PAGE 2
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
101 102 1.049 L 8.00 C=120 PT 7.55 (102)
Q 21.98 F=0 F 0.00 PE 0.00
BN T 8.00 0.1550 PF 1.24
13 101DQ 23.58 1.049 L 3.00 C=120 PT 8.79 (101)
Q 45.56 F=E F 2.00 PE 0.00
BN1 T 5.00 0.5969 PF 2.98
12 13 1.049 L 4.33 C=120 PT 11.77 ( 13)
Q 45.56 F=T,BV F 6.00 PE 1.88
FR1 T 10.33 0.5969 PF 6.17
11 12 1.049 L 1.00 C=120 PT 19.82 ( 12)
Q 45.56 F=E F 2.00 PE 0.00
FM1 T 3.00 0.5969 PF 1.79
10 11 1.049 L 6.00 C=120 PT 21.61 ( 11)
Q 45.56 F=E F 2.00 PE -2.60
FM1 T 8.00 0.5969 PF 4.78
9 10 1.049 L 0.33 C=120 PT 23.79 ( 10)
Q 45.56 F=E F 2.00 PE -0.14
FM1 T 2.33 0.5969 PF 1.39
8 9 1.049 L 20.00 C=120 PT 25.04 ( 9)
Q 45.56 F=E F 2.00 PE -8.67
FM1 T 22.00 0.5969 PF 13.13
7 8 1.049 L 10.00 C=120 PT 29.50 ( 8)
Q 45.56 F=T F 5.00 PE 0.00
FM1 T 15.00 0.5969 PF 8.95
6 7 2.635 L 27.00 C=120 PT 38.45 ( 7)
Q 45.56 F=2E F 8.60 PE -0.43
FM T 35.60 0.0067 PF 0.24
5 6 3.260 L 14.00 C=120 PT 38.26 ( 6)
Q 45.56 F=0/T F 13.00 PE 0.00
FM T 27.00 0.0024 PF 0.06
4 5 4.260 L 10.00 C=120 PT 38.32 ( 5)
Q 45.56 F=0 F 0.00 PE 0.00
FM T 10.00 0.0006 PF 0.01
SUBMITTAL SERIAL NO:2142HY12
HUSKY TRUCK B-28100
EXTRA HAZARD OCCUPANCY GROUP II
.40 GPM DENSITY / ENTIRE PAINT BOOTH
ADD 500 GPM FOR INSIDE/OUTSIDE HOSE
WET PIPE SYSTEM PAINT BOOTH
05-22-2008 PAGE 3
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
3 4 6.357 L 40.00 C=120 PT 38.33 ( 4)
Q 45.56 F=0 F 0.00 PE 0.00
FM T 40.00 0.0001 PF 0.00
2 3 8.249 L 108.00 C=120 PT 38.33 ( 3)
Q 45.56 F=E F 13.00 PE 0.00
FM T 121.00 0.0000 PF 0.00
1 2 8.249 L 17.50 C=120 PT 38.33 ( 2)
Q 45.56 F=CV/E F 58.00 PE 7.58
FR T 75.50 0.0000 PF 0.00
0 1 8.450 L 150.00 C=140 PT 45.91 ( 1)
Q 45.56 F=T,GV/E F 69.20 PE 0.00
UN T 219.20 0.0000 PF 0.00
PT 45.91 ( 0)
w
.y: L r ' /E/a� Gann
I cowl -to I ti l e,e
(Mpg V-eba,i�� e59
.taro 1 v tr%mt.
(l r2
10-+1.
J
iL• t to
ID
1>G,47 S brA1 U *1 #
iota
CC E.PTED
Without Comments
As Noted In Red
Per The Attached Letter
!nese plans have been reviewed by The Tukwila Fire
:prevention Bureau for conformance with current city
'.1ndards. Acceptance is suh ect to errors and
nissibns which do not authorize violations of adopted
naaras and ordinances. The responsibility for the
,,11equacy of design rests totally with the designer.
Additions, deletions or revisions to these drawings after
is date will void this. acceptance and wit require a
submittal of revised drawings for subsequent approval.
•nal acceptance is subject to field test and Inspection by
,'►e Tukwila Fire, Prevention Bureau.
Date:
By: 07 2c
fUKWILA FIRE DEPARTIVIE tv't.
Please call: 575.4.407
and give this job
and exact address for shut-
down or restoration aouroval
s p,Aik yes. -
NOTICE
Weld stamps must be
inspected before pipe is
hung. po not paint piping
prior to hydrostatic test
approval.
/VET:
3(23 v c" 41,1,
I L , ` El% C_
SECURITY
SOUTH PRAIRIE, WASHINGTON 98385
FIRE PROTECTION
(360) 897-6839 FAX (360) 897-6839
WASHINGTON LICENSE NUMBER SECURFPOOOBF
1
SECURITY FIDE
i'RQD'ECTI(INIMPORTANT NOT
s
Fire Sprinklers Save Livesuse of increased demand s ur
inspectors' schedules are booked
3-7 days ahead. Therefore, you
will need to call 206-5754407 to
schedule your inspections a
minimum of 48 hours in advance
of the date you want an
inspection.
s -20-0a