Fire Department Review
Control #D2000-196
Re: Fosterview Estates — lot 6 — 4214 South 137th Street
Dear Sir:
The attached set of building plans has been reviewed by The Fire Prevention Bureau and are acceptable
with the following concerns:
1. The minimum fire flow and flow duration requirements for one- and two-family dwellings having
a fire area which does not exceed 3,600 square feet (344.5 m2) shall be 1,000 gallons per
minute (3785.4 L/min.). Fire flow and flow duration for dwellings having a fire area in excess of
3,600 square feet (344.5 m2) shall not be less than that specified in Table A -III -A-1. Exception:
A reduction in required fire flow of 50 percent, as approved by the chief, is allowed when the
building is provided with an approved automatic sprinkler system. (UFC Appendix III -A, sec. 5.1)
2. Acceptance of residential fire sprinkler systems shall include field verification of GPM and residual
pressures meeting or exceeding the listing for the sprinkler type.
All new sprinkler systems and all modifications to existing sprinkler systems shall have fire
department review and approval of drawings prior to installation or modification. New sprinkler
systems and all modifications to sprinkler systems involving more than 50 heads shall have the
written approval of the W.S.R.B., Factory Mutual, Industrial Risk Insurers, Kemper or any other
representative designated and/or recognized by The City of Tukwila, prior to submittal to the
Tukwila Fire Prevention Bureau. No sprinkler work shall commence without approved drawings.
(City Ordinance #1742)
Contact the Tukwila Fire Prevention Bureau to witness all required inspections and tests. (UFC
10.503) (City Ordinance #1742)
3. All electrical work and equipment shall conform strictly to the standards of The National Electrical
Code. (NFPA 70)
An aisle to and working space shall be provided for each electrical panel. An aisle width not less
than 24 inches shall provide access to the panel and 30 inches of working space shall be provided
directly in front of the panel. (NEC 110-16(a), NEC 110-16(c))
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: 206-575-4404 • Fax: 206-575-4439
Steven M Mullet, Mayor
Fire Department Thomas P. Keefe, Fire Chief
Page number 2
Each circuit breaker shall be legibly marked to indicate its purpose. (NEC 110-22)
Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply
approval of such condition or violation.
Yours truly,
The Tukwila Fire Prevention Bureau
Cc: TFD file
Ncd
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: 206-575-4404 • Fax: 206-575-4439
Cizy of Tukwila
Steven M. Mullet, Mayor
Fire Department Thomas P. Keefe, Fire Chief
TUKWILA FIRE DEPARTMENT
FINAL APPROVAL FORM
Permit No. 2-00( 1 L
Project Name C3 -y1 i`�� t ,J -s
Address 1,2-11 CS. -1
Retain current inspection schedule
Needs shift inspection
Suite #
Approved without correction notice
Approved with correction notice issued
Sprinklers:
Fire Alarm:
Hood & Duct:
Halon:
Monitor:
Pre -Fire:
Permits:
LL2-0 ( (A
Authorized Signature Date
FINALAPP.FRM
Rev. 2/19/98 T.F.D. Form F.P. 85
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: 206-575-4404 • Fax: 206-575-4439