HomeMy WebLinkAboutPP - 4242 S 137TH PL - FOSTERVIEW ESTATES - PERMITS AND PLANS4242 S 137TH PL
ASSOCIATED PERMITS
D2000-175
Cizy of Tukwila
Steven M. Mullet, Mayor
Fire Department
Fire Department Review
Control #D2000-175
(510)
Re: Fosterview Estates - Lot 13 -
Dear Sir:
The attached set of building plans
The Fire Prevention Bureau and are
following concerns:
1. The minimum fire flow and flow duration requirements
for one- and two-family dwellings having a fire area which
does not exceed 3,600 square feet (344.5 m2) shall be 1,000
gallons per minute (3785.4 L/min.). Fire flow and flow
duration for dwellings having a fire area in excess of
3,600 square feet (344.5 m2) shall not be less than that
specified in Table A -III -A-1. Exception: A reduction in
required fire flow of 50 percent, as approved by the chief,
is allowed when the building is provided with an approved
automatic sprinkler system. (UFC Appendix III -A, sec. 5.1)
Thomas P. Keefe, Fire Chief
June 8, 2000
4242 South 137th Place
have been reviewed by
acceptable with the
2. Acceptance of residential fire sprinkler systems shall
include field verification of GPM and residual pressures
meeting or exceeding the listing for the sprinkler type.
All new sprinkler systems and all modifications to
existing sprinkler systems shall have fire department
review and approval of drawings prior to installation
or modification. New sprinkler systems and all
modifications to sprinkler systems involving more than
50 heads shall have the written approval of the
W.S.R.B., Factory Mutual, Industrial Risk Insurers,
Kemper or any other representative designated and/or
recognized by The City of Tukwila, prior to submittal
to the Tukwila Fire Prevention Bureau. No sprinkler
work shall commence without approved drawings. (City
Ordinance #1742)
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: 206-575-4404 • Fax: 206-575-4439
Ciiy of Tukwila
Steven M Mullet, Mayor
Fire Department Thomas P. Keefe, Fire Chief
Page number 2
Contact The Tukwila Fire Prevention Bureau to witness
all required inspections and tests. (UFC 10.503)
(City Ordinance #1742)
3. All electrical work and equipment shall conform
strictly to the standards of The National Electrical Code.
(NFPA 70)
An aisle to and working space shall be provided for
each electrical panel. An aisle width not less than
24 inches shall provide access to the panel and 30
inches of working space shall be provided directly in
front of the panel. (NEC 110-16(a), NEC 110-16(c))
Each circuit breaker shall be legibly marked to
indicate it's purpose. (NEC 110-22)
Any overlooked hazardous condition and/or violation of the
adopted Fire or Building Codes does not imply approval of
such condition or violation.
Yours truly,
The Tukwila Fire Prevention Bureau
cc: TFD file
ncd
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: 206-575-4404 • Fax: 206-575-4439
Aw
l
Retain current inspection schedule
Needs shift inspection
Approved without correction notice
Approved with correction notice issued
Sprinklers:
Fire Alarm•
Hood & Duct:
Halon:
Monitor:
Pre -Fire:
Permits:
FINALAPF.FRM