HomeMy WebLinkAboutPP - 4817 S 136TH ST - RESIDENCE - PERMITS AND PLANS4817 S 136TH ST ASSOCIATED PERMITS D98-0199 City of Tukwila FILE John W. Rants Mayor Fire Department Thomas P. Keefe, Fire Chief August 12, 1998 Fire Department Review Control #D98-0199 (511) Re: Russell/Allen residence - 4817 South 136th Street Dear Sir: The attached set of building plans have been reviewed by The Fire Prevention Bureau and are acceptable with the following concerns: 1. For short plat development (four single family homes or less), hydrants shall be placed so that a hydrant is within 250 feet of a building. Distance from a hydrant to a building is measured along the path of vehicular travel. Fire hydrants shall conform to American Water Works Association specifications C-502-54; it shall be compression type, equipped with two 2 1/2" N.S.T. hose ports and one 5" Storz pumper discharge port, and shall have a 1 1/4" Pentagon open -lift operating nut. All required hydrants and surface access roads shall be installed and made serviceable prior to and during the time of construction. (UFC 901.3) 2. Your street address must be conspicuously posted on the building and shall be plainly visible and legible from the street. Numbers shall contrast with their background. (UFC 901.4.4) Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of such condition or violation. Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone(206) 575-4404 • Far (206) 575.44139 City of Tukwila John W. Rants, Mayor Fire Department Thomas P. Keefe, Fin' Chief Page number 2 Yours truly, The Tukwila Fire Prevention Bureau cc: TFD file ncd Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 57$4404 • Fax (206) 575-4439