HomeMy WebLinkAboutPP - 4225 S 116TH ST - DOAK HOMES LOT 10 - PERMITS AND PLANS4225 5116TH ST
ASSOCIATED PERMITS
D2000-148
Steven M. Mullet, Mayor
Fire Department Thomas P. Keefe, Fire Chief
June 1, 2000
Fire Department Review
Control #D2000-148
(510)
Re: Doak Homes Lot 10 - 4225 South 116th Street
Dear Sir:
The attached set of building plans have been reviewed by
The Fire Prevention Bureau and are acceptable with the
following concerns:
1. The minimum fire flow and flow duration requirements
for one- and two-family dwellings having a fire area which
does not exceed 3,600 square feet (344.5 m2) shall be 1,000
gallons per minute (3785.4 L/min.). Fire flow and flow
duration for dwellings having a fire area in excess of
3,600 square feet (344.5 m2) shall not be less than that
specified in Table A -III -A-1. Exception: A reduction in
required fire flow of 50 percent, as approved by the chief,
is allowed when the building is provided with an approved
automatic sprinkler system. (UFC Appendix III -A, sec. 5.1)
Acceptance of residential fire sprinkler systems shall
include field verification of GPM and residual
pressures meeting or exceeding the listing for the
sprinkler type.
2. Your street address must be conspicuously posted on
the building and shall be plainly visible and legible from
the street. (UFC 901.4.4)
3. All electrical work and equipment shall conform
strictly to the standards of The National Electrical Code.
(NFPA 70)
An aisle to and working space shall be provided for
each electrical panel. An aisle width not less than
24 inches shall provide access to the panel and 30
inches of working space shall be provided directly in
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: 206-575-4404 • Fax: 206-575-4439
Cizj' of Tukwila
Steven M Mullet, Mayor
Fire Department Thomas R Keefe, Fire Chief
Page number 2
front of the panel. (NEC 110-16(a), NEC 110-16(c))
Each circuit breaker shall be legibly marked to
indicate it's purpose. (NEC 110-22)
Any overlooked hazardous condition and/or violation of the
adopted Fire or Building Codes does not imply approval of
such condition or violation.
Yours truly,
The Tukwila Fire Prevention Bureau
cc: TFD file
ncd
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: 206-575-4404 • Fax: 206-575-4439
FILE
Tukwila
9 X001
City of l ukwila John W Rants, Mayor
Fire Department Thomas P. Keefe, Fire Chlef
TUKWILA FIRE DEPARTMENT
FINAL APPROVAL FORM
Project Name lam' X14 rC 1 m S
Address 'h Z S 5, /,4TH
Permit No. /„ci'0 / Yg
Retain current inspection schedule
Needs shift inspection
S•F•R •
Suite #
YApproved without correction notice
Approved with correction notice issued
Sprinklers:
Fire Alarm:
Hood & Duct:
Halon:
Monitor:
Pre -Fire:
Permits:
Authorize`Signature
FINALAPP.FRM
Date
3/7/0/
T.F.D. Form F.P. 85
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (2061575-4404 • Fax (206) 575-44.39