HomeMy WebLinkAboutPP - 4718 S 104TH PL - MCCAMMANT HOMES - PERMITS AND PLANS4718 S 104TH PL
ASSOCIATED PERMITS
D97-0129
FILE
City of Tukwila John W Rants, Mayor
Fire Department Thomas P. Keefe, Are Chief
May 21, 1997
Fire Department Review
Control #D97-0129
(511)
Re: McCammant Homes - Lot B - 4718 South 104th Place
Dear Sir:
The attached set of building plans have been reviewed by
The Fire Prevention Bureau and are acceptable with the
following concerns:
1. Every building shall be accessible to Fire Department
apparatus by way of access roadways with all-weather
driving surface of not less than 20' wide and 13'6"
vertical clearance. Access roads in excess of 150' shall
be provided with an approved turn -around area. Access
shall be within 150' of all portions of the buildings. (UFC
902.2.2.1, UFC 902.2.1)
2. For short plat development (four single family homes
or less), hydrants shall be placed so that a hydrant is
within 250 feet of a building. Distance from a hydrant to
a building is measured along the path of vehicular travel.
The hydrant must flow a minimum of 1000 gpm at 20 psi
residual pressure.
3. Fire hydrants shall conform to American Water Works
Association specifications C-502-54; it shall be
compression type, equipped with two 2 1/2" N.S.T. hose
ports and one 5" Storz pumper discharge port, and shall
have a 1 1/4" Pentagon open -lift operating nut.
4. All required hydrants and surface access roads shall
be installed and made serviceable prior to and during the
time of construction. (UFC 901.3)
5. In lieu of a fire hydrant, an approved residential
fire sprinkler system may be installed when vehicular
Headquarters Station: 444 Andover Park East • Tukwila Washington 98188 • Plion&. 12(16) S71.44041 . Fir. /9M1 s7s swzo
City of Tukwila
Fire Department
Page number 2
John W. Rants, Mayor
Thomas P. Keefe, The Chief
travel distance from the nearest hydrant exceeds 250 feet.
Acceptance of residential fire sprinkler systems shall
include field verification of GPM and residual
pressures meeting or exceeding the listing for the
sprinkler type.
6. Your street address must be conspicuously posted on
the building and shall be plainly visible and legible from
the street. Numbers shall contrast with their background.
(UFC 901.4.4)
Contact The Tukwila Fire Prevention Bureau to witness all
required inspections and tests. (UFC 10.503) (City
Ordinance #1742)
Any overlooked hazardous condition and/or violation of the
adopted Fire or Building Codes does not imply approval of
such condition or violation.
Yours truly,
The Tukwila Fire Prevention Bureau
cc: TFD file
ncd
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • .hone: 12061 37544111• Far. »hs) C74:4.1120