FIRE PROTECTION SYSTEMS PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Site Address: 70,2/ S /2
Tenant Name: C4.2 At y FAA
Property Owner's Name: Cali 4g y
Mailing Address: x/0.21 S 42C f&
**PLEASE PRINT**
King Co. Assessor's Tax No.:
Suite Number: Floor:
New Tenant?/�- Yes ❑ - No
CONTACT PERSON -if there are questions about the submittal.
Name h. 01A » raJ ?
Company Name: k+ vc SD(ir(toPtS
t.,JJ c,
City State Zip
Day Telephone:
Mailing Address: I710 AUbUV IN. (A..)41. i,j ikcioui . W a ` ID ("X7 Z.
watt City State Zip
E-mail Address: trot& 1f .tM 6) kok att. cow, Fax Number:
Contractor's City of Tukwila
NICET III number:��il 5)123—�isis t
^ ( Business License number:
Total number of new/relocated devices or sprinkler heads: SO
Valuation of Project (contractor's bid price): $ 5/00
Scope of Work (please provide detailed information): t .96.4) kat) airy fl 5174.41,14-
PERMIT
174. 1,14 -
PERMIT APPLICATION NOTES
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules.
Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit
is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or
abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in
writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE
UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY
FOR THIS PERMIT.
BUILDING OWNER OR AUTHORIZED AGENT:
Plan Permit App.doc
PAID
APR 2 4 2019
rU K Y I LDa!'I elephone:
Date: I j1q —./?
8/22/14 TFD FP Form 8
3
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
D�8 -o►c03
l9-s-o8`i
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Project�G� // (
��
Type of Ins /n:
Address:
Suite #: Y02,7
Hood & Duct:
Contact Person:
S, /24
Special Instructions:
Permits:
Phone No.:
proved per applicable codes.
COMMENTS:
Corrections required prior to approval.
tars tee rr}
Needs Shift Inspecti : 11
Sprinklers: 70ZFire
Alarm:
6"
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Inspector(
n/113
Date: /0/Z3//ff
Hrs.:
!. a
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspecton.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
Z
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
1116- otu
/9-S - 0•549
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
444 Andover Park East, Tukwila, Wa. 98188 206-575-4407
Project:
Type of Ins ection:
lki'GkyoJ 7..c2
Address:--\--),,
Suite #: yDZ S, 1 LAP
Contact Person:
Special Instructions:
Phone No.:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
DV o r
QA
:
1) No Foa,,r,-k.a 4-0
bat s4vrc.cf Iv 4.6kIre
-
2) 0-0 .-rDed.vbc- iv
6 ottecte
?..)le-tk 1 1,3% i-
,,,,c,Altr-, ItNs elksrf
`70 CO (
1"a r
1 v
iti
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Inspectors
,i43
Date: /0/ts-A9
Hrs.:
/,
0
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
t e City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address: .ro Z kl #y,rk Si -
City: S'eics.,Tt.t_
Word/Inspection Record Form.Doc
State: Wf
Zip: 98i0‘
6/11/10
T.F.D. Form F.P. 113
i
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Project:J - f,�
Sprinklers:
Fire Alarm:
Type of Inspection • iterV
Address://
Suite #: �U
5
A--
(7i6
Contact Person:
Special Instructions:
Phone No.:
.4> pproved per applicable codes.
Corrections required prior to approval.
COMMENTS:
(?(-1 P‘re 141P P-Cnie
C-e\f‘e lc_ cat' G.Tect 5 42A-cep7L-- v -,c
5 �zt c ✓s — ACJ f'lE*3 -PQ �
Iii� r s
r�- a
C,(444-<-4-
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Typ .
Inspector: ,!k--74/7 b 4
Date: //-/
Hrs.:
l V
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. CaII to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
19-5-(-'
Hydraulic Calculations Sheet 1
for
Project Name: Tukwila Residence
Location: 4027 So 126th Tukwila, WA
Design:
Occupancy classification:
Density:
Area of application:
Coverage per sprinkler:
Type of sprinklers calculated:
No. of sprinklers calculated:
Total water required:
Including hose streams
Type of System:
Date 04/23/19
Job: TUKWILAR
NFPA 13D
0.05 gpm/sq.ft.
512 square feet
16' x 16' max.
Reliable Conceald Res.K=4.9
2 heads
38.52 psi @ 26.1 gpm @ Supply
80.00 psi available @ 26.1 gpm
Below curve by 41.48 psi
Wet
Water Supply Information: 80.00 psi Static
Name of Contractor: 1st Fire Solutions
Phone Number:
Authority Having Jurisdiction: NFPA-13
Program: 'HydroCalc' by Micro Space Systems
www.MicroSpaceSystems.com
■
WASHINGTON STATE I
CERTIFICATE Of COMPETENCY is
FIRE PROTECTION SPRINKLER SYSTEMS a
Rick Berger
3928-0691•CG Level 3
1st Fire Solutions, L.L.C.
1 'FIFO !1 F q 4
111.1111111•111 00000MNIONINBOalle 0000
Flow Test Summary Sheet N1.85
Z 3aa4S
•
co
(ISd) amssaJd
M
0
O
O
N
1!)
O
O
• Static = 80 psi.
Tukwila Residence Sheet 3
1st Fire Solutions
Description of Fitting abbreviations
Code Description
PT Plastic Tee
PE Plastic 90 degree Elbow
BKF Backflow preventor
MTR Meter Loss
Description of Other abbreviations
Code Description
AO Arm -over
BL Branch Line
CM Cross Main
PT Total pressure
PE Pressure loss due to elevation changes
PF Pressure loss due to friction
".5 Raised to the power of .5 (Square Root)
L Actual pipe length
F Fitting equivalent pipe length
T Total pipe length
TUKWILAR 04/23/19 9:54am Sheet 4
1st Fire Solutions
Sprinkler Systems Hydraulic Flow Calculations
Tukwila Residence
4027 So 126th Tukwila, WA
Raw data previous to any calculations
No. Code Diam Length Kfacl Kfac2 Press Elev Hose HW Vel Fittings
1 AO1 1.109 5.50 4.9 7.000 0.000 0.0 150 32 1PT
2 BL1 1.109 29.00 4.9 7.000 0.000 0.0 150 32 1PT
3 BL2 1.109 20.70 AO1 0.000 0.000 0.0 150 32 1PT
4 CM1 1.109 7.00 BL1 0.000 0.000 0.0 150 32 1PT
5 CM2 1.109 9.00 BL2 0.000 0.000 0.0 150 32 1PT
6 BU1 1.109 10.00 CM1 CM2 0.000 0.000 0.0 150 32 1PE
7 BUl 1.109 8.20 0.000 0.000 0.0 150 32 1PT
8 BU1 1.109 6.00 0.000 0.000 0.0 150 32 1PE
9 RI1 1.109 10.00 BU1 -7 0.000 20.000 0.0 150 32 1BKF,1PE
10 UG1 1.554 35.00 RI1 -7 0.000 0.000 0.0 150 32 1MTR,1PE
TUKWILAR 04/23/19 9:54am Sheet 5
1st Fire Solutions
Sprinkler Systems Hydraulic Flow Calculations
Tukwila Residence
402'/ So 126th Tukwila, WA
Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Notes
Arm -over 1 C = 150
L 5.5 PT. 7.00 1
13.0=4.90(7.00)^.5 F 5.0 PE 0.00
1 13.0 1.109 1PT T 10.5 0.02945 PF 0.31 4.3
PT 7.31 3 B1 Jct
K -factor for arm -over 1 = 13.0/(7.31)^.5 = 4.81
TUKWILAR 04/23/19 9:54am Sheet 6
1st Fire Solutions
Sprinkler Systems Hydraulic Flow Calculations
Tukwila Residence
4027 So 126th Tukwila, WA
Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps)
Notes
Branchline No. 1 C = 150
L 29.0 PT 7.00 2 End head
13.0=4.90(7.00)^.5 F 5.0 PE 0.00
2 13.0 1.109 1PT T 34.0 0.02945 PF 1.00 4.3
PT 8.00 4 Cross main Jct
K -factor for branchline no. 1 = 13.0/(8.00)^.5 = 4.60
Branchline No. 2 C = 150
L 20.7 PT 7.31 3 A01
13.0=4.81(7.31)^.5 F 5.0 PE 0.00
3 13.0 1.109 1PT T 25.7 0.02961 PF 0.76 4.3
PT 8.07 5 Cross main Jct
K -factor for branchline no. 2 = 13.0/(8.07)^.5 = 4.58
TUKWILAR 04/23/19 9:54am Sheet 7
1st Fire Solutions
Sprinkler Systems Hydraulic Flow Calculations
Tukwila Residence
4027 So 126th Tukwila, WA
Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Notes
Cross main 1 C = 150
L 7.0 PT 8.00 4 BL1
13.0=4.60(8.00)^.5 F 5.0 PE 0.00
4 13.0 1.109 1PT T 12.0 0.02960 PF 0.36 4.3
PT 8.36 6 Bulk Jct
K -factor for Cross main 1 = 13.0/(8.36)^.5 = 4.50
Cross main 2 C = 150
L 9.0 PT 8.07 5 BL2
13.0=4.58(8.07)^.5 F 5.0 PE 0.00
5 13.0 1.109 1PT T 14.0 0.02960 PF 0.41 4.3
PT 8.48 6 Bulk Jct
K --factor for Cross main 2 = 13.0/(8.48)^.5 = 4.46
TUKWILAR 04/23/19 9:54am Sheet 8
1st Fire Solutions
Sprinkler Systems Hydraulic Flow Calculations
Tukwila Residence
4027 So 126th Tukwila, WA
Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps)
Bulk
Notes
C = 150
K=8.96=4.50+4.46 L 10.0 PT 8.48 6 CM 1 + CM 2
26.1=8.96(8.48)^.5 F 7.0 PE 0.00
6 26.1 1.109 1PE T 17.0 0.10743 PF 1.83 8.7
L 8.2 PT 10.31 7
F 5.0 PE 0.00
7 26.1 1.109 1PT T 13.2 0.10743 PF 1.42 8.7
L 6.0 PT 11.72 8
F 7.0 PE 0.00
8 26.1 1.109 1PE T 13.0 0.10743 PF 1.40 8.7
PT 13.12 9
K -factor for Bulk = 26.1/(13.12)^.5 = 7.21
Riser C = 150
L 10.0 PT 13.12 9 Top of Riser
F 7.0 PE 8.66 (EL= 20.0 ft)
9 26.1 1.109 1BKF 1PE T 17.0 0.10748 PF 8.83 8.7 1BKF = 7.00#
PT 30.61 10 B.O.R.
K -factor for Riser = 26.1/(30.61)^.5 = 4.72
Under ground
L 35.0 PT 30.61 10
F 9.0 PE 0.00
10 26.1 1.554 1MTR 1PE T 44.0 0.02079 PF 7.91
PT 38.52 11
Supply pressure available with 26.1 gpm flowing is 80.00 psi,
C = 150
B.O.R.
4.4 1MTR = 7.00#
Supply Jct
thus system requirement is 41.48 psi below supply curve. (51.8%)
TUKWILAR 04/23/19 9:54am Sheet 9
Supply Analysis
Node at Static Residual Available Total Required
Source Pressure Pressure Flow Pressure Demand Pressure
11 80.00 0.00 0.0 80.00 26.1 38.52
Node Analysis
Elevation Node Type Pressure Discharge
Node (ft) K -Value Source (psi) (glom) Notes
1 20.00 Orif= 4.90
2 20.00 Orif= 4.90
3 20.00
4 20.00
5 20.00
6 20.00
7 20.00
8 20.00
9 20.00
10 0.00
11 0.00
Supply
7.00 13.0
7.00 13.0
7.31 -
8.00
8.07
8.48
10.31
11.72
13.12
30.61
38.52
TUKWILAR 04/23/19 9:54am Sheet 10
' Pipe Information
Nodel Elevl Kfactor Qadd Nominal Fittings L (ft) Cfac Total Pt
Pipe (ft) Hose ID F (ft) Vel Elev Pe
Node2 Elev2 Qtot Actual Length T (ft) Psi/Ft Fric Pf Notes
1 20.00 4.90
1
3 20.00
13.0 1" 1PT
13.0 1.109
L 5.5 150 Pt 7.00
F 5.0 4.3 Pe 0.00
5.0 T 10.5 0.0295 Pf 0.31 A01:K=4.81
2
2 20.00 4.90
13.0 1" 1PT
4 20.00 13.0 1.109
L 29.0 150 Pt 7.00
F 5.0 4.3 Pe 0.00
5.0 T 34.0 0.0295 Pf 1.00 BL1:K=4.60
3 20.00 4.81 [13.0] 1" 1PT L 20.7 150 Pt 7.31 A01
3 F 5.0 4.3 Pe 0.00
5 20.00 13.0 1.109 5.0 T 25.7 0.0296 Pf 0.76 BL2:K=4.58
4 20.00 4.60 [13.0] 1" 1PT L 7.0 150 Pt 8.00 BL1
4 F 5.0 4.3 Pe 0.00
6 20.00 13.0 1.109 5.0 T 12.0 0.0296 Pf 0.36
5 20.00 4.58 [13.0] 1" 1PT L 9.0 150 Pt 8.07 BL2
5 F 5.0 4.3 Pe 0.00
6 20.00 13.0 1.109 5.0 T 14.0 0.0296 Pf 0.41
6
6 20.00
7 20.00
1" 1PE L 10.0 150 Pt 8.48 CM 1 + CM 2
F 7.0 8.7 Pe 0.00
26.1 1.109 7.0 T 17.0 0.1074 Pf 1.83
7
7 20.00
8 20.00
1" 1PT L 8.2 150 Pt 10.31
F 5.0 8.7 Pe 0.00
26.1 1.109 5.0 T 13.2 0.1074 Pf 1.42
8
8 20.00
9 20.00
1" 1PE L 6.0 150 Pt 11.72
F 7.0 8.7 Pe 0.00
26.1 1.109 7.0 T 13.0 0.1074 Pf 1.40
9
9 20.00
10 0.00
1" 1BKF 1PE L 10.0 150 Pt 13.12 Top of Riser
F 7.0 8.7 Pe 8.66 1BKF = 7.00#
26.1 1.109 7.0 T 17.0 0.1075 Pf 8.83
10 0.00 1 1/2" 1MTR 1PE L 35.0 150 Pt 30.61
10 F 9.0 4.4 Pe 0.00 1MTR = 7.00#
11 0.00 26.1 1.554 9.0 T 44.0 0.0208 Pf 7.91 Supply
REVISIONS
BY
MAXIMUM ALLOWABLE DISTANCE OF RESIDENTIAL HEADS IN GWB CEILING AREAS
DEFLECTOR ABOVE SURFACE MOUNTED LIGHT FIXTURES
GWB CEILING
"A' DISTANCE FROM SPRINKLER
TO SIDE OF FIXTURE
Less than 1 ft 0"
One ft to -less-than 1 ft 6 in. 0
1 ft 6 in. to less than 2 ft 1"
2 ft to less than 2 ft 6 in. 1"
2ft6in.tolessthan3ft 1"
3 ft to less than 3 ft 6 in, 3"
3 ft 6 in. to less than 4 ft 3"
4fttoless than 4ft6in. 5"
4 ft 6 in. to less than 5ft 7"
5 ft to less than 5ft 6 in 7"
S ft 6 in. to Tess than 6ft 7"
6 ft to less than 6ft 6 in 9"
6ft6intoless than 7ft 11"
7 ft and greater 14"
"B" MAXIMUM ALLOWABLE DISTANCE OF DEFLECTOR
ABOVE. BOTTOM OF FIXTURE
VIP
1) System Type: Wet
2) All material shall be new and U,L, listed or RM.
approved
3) Fire sprinkler system to be installed braced and tested
in accordance with N;FP.A. #13
4) in localities subject to freezing conditions, it is the owners
responsibility to provide heat throughout the wet pipe
sprinkler system areas and in enclosures 'for valves
controlling water supplies to sprinkler systems
5) Pipe and fittings to be CPVC "SLAZEMASTER"
6) Hangers to be TOLCO #22 or #23 (or equal)
7) Hangers spacing; Maximum distance between hangers for CPVC pipe
3/4" 1" 1 1/4" 1 1/2" 2"
6'6" 6'0" 6'6" 7'O" 8'O"
8) Locate a hanger within 6" of each sprinkler head
9) Sprinkler system designed per N.F.P.A: 13D
10) 16' x 16' Maximum Head Spacing 3'-0" Dead end piping max.
E ED 4TT1C SPACE
CEILING! :JSULATI IN--_
(BYOTHERS)
MINIMUM 6
MIN.
TRUSS CHORD
OR JOIST
SPRINKLER PIPE
/2" GYPRCCK --
(BY OTHERS)
APOUR BARRIER
(BY OTHERS)
ED Without Comments
As Noted in Red
❑ Per The Attached Letter
CPVC PIPE STRAP
HANGER APPLICATION
RESTRAINER APPLICATION
HANGER CLIP
6"'MIN.
CEILING INSULATION
(BY OTHERS)
T TRUSS CORD
These plans have been reviewed by The Tukwila Fire
evention Bureau for conformance with current City
;tenaards. Acceptance is subject to en -ors and
_'nlsslons which do not authorize violations of adopted
andards and ordinances. The responsibility for the
adequacy of design rests Cu lly with the designer.
Additions, deletions or revisions to these drawings after
I this date will void thL3 acceptance and will require a
resubmittal of revised drawings for subsequent approve'
Final acceptance is s. bject: to If eid test and Inspection by
The Tukwila Fire P 'v''ei'l Iva; Bureau.
Date: 5.
By. Jr i I
CPVC PIPE- HEX HEAD SELF
TAPPING SCREW
CPVC PIPE
DOUBLE FASTENER SINGLE FASTENER
CPVC PIPE STRAP CPVC PIPE STRAP
1/2" GYPROCK
VAPOUR BARRIER
(BY OTHERS)
Rau r, ri11YR 9i7YureMMMMMM we"
i lk.TtP%tCATR-Olt C®MNl&TNNCY
I9 a $I1:.111CTION IIPRIINKLER 411Y4111111,
• I •C0 L 13`
Drawn e
Sheet
Of / Sheets
Ammommilik
30 X 42
PRINTED ON NO. 1000H CLEARPRINT®