HomeMy WebLinkAboutPP - 12785 GATEWAY DR - GATEWAY CORPORATE CENTER BUILDING #6 / RADIXOS - PERMITS AND PLANS12785 GATEWAY DR
ASSOCIATED PERMITS
07-F-072
BATTERY CALCULATION WORK SHEET
Contractor:
C ., C & R Electric, Inc.
919 S.W. 150th St. Suite A
Burien, WA 98166-1829
Office (206) 937-3654
FAX (206) 932-8538
Customer:
Chinn Construction LLC
Attn: Kevin Chinn
1 Lake Bellevue Dr. #104
Bellevue WA. 98005
FIRE PANEL
6'7- .-o7Z
Job Site:
Alligis At
Gateway Corporate Center
12761 Gateway Drive Building 6
Tukwila, WA 98168-3308
Date:
Panel Type:
Module:
Office
FAX
3/6/2007
Silent Knight
5820XL
NFPA 72A Local systems Require 24 hours of standby plus 5 minutes of alarm
operation at the end of the 24 hour period. You must use battery ampere hours
(A.ii) calculations to verify compliance with NFPA 72A. The following formula
includes the calculation for 5 minutes of alarm operation at the end of the 24 hour
period, as well as a 10% contingency factor which allows for depletion of battery
capacity with age.
PART#
Qt
STANDBY
ALARM
UNIT
CURRENT
TOTAL
CURRENT
UNIT
CURRENT
TOTAL
CURRENT
Panel
5820
1
0.215
.2150
0.385
.3850
Smoke Det.
SD505APS
6
0.00055
.0033
0.00055
.0033
Duct Base
SD505ADHR
5
0.035
.1750
0.035
.1750
Cantact Module
SD500AIM
3
0.00055
.0017
0.00055
.0017
Pull Station
SD500PS
10
0.00055
.0055
0.00055
.0055
Horn/Strobe (110cd)
WH -129404
9
0
.0000
0.244
2.1960
Horn/Strobe (75cd)
WH -129404
2
0
.0000
0.184
.3680
Horn/Strobe (30cd)
WH -129404
9
0
.0000
0.107
.9630
Strobe (15cd)
WH -129400
2
0
.0000
0.041
.0820
Outside Strobe (110cd)
WH -129013
1
0
.0000
0.138
.1380
Outside Bell
WH -103943
1
0
.0000
0.03
.0300
.0000
.0000
Total Standby .4005
Total Alarm 4.3475
Capacity
Formula
Calc Value
Standby Capacity
Total standby load X 24 hours X 1.1 Contingency factor.
10.5719
Alarm Capacity
Total alarm load X .083 hours (5 minutes)
.3608
Total Capacity
Standby and alarm capacity
10.9327
NFPA 72A Local systems Require 24 hours of standby plus 5 minutes of alarm
operation at the end of the 24 hour period. You must use battery ampere hours
(A.ii) calculations to verify compliance with NFPA 72A. The following formula
includes the calculation for 5 minutes of alarm operation at the end of the 24 hour
period, as well as a 10% contingency factor which allows for depletion of battery
capacity with age.
QT
QT
PART #
SYMBOL
DESCRIPTION
1
N
N
5820XLY,K,
FIRE ALARM CONTROL PANEL
5860R
FIRE ALARM ANNUNCIATOR
5895XL
BS I R
SIGNAL BOOSTER
2
RJ31 PHONE CONNECTION
RJ
1
SD505APS
SD5056AB
SMOKE DETECTOR
5
SD505APS
SD505ADHR
D
DUCT SMOKE DETECTOR
BK -5603
0
FIXED TEMP. HEAT DETECTOR
(Cy
SD500PS
PULL STATION
F
1
SPRINKLER WATERFLOW
2
SPRINKLER TAMPER
A
SPRINKLER SUPERVISORY
3
SD500AIM
ID
P❑INT ID MODULE
20
WH -129404
ADA HORN -STROBE 15/30/75/110
WH-127808LK
ADA HORN -STROBE 75
2
WH -129400
ADA STROBE 15/30/75/110
1
WH -129013
1
OUTSIDE STROBE
1
WH -123943[10
FIRE ALARM BELL
WH-138484FA
MINI HORN 24V WHITE
WH -126374
DUAL SYNC MODULE
SM
AI15O4AQ
MAGNITIC DOOR HOLDER
DH
SD500-ARM
RM
RELAY MODULE
J
J BOX
i
AID
MAR 12 2007
12785 GATEWAY DR Tukwila Fire
07-F-072 J -#25-000
7C
C IR 3Lectric, I
Fire/Security/Access Systems
919 S.W. 150th St. Burien, WA 98166-1829
PHONE: (206) 937-3654 / FAX: (206) 932-8538
Alligis At Gateway Corporate
Center
FIRE SYSTEM
12761 Gateway Dr. Bldg. #6
Tukwila, WA 98168
DRAWING ISSUE
DRAWING TITLE
SCALE:
PLOT DATE:
CAD FILE:
PROJ. MGR.:
DRAFTER:
SHEET NO.
N
N
TO FACP
ZN 9
ZN 8
ZN 7
ZN 6
ZN 5
NOTICE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate must be presented
to the Inspector prior to
commencement of Acceptance
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
terminationf the testing.
110,40.050-l�'slMolt AvAtrA PyNNtJitGIA~f1oN/��
,Ic-v14
1yfzetwooll OAA 11✓ (AN' ti poo, 15 Not
V'ty►b(K MAIO Gtr -P` 4
lig. t o. oho —0{- cove 5thoccu (;) t 2.3 •�l •5
VAL 1(a .4o. O/o- %w tiL~t Q� vosc D
�/INta1C/A1' 1417 ublA15 1N
�tvlra o � 1k� I�v� c� �utc•� �� - m,�tas ��
COW* DIM/an � OW ' t (149(UPeC\014 A9 iccfPatun VI 0(2 N r p
ACCEPTED
02 Without Comments
As Noted In Red
0 Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current city
standards. Acceptance is subject to errors and
omissions which do not authorize violations of adopted
standards and ordinances. The responsibility for the
adequacy of design rests totally with the designer.
Additions, deletions or revisions to these drawings atter
this date will void this, acceptance and will require a
resubmittal of revised drawings for subsequent approval.
110cd
Final acceptance is subject to field test and inspection by
The Tukwila Fire,Prevention Bureau.
Date: SI15/0/ By: i-W1512-
fUKWILA
FIRE DEPART1vgtivi
Please call: 575.4407
and give this job
No. n4 -f- on
and exaa°'.#:address for shut*
down or rstoration approval.
a
i
FROM FACP
HC 1
ZN 10
110cd
a HC 2.2
FROM FACP
HC 2
110cd=
QT
QT
PART #
SYMBOL
DESCRIPTION
1
5820XL
FIRE ALARM CONTROL PANEL
5860R
FIRE ALARM ANNUNCIAT❑R
5895XL
ES
IR
SIGNAL BOOSTER
2
RJ31 PHONE CONNECTION
Ej
1
SD505APS
SD5056AB
SMOKE DETECTOR
5
SD505APS
SD505ADHR
rak
p
DUCT SMOKE DETECTOR
BK -5603
•
FIXED TEMP. HEAT DETECTOR
(p
SD500PS
F
PULL STATI❑N
1
4
SPRINKLER WATERFLOW
2
SPRINKLER TAMPER
A
SPRINKLER SUPERVISORY
3
SD500AIM
ID
P❑INT ID MODULE
20
WH -129404
ADA HORN—STROBE 15/30/75/110
WH -127808
ADA HORN—STROBE 75
2
WH -129400
1
ADA STROBE 15/30/75/110
1
WH-129013LI
OUTSIDE STROBE
1
WH -123943
DO
FIRE ALARM BELL
WH-138484TA
MINI HORN 24V WHITE
WH -126374
DUAL SYNC MODULE
SM
AI1504AQ
MAGNITIC DOOR HOLDER
DH
SD500-ARM
RM
RELAY MODULE
J
J BOX
C.) cfc:
(1)
rn
U
U
(1)
L":14
rnCO
CcoCV 00
O
ao
- I
I
CO co
cD
CO
CZ
O
rn
0
110cd
110cd
110cd
EOLR
75cd
HC 3.8
15cd
HC 3.6
30cd
HC 3.4
Hood
�.a
HC 3.3
30cd
EOLR
HC 4.7
15cd
FROM FACP
HC 3
taziD
FESIIIMESEI
HC 4.4
30cd ►►
30cd
HC 4.3
ZN 13
ZN 2
ZN 3
ZN 4
DRAWING ISSUE
DRAWING TITLE
FIRE SYSTEM
SCALE: 1/8" = 1'
PLOT DATE:
CAD FILE:
PROJ. MGR.:
DRAFTER:
SHEET NO
CO
czis