HomeMy WebLinkAboutPP - 13311 37TH AVE S - SHIKARNY HOMES - PERMITS AND PLANS13311 37TH AVE S ASSOCIATED PERMITS 12-5-241 SHINARNY HONES - SFR1 Drawing Date:10-30-12 10/29/12 9: 2 Job Name: Location: Drawing Date: Contractor: HYDRAULIC DESIGN INFORMATION SHEET SHIKARNY HOMES - SFR1 13311 37TH AVENUE TUKWILA, WA 10-30-12 BURNS FIRE SYSTEMS PO BOX 1110 GRANITE FALLS, WA 98252 Designer: NICK/DAVE Calculated By:SprinkCAD www.sprinkcad.com 451 N. Cannon Ave. Lansdale, PA 19446 Construction: WOOD FRAME Reviewing Authorities:TUKWILA Remote Area Number: 1 Telephone:1-877-388-0124 Occupancy:RESIDENSE SYSTEM DESIGN Code:NFPA 13 D Hazard:DWELLING System Type:WET Area of Sprinkler Oper. Density (gpm/sq ft) Area per Sprinkler Hose Allowance Inside Hose Allowance Outside 512 sq ftl 0.055 I 324.0 sq ftl 0 gpm I 0 gpm I Sprinkler or Nozzle Make: Model: LF II K -Factor: 4.90 Temperature Rating: 155 CALCULATION SUMMARY 2 Flowing Outlets gpm Required: 35.7 psi Required: 74.1 @ CITY CONN WATER SUPPLY Water Flow Test Date of Test Static Pressure Residual Pres At a Flow of Elevation 10-26-12 99.0 psi 20.0 psi 1100 gpm 0" Pump Data Rated Capacity. Rated Pressure Elevation Make: Model: 0 gpm 0.0 psi 0 Location: SITE MAIN Source of Information: TUKWILA WATER DEPARTMENT SYSTEM VOLUME 18 Gallons Notes: SH1KARNY HOMES - SFR1 Drawing Date:10-30-12 10/29/12 9: 2 HYDRAULIC CALCULATION DETAILS QTY DESCRIPTION HYDRAULIC FLOW LOSS LENGTH C ID gpm psi TOTALS Hydr Ref W Required at Hyd Area 1 Total Loss 1 Pipe 1" 42x21 GALV 1 1" Thrd Gate Valve Kennedy 1 1" Thrd Back Flow Valve WILKINS for TO SYSTEM 8' 120 1.049 0' 120 1.049 " CHART LOSS Total Loss for THRU RISER Hydr Ref R1 Required at AT BASE OF RISER Total Loss 1 Pipe 1" PVx30 BlazeMa Plastic 1 1" Other Valve METER 1 Pipe 1" PVx30 BlazeMa Plastic for THRU UNDG 50' 150 1.101 CHART LOSS 10' 150 1.101 36 36 3.0 36 0.0 36 5.5 36 36 36 36 9.9 7.1 2.0 46.5 psi 0.0 psi 8.6 psi 55.1 psi 0.0 psi Hydr Ref R2 Required at CITY CONN 36 74.1 psi Water Source 99.0 psi static, 20.0 psi residual @ 1100 gpm 36 gpm 98.9 psi SAFETY PRESSURE Available Pressure of 98.9 psi Exceeds Required Pressure of 74.1 psi This is a safety margin of 24.7 psi or 25 % of Supply Maximum Water Velocity is 12.2 fps 24.7 psi SHIKARNY HOMES - SFR1 Drawing Date:10-30-12 10/29/12 9: 2 Page 3 FITTING NAME TABLE ABBREV. NAME C Coupling E 90' Standard Elbow F 45' Elbow S Straight Flow Thru Tee T 90' Flow Thru Tee ✓ Valve LEGEND HYD REF Hydraulic reference. Refer to accompanying flow diagram. _ K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\/P Qa Flow added or subtracted Qt Total flow DIA Actual internal diameter of pipe C Hazen Williams pipe roughness factor Pf/ft Friction loss per foot of pipe PIPE Length of pipe FTNG'S Number of fittings. See table above. TOTAL Total length (PIPE + FTNG'S) Pt Total pressure (psi) at fitting Pe Pressure due to change in elevation where Pe = 0.433 x change in elevation Pf Friction loss (psi) to fitting where Pf = 1 x 4.52 x (Q/C)^1.85 / ID^4.87 Pv Velocity pressure (psi) where Pv = 0.001123 x Q^2/ID^4 Pn Normal pressure (psi), where Pn = Pt - Pv NOTES: - Pressures are balanced to 0.01 psi. Pressures are listed to 0.1 psi. Addition may vary by 0.1 psi due to accumulation of round off. - Calculations conform to NFPA 13. - Velocity Pressures are not considered in these Calculations SH1'IARNY HOMES - SFR1 Drawing Date:10-30-12 10/29/12 9: 2 Page 4 NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL NUMBER K -FACTOR FLOW FLOW DENSITY (FT) (GPM/(PSI^)) (PSI) (GPM) (GPM) (GPM/SQ.FT) 1 18.50 1S 18.00 2 18.50 2S 18.00 18 18.50 19 18.50 20 18.50 21 18.50 23 9.50 24 9.50 30 9.50 31 9.50 W -4.00 4.90 4.90 13.5 13.2 13.6 13.3 14.0 13.9 13.8 15.0 21.9 22.1 25..7 20.7 46.5 17.8 17.9 Max velocity of 12.15 occurs in the pipe from W TO 30 17.8 0.05 13.0 0.09 Nodes with "S" indicate a node at the top of a sprig or bottom of drop pendent. The node without an "S" is on the branch. SHIkARNY HOMES - SFR1 Drawing Date:10-30-12 Tyco Fire Products 10/29/12 9: 2 Page 5 HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn PATH 1 FROM HYDRAULIC REFERENCE 1 TO W (PRIMARY PATH) 1S 17.82 1.101 1T 0.50 13.2 13.2 K = 4.90 C=150 7.56 -0.2 0.0 17.82 0.055 8.06 0.4 13.2 Vel = 6.06 1 1.101 1T 5.88 13.5 13.5 EqK = 4.86 C=150 7.56 0.0 0.0 12.26 0.028 13.44 0.4 13.5 Vel = 4.17 10.37 1.101 1T 6.23 13.8 13.8 20 C=150 7.56 0.0 0.0 See PATH 3 22.63 0.086 13.78 1.2 13.8 Vel = 7.70 13.09 1.101 9.00 15.0 15.0 21 C=150 0.00 3.9 0.0 See PATH 2 35.72 0.199 9.00 1.8 15.0 Vel = 12.15 -13.10 1.101 1T 6.70 20.7 20.7 31 C=150 7.56 0.0 0.0 See PATH 5 22.62 0.085 14.25 1.2 20.7 Vel = 7.70 -4.25 1.101 1E 31.78 21.9 21.9 23 C=150 4T 33.24 0.0 0.0 See PATH 6 18.37 0.058 65.03 3.8 21.9 Vel = 6.25 17.35 1.101 1E 72.09 25.7 25.7 30 C=150 3.02 5.8 0.0 See PATH 5 35.72 0.1.99 75.11 14.9 25.7 Vel = 12.15 W 35.72 46.5 K = 5.24 PATH 2 FROM HYDRAULIC REFERENCE 1 TO 21 1S 17.82 1.101 1T 0.50 13.2 13.2 K = 4.90 C=150 7.56 -0.2 0.0 17.82 0.055 8.06 0.4 13.2 Vel = 6.06 UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) SHIKARNY HOMES - SFR1 Drawing Date:10-30-12 10/29/12 9: 2 Tyco Fire Products Page 6 HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn PATH 2 FROM HYDRAULIC REFERENCE 1 TO 21 CONTINUED 1 1.101 1E 50.35 13.5 13.5 EqK = 4.86 C=150 2T 18.13 0.0 0.0 5.56 0.006 68.48 0.4 13.5 Vel = 1.89 1.101 1T 9.74 13.9 13.9 19 C=150 7.56 0.0 0.0 5.56 0.006 17.30 0.1 13.9 Vel = 1.89 7.53 1.101 1E 21.70 14.0 14.0 18 C=150 1T 10.58 0.0 0.0 See PATH 4 13.09 0.031 32.28 1.0 14.0 Vel = 4.45 21 13.09 15.0 K = 3.38 PATH 3 FROM HYDRAULIC REFERENCE 2 TO 20 17.90 1.101 1T 0.50 13.3 13.3 K = 4.90 2S C=150 7.56 -0.2 0.0 17.90 0.055 8.06 0.4 13.3 Vel = 6.09 2 1.101 1T 4.83 13.6 13.6 EqK = 4.86 C=150 7.56 0.0 0.0 10.37 0.020 12.38 0.2 13.6 Vel = 3.53 ' 20 10.37 13.8 K = 2.79 PATH 4 FROM HYDRAULIC REFERENCE 2 TO 18 17.90 1.101 1T 0.50 13.3 13.3 K = 4.90 2S C=150 7.56 -0.2 0.0 17.90 0.055 8.06 0.4 13.3 Vel = 6.09 2 1.101 2T 23.10 13.6 13.6 EqK = 4.86 C=150 15.11 0.0 0.0 7.53 0.011 38.21 0.4 13.6 Vel = 2.56 UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) SHIKARNY HCNIES - SFR1 Drawing Date:10-30-12 10/29/12 9: 2 Tyco Fire Products Page 7 HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn 18 7.53 14.0 K = 2.01 PATH 5 FROM HYDRAULIC REFERENCE 31 TO 30 13.10 1.101 3E 20.23 20.7 20.7 31 C=150 2T 24.18 0.0 0.0 See PATH 1 13.10 0.031 44.40 1.4 20.7 Vel = 4.46 4.25 1.101 3T 46.50 22.1 22.1 24 C=150 22.67 0.0 0.0 See PATH 6 17.35 0.052 69.16 3.6 22.1 Vel = 5.90 30 17.35 25.7 K = 3.42 PATH 6 FROM HYDRAULIC REFERENCE 23 TO 24 4.25 1.101 2T 26.93 21.9 21.9 23 C=150 15.11 0.0 0.0 See PATH 1 4.25 0.004 42.04 0.2 21.9 Vel = 1.45 24 4.25 22.1 K = 0.90 UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) 0 0 0 O 0 0 O O O 11 0 w .► .o 3 0 O .p 01 0 — CA 11 0 0 0 0 0 0 1 I 05 c y 0 a co co 33� W SHIkARNY HOMES - SFR1 Drawing Date:10-30-12 10/29/12 9: 2 Job Name: Location: Drawing Date: Contractor: HYDRAULIC DESIGN INFORMATION SHEET SHIKARNY HOMES - SFR1 13311 37TH AVENUE TUKWILA, WA 10-30-12 BURNS FIRE SYSTEMS PO BOX 1110 GRANITE FALLS, WA 98252 Designer: NICK/DAVE Calculated By:SprinkCAD www.sprinkcad.com 451 N. Cannon Ave. Lansdale, PA 19446 Construction: WOOD FRAME Reviewing Authorities:TUKWILA Remote Area Number: 2 Telephone:1-877-388-0124 Occupancy:RESIDENSE SYSTEM DESIGN Code:NFPA 13 D Hazard:DWELLING System_Type:WET Area of Sprinkler Oper. Density (gpm/sq ft) Area per Sprinkler Hose Allowance Inside Hose Allowance Outside 648 sq ftf 0.068 196.0 sq ftl 0 gpm 1 0 gpm I Sprinkler or Nozzle Make: Model: LF II K -Factor: 4.90 Temperature Rating: 155 CALCULATION SUMMARY 1 Flowing Outlets gpm Required: 13.3 psi Required: 30.1 @ CITY CONN WATER SUPPLY Water Flow Date of Test Static Pressure Residual Pres At a Flow of Elevation Test 10-26-12 99.0 psi 20.0 psi 1100 gpm 0" Pump Data Rated Capacity 0 gpm Rated Pressure 0.0 psi Elevation 0 Make: Model: Location: SITE MAIN Source of Information: TUKWILA WATER DEPARTMENT SYSTEM VOLUME 18 Gallons Notes: SHIkARNY BOMBS - SFR1 Drawing Date:10-30-12 10/29/12 9: 2 HYDRAULIC CALCULATION DETAILS QTY DESCRIPTION Hydr Ref W HYDRAULIC FLOW LOSS LENGTH C ID gpm psi TOTALS Required at Hyd Area 2 Total Loss 1 Pipe 1" 42x21 GALV 1 1" Thrd Gate Valve Kennedy 1 1" Thrd Back Flow Valve WILKINS • for TO SYSTEM 8' 120 1.049 0' 120 1.049 " CHART LOSS Total Loss for THRU RISER Hydr Ref R1 Required at AT BASE OF RISER Total Loss 1 Pipe 1" PVx30 BlazeMa Plastic 1 1" Other Valve METER 1 Pipe 1" PVx30 BlazeMa Plastic Hydr Ref R2 Required at Water Source 99.0 psi static, 20.0 psi for THRU UNDG 50' 150 1.101 CHART LOSS 10' 150 1.101 13 13 13 13 13 13 13 13 0.5 0.0 4.1 1.6 2.5 0.3 21.1 psi 0.0 psi 4.6 psi 25.7 psi 0.0 psi CITY CONN 13 30.1 psi residual @ 1100 gpm 13 gpm 99.0 psi SAFETY PRESSURE Available Pressure of 99.0 psi Exceeds Required Pressure of 30.1 psi This is a safety margin of 68.9 psi or 70 % of Supply Maximum Water Velocity is 4.5 fps 68.9 psi SRIKARNY HONES - SFR1 Drawing Date:10-30-12 10/29/12 9: 2 Page 3 FITTING NAME TABLE ABBREV. NAME C Coupling E 90' Standard Elbow F 45' Elbow S Straight Flow Thru Tee T 90' Flow Thru Tee ✓ Valve LEGEND HYD REF Hydraulic reference. Refer to accompanying flow diagram. _ K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\/P Qa Flow added or subtracted Qt Total flow DIA Actual internal diameter of pipe C Hazen Williams pipe roughness factor Pf/ft Friction loss per foot of pipe PIPE Length of pipe FTNG'S Number of fittings. See table above. TOTAL Total length (PIPE + FTNG'S) Pt Total pressure (psi) at fitting Pe Pressure due to change in elevation where Pe = 0.433 x change in elevation Pf Friction loss (psi) to fitting where Pf = 1 x x (Q/C)^1.85 / ID^4.87 Pv Velocity pressure (psi) where Pv = 0.001123 x Q^2/ID^4 Pn Normal pressure (psi), where Pn = Pt - Pv NOTES: - Pressures are balanced to 0.01 psi. Pressures are listed to 0.1 psi. Addition may vary by 0.1 psi due to accumulation of round off. - Calculations conform to NFPA 13. - Velocity Pressures are not considered in these Calculations SHIRARNY HONES - SFR1 Drawing Date:10-30-12 10/29/12 9: 2 Page 4 NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL NUMBER K -FACTOR FLOW FLOW DENSITY (FT) (GPM/(PSI")) (PSI) (GPM) (GPM) (GPM/SQ.FT) 1 18.50 2 18.50 3 18.50 3S 18.00 18 18.50 19 18.50 20 18.50 21 18.50 23 9.50 24 9.50 30 9.50 31 9.50 W -4.00 4.90 7.6 7.7 7.3 7.4 7.6 7.3 7.7 7.8 12.2 12.3 12.8 12.0 21.1 13.3 Max velocity of 4.54 occurs in the pipe from W TO 30 13.3 0.07 Nodes with "S" indicate a node at the top of a sprig or bottom of drop pendent. The node without an "S" is on the branch. SHI'KARNY HOMES - SFR1 Drawing Date:10-30-12 10/29/12 9: 2 Tyco Fire Products Page 5 HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn PATH 1 FROM HYDRAULIC REFERENCE 3 TO W (PRIMARY PATH) 13.33 1.101 1E 0.50 7.4 7.4 K = 4.90 3S C=150 3.02 -0.2 0.0 13.33 0.032 3.52 0.1 7.4 Vel = 4.54 3 1.101 1.24 7.3 7.3 EqK = 4.93 C=150 0.00 0.0 0.0 13.33 0.032 1.24 0.0 7.3 Vel = 4.54 - 4.67 1.101 1T 9.74 7.3 7.3 19 C=150 7.56 0.0 0.0 See PATH 2 8.66 0.014 17.30 0.3 7.3 Vel = 2.95 - 3.09 1.101 1E 21.70 7.6 7.6 18 C=150 2T 18.13 0.0 0.0 See PATH 3 5.57 0.006 39.83 0.3 7.6 Vel = 1.90 7.75 1.101 9.00 7.8 7.8 21 C=150 0.00 3.9 0.0 See PATH 2 13.33 0.032 9.00 0.3 7.8 Vel = 4.54 -4.89 1.101 1T 6.70 12.0 12.0 31 C=150 7.56 0.0 0.0 See PATH 4 8.44 0.014 14.25 0.2 12.0 Vel = 2.87 -1.59 1.101 1E 31.78 12.2 12.2 23 C=150 4T 33.24 0.0 0.0 See PATH 5 6.85 0.009 65.03 0.6 12.2 Vel = 2.33 6.47 1.101 1E 72.09 12.8 12.8 30 C=150 3.02 5.8 0.0 See PATH 4 13.33 0.032 75.11 2.4 12.8 Vel = 4.54 W 13.33 21.1 K = 2.90 PATH 2 FROM HYDRAULIC REFERENCE 19 TO 21 UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) SHIRARNY BCMES - SFR1 Drawing Date:10-30-12 Tyco Fire Products 10/29/12 9: 2 Page 6 HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn PATH 2 FROM HYDRAULIC REFERENCE 19 TO 21 CONTINUED 4.67 1.101 1E 50.35 7.3 7.3 19 C=150 1T 10.58 0.0 0.0 See PATH 1 4.67 0.005 60.93 0.3 7.3 Vel = 1.59 1 1.101 1T 5.88 7.6 7.6 C=150 7.56 0.0 0.0 4.67 0.005 13.44 0.1 7.6 Vel = 1.59 3.09 1.101 1T 6.23 7.7 7.7 20 C=150 7.56 0.0 0.0 See PATH 3 7.75 0.012 13.78 0.2 7.7 Vel = 2.64 21 7.75 7.8 K = 2.77 PATH 3 FROM HYDRAULIC REFERENCE 18 TO 20 3.09 1.101 1T 23.10 7.6 7.6 18 C=150 7.56 0.0 0.0 See PATH 1 3.09 0.002 30.65 0.1 7.6 Vel = 1.05 2 1.101 1T 4.83 7.7 7.7 C=150 7.56 0.0 0.0 3.09 0.002 12.38 0.0 7.7 Vel = 1.05 20 3.09 7.7 K = 1.11 PATH 4 FROM HYDRAULIC REFERENCE 31 TO 30 4.89 1.101 3E 20.23 12.0 12.0 31 C=150 2T 24.18 0.0 0.0 See PATH 1 4.89 0.005 44.40 0.2 12.0 Vel = 1.66 1.59 1.101 3T 46.50 12.3 12.3 24 C=150 22.67 0.0 0.0 See PATH 5 6.47 0.008 69.16 0.6 12.3 Vel = 2.20 UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) SHlKARNY HOMES - SFR1 Drawing Date:10-30-12 10/29/12 9: 2 Tyco Fire Products Page 7 HYD. ' Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn 30 6.47 12.8 K = 1.81 PATH 5 FROM HYDRAULIC REFERENCE 23 TO 24 1.59 1.101 2T 26.93 12.2 12.2 23 C=150 15.11 0.0 0.0 See PATH 1 1.59 0.001 42.04 0.0 12.2 Vel = 0.54 24 1.59 12.3 K = 0.45 UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) • al rnrn 000 • 8 =EO E E '. v) a a ('w 0.0)0)0.0. c'4) M O) LC) or`'aooi co co E mina n. Q rn 000- oi�Z ON -NQ to ( O G) N 0.Q • Ira3 y c0. sunt —J 22 W W W Z W 0 ' <" �0 F_ga ‘7.•oicoD iV)rj-Q' 0 0 0 N 0 r 0 CO acn- 0 CO 0 0 N Zn 0 to v 0 0 0 I0 ch 0 0 co O to N 0 0 N 0 In r o r d 0 0 •N0 0. t vi 1 • • 0 0 N 0 r 0 CO acn- 0 CO 0 0 N i PLAN VIEW THE NATER METER 18 INSTALLED BY CRY STAFF 1' COUPUNO MUELLER 110 X ANGLE STOP BALL VALVE 8-24250 TO MAIN - TYPE K COPPER PPE -PVC Y ETHYLENE FIRE TO SERVICE TYPE K COPPER (DCVA) DOUBLE CHECK VALVE T MUELLER 300 BALI. CURB VALVE FULL PORT &20205 THIS VALVE IS ROTATED TOA VERTICAL POTION THIS VALVE IS TO BE SEALED IN A OPEN POSMON 1' MUELLER REED. FIRE SERVICE CONNECTION VNTH F.I.P. CONNECTIONS & LOCKABLE ANGLE BALI. VALVE THIS VALVE IS INA HORIZONTAL POSTION DOMESTIC TO SERVICE • TYPE K COPPER PPE -PVC -POLYETHYLENE FITIINGS USED ON THE PIPES LEADING TO THE HOUSE FROM THE MUELLAR TEE SHALL BE MUELLER 110 TYPE FITTINGS OR EQUAL. METER INSTALLED BY CITY MUELLER RES. FIRE SERVICE CONNECTION 1" FIRE SERVICE PARTS LIST: 1-B-24258 - 1" COUPLING MUELLER 110 X ANGLE STOP - BALL 1-B-25028 - 1" CORP STOP - BALL 1 - TAILPIECE WITH FEMALE IRON PIPE THREADS NOTES: 1. NO METER BOXES IN SIDEWALKS AND DRIVEWAYS WHERE POSSIBLE. 2. USE CLEAN 5/8" MINUS CRUSHED ROCK TO BACKFILL AROUND CORP STOP AND SERVICE LINE. 3. THE FIRE SPRINKER SYSTEM SHALL BE DESIGNED PER APPENDIX R AND NFPA13D 4.THE DOUBLE CHECK VALVE SHALL BE INSTALLED WITHIN 5' OF THE WATER METER. 5. THE DOUBLE CHECK VALVE SHALL BE INSTALLED TO PROTECT FROM FREEZING. NOT TO SCALE • City of Tukwila 1" FIRE / DOMESTIC SERVICE SHEET: XX -XX REVISION #1: 1-11-2012 LAST REVISION: APPROVAL: I s COMPOSITION SHINGLES 0/ I/2' COX OR 0.88. OVER 810 PELT OVER TRUSSES COMP. SHINGLES TVP. 6.12 J 118/11111 111 111111 1 111411141 11111 1111 11111111111 111 181111 111/1114111 11111 NU 101;111111 14 181111 miiiiIIR- - 111.. 1110111uI 114, 1111/1/11 1111111 mum ', 111111111 vnaH 111 1111 111111 1. ,. , 1111: .1111111 11111111 E1 1E1111El 1111 1111!1 1/.111111/11111111 1111 I4 11861118111111111 1111811881111 UPPER FLOOR PL. • MAIN PLR 4 PORCH MAIN FLOOR TVP. F ON4.0T ELEV4TION 8CAL&V4'•' BOARD 4 PATTEN 64.111JGLE SIDING CORNER TRIM CONT. METAL GUTTER ON 8/4x8 PAOCIA BOARD TYP. O' LAP SIDIN . WRAP -ROUND Co1.W'TL TTP. OPTIONAL 36' H. GUARDRAIL a l„ vATIOM NQ1E$: 1 VE &IBAR WALL NAILING 1 HOLDOa 45 PER PLAN PRIOR TO INDTALLMS 010440. 2. MASONRY 4 WOOD PRAMS CHIMNEYS AlE TO OE CONSTRUCTED PER IRC. CHAPTER 10 D. CAULK ALL /Daemon JOIN10 4 PENETRATIO40. 4. PROVIDE APPROVED CORROSION RESISTANT PLASHING AT EXTERIOR WALL ENVELOPE PER INC. 47038 D. PR0vtQ9.R4.A0HING AT.ROOP PENETRATIONS PER IRC, 48083 t 448033.1 0. pR7YtDE. WEATHER STRIPPING AT ALL EXTERIOR J GA$AGE-P4111RIOR DOORS. ? 0YIDe. CONT4WQU6 GUTTER$ t 0O12•240OUTS • ALL EAve8. TTP. T. 8. ADORE80 OR 104368 14 844 TO 08 POSTe0 ANC PLAINLY vt61141MS Ff412114 1848 OTTNEIT FRDNTA48. 4144. 4+"1$21614T, U2' STROKE W10TH AND COHTRA6TMG eAcrzataur4D. 8. 94Ov108 STAIRWAY ILLUMINATION rem uta. $303* Ult. Bee OMIT At FOR ADDITIONAL NOTES. 44..880 1 HOUr� II a10' MIK ;AWAY LT ELEVATION NOTE. CONTRACTOR TO v@RIPY ALL DIMENSIONS AND CONDITIONS OF PROJECT AND REPOgt1 ANY OMISSIONS / DISCREPANCIES TO DESIGNER PRIOR TO COMMENCING I110P2K DESIGNER SHALL NOT 8E BUILDING ELEVATIONS ARE 1/8"= r-0" SCALE - SPRINKLER RIS. ELECTRIC BELL CKFLOW PREVENTDR GARAG DR`SIiEV INTO COLD 35' 4LL EXPOSURE PROTECTIEI GARAGE, FIELD FIT 4-5 L.1.JNDRY (1a' FAMILY ®414 2-11 Om' BATH. DEN 4 NOOK 1 49' 1 2 RISE TO FUER ABOVE 11 7ti FOY « � 1 001:20 PO= DINING 11 /9' rat 1 1 /0I LIVING CITY MAIN 35' REMOTE AREA 141 TWO OPERATING HEADS FIRST FLOOR PLAN & SITE PLAN 1/8"=1'-0" 1' WATER METER 1" PV SUPPLY TO BASE OF RISER 1' CITY CONNECTION 37TH AVE, TUKWILA BATH V-01 TOILET 10 418' ED `418' 196 42 14'X14 MAX X SPACING 1' MAX . FROM WALL r-e* BED 18'X18' MAX OMAC1NG X FROt 324 1 DRO. (20 ).� FLOI 1 1 LOFT 13-211 2 14'X14 (9.1 'or 7 MAX F 196 1 •- CL 1 10-7 BED REMOTE AREA 02 ONE OPERATING HEAD SECOND FLOOR PLAN 1/8"=r-0" ALL CPVC SINGLE FASTENER STRAP TYPE HANGER HANGER IETAIL sitti CPVC InDat flOpPXOT , N81Y S CPUC MIELE FASTENER CPVC IERE FASTENER 1EaJrHANGER -APE HAL ER HANGER DETAIL ®HAFOZR IETAIL mom for I' • cvc SZ2 ISS r V r�. Alt vitas r T SIC! 123 du Tato.. tom MAXIMUM ALLOWABLE DISTANCE OF RESIDENTIAL HEADS IN GWB CEILING AREAS DEFLECTOR- ABOVE SURFACE ..,TE __ . _11.11:.__, _1111 _..._....:_...__. ................ �l� Il• L� FIXTURES SURFACE MUNTED LIGHT FIXTURE 'A' DISTANCE FROM SPRINKLER A SEMI -RECESSED HEAD DEFLECTOR 'B' MAXIMUM ALLOWABLE DISTANCE OF DEFLECTOR TO SIDE OF FIXTME ABOVE BOTTOM OF FIXTURE Less than 1 ft One ft to less than 1 ft 6 In. 1 ft 6 In, to less than 2 ft 2 ft to less than 2 ft 6 In. 2 ft 6 In. to less than 3 ft 3 ft to less than 3 ft 6 In. 3 ft 6 In. to less than 4 ft 4 ft to less than 4 ft 6 In. 5 ;1 To less than1PAr 4511r1 ft oIn to less t n 7ft 7 ft and greater 0' 0' 1' 1' 1' 3' 3' 5' 7� r 'r 14' SURGE RESTRAINER FOR STEEL OR CPUC PLASTIC PIPE (DFKI4KER DETAIL. sa sit r. Yr VISQUINE VAPOR BARRIER AND BATT INSULATION OVER PIPING TYPICAL IN COLD AREAS GWB SPRI = PIPING CPVC COUPLING MODIFICATION FOR VERTICAL RISER SUPPORT OCPVC RISER SUPPORT DETAIL WAX GENERAL NOTES' PIPING. IS CPVC TYPICAL EXCEPT SYSTEM RISER WHICH WILL BE COPPER OR GALV. STEEL. ALL CPVC PIPING TO BE CONCEALED IN BUILDING : CONSTRUCTION, ALL HEADS ARE LISTED RESIDENTIAL SPRINKLERS ALL WORK SHALL CONFORM TO NFPA 13-D -{- = CENTERLINE OF PIPING ABOVE 1ST FLOOR +-- _.._............�.., ,.._...,....... ,.�...... ._.,... .._.,._ 111.1.__. _......._. __111.1_. 1.1.11... .__�. _1111. _.._._ FREEZE PROTECTION FDR ALL PIPING BY OVNER ALL ELECTRICAL WIRING BY OWNER 1' 113 SPRINKLERS SEE PLAN ® O 1• PV IMERBROIRO BY ODORS le MED vEXErCAL BAOOLCO PRIM= 1' RIM ASS2OLY e MAN1 f FLOW SMTCH 1• ro moms E EC1VDC MAMA EU FOR 1" SPRINKLER RISER IN LAUNDRY ROOM DETAIL FOR ATTIC PIPING TYPICAL NO SCALE RISER ELEVATION NO SCALE ru +a,= .11x1 .z AA4li Mt1 'IVYat D E XIX w.•r tione Ad Ear or d s Ira d ate►» �.I Ea". aI0D . Samoa 34.0PO � ` 1t Odd Woad � Ikea RAND r 8 E6.It «pi to 1x/1 1 SIDE PO DAD •.. ., l lS ' i 130 Nod C 17.11 ,� t9�1{ D ice: TY1334 Nam b or Wads 03.0 ' Ij'd d 121.1 lla�1 0.000 at DU af a 1•"L1 . d la.e. Palms DUO Add& Phnom of MO pat 0 Mt pd PEND 11tHI1 E `1;43 •':11 '.i .` .. 1'x3 _- o-_. 1/113 PN OW Nutt WU 17.0 Nod XIX 1111 ESA 1� D ter_ t,2ti 12.2 LF II o.iar' ' 0 1 17 00 01 4 0.011E CHROME 155 5.60 cE eml awD 4aa. Eons -1gAt ffi VA Dswd a03D DS1 t0 d..: !. • WOO* 10-3212 es Pad LOAM BEW %did VIOLA 1 ! i�W4Aa1. 0.003 1110 w „ v 0 4 Mwe: Add Itandadder Pogo Odd L7` Wit€lout Comments As Noted in Red ❑ Per The Attached Letter These plans have been re\ ie ed by The Tukwila Fire Prevention Bureau `k r conformance with current City standards. Acceptance is subct to errors and omissions which do not au horize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance, and will require a resubm%tcai of revised c swings for subsequent' approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: if -1 LH)" By: IM J 1 ( 6.5.3 A warning sign, with minimum 1/4 inch letters, shall be affixed adjacent to the main shutoff valve and shall state the following: WARNING: The water system for this home supplies fire sprinklers that require certain flows and pressures to fight a fire. Devices that restrict the flow or decrease the pressure or automatically shut off the water to the fire sprinkler system, such as water softeners, filtration systems, and automatic shut-off valves, shall not be added to this system without a review of the fire sprinkler system by a fire protection specialist. Do not remove this sign. TUKWILA FIRE DEPARTMENT Please call 206-575 1107 and give this Fire Permit No. /D.-S-iLl and exact address for shut- down or res or tion approval. PAID NOV 02 2012 TUKWILA.SFS �2-- NOTES ONS SPRINKLER SYMBOLS BY SYM i R POS Ti[ei K S 1 8 d 1 SIDE WHITE 151'3 4.20 1/2' TY1334 Tyco LFII 24 PEND 11tHI1 E `1;43 4. 1/2' CSC LF II 2 SIDE CHROME 155 5.60 1' ty333S tyro DS1 BURNS FIRE SYSTEMS PO BOX 1110 GRANITE FALLS, WA 98252 1-877-388-0124 SHIKARNY HOMES - SFR1 13311 37TH AVENUE TUKWILA, WA PERMIT NO. CONTRACT NO. APPROVAL DRAWN BY NICK/DAVE 1/8" = 1'-0" DATE 10-30-12 PLor11D 1 FP 1 of 1