HomeMy WebLinkAboutPP - 14211 37TH AVE S - RESIDENCE - PERMITS AND PLANS14211 37TH AVE 5 ASSOCIATED PERMITS 95-5-191 TRIANGLE FIRE PROTECTION FIRE PROTECTION CONTRACTORS P.O. BOX 264 WOODINVILLE, WASHINGTON 98072 483-5211 HYDRAUL IC CALCULAT IONS PREPARED FOR DEMPERE RESIDENCE - 1ST FLOOR WATER SUPPLY STATIC PRESSURE (psi) 65 RESIDUAL PRESSURE (psi) 20 RESIDUAL FLOW (gpm) 807.2 NUMBER OF BOOSTER PUMPS 0 BOOSTER PUMPS SPRINKLERS MINIMUM FLOW PER SPRINKLER (gpm) 14 7-2 S=OS nick' & an C nN Co °A tiw:ellnmiiAnp""1 MT; H, g 11„,"":n:: inn,„N„ �"nN""li Q "Nn°11 d "N"n8 An„x"°N C„11.:11 11.117:.111! A„�;;; „ �n,1i A:"„r1 11n,mRo� Nu,lln"u A�,7i" N „ "".i ° "nii CO tl' "J A":11 rN""II 1""n„ A"„ 1 ° nfl.A *Shit EN"n11 n1"„ N &n'A" C.,N„ N AN1111 E"".R"0 115 :11 13;11n13n"Nn',0 C.,r111,° a,",;R VN",) R"":R11 n.nwn 0 S:i N"'"N"°A A orl --NZ; ral Ru' Hf:o Nn "N uN A:"nn,1"11 nnn"mdl A..m.A NN",, can Lull1:uyn 1 An„"R41:n1iti�nN � 1301 Curl 151:1i �n,n,1M IS) &","A ) cm coff:A 1,n,11��1 R„" 1115 „ A1'7rSD( ._ I N °1n� it (� ...-...... j .... 1117." PlI11113 till 1117:111 .......i .- ...... ..._..- .... * ..W.._ __•--.-- .»..._•- --_____.-...__ ..._•-_ _ 11:1 1111 1. N PIO It.MHO "°13% I,"n °„1 rill i .1,„,,, 1: .11 "a"rry,1„R ..-.-.-_ ___---.:........ ..............._ .. ...._i..-......_........._. '....-.....-.L........_ ._ ......_. ..__.._..........--..iF._....._...4............. j L....... , 3,:.i c iI —i TRIANGLE FIRE PROTECTION FIRE PROTECTION CONTRACTORS DEMPERE RESIDENCE - 1ST FLOOR PAGE 1 SYSTEM ANALYSIS TO SHOW MAXIMUM FLOW WITH ZERO PRESSURE REMAINING NNNN N Nw.H N NNNNN NNNNNN NNNN N NN N........ NNNN N ................ N N.. .. ..NN N NNNNNNN N NNN N N [ ] TEST AREA 1 REF. PT. THE FOLLOWING SPRINKLERS ARE OPERATING IN: [ ] TEST AREA 2 [ ] TEST AREA 3 [ ] REMOTE AREA K ELEV. FLOW PRESSURE ft gpm psi 200 4.30 23.33 14.31 11.08 201 4.30 23.33 14.27 11.01 THE SPRINKLER SYSTEM FLOW IS THE OUTSIDE HOSE FLOW AT REFERENCE POINT NO. 1 IS [ ] THE INSIDE HOSE [ ] RACK SPKLR'S. [ ] YARD HYDT. FLOW IS THE FOLLOWING PRESSURES & FLOWS OCCUR ---> AT REF. PT. 1 <--- STATIC PRESSURE 65.00 psi RESIDUAL PRESSURE 20.00 psi AT 807.20 gpm TOTAL SYSTEM FLOW 28.58 gpm AVAILABLE PRESSURE 64.91 psi AT 28.58 gpm MIN. PRESS. REQUIRED 64.91 psi AT 28.58 gpm PRESSURE REMAINING 0.00 psi 28.58 gpm 0.00 gpm 0.00 gpm THE ABOVE RESULTS INCLUDE 5 psi FRICTION LOSS AT REF. PT. # 11 FOR A [ [ BACKFLOW PREVENTER DETECTOR CHECK VALVE [ ] METER [ ] OTHER DEVICE TRIANGLE FIRE PROTECTION FIRE PROTECTION CONTRACTORS DEMPERE RESIDENCE - 1ST FLOOR [ ] TEST AREA 1 REF. PT. K PAGE 2 HYDRAULIC CALCULATIONS AT SPECIFIED FLOW THE FOLLOWING SPRINKLERS ARE OPERATING IN: [ 3 TEST AREA 2 [ ] TEST AREA 3 [ ] REMOTE AREA 200 4.30 201 4.30 ELEV. ft 23.33 23.33 THE SPRINKLER SYSTEM FLOW IS FLOW PRESSURE gpm psi 14.05 10.67 14.00 10.60 THE OUTSIDE HOSE FLOW AT REFERENCE POINT NO. 1 IS [ ] THE INSIDE HOSE [ ] RACK SPKLR'S. [ ] YARD HYDT. FLOW IS THE FOLLOWING PRESSURES & FLOWS OCCUR ---> AT REF. PT. 1 <--- STATIC PRESSURE RESIDUAL PRESSURE TOTAL SYSTEM FLOW AVAILABLE PRESSURE MIN. PRESS. REQUIRED PRESSURE REMAINING THE ABOVE RESULTS INCLUDE [] [] BACKFLOW PREVENTER DETECTOR CHECK VALVE 65.00 psi 20.00 psi 28.05 gpm 64.91 psi 63.15 psi 1.77 psi AT 807.20 gpm AT 28.05 gpm AT 28.05 gpm 5 psi FRICTION LOSS 28.05 gpm 0.00 gpm 0.00 gpm AT REF. PT. # 11 FOR A [ ] METER [ ] OTHER DEVICE TRIANGLE FIRE PROTECTION FIRE PROTECTION CONTRACTORS DEMPERE RESIDENCE - 1ST FLOOR FROM TO FLOW PIPE (gpm) (ft) NNNNNNNNNNNN 1 2 28.05 2 3 28.05 3 4 28.05 4 10 28.05 10 11 28.05 11 12 28.05 12 13 28.05 13 14 28.05 14 20 0.00 20 100 0.00 20 101 0.00 14 15 28.05 15 200 14.05 15 16 14.00 16 201 14.00 16 17 0.00 17 18 0.00 18 300 0.00 18 301 0.00 37.50 5.00. 161 .25 6.00 1.00 1.75 5.00 18.75 8.50 5.25 4.75 9.00 13.00 6.00 5.25 9.00 8.00 5.00 3.00 EQV. H -W DIA. FRIC. ELEV. FROM ft. C (in) (psi) (psi) (psi) 39.31 150 2.00 37.79 150 1.11 16.63 150 1.11 15.98 150 1.05 13.70 150 1.25 6.05 150 1.25 3.00 120 1.38 6.00 120 1.38 0.00 120 1.38 5.00 120 1.05 5.00 120 1.05 6.00 120 1.38 13.00 120 1.05 7.00 120 1.05 9.00 120 1.05 6.00 120 1.38 6.00 120 1.38 6.00 120 1.38 6.00 120 1.38 0.01 0.12 0.12 0.16 0.07 0.07 0.06 0.06 0.00 0.00 0.00 0.06 0.07 0.07 0.07 0.00 0.00 0.00 0.00 O .00 0.00 4.33 O .00 O .00 0.00 2.17 0.00 O .00 0.00 O .00 3.90 -0.29 O .00 -0.29 3.90 O .00 0.00 O .00 63.15 62.62 57.38 31.25 27.82 26.80 21.25 18.57 16.99 16.99 16.99 16.99 12.13 12.13 11.27 11.27 7.37 7.37 7.37 A MAX. VELOCITY OF 10.29 ft./sec. OCCURS BETWEEN REF. PT. Sprinkler-CALC Release V By Walsh Engineering Inc. North Kingstown R.I. U.S.A. PAGE 3 TO DIFF (psi) (Psi) 62.62 57.38 31.25 27.82 26.80 21.25 18.57 16.99 16.99 16.99 16.99 12.13 10.67 11.27 10.60 7.37 7.37 7.37 7.37 4 AND 10 O .53 5.24 21.79 3.43 1 .02 5.55 O .51 1.58 O .00 O .00 O .00 0.96 1.75 0.87 O .96 -0.00 O .00 0.00 O .00 71-1, r,) NAL' E=L—CriarovirELNEr STAR GALAXY RESIDENTIAL HORIZONTAL SIDEWALL The world's first, balanced flow residential sprinklers provide the lowest total system demand. Watch profits soar with Star Galaxy residential sprinklers — the world's first residential sprinklers with balanced flow rates. Thanks to a patented, new design, the flow rate of the Star Galaxy horizontal sidewall nearly equals that of the Star Galaxy pendent. Together, they substantially lower Total System Demand. Lower TSD means lower costs — and an improved bottom line. E ,:, s TAR SPRINKLER ADVANTAGES: 14'114' 12'114• v4• 121 Ir 1.114' b•ty main f� + pp• 1ta1t' 14.11.' pips ,Sa12' Balanced flow permits use of both pendent and sidewall sprinklers •10% less piping substantially reduces installation and material costs • Total Flow: 38 GPM • Total Water Requirements: 380 gallons COMPETITIVE SPRINKLER DISADVANTAGES: 14'14• 0 19 PIP* 1-1M• to city mein ,salt' 1ta+r Flow rates require use of pendent sprinkler only • Substantially more piping increases installation and material costs • Total Flow: 40.1 GPM • Total Water Requirements: 401 gallons FEATURES • Unique design requires very low flow rotes and pressures... • Only residential horizontal sidewalls with flow rates comparable to residential pendent's... • Extremely small, streamlined frame design... • Glass bulb element doesn't extend beyond the width of the sprinkler base... BENEFITS helping reduce pipe sizes and water supply requirements. for easy balandng of the system. is very aesthetically pleasing for use in the most architecturally sensitive projects. reducing the risk of damage during installation. 4:: ECHNICAL DATA APPROVAL UL listed for residential use. TEMPERATURE RATING 155 °F (68°C), Bulb Color Red SG RESIDENTIAL SPRINKLERS SPRINKLER TYPE COVERAGE AREA SINGLE SPRINKLER MULTIPLE . SPRINKLERS K FACTOR WIDTH LENGTH FLOW PRESSURE HOW PRESSURE Recessed Pendent 12' 12' 16 GPM 13.8 psi 11 GPM 6.5 psi 4.3 14' 14' 16 GPM 13.8 psi 11 GPM 6.5 psi 4.3 16' 16' 17 GPM 15.6 psi 13 GPM 9.1 psi 4.3 18' 18' 17 GPM 15.6 psi 13 GPM 9.1 psi 4.3 20' 20' 21 GPM 23.8 psi 17 GPM 15.6 psi 4.3 Pendent 12' 12' 16 GPM 13.8 psi 11 GPM 6.5 psi 4.3 14' 14' 16 GPM 13.8 psi 11 GPM 6.5 psi 4.3 16' 16' 17 GPM 15.6 psi 13 GPM 9.1 psi 4.3 18' 18' 19 GPM 19.5 psi 14 GPM 10.6 psi 4.3 20' 20' 20 GPM 21.6 psi 17 GPM 15.6 psi 4.3 Recessed Horizontal 12' 12' 16 GPM 13.8 psi 14 GPM 10.6 psi 4.3 14' 14' 16 GPM 13.8 psi 14 GPM 10.6 psi 4.3 Horizontal ik 12' 12' 16 GPM 13.8 psi 14 GPM 10.6 psi 4.3 14' 14' 16 GPM 13.8 psi 14 GPM 10.6 psi 4.3 16' 16' 18 GPM 17.5 psi 14 GPM 10.6 psi 4.3 16' 20' 29 GPM 25 psi 26 GPM 20.1 psi 5.8 For full technical and specification information, see individual product data sheets. PECIFICATIONS1. : ' Furnish and install an approved residential fire sprinkler system in accordance with NFPA 13D, NFPA 13R or NFPA 13. The sprinklers used must be capable of covering a 16'x16' room utilizing a maximum flow of 18 gpm, flowing from a single sprinkler. This requirement must be achieved using either a pendent or horizontal sidewall sprinkler, with K factors of 4.3 or 5.8 as required. All sprinklers must be provided by the same manufacturer. The system should be designed to use a minimum of piping. To accomplish this, low flow horizontal sprinklers must be used wherever possible. The finish of sprinkler will be determined by the architect but must be available in the following finishes: Bross, White, Chrome, Block and Decorator Almond. Matching escutcheons must be available. Sprinklers furnished shall be Star Galaxy Residential models or approved equal. CTr4F SPF: l A'I: LEE' CDR PO F 4 TI D A' Po. Box 511 • Milwaukee, WI 53201.800.558-5236 • IN WI: 414-769-5500 • FAX: 800-877-1295 • WI FAX: 414-769-8535 TRIANGLE FIRE PROTECTION FIRE PROTECTION CONTRACTORS P.O. BOX 264 WOODINVILLE, WASHINGTON 98072 483-5211 HYDRAULIC CALCULATIONS PREPARED FOR DEMPERE RESIDENCE - 2ND FLOOR WATER SUPPLY STATIC PRESSURE (psi) 65 RESIDUAL PRESSURE (psi) 20 RESIDUAL FLOW (gpm) 807.2 NUMBER OF BOOSTER PUMPS 0 BOOSTER PUMPS SPRINKLERS MINIMUM FLOW PER SPRINKLER (gpm) 13. °YA t_I' j A,„ :�:5 pmuuYm Go N"AAA„A tri AunU�m11 Nnn° I 311!1: m,,, mYulm u A _II xxtlA muMNilpMx �q x,lall: pmmq,a' C"11. N Q::„Ax„N C"axhN Nwq N 0.5 "gpgq"Nu Negg11aullll°118 n:.„°" u::7"0 AxulP':IA m,nYq�ll gl,l'YY�! Nu Nw N �'. wsh„ co ;"ux,";11 pr:..1„ co r...7,N c . 1.- ax AvxxrI! A41:N A gK.> OD "II Pii. CH's18a co1°tl �gYAggN „�p. ■ -1/4421 °317,:11 c,..N 111.•' A OI:IIYYYU YW��I�pyyii� YY �YAqq"a NNpI'• q u� YWI AYIINiYf Y "Ag N cu. �ytl'' Ylglgq 11 °YWII) blgAllll•' °N"1°� Ygll^YWI _II A a,� NYmm°'g CD cm ao° cm I YYW�Y° Awq� A C A C.11 A°YY� a Nom, I�mNil,� N: ri es) Nw ro ° 11 °cm CAN NSID YN Y NYYm gN xj MI el iY°xq I� n M ..11"7 ......... N.. ' "awing CAN I!? YYANMYn IC) linCil ° 1 1 .1 1 ° A xj TRIANGLE FIRE PROTECTION FIRE PROTECTION CONTRACTORS DEMPERE RESIDENCE - 2ND FLOOR PAGE 1 SYSTEM ANALYSIS TO SHOW MAXIMUM FLOW WITH ZERO PRESSURE REMAINING [ ] TEST AREA 1 REF. PT. K THE FOLLOWING SPRINKLERS ARE OPERATING IN: [ ] TEST AREA 2 [ ] TEST AREA 3 [ ] REMOTE AREA 300 4.30 301 4.30 ELEV. FLOW ft gpm 33.00 33.00 THE SPRINKLER SYSTEM FLOW IS PRESSURE psi 13.15 9.35 13.17 9.38 THE OUTSIDE HOSE FLOW AT REFERENCE POINT NO. 1 IS [ ] THE INSIDE HOSE [ ] RACK SPKLR'S. [ ] YARD HYDT. FLOW IS THE FOLLOWING PRESSURES & FLOWS OCCUR ---> AT REF. PT. 1 <--- STATIC PRESSURE RESIDUAL PRESSURE TOTAL SYSTEM FLOW AVAILABLE PRESSURE MIN. PRESS. REQUIRED PRESSURE REMAINING THE ABOVE [] [] 65.00 psi 20.00 psi 26.32 gpm 64.92 psi 64.92 psi 0.00 psi AT 807.20 gpm AT 26.32 gpm AT 26.32 gpm 26.32 gpm 0.00 gpm 0.00 gpm RESULTS INCLUDE 5 psi FRICTION LOSS AT REF. PT. # 11 FOR A BACKFLOW PREVENTER DETECTOR CHECK VALVE [ ] METER [ ] OTHER DEVICE TRIANGLE FIRE PROTECTION FIRE PROTECTION CONTRACTORS DEMPERE RESIDENCE - 2ND FLOOR PAGE 2 HYDRAULIC CALCULATIONS AT SPECIFIED FLOW [ ] TEST AREA 1 REF. PT. K THE FOLLOWING SPRINKLERS ARE OPERATING IN: [ ] TEST AREA 2 [ ] TEST AREA 3 [ ] REMOTE AREA 300 4.30 301 4.30 ELEV. FLOW ft gpm 33.00 33.00 THE SPRINKLER SYSTEM FLOW IS PRESSURE psi 13.00 9.14 13.02 9.17 THE OUTSIDE HOSE FLOW AT REFERENCE POINT NO. 1 IS [ ] THE INSIDE HOSE [ ] RACK SPKLR'S. [ ] YARD HYDT. FLOW IS THE FOLLOWING PRESSURES & FLOWS OCCUR ---> AT REF. PT. 1 <--- STATIC PRESSURE RESIDUAL PRESSURE TOTAL SYSTEM FLOW AVAILABLE PRESSURE MIN. PRESS. REQUIRED PRESSURE REMAINING 65.00 20.00 26.02 64.92 63.97 0.96 THE ABOVE RESULTS INCLUDE 5 [] C] BACKFLOW PREVENTER DETECTOR CHECK VALVE psi psi gpm psi psi psi AT 807.20 gpm AT 26.02 gpm AT 26.02 gpm psi FRICTION LOSS AT REF. [ ] METER [ ] OTHER DEVICE 26.02 gpm 0.00 gpm 0.00 gpm PT. # 11 FOR A TRIANGLE FIRE PROTECTION FIRE PROTECTION CONTRACTORS DEMPERE RESIDENCE - 2ND FLOOR PAGE 3 FROM TO FLOW PIPE EQV. H -W DIA. FRIC. ELEV. FROM TO DIFF (gpm) (ft) ft. C (in) (psi) (psi) (psi) (psi) (psi) 1 2 26.02 37.50 2 3 26.02 5.00. 3 4 26.02 161.25 4 10 26.02 6.00 10 11 26.02 1.00 11 12 26.02 1.75 12 13 26.02 5.00 13 14 26.02 18.75 14 20 0.00 8.50 20 100 0.00 5.25 20 101 0.00 4.75 14 15 26.02 9.00 15 200 0.00 13.00 15 16 26.02 6.00 16 201 0.00 5.25 16 17 26.02 9.00 17 18 26.02 8.00 18 300 13.00 5.00 18 301 13.02 3.00 39.31 37.79 16.63 15.98 13.70 6.05 3.00 6.00 0.00 5.00 5.00 6.00 13.00 7.00 9.00 6.00 6.00 6.00 6.00 150 150 150 150 150 150 120 120 120 120 120 120 120 120 120 120 120 120 120 2.00 1.11 1.11 1.05 1.25 1.25 1.38 1.38 1 .38 1.05 1.05 1.38 1.05 1.05 1 .05 1.38 1.38 1.38 1 .38 0.01 0.11 0.11 0.14 0.06 0.06 0.06 0.06 0.00 0.00 0.00 0.06 0.00 0.21 0.00 0.06 0.06 0.02 0.02 0.00 0.00 4 .33 0.00 0.00 0.00 2.17 0.00 0.00 0.00 0.00 3.90 -0.29 0.00 -0.29 3.90 0.00 0.00 0.00 63.97 63.51 58.94 35.64 32.66 31.76 26.29 23.68 22.30 22.30 22.30 22.30 17.57 17.57 14.82 14 .82 10.09 9.31 9.31 63.51 58.94 35.64 32.66 31.76 26.29 23.68 22.30 22.30 22.30 22.30 17.57 17.86 14.82 15.11 10.09 9.31 9.14 9.17 A MAX. VELOCITY OF 9.65 ft./sec. OCCURS BETWEEN REF. PT. 15 AND 16 Sprinkler-CALC Release V By Walsh Engineering Inc. North Kingstown R.I. U.S.A. O .46 4.56 18.97 2.99 O .89 5.47 O .45 1.38 0.00 0.00 O .00 0.83 0.00 2.75 -0.00 0.83 0.78 0.17 O .14 TRIANGLE FIRE PROTECTION FIRE PROTECTION CONTRACTORS P.O. BOX 264 WOODINVILLE, WASHINGTON 98072 483-5211 HYDRAULIC CALCULATIONS DEMPERE RESIDENCE - BASEMENT PREPARED FOR WATER SUPPLY STATIC PRESSURE (psi) 65 RESIDUAL PRESSURE (psi) 20 RESIDUAL FLOW (gpm) 807.2 NUMBER OF BOOSTER PUMPS 0 BOOSTER PUMPS SPRINKLERS MINIMUM FLOW PER SPRINKLER (gpm) 14.82 17.74 4Alay a &' P°II �m�p 1"A� pJ ::c pmtlw n Atte°°.k Aldi° :k N:Itn pt"I tal �°�� .� Wt"IaY� Nrit �mwapl: F...l: IN> AN�NyA �,l fia,fiDnifi A." O Atln al„ Yfi"iui AY ri AwYll"� A"aa"1"d fl"YYI�'"Y B;„1""p —.4.1 WW.a OD 1.71 ISH "'1 0pn fiA find 11mtlmpn "ww" p ° dllnitl Poittl Yfi fill t�� n'k COI 6" tHn; II ppaa °H C p fllin Au�ilnHil w n� Ytl an "m A a, COYmI"u k p„ Yfinn ors �nnmdlu AuWI^ 9 °aal un°Itl wl i &:"Yu Crii NY fill fill fill fill till fill fill "II WI fill fill fill ,,�{fin p q�"�puY..t�ptIp�.p0pp���� YII OII fill INI ml Oa w t'� ps°°I I�"YW°A A.,, tl°tl"w"dl is7,1 AYmIA� tlnntl Itn" pY"Yfin" fi.etl^ 1 W'°wa t ! Il'tl""YfivA AWmn .uutl CM "°onA Attlwnfl LSD GD m l CA i CA C -n Cnt n CO CM Clue CM a) Uri MI C-11 Ce:11 I3niil nY Atlm'mH 11•••g • _._.=_....__._ ..___......."nun II . 1 1---- II , "...---........._........._ — .,,., 1:011tliJ tie 'Y pp M .- . . . BASEMENT i I UoTTO eA MP9 a .V / `irMA N'I IMAM e fi s' 1 • IH TRIANGLE FIRE PROTECTION FIRE PROTECTION CONTRACTORS DEMPERE RESIDENCE - BASEMENT PAGE 1 SYSTEM ANALYSIS TO SHOW MAXIMUM FLOW WITH ZERO PRESSURE REMAINING [ ] TEST AREA 1 REF. PT. 100 101 THE FOLLOWING SPRINKLERS ARE OPERATING IN: [ ] TEST AREA 2 [ ] TEST AREA 3 [ ] REMOTE AREA K ELEV. FLOW PRESSURE ft gpm psi 5.60 15.00 5.60 15.00 THE SPRINKLER SYSTEM FLOW IS 15.90 8.06 15.93 8.09 THE OUTSIDE HOSE FLOW AT REFERENCE POINT NO. 1 IS [ ] THE INSIDE HOSE [ ] RACK SPKLR'S. [ ] YARD HYDT. FLOW IS THE FOLLOWING PRESSURES & FLOWS OCCUR ---> AT REF. PT. 1 <--- STATIC PRESSURE 65.00 psi RESIDUAL PRESSURE 20.00 psi AT 807.20 gpm TOTAL SYSTEM FLOW 31.82 gpm AVAILABLE PRESSURE 64.89 psi AT 31.82 gpm MIN. PRESS. REQUIRED 64.89 psi AT 31.82 gpm PRESSURE REMAINING 0.00 psi 31.82 gpm 0.00 gpm 0.00 gpm THE ABOVE RESULTS INCLUDE 5 psi FRICTION LOSS AT REF. PT. # 11 FOR A [ ] BACKFLOW PREVENTER [ ] METER [ ] DETECTOR CHECK VALVE [ ] OTHER DEVICE TRIANGLE FIRE PROTECTION FIRE PROTECTION CONTRACTORS DEMPERE RESIDENCE - BASEMENT PAGE 2 HYDRAULIC CALCULATIONS AT SPECIFIED FLOW [ ] TEST AREA 1 REF. PT. THE FOLLOWING SPRINKLERS ARE OPERATING IN: [ ] TEST AREA 2 [ ] TEST AREA 3 [ ] REMOTE AREA K ELEV. FLOW ft. gpm 100 5.60 101 5.60 PRESSURE psi 15.00 14.82 7.00 15.00 14.85 7.03 THE SPRINKLER SYSTEM FLOW IS THE OUTSIDE HOSE FLOW AT REFERENCE POINT NO. 1 IS [ ] THE INSIDE HOSE [ ] RACK SPKLR'S. [ ] YARD HYDT. FLOW IS THE FOLLOWING PRESSURES & FLOWS OCCUR ---> AT REF. PT. 1 <--- STATIC PRESSURE RESIDUAL PRESSURE TOTAL SYSTEM FLOW AVAILABLE PRESSURE MIN. PRESS. REQUIRED PRESSURE REMAINING THE ABOVE RESULTS INCLUDE 65.00 psi 20.00 psi 29.67 gpm 64.90 psi 58.33 psi 6.57 psi AT 807.20 gpm AT 29.67 gpm AT 29.67 gpm 5 psi FRICTION LOSS AT REF. [ ] BACKFLOW PREVENTER [ ] METER [ ] DETECTOR CHECK VALVE [ ] OTHER DEVICE 29.67 gpm 0.00 gpm 0.00 gpm PT. # 11 FOR A TRIANGLE FIRE PROTECTION FIRE PROTECTION CONTRACTORS DEMPERE RESIDENCE - BASEMENT PAGE 3 FROM TO FLOW PIPE EQV. H -W DIA. (gpm) (ft) ft. C (in) 1 2 2 3 3 4 4 10 10 11 11 12 12 13 13 14 14 20 20 100 20 101 14 15 15 200 15 16 16 201 16 17 17 18 18 300 18 301 29.67 37.50 29.67 5.00 29.67 161.25 29.67 29.67 29.67 29.67 29.67 29.67 14.82 14.85 0.00 O .00 O .00 O .00 0.00 O .00 0.00 O .00 6.00 1.00 1.75 5.00 18.75 8.50 5.25 4.75 9.00 13.00 6.00 5.25 9.00 8.00 5.00 3.00 39.31 150 2.00 37.79 150 1.11 16.63 150 1.11 15.98 150 1.05 13.70 150 1.25 6.05 150 1.25 3.00 120 1.38 6.00 120 1.38 0.00 120 1.38 5.00 120 1.05 5.00 120 1.05 6.00 120 1.38 13.00 120 1.05 7.00 120 1.05 9.00 120 1.05 6.00 120 1.38 6.00 120 1.38 6.00 120 1.38 6.00 120 1.38 FRIC. ELEV. (psi) (psi) O .01 0.14 0.14 0.17 O .08 0.08 0.07 O .07 0.07 0.07 O .07 O .00 O .00 0.00 O .00 O .00 O .00 0.00 O .00 0.00 0.00 4.33 0.00 0.00 0.00 2.17 0.00 0.00 0.00 0.00 3.90 -0.29 0.00 -0.29 3.90 0.00 0.00 0.00 FROM TO DIFF (psi) (psi) (psi) 58.33 57.74 0.59 57.74 51.92 5.82 51.92 23.40 24.19 23.40 19.59 3.81 19.59 18.45 1.14 18.45 12.86 5.60 12.86 10.12 0.57 10.12 8.37 1.75 8.37 7.77 0.60 7.77 7.00 0.76 7.77 7.03 0.73 8.37 4.47 0.00 4.47 4.76 0.00 4.47 4.47 0.00 4.47 4.76 0.00 4.47 0.57 0.00 0.57 0.57 0.00 0.57 0.57 0.00 0.57 0.57 0.00 A MAX. VELOCITY OF 10.88 ft./sec. OCCURS BETWEEN REF. PT. Sprinkler-CALC Release V By Walsh Engineering Inc. North Kingstown R.I. U.S.A. 4 AND 10 GR Pi t/421= I=oa 17-71_06e.. 3O t ST. -tel 2x4 tft:CK PiPf HYDRAULIC INFORMATION Gw E. t CE1t� SOtST_ 1 1 x-11 tN SUL&r(vF-1 MrwitAlori ELc Cc AWL 5 PAC tNsuLATi©r!/ H Ar 1C- rEe D€ r# a L.._ Ko Sc� i E - 1 11 Z' -7`t i 142 -Qu 1_71 1.--‘ v 1t-.1 R4nt5 t1. C -I Er`tT Z (L Pi),Iu-J FIRS FLOOR. Pi 7I1\14 FLAN i/4"=1 -D' 'iNSUTiNzn Nio ovCR Pi PC w t3 p, it s1?_ ATTtC 1PILNLATIO / 1\ILER. DE T AUL_ Na SL ecLE 1 Au_ PIPE LALcLJ LA -TEL AS 4o 7i t_ Z Q— DEtic��� HYD ULIL REMLEKILEt7UirJT 3 4- - DE -k1 LOTES GENERAL NOTES HANGER LEGEND a i -di T114. De13-1- pod Pe „0440 4 141 OD P/ r ,' V4 rte -v4 ix!), i.ft TEE .4/ 14" F7'C oUTEr R C %T not..1t4 U SPRINKLER HEAD SYMBOLS 'h ALARM K is cp.. DTZ -1 L t't AL Ft-ooR- Kip TE MAP PACE Land Surveyors Certific3ate This Short Plat correctly represents a survey rade by ■e or under +ny direction in onnforrn.nce with the requirements of appropriate State statute and has Leen properly staked Eugene Aarae, P L S. Certificate No 6012 24 May, 1991 Map on file in vault REVISIONS 1` 1 TNiS GRAWir,1G 15 FOL i)kcra - r C`EST/`tNAIt.!cr. A Pt ,T TALL A i{E r D3=r("Tr lac._ `1PRt}JbC L -E c Yf Y `THE t- TtiE NC )SE rJLY TK//\i!-,LE ec f.C'T f^+tJStr3�� �r� lr�t- 7t1L���ii�nJ _n r ^I n4V/V !,v/LL P,»V Fc1f'_ ALL PLPHi7 , /1/41 < r-Ecsi Otif 7-5 Oa dw 4� to %O 3 /s Co v V n 1 +t� t't 7 ea n a \I 4. .•i�� rs,44re Ar, t • "e/J ere -e—." 7277' r NG V t • tat ` r • ti t y 74 c N2 %9Dy N 31 3 ti • "1 • 471 1 Deed cearings have tea- rotated RCASA S 'meridian i' eq $ D to —� "/e--. s2 —o- Ja¢/%7i�r �•x+.. 3 �-. l-2!.�t.44°. rtv 5v"G.Ot4. Page _-- of Short Nal Numher STATICPSI Ca FLOWING G P M Sol /3 RESIDUAL P S I 20 THIS SYSTEM DESIGNED TO DELIVER G_P M OVER THE HYDRAULIC REMOTE 2 t•t os SQ FT WHEN SUPPLIED WITH WATER AT THE BASE OF RISER ATARATEOF 25 OL GPM AT CA- 70 PSI OUTSIDE HOSE -0- INSIDE HOSE -.Ea RACK SPRK - 1) INSTALLATION TO CONFORM TO N F P A # 13D AND G ITY QF 'TIU K\rl l L4- 2) ALL MATERIALS NEW ANDI L 1 L_ _ APPROVED 3) ALL WELDING PERFORMED IN SHOP AND IN ACCORD- ANCE WITH AWS D-10 9 1 4) PAINTING OF PIPE NOT I1'4 CONTRACT 5) ELECTRICAL WIRING NOI1 IN CONTRACT 6) EARTHQUAKE BRACING PER CODE 7) USE FIG # 401 POLISHED ALUM CANOPY U N 0 #1 #2 #3 #4 #5 #6 #7 #8 #9 - EXP SHELL, ROD & RING - C CLAMP ROD & RING - POWDER STUD ROD & RING - ANGLE CLIP ROD & RING - L ROD & RING - EYEROD & RING - COACH SCREW ROD & RING - CEIL FLG ROD & RING - U HOOK 0 0 3*5 1 UPRIGHT ON LINE UPRIGHT ON 1 SPRIG UP PENDENT ON LINE PENDENT ON 1 DROP-rs:oftin SPR" VKLERS ORIF TYPE DEGREE FINISH QTY ME -1.) I/ z UPRIGHT & PENDENT DROP UPRIGHT SPRIG & PENDENT DROP SIDEWALL- t7.L5 to flirt' -.L DRY SIDEWALL DRY PENDENT DROP / 14, Imp n RY Fe -lo L's 5W, Frio 165 I S5' ISS c►+pr-tE WHITE 1 FIE PL, -k1 NTS NORTH 1 ACCEPTED ® ITHOUT COMMENTS AS NOTED IN RED PER THE ATTACHED LETTER The drawings affixed hereto have been reviewed and accepted by the City of Tukwila Fire Dept Additions, deletions or revisions to these irawings after this date will void thi 5 Jtance and will require a resubimtl.{ or revised drawings Final acceptaice is subject to field inspection by a representative of this department DATE CITY OF TUKWILA 575 4407 TUKWILA FIRE DEPARTMENT Please call 575-4407 and give this job / ‘16 No and exact address for shut- down or restoration appr c/( 6{ t t,J) 7-24' E EN1PERE KE5I DEME J' JUL 2 71935 14:2_ 11 57T1 AVENUE SOUTH TJKWI L A , WA FP TRIANGLE FIRE PROTECTION PO BOX 264 WOODINVILLE, WA 98072 527-5211 483-5211 TOTAL SPRINKLERS CONTRACT WITH E WA. STATE CONT UC NO TR - IA - NF P2740P SCALE AS AV L1 TFI) DATE 7- f 5 BY CAR KtAHAtJ JOB# 'J -►©I 10 THE COMPLETE LINE/ 154648 "'2111 .i/z7 s7 e 1 'I I Tn t t F -T- a£ D P- t -j I Kr { .' 4D r4 t:--d7tclb- f3,6 -J-14 _ _._ No ,z* S — Epp -Lt... t, a _i_i -tiv L _.tom _-;-,F' _ ny y -di T114. De13-1- pod Pe „0440 4 141 OD P/ r ,' V4 rte -v4 ix!), i.ft TEE .4/ 14" F7'C oUTEr R C %T not..1t4 U SPRINKLER HEAD SYMBOLS 'h ALARM K is cp.. DTZ -1 L t't AL Ft-ooR- Kip TE MAP PACE Land Surveyors Certific3ate This Short Plat correctly represents a survey rade by ■e or under +ny direction in onnforrn.nce with the requirements of appropriate State statute and has Leen properly staked Eugene Aarae, P L S. Certificate No 6012 24 May, 1991 Map on file in vault REVISIONS 1` 1 TNiS GRAWir,1G 15 FOL i)kcra - r C`EST/`tNAIt.!cr. A Pt ,T TALL A i{E r D3=r("Tr lac._ `1PRt}JbC L -E c Yf Y `THE t- TtiE NC )SE rJLY TK//\i!-,LE ec f.C'T f^+tJStr3�� �r� lr�t- 7t1L���ii�nJ _n r ^I n4V/V !,v/LL P,»V Fc1f'_ ALL PLPHi7 , /1/41 < r-Ecsi Otif 7-5 Oa dw 4� to %O 3 /s Co v V n 1 +t� t't 7 ea n a \I 4. .•i�� rs,44re Ar, t • "e/J ere -e—." 7277' r NG V t • tat ` r • ti t y 74 c N2 %9Dy N 31 3 ti • "1 • 471 1 Deed cearings have tea- rotated RCASA S 'meridian i' eq $ D to —� "/e--. s2 —o- Ja¢/%7i�r �•x+.. 3 �-. l-2!.�t.44°. rtv 5v"G.Ot4. Page _-- of Short Nal Numher STATICPSI Ca FLOWING G P M Sol /3 RESIDUAL P S I 20 THIS SYSTEM DESIGNED TO DELIVER G_P M OVER THE HYDRAULIC REMOTE 2 t•t os SQ FT WHEN SUPPLIED WITH WATER AT THE BASE OF RISER ATARATEOF 25 OL GPM AT CA- 70 PSI OUTSIDE HOSE -0- INSIDE HOSE -.Ea RACK SPRK - 1) INSTALLATION TO CONFORM TO N F P A # 13D AND G ITY QF 'TIU K\rl l L4- 2) ALL MATERIALS NEW ANDI L 1 L_ _ APPROVED 3) ALL WELDING PERFORMED IN SHOP AND IN ACCORD- ANCE WITH AWS D-10 9 1 4) PAINTING OF PIPE NOT I1'4 CONTRACT 5) ELECTRICAL WIRING NOI1 IN CONTRACT 6) EARTHQUAKE BRACING PER CODE 7) USE FIG # 401 POLISHED ALUM CANOPY U N 0 #1 #2 #3 #4 #5 #6 #7 #8 #9 - EXP SHELL, ROD & RING - C CLAMP ROD & RING - POWDER STUD ROD & RING - ANGLE CLIP ROD & RING - L ROD & RING - EYEROD & RING - COACH SCREW ROD & RING - CEIL FLG ROD & RING - U HOOK 0 0 3*5 1 UPRIGHT ON LINE UPRIGHT ON 1 SPRIG UP PENDENT ON LINE PENDENT ON 1 DROP-rs:oftin SPR" VKLERS ORIF TYPE DEGREE FINISH QTY ME -1.) I/ z UPRIGHT & PENDENT DROP UPRIGHT SPRIG & PENDENT DROP SIDEWALL- t7.L5 to flirt' -.L DRY SIDEWALL DRY PENDENT DROP / 14, Imp n RY Fe -lo L's 5W, Frio 165 I S5' ISS c►+pr-tE WHITE 1 FIE PL, -k1 NTS NORTH 1 ACCEPTED ® ITHOUT COMMENTS AS NOTED IN RED PER THE ATTACHED LETTER The drawings affixed hereto have been reviewed and accepted by the City of Tukwila Fire Dept Additions, deletions or revisions to these irawings after this date will void thi 5 Jtance and will require a resubimtl.{ or revised drawings Final acceptaice is subject to field inspection by a representative of this department DATE CITY OF TUKWILA 575 4407 TUKWILA FIRE DEPARTMENT Please call 575-4407 and give this job / ‘16 No and exact address for shut- down or restoration appr c/( 6{ t t,J) 7-24' E EN1PERE KE5I DEME J' JUL 2 71935 14:2_ 11 57T1 AVENUE SOUTH TJKWI L A , WA FP TRIANGLE FIRE PROTECTION PO BOX 264 WOODINVILLE, WA 98072 527-5211 483-5211 TOTAL SPRINKLERS CONTRACT WITH E WA. STATE CONT UC NO TR - IA - NF P2740P SCALE AS AV L1 TFI) DATE 7- f 5 BY CAR KtAHAtJ JOB# 'J -►©I 10 THE COMPLETE LINE/ 154648 "'2111 .i/z7 s7