FIRE ALARM SYMBOL LEGEND
FIRE ALARM CONTROL PANEL
HEAT DETECTOR
HORN/STROBE
FS MANUAL PULL
SMOKE DETECTOR
STROBE
END OF LINE
RESISTOR
GENERAL NOTES:
1. ALL WORK IS TO CONFORM TO NATIONAL ELECTRIC CODE STANDARDS.
2. WIRING METHOD IS TO BE OPEN CABLING EXCEPT WHERE IT IS EXPOSED AND
BELOW SEVEN FEET -THEN IT IS TO BE IN CONDUIT.
3. ALL JUNCTION BOXES, COVERS AND BACK BOXES ARE TO BE PAINTED RED.
4. PULL STATIONS ARE TO BE MOUNTS AT 48" TO 53" ABOVE THE FLOOR.
5. ALL INDOOR HORNS. STROBES, HORN STROBES AND MINI HORN STROBES ARE TO BE
MOUNTED 80" ABOVE THE FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER.
6. SMOKE DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE FOLLOWING:
A)
8 36O" AWAY
LORSOMPAOXY MAIfR HAN
TO DL
ANY GFLSUYOSRTEESMCEDNFTIFDIFFUSER
FIXTURES
All devices are addressable and on
single SLC loop. 11 smoke
detectors, 4 manual pull stations
and 12 heat detectors.
7. EXTERIOR HORN/STROBE SHALL BE MOUNTED ON THE TOP 'h OF THE OUTSIDE WALL OF THE BUILDING, AS
HIGH AS POSSIBLE FOR MAXIMUM VISIBIUTY FROM THE FIRE DEPARTMENT ACCESS ROADWAY.
8. ALL WIRING PENETRATING ANY FIRE RATED BARRIER SHALL BE SEALED WITH
MATERIAL WHICH WILL PREVENT PASSAGE OF FLAME AND HOT GASSES.
9. OFFICE SPACE HAS DROPPED CEILING AT 9'0". WAREHOUSE WALLS EXTEND
TO APPROXIMATELY 2D'.
DOWN FROM 2ND FLOOR
UP TO 2ND FLOOR
Ea
OCD
ccounting '
Office 1
Office 2
OCDIX
=1.
10CD
H AC
Warehouse
See Item 9 un
General Notes
Dispatch
See Item 9 un e
General No
D
ice 4
110CD
FAAP
See Item 9 under 11 OCD
General Notes
F
RST FLOOR
athr••m
Exis ng -
no changes
t is permit
10C• 1`1110CD
ED
O Without Comments
V As Noted in Red
0 Per � The Attached Letter
•
These.plans have reviewed by The Tukwila Fire
Prevention Bureiu fc,i' conformance with current City
standards. Acceptar e is subject to errors and
omissions. which do not authorize violations of adopted
standards and ordinances. The.responsibility for the
-adequacy of design rests totally with. the designer.
Additions; deletions ,:ir revisions to these drawings after
this date will void til +:::ce.;: ince and will require a
-resubmittal of : evis Li epi, : for subseequent approval
Final acceptante_ .T;;: -..id test and inspection by.
The Tukwila Fire Pry :- i:;; 5uresu.°
Date: D - "a '0 9
-1.7►1s , l c, -Are_ cep4-. fC+NQx I(P7.ox
`6ckov devic-e 444
Ell-C.zrcv'} Irtq,Le-.
?o'ih 1S' Arto4SiIl1-� tPgvi t ot�Cev-{-i- '1
C iliVALA PERE DEPART
Please call: 575-4407
and give this job
No. - f- 0YO
and exact address for shut'
Ouwn or r.?stGration approve.
!herniae=
Co Op Air Conclitioning and Heating
6424 South 143rd Place
Tukwila, Wa. 98168
Prepareui By:
Mark Mc1h sain
Washington Alarm Inc.
1253 South Jackson Street
Seattle, Wa S8144
206-328-3288
Circuit:
Class B @ 16 AWG
Filtered (DC) 24 -volt Supply (1.5 amp circuit)
Starting Voltage = 20.4
Natitsz
NAC 1 Fnt of
ng
d:, .
Wire Legend
Type
D
DESCRIPTION
A
16 AWG,
4 CONDUCTOR 'FPLP' JACKETED CABLEI
GENERAL NOTES:
1. ALL WORK IS TO CONFORM TO NATIONAL ELECTRIC CODE STANDARDS.
2. WIRING METHOD IS TO BE OPEN CABLING EXCEPT WHERE IT IS EXPOSED AND
BELOW SEVEN FEET -THEN IT IS TO BE IN CONDUIT.
3. ALL JUNCTION BOXES, COVERS AND BACK BOXES ARE TO BE PAINTED RED.
4. PULL STATIONS ARE TO BE MOUNTS AT 48" TO 53" ABOVE THE FLOOR.
5. ALL INDOOR HORNS. STROBES, HORN STROBES AND MINI HORN STROBES ARE TO BE
MOUNTED 80" ABOVE THE FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER.
6. SMOKE DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE FOLLOWING:
A)
8 36O" AWAY
LORSOMPAOXY MAIfR HAN
TO DL
ANY GFLSUYOSRTEESMCEDNFTIFDIFFUSER
FIXTURES
All devices are addressable and on
single SLC loop. 11 smoke
detectors, 4 manual pull stations
and 12 heat detectors.
7. EXTERIOR HORN/STROBE SHALL BE MOUNTED ON THE TOP 'h OF THE OUTSIDE WALL OF THE BUILDING, AS
HIGH AS POSSIBLE FOR MAXIMUM VISIBIUTY FROM THE FIRE DEPARTMENT ACCESS ROADWAY.
8. ALL WIRING PENETRATING ANY FIRE RATED BARRIER SHALL BE SEALED WITH
MATERIAL WHICH WILL PREVENT PASSAGE OF FLAME AND HOT GASSES.
9. OFFICE SPACE HAS DROPPED CEILING AT 9'0". WAREHOUSE WALLS EXTEND
TO APPROXIMATELY 2D'.
DOWN FROM 2ND FLOOR
UP TO 2ND FLOOR
Ea
OCD
ccounting '
Office 1
Office 2
OCDIX
=1.
10CD
H AC
Warehouse
See Item 9 un
General Notes
Dispatch
See Item 9 un e
General No
D
ice 4
110CD
FAAP
See Item 9 under 11 OCD
General Notes
F
RST FLOOR
athr••m
Exis ng -
no changes
t is permit
10C• 1`1110CD
ED
O Without Comments
V As Noted in Red
0 Per � The Attached Letter
•
These.plans have reviewed by The Tukwila Fire
Prevention Bureiu fc,i' conformance with current City
standards. Acceptar e is subject to errors and
omissions. which do not authorize violations of adopted
standards and ordinances. The.responsibility for the
-adequacy of design rests totally with. the designer.
Additions; deletions ,:ir revisions to these drawings after
this date will void til +:::ce.;: ince and will require a
-resubmittal of : evis Li epi, : for subseequent approval
Final acceptante_ .T;;: -..id test and inspection by.
The Tukwila Fire Pry :- i:;; 5uresu.°
Date: D - "a '0 9
-1.7►1s , l c, -Are_ cep4-. fC+NQx I(P7.ox
`6ckov devic-e 444
Ell-C.zrcv'} Irtq,Le-.
?o'ih 1S' Arto4SiIl1-� tPgvi t ot�Cev-{-i- '1
C iliVALA PERE DEPART
Please call: 575-4407
and give this job
No. - f- 0YO
and exact address for shut'
Ouwn or r.?stGration approve.
!herniae=
Co Op Air Conclitioning and Heating
6424 South 143rd Place
Tukwila, Wa. 98168
Prepareui By:
Mark Mc1h sain
Washington Alarm Inc.
1253 South Jackson Street
Seattle, Wa S8144
206-328-3288
Circuit:
Class B @ 16 AWG
Filtered (DC) 24 -volt Supply (1.5 amp circuit)
Starting Voltage = 20.4
Natitsz
NAC 1 Fnt of
ng
d:, .
ata
C
D
Total
12
14
1�6
WASHINGTONALARM
Wail Ho r /Strobe (2 Wire) P2R
110
0201
2
2
20.3'3
20.39
20.38
20.37
Wall Strobe SR
110
0.202
2I,1
22
20.34
20.31
20.26
20.18
Wall Hon /Strol a (2 4''re) P2R
110
0.201
6
28
20.34
20.30
20.24
20.14
Wall i lorrs!`5trixbe (2'i "tre) P2R
lit?
0.201
59
Silent Knight Fire Panel
20.30
20.25
20.15
20.01
1 etlrrapa 0.805
vdc lows
0.10
0.15
0.25
0 35+
NOTICE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate must be presented
to the Inspector prior to
commencement of Acceptance
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
termination of the testing.
IMPORTANT NOTICE
Because of increased demand our
inspectors' schedules are booked
3-7 days ahead. Therefore, you
will need to call 206-575-4407 to
schedule your inspections a
minimum of 48 hours in advance
of the date you want an
inspection.
A
B
C
D
E
F
G
WASHINGTONALARM
DEVICE/
MODULE
MODEL
NUMBER
QUANTITY
OF DEVICE/
MODULE
STANDBY
CURRENT
(AMPS)
TOTAL
STANDBY
CURRENT
(CxD)
ALARM
CURRENT
(AMPS)
TOTAL
STANDBY
CURRENT
(CxF)
16
Co Op Air and Heating
Wall Stets
110
0.202
12
12
20.37
20.35
20.33
20.28
Wall Horn/Stittbe (2 V1-ct e) P2R
110
0.201
37
49
20.31
CONTROL PANEL AND MODULES
20.18
20.04
Wall Ho Strobe (2 'Afire) p2R
0
0.201
0
59
Silent Knight Fire Panel
5700
1
0.2
0.2
0.325
0.325
81.1.5
0.25
61.31
0
0
0
0
0
o
0
Battery 12 VOLTS
NP7-12
0
0
0
o
0
o
0
o
0
o
0
o
0
INITIATING DEVICES
,
Smoke Detector
SD505-APS
11
0.00055
0.00605
0.00055
0.00605
Manual Pull Stations
SD505-PS
4
0.00055
0.0022
0.00055
0.0022
Heat Detector
SD505-AHS
12
0.00055
0.0066
0.00055
0.0066
o
0
o
0
0
0
o
0
NOTIFICATION APPLIANCES
Horn
0
Strobe
SR
2
0.077
0.154
Horn/Strobe Combination
P2R
5
0.212
1.06
Bell
0
0.111
0
0
0
0
0
Sum
Column For
Standby
Load
(Amps)
0.215
Multiply By
Required
Standby
Time (24 or
60 Hours)
24
Total
Standby AH
5.156
(G)
Sum
Column For
Alarm Load
(Amps)
1.554
Multiply By
Required
Alarm Time
(5 min =
.083)
0.083
Total Alarm
AH
0.129
(H)
TOTAL
STANDBY
AH (G)
TOTAL
ALARM AH
(H)
REQUIRED
AH (G+H)
SAFETY
FACTOR
(Multiply)
TOTAL
SYSTEM
AMPERE-
HOURS
REQUIRED
TOTAL
SYSTEM
AMPERE -
HOURS
PROVIDED
5.156
0.1289696
5.285
1.3
6.871
14AH
WASHINGTONALARM
Washington Alarm Inc.
1253 S. Jackson Street
Seattle, Washington 98144
Ph: 206-328-3288
Fax: 206-322-7214
0
U
n
L
O
U
E
U
N
NI
FILA
DATE: 2-20-09
DRAB. B. S. Banks
TPS: 09-0057
Sheet 01
v
PAID
FT, 2 Zoos
Tukwila Fire
.1zlGYl3
Preenbees: Ci
Co Op Air Camitiorting and Heating Class B @ 16 AWG
6424 South 143rd Place Filtered (DC) 24 -volt Supply (1.5 amp circuit)
Tukwila, Wa. 98168 Starting Voltage = 20.4
Prepereut By: Maps:
Mark Mcliwain NAC =2. Back of Building
Washington Alarm Inc.
1253 South Jackson Street
Seattle, Wa 98/44
2-328-3288
Type std ei
8rrtt
Next
TSI
12
14
16
1:0
Wall Stets
110
0.202
12
12
20.37
20.35
20.33
20.28
Wall Horn/Stittbe (2 V1-ct e) P2R
110
0.201
37
49
20.31
20.26
20.18
20.04
Wall Ho Strobe (2 'Afire) p2R
110
0.201
10
59
20.30
2025
20.15
20.01
Total errei/amps 0.604
vdc Ism
0.10
81.1.5
0.25
61.31
WASHINGTONALARM
Washington Alarm Inc.
1253 S. Jackson Street
Seattle, Washington 98144
Ph: 206-328-3288
Fax: 206-322-7214
0
U
n
L
O
U
E
U
N
NI
FILA
DATE: 2-20-09
DRAB. B. S. Banks
TPS: 09-0057
Sheet 01
v
PAID
FT, 2 Zoos
Tukwila Fire
.1zlGYl3