Loading...
HomeMy WebLinkAboutPP - 4028 S 146TH ST - PACIFIC COURT APARTMENTS - PERMITS AND PLANS4028 S 146TH ST ASSOCIATED PERMITS 10-F-201 Farenhyt Panel ID: .Location: IFP -50 Calculations Version 12 10.08 f?roJed 'Values. Project Name Project ID: Prepared By: Date I9/13/2010 PACIFIC COURT COMMONS FJPF ,Standby Flours: Alarm Mins: 24 5 DeratingT-actor: Voltage Drop blaming -Threshold % . 1.2 10 (IFP -50 IDP Devices (Storage Rm. tModel: IFP -50 Fire -Alarm Control _anal Volts: X24 VDC Part:# Description Qty AFP -50 IFP -50 Fire Panel 1 IDP Photo, Photo -T 8 ADP lon IDP - Heat, Heat -HT CIDP Heat ROR 1 CurrentDraw Standby 'Alarm 0.325 0.002 0.000 0.000 0.200 0.002 0.000 0.000 IDP- Beam, Beam -T ID? Pduct (non relay) IDP Pduct-R (with relay) IDP IDP Acclimate ROR IDP Control 1DP Control -6 ADP Monitor, Minimon .:IDP Monitor -2 ADP' Monitor -10 1DP Pull -SA, Pull -DA IDP Relay 'FDP Relay -6 `IDP Zone, Zone -6 ADP SSB224BI SSB5OIBHT',' SSB224RB' :2TS451 RTS431FSEY'' PA2100Z RA -100 ARA -1 3824 5496 RPS -1000 ,5865-4 ;58653 5880 5883 Iso (Isolator Module) Isolator Base Sounder Base Relay Base Magnetic Remote Test Key Activated Test Remote LED LCD Remote Annunc LCD Remote Annunc Serial/Parallel Module NAC#1` NAC #2 Power Expander Power Expander LED Annunciator (4G) LED Annunciator (3G) LED Driver Module Relay Module 0.001 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.020 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.025 0.000 0.000 0.000 0.000 0.000 0.000 0.000 Notification Appi Circuit Notification Appl Circuit 0.000 0.000 ate -Standby- -urrent (Amps)0.224 • Wire:AWG 4 Type .Max`NAC Current: 2:5 Amps :MaxPanel Current: 2.3 Amps Ohms Per ..Length(ft) 1000.Ft. One -Way %Drop 1.234 #12 Solid 1.59 0.000 #12 Solid 139 1.588 Intal Alarm Current (Amps) 150 0:48 "19:81 ;0:00 1 '20.40 2.89% 0.00% :Standbymime:lnl•tours 24 t Total StandlbvWHWReouired :3374; 0:083 Alarm?irnie ln'Minutes /'60 (3Mins) `0.132 ' Total=Alarm AH'Reauired Total .Combined.A . R quired 3:51 :Multiply"By-The'DeratingRactor 120 'Minimum13attery AmpHours"Required X961 Command Shortcuts Configure Circuits J ( Print Page J SILEVI 10.1(:11 I Circuit Configuration roject Information Project Name: PACIFIC COURT COMMONS Prepared By: JPF Project ID: 0 Date: 9/13/2010 Ckt. Number NAC#1 Ckt. Name Notification Appl Circuit Panel ID: IFP -50 IDP Devices Use Notification Appl Circuit v - CurrentDraw Each Current Dravv Total Qty Device Standby Alarm Standby._ Alarm 2 System Sensor P2/PC2 Horn/Strobe (110cd) 0.000 0221 0.000 '0,442 1 System Sensor P2/PC2 Horn/Strobe (75cd) 0.000 0.176 0.000 0.176 2 System Sensor P2/PC2 Horn/Strobe (75cd) 0.000 0.176 0D00 0352 4 System Sensor S/SC Strobe (15cd) 0.000 0.056 0000 0264 0.000 D.000 Totals 0.000 1.234 Ckt.Number:NAC42 Ckt. Name: Notification Appl Circuit Panel ID: IFP -50 IDP Devices _Used Notification Appl Circuit Qty Device Current Draw Each Current Draw Iota I Standby Alarm Standby Alarm Unused 0.000 D.000 0:000 Unused 0:000 0.0.00 0.000 0:000 Unused 0.000 0.000 0.000 0.000 Unused '0.000 0.000 0.000 ODOO 0.000 Totals 0.000 0.000 Symbol Legend Make/Model No. Qty. F1RE ALARM CONTROL PANEL wall mount 0 60" to center of enclosure F1RE ALARM REMOTE ANNUCIATOR wall mount 0 60" to center of enclosure back box = standard 2 gang ANALOG/ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR back box = standard 4" round SILENT KNIGHT IFP -50 SILENT KNIGHT RA -1000 SILENT KNIGHT IDP—Photo 0 FIi 0 1 3'-0" MAX. FROM FACP M33: SO COMMUNI I i ROOM 3'-0` MAX l--TONFERENCE Rp:1:. 33:S05 Sensor Point List DT pee Point Description $Typpel IDP—Photo M33:SO1 OFFICE SMOKE DETECTOR ALARM IDP—Photo M33: SO2 COMMUNITY ROOM SMOKE DETECTOR (NORTH) ALARM IDP—Photo M33:S03 COMMUNITY ROOM SMOKE DETECTOR (SOUTH) ALARM IDP—Photo M33: SO4 HALLWAY SMOKE DETECTOR ALARM IDP—Photo M33:S05 CONFERENCE ROOM SMOKE DETECTOR ALARM IDP—Photo M33:S06 STORAGE ROOM SMOKE DETECTOR ALARM IDP—Heat—ROR M33:S07 MEN'S ROOM HEAT DETECTOR ALARM IDP—Heat—ROR M33:S08 WOMEN'S ROOM HEAT DETECTOR ALARM IDP—Photo M33:S09 COMPUTER ROOM SMOKE DETECTOR ALARM IDP—Photo M33: S10 MEETING ROOM/OFFICE SMOKE DETECTOR ALARM IDP—Heat—HT M33:S11 ATTIC HEAT DETECTOR ALARM Module Point List Device Poi t Description Signal IDP—PuI—SA M33:MO1 OFFICE MANUAL PULL STATION ALARM IDP—PuI—SA M33:M02 COMMUNITY ROOM MANUAL PULL STATION ALARM IDP—PuI—SA M33:M03 HALLWAY MANUAL PULL STATION ALARM Sequence of Operations SMOKE DETECTOR HEAT DETECTOR MANUAL PULL STATION SYSTEM TROUBLE AUDIBLE & VISUAL ALARM INDICATION 0 FACP ACTIVATE NOTIFICATION DEVICES TRANSMIT ALARM SIGNAL TO CENTRAL STATION AUDIBLE & VISUAL TROUBLE INDICATION 0 FACP • TRANSMIT TROUBLE SIGNAL TO CENTRAL STATION ANALOG/ADDRESSABLE 135' RATE OF RISE HEAT DETECTOR back box = standard 4" round ANALOG/ADDRESSABLE 190' FIXED TEMP. HEAT DETECTOR located above ceiling/attic space back box = standard 4" round SILENT KNIGHT IDP—Heat—ROR SILENT KNIGHT IDP—Heat—HT ANALOG/ADDRESSABLE SINGLE ACTION MANUAL PULL STATION wall mount 0 48" A.F.F. to bottom of back box back box = standard 2 gang w/ 1 gang mud ring HORN/STROBE COMBINATION wall mount 0 80" A.F.F. to bottom of back box back box = standard 2 gang w/ 1 gang mud ring cd = candela rating of strobe light SILENT KNIGHT IDP—Pull—SA SYSTEM SENSOR P2R WEATHERPROOF HORN/STROBE COMBINATION wall mount 0 12'-0" A.F.G. to bottom of back box back box = provided with device cd = candela rating of strobe light STROBE LIGHT wall mount 0 80' A.F.F. to bottom of back box back box = standard 2 gang w/ 1 gang mud ring cd = candela rating of strobe light STROBE LIGHT ceiling mounted back box = standard 2 gang w/ 1 gang mud ring cd = candela rating of strobe Tight INDICATES END OF UNE DEVICE SYSTEM SENSOR P2RK SYSTEM SENSOR SR SYSTEM SENSOR SCW 1 ,;s_E 11NG h:4./ l 1 OFFICE \\ 15cd ''rC�_� � I E•3; 9 N1-5 Wire Legend SIGNAL UNE CIRCUIT (SLC) 3'—O" MAX. M33: S03 N.A.C. NO. 1 N.A.C. NO. 1 (2) #18AWG. FPLR (FIRE RATED CABLE) (4) #18AWG. FPLR (FIRE RATED CABLE) (2) #14AWG. FPLR (FIRE RATED CABLE) N.A.C. NO. 1 (FEED/RETURN) (4) #14AWG. FPLR (FIRE RATED CABLE) M33: SO4© HALLWAY DEDICATED 120VAC'CIRCUIT Q 4 4 r,= a 4 4©© 4 4 0 4 iI 11610 Ct~:i'UTE1 RM.'; ! 15cd — 1E3; 2j.i 15cd 33: S06 12VDC 7 AMP. HR BATTERY 12VDC 7 AMP. HR BATTERY *'DO NOT RUN CONDUIT INTO BOTTOM OF ENCLO' 33: Si 0 33: S091 MEN I ' X133: S07 Riser Diagram O . - Without Comments ,tir As Noted In Red O Per The Attached Letter Fire Alarm Plan SCALE: 1/4" = 1' — 0" NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be present-=� to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. Building Data ADDRESS: 4028 S. 146th ST. TUKWILA, WA 98168 PARCEL NO.: 0040000250 TYPE OF CONSTRUCTION: OCCUPANCY: BUILDING AREA: 1,454 SF Vicinity Map These plans have been reviewed by The Tukwila Fire, Prevention Bureau for conformance with current city t3ndards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawingsafter this date will void this acceptance and will require ka resubmittal of revised drawings fbr subsequent approval. Final acceptance is subject to Feld test and Inspection by The Tukwila Fire Prevention Bureau. Date: %~ / i- /C7 By:.1.y " 5 1 1 -" 'US+ addvIrssa ;1#11y re „:red dor• euc .. 16,3-,c "5 c�teu;C' , '"-tbj4*Il breyk.t#" L Ilk etc1 , 0'. dLto��Ck Fina ? clew: regkev. 44 I( dicot. &v% ,rte 64YA . 1u1'SWiL.A FIRE DEPART >t, Please call: 576-440 and give this job ma. 12 -F -2-o : :x.. i address for shun y ' v+• rgst.;rc.+tion ai$crouiIl. PROJECT NAME: ' aci lc ourt ' partments New Community Building 4028 S. 146th ST. Tukwila, WA 98168 FIRE ALARM & DETECTION ALARMCI055CW DATE: 9/9/10 SCALE: AS SHOWN DATE SYSTEM TYPE: CONTRACTORS LICENSE NO.: REVISION REVISION ACE FIRE & SECURITY SYSTEMS ADIVISIONOFALARMCENTER, INC. 1-800-354-1555 P.O. BOX 3363 FA1 LACEY, WA 98509-3363 1 of 1 SHEET NO.