Pacific Fire Protection, Inc.
Date 06/11/93
Job: J0HN1154
PROJECT INFORMATION
Job_ OAK TREE HOMES HOUSE #1154
13445 48TH PL S. TUKWILA, WA
Occupancy
...,&I FEL 13P_
Area per Sprinkler 16'x 16' Room Maximum
Number of Sprinklers Calculated: 2 heads
Authority having Jurisdiction_ _ NFPA-13 D
System type_ _ Wet
Water Supply _ 100.00 psi Static, 20.00 psi Residual 0 840.0 gpm
Sprinklers _ _ 7/16 inch orifice
Demand
Notes:
CALCULATION SUMMARY
73.13 psi 0 28.8 gpm @ Supply
99.84 psi available 0 28.8 gpm
Demand is below curve by 26.71 psi
Sheet
OAK TREE HOMES HOUSE #1154
13445 48TH PL S. TUKWILA, WA
*: Static = 100.00 psi Residual = 20.00 psi at a flow of 840.0 gpm
D: System demand = 73.13 psi with 28.8 gpm flowing.
*: Pressure available = 99.84 psi when 28.8 gpm is flowing.
Demand is below curve by 26.71 psi. (26.8%) for Remote Area 1
PSI Multiply pressure scale by 10 N1.85 Graph
10 +--+---+ + + +
9
8
D
7+
6+
5
4
3
2
1
+
+ +
0++---+---+ + + + + + + +
1 2 3 4 5 6 7 8 9 10
GPM
Multiply flow scale by 100
Sheet
Pacific Fire Protection, Inc.
Description of Fitting abbreviations
Code Description
T Tee
E Ninety degree elbow
PT Plastic Tee
PE Plastic 90 degree Elbow
BKF Backflow preventor
MTR Meter Loss
Description of Other abbreviations
Code Description
AO Arm -over
DR Drop
PT Total pressure
PE Pressure loss due to elevation changes
PF Pressure loss due to friction
PV Velocity Pressure
.5 Raised to the power of .5 (Square Root)
A Actual pipe length
F Fitting equivalent pipe length
T Total pipe length
JOHN1154 06/11/93 9:54am
No. Code
1 DR1
2 A01
3 A02
4 BU1
5 BU1
6 BU1
7 RI1
8 UG1
Pacific Fire Protection, Inc.
Sprinkler Systems Hydraulic Flow Calculations
OAK TREE HOMES HOUSE #1154
13445 48TH PL S. TUKWILA, WA
Raw data previous to any calculations
Sheet
Diam Length Kfac1 Kfac2 Press Elev Hose HW Vel Fittings
O .884 0.5 4.3
0.884 6.0 DR1
O .884 0.5 DR1
0.884 20.3 A01
O .884 9.0
0.884 8.5
1.049 8.5 BU1
1.109 75.0 RI1
10.60 -0.50
0.00 0.00
O .00 0.00
A02 0.00 0.00
O .00 9.00
0.00 0.00
-5 0.00 8.50
-5 0.00 0.00
O .0 150 32 1PE
0.0 150 32 1PE,1PT
0.0 150 32 1PT
0.0 150 32 2PE
O .0 150 32 1PE
0.0 150 32 1PE
O .0 120 32 2E ,1BKF ,1T
0.0 150 32 2PE,1MTR,1T
J0HN1154 06/11/93 9:54am Sheet
Pacific Fire Protection, Inc.
Sprinkler Systems Hydraulic Flow Calculations
OAK TREE HOMES HOUSE #1154
13445 48TH PL S. TUKWILA, WA
Pipe Flow Dia. Fitting Length Fr Loss Press Hyd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Notes
Drop 1 C = 150
14.0=4.30(10.60)-.5 F 7.0 PE -0.22 (EL= -0.50 f t )
1 14.0 0.88 1PE T 7.5 0.10244 PF 0.77 7.32
PT 11.15 2 B1 Jct
A 0.5 PT 10.60 1
K -factor for drop 1 = 14.0/(11.15).5 = 4.19
at Hyd Ref Pts 2 3
Arm -over 1 C = 150
A 6.0 PT 11.15 2 DR1
14.0=4.19(11.15)-.5 F 10.0 PE 0.00
2 14.0 0.88 1PE 1PT T 16.0 0.10244 PF 1.64 7.32
PT 12.79 4 Bi Jct
K -factor for arm -over 1 = 14.0/(12.79)-.5 = 3.91
Arm -over 2 C = 150
A 0.5 PT 11.15 3 DR1
14.0=4.19(11.15)-.5 F 3.0 PE 0.00
3 14.0 0.88 1PT T 3.5 0.10244 PF 0.36 7.32
PT 11.51 4 61 Jct
K -factor for arm -over 2 = 14.0/(11.51)-.5 = 4.13
J0HN1154 06/11/93 9:54am Sheet
Pacific Fire Protection, Inc.
Sprinkler Systems Hydraulic Flow Calculations
OAK TREE HOMES HOUSE #1154
13445 48TH PL S. TUKWILA, WA
Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Notes
Bulk C = 150
K=8.04=3.91+4.13 A 20.3 PT 12.79 4 A01 + A02
28.8=8.04(12.79)-.5 F 14.0 PE 0.00
4 28.8 0.88 2PE T 34.3 0.38802 PF 13.31 15.03
A 9.0 PT 26.10 5
F 7.0 PE 3.90 (EL= 9.00 ft)
5 28-8 0.88 1PE T 16.0 0.38802 PF 6.21 15.03
A 8.5 PT 36.21 6
F 7.0 PE 0.00
6 28.8 0.88 1PE T 15.5 0.38802 PF 6.01 15.03
PT 42.22 7
K -factor for Bulk = 28.8/(42.22)-.5 = 4.43
Riser C = 120
A 8.5 PT 42.22 7 Top of Riser
F 9.0 PE 3.68 (EL= 8.50 ft)
7 28.8 1.05 2E 1BKF T 17.5 0.25547 PF 9.47 10.69 1BKF = 5.00#
1T PT 55.37 8 B.O.R.
K -factor for Riser = 28.8/(55.37)-.5 = 3.87
Under ground C = 150
A 75.0 PT 55.37 8 B.O.R.
F 23.9 PE 0.00
8 28.8 1.11 2PE 1MTR T 98.9 0.12895 PF 17.75 9.57 1MTR = 5.00#
1T PT 73.13 9 Supply Jct
Available flow at 73.13 psi is 465.8 gpm which is 437.0 gpm from curve.
Supply pressure available with 28.8 gpm flowing is 99.84 psi,
thus system requirement is 26.71 psi below supply curve. (26.8%)
1 71 OIQCfC
U26 HA
2 X 12
CROSS
1 1
L— — — --1
SECTION
SCALE:. 1/4" = 1'-0"
NGER
CAPPED HALF WALL
2ND FLOQR
•
1 ,
-- APP OVED HANDRAIL
,
--1/2 NOSING
AMING
STRINGERS
NOTE:
CROSS-SECTIONS ILLUSTRATE
GENERAL STRUCTURE OF BUILDING.
FOR DETAILS SEE TYPICAL
WALL SECVION AND RESPECTIVE
FRAMING PLANS.
LI 0
LTJ
HEADROOM
1ST FLOOR
STAIRWAY PROFILE
Lot 4 intlus
according t
of Plats, Pa
Kirg Count'
8
�-'-
111I-2."
8=651/211
60' X 32' TUB/
SHOWER COMB.
W/ INTEGRAL
SURROUND.
VERIFY FRAME -
IN REO:TS.
H GER RODS
CLOSET
0
INSULATED
METAL CHIMN'
,FLUE, INSTALL
CODE 6 MFR'O
INSTRUCTION'
5-0
OM 2 6
0 IA,
..DROOP
4
bBYPASS
N
111
CLOSET
HANGER ROD
t2 42 BYPASS
0
BED00M 3
CARPET
60' X 32' TUB/
SHOWER COMB.
W/ INTEGRAL
SURROUND.
VERIFY FRAME -
IN REO'TS,
LINES OF ROOF BELOW
I CF i/ Il
14*
01, 2 y2) i
fl
• SSICON t ? FLOORr,-\N
SCALE: 1/4" = 1'-0"
ELECTRIC ELL: +,-
O
C A'BO /.. MAIN DgJ DI
INSPECTORS- . TEST _VA:
waTP Flow SW )TC H
Cot -NE -CT TO ELEL.TRIG BELL_
O
MAIN CON1T Fit VALVE
pficrnG FIAF- T
5roAr•t1r-'c'
<1- nl-•1
BA( KFL-.OW PREVarTEI
WATEK L(A1J6 E
ORION TO 0uTSIDE_..-
n
DOMESTIC, SNUr-OFF VALVE
,O
3-10 r,
L8"
ELECTRI
W2
FURNACE
ECTRIC
PANEL
PRYER
NOTE:
FOR FURNACE AND WATER HEATER
CONTRACTOR SHALL
PROVIDE TYPE, SPEC'S., DIS-
TRIBUTION ANO
DESIGN LOADS
DRYER VENT
�a \
100 CFM
WASHER
UTILIT,rROOM
v& .-�
0
RE RIG.
cc INE OF
CABINETS ABO
24
11'07 -
HANGER RO
CLOSET
0
DINING ROOM
4i�!''liar`�rf'�;iP!shit,U;i�yaP"�,`�,`i�r".vt�'�3+
SW2 111 SW2 ODE;
ENTRY
NOTE:
FLOOR PLAN DIMENSIONS ARE
TO FACE OF STUDS. CENTERLINE
OF STRUCTURAL FRAMING OR
CENTERLINE OF DOOR
OR WINDOW LOCATIONS
el- TO DOMESTIC SYSTEM
ISE
p Vc
D[TAfL
N.T 5.
STANDARD SYi ''OI_S
P P LY ---
STAT ;T)ARD SYMBOLS
NOTE:
ALL HEADERS OVER DOORS
ANC) WINDOWS ARE, (2) 2 X 6 11E2
UNLESS OTHERWISE
NOTED.
LINE OF ROOF ABOVE
NOTE:
FOR WINDOW
SIZES AND FUNCTION,
SEE EXTERIOR
ELEVATIONS
71,2.16_II
6' RISER
6' RISER
41 c0/2."
NOTE:
EXTERIOR WALLS ARE FRAMED WITH
2 X 6 @ 16' O,C.,
INTERIOR WITH 2 X 4 @ 16. O.C.,
TYPICAL UNLESS OTHERWISE NOTED
NOTE • SHEARWALLS:
CONTINUE SHEARWALL
CONSTRUCTION
@ FIRST FLOOR LEVEL
THROUGH TO ROOF
IN SECOND STORY WALLS:
i
l o', 2.27--2.
23 1-0'1
SPRINKLER HEAD SYMBOLS ALARM r-tovi -SCJ•
1#1. — KWIK BOLT, ROD & RING
#2. — BEAM CLAMP, ROD & RING
AI#3. — HILTI STUD, ROD & RING
#4. — SIDE BEAM BRACKET, ROD & RING
#5. — TJI BRACKET, L -ROD & RING
�i
1116. — EYE ROD & RING
#'l. — COACH SCREW ROD & RING
014
n} #8 —CEILING FLANGE, ROD & RING
BRUNING 40-5000
Iq — POST INDICATOR VALVE
— KEY GATE VALVE
103— FIRE HYDRANT
--Q — WATERFLOW SWITCH
•Gj' — 2 -WAY EARTHQUAKE BRACE
— 4 -WAY EARTHQUAKE BRACE
NEW UNDERGROUND
__— EXISTING UNDERGROUND
17- — ALARM CHECK VALVE
-- RISER W/ALAFIM VALVE
f> — RISER W/DRY VALVE
t�) — SWING CHECK VALVE
� I — O.S.&Y. GATE VALVE
— WATET MOTOR GONG
ELEC T;IC BELL
y — FIRE DEPT. CONNECTION
— UP -RIGHT ON 1/2" ;OUTLET
® — PENDENT ON 1/2" OUTLET
0 — UPRIGHT ON 1" STUB -UP
C — PENDENT ON 1" DROP
— UPRIGHT ON 1/2" CUTLET &
PENDENT ON 1" ?'
— FLUSH ON 1" ORC''•
- DRY PENDENT ON 1" DROP
SPFII I tLERS
`j CENTI',A L toorc SBP,
CONCEALL=D
FIRST FLOOR PLAN
SCALE: 1/4" = 1'-0"
SHEAR WALLS:
SW 1- 1/2' CDX W/ 8d @ 6',.
EDGES AND @ 12', INTERIOR
SW2- 1/2' CDX W/ 8d @ 4';
EDGES AND @ 12', INTERIOR
SW3- 1/2' CDX W/ 8d @ 3',
EDGES AND @ 12', INTERIOR
HOLDDOWNS:
SIMPSON PA 18, EMBED INTO
CONC.FOUNDATION
WALL, LOCATE WHERE
SHOWN (*)
1 60.27 PROPERTY L SNE
1"(O/
T` -
:^..�1: r4'Rw'?�:•7�'!tG!.^2!m.�a!r"n!!NNYM>dwYtr.....x,v.w.rvm
FOR ROOF SLOPES
SEE EXTERIOR ELEVATIONS
ROOF TRUSSES
SEE ROOF FRAMING PLA
.ZNSUL. OVE'
►�Z\1 PI P/nJCi (TYP
SEE SECOND FLOOR
FRAMING PLAN
SECOND FLOOR
L-".BEANING WALL
FIRST FLOOR
et AWL SPACE
FLOOR BEAM
SEE FOUNDATION PLAN •
NOTE:
FOR PRESCRIPTIVE
INSULATION
REQUIREMENTS SEE SHT.7
NOTES:
1) PIPE AND FITTINGS TO BE CPVC "BLAZEMASTER".
2) OWNER TO INSURE ALL PIPING IS PROPERLY INSULATED TO
PREVENT FREEZING. -'
3) HANGERS TO BE TOLCO #22.
4) HANGERS SPACEING : MAXIMUM DISTANCE BETWEEN HANGERS FOR
CPVC PIPE.
3/4" 1" 1 1/4" 1 1/2" 2"
5'-6" 6' 0" 6'6" 7'0" 8'0"
5) LOCATE A HANGER WITHIN 6" OF EACH SPRINKLER HEAD.
211,011
1 II
:P.ROPOSED
CARPORT
> ESIDENCE
rJPi?{'L Mw4T'
7c -,cc
TYPE DEGREE.k QTY.
15 -
4, I GJI PROPERTY LINE
9n- j3.
i1.
WALK WAY
1-
s Nt.7(..7ii•
OYr•C;HSMC4 ABOVE
DRIVEWAY APRON
SI' ALiL...'CONFOR?,1
IV (MTV fii D I47.C:
ov alrasv ME= V. W »K7I.S
REVISIONS — LOCATE BY GRID COORDIN.ATES
H
NOTE:
CONTRACTOR SHALL VERIFY LOCATION
13F UTILITIES AND COORDINATE SERVICES
INSTALLATION.
FIELD INSPECTION BY
1r
PHONE CONTRACT WITH
rITHOUT COMMENTS.
AS NOTED IN RED
PER THE ATTACHED LETTER
4ruminvsitio.t Asinfillkoirtfyl flteetriotthirs
Ir'd krAlc954411/1'sa/dpare and will
eegtziptrii resubmittal of revised drawings.
,.VItealhingtietnnce is subject to field -
inspection by a representative of this
department
DATE:W:d3
CITY OF TUKWILA
575-4407
Please call: 576-4407
• and give this Job
and exact address for shut,.
kwil or restoration approval.
PMEFI;;:"
41
A
PHONE
ARCHITECT
— SIDEWALL ON 1/2" CUTLET TOTAL SPRINKLERS THIS DRAWING .
YAMIT
ADDRESS
CITY
SCALE:
PHONE PHONE Auburn, Wash.ington 98071
TITLE: FIRE PROTECT! DIV DRAM Ne
DRAWN: j6 F
Pacific Fire
P.O. Box 758
vonevarnmenasumzementrammareffnevareffonmemprzarnorne DATE: _c73
Protection Inc.
DRAWING NO:
1154 A
Auburn (206) 939-6988
if,:
, , 1993 0!
OF