HomeMy WebLinkAboutPP - 15650 51ST AVE S - UNKNOWN - PERMITS AND PLANS15650 51STAVE S
ASSOCIATED PERMITS
97-5-325
SEWING ROOL
THREE CAR GARAGE
RISER 300ft F
CITY MAIN ®
ELEVATION
DZEREIELDECIS
FIRST FLOOR PLAN
SCALE 1/8" = 1'-0"
THREE CAR GARAGE
GREAT ROOM
TOW DAMS OMER SUM MO Mai
1" DRAIN VA. & INSP. TEST
SFCON7 FLOOR
SCALE 1/8" = 1'-0"
1" CPVC 1" SCH 40
WATER PRESSURE GAUGE
WATER FLOW IND
PIPE STAND
1" BACKFLOW PREVENTOR
11E—IN TO DOMESTIC WATER
1 1/2" COPPER
RISER DETAIL
NOT SCALE
GENERAL NOTES
1. bVERHEAD SPRINKLER PIPING AND FITTINGS TO BE- CPVC, INSTALLED AND TESTED PER
N F P.A. #13D, CITY OF TUKWILA AND THE MANUFACTURERS SPECIFICATIONS -
2 PIPE SIZED PER HYDRAULIC CALCULATIONS SYSTEM DESIGNED PER N.F.P.A. #13D WITH
HEADS SPACED ® 400 SQ FT MAX. (20X20) PER MANUFACTURERS SPECIFICATIONS
HEADS ARE CENTRAL GBR-2 K=4 3, 2OFT. MAX. BETWEEN HEADS 10FT. MAX OFF WALL
3. MANGERS TO BE TOLCO FIG 23 AND 24 FOR USE WITH CPVC PIPE (SEE DETAIL) -
4 MAXIMUM DISTANCE BETWEEN HANGERS PER CPVC 3 MANUFACTURER
I1/2" CPVC -- 7'—O"
1/4" CPVC -- 6'-6"
i" CPVC -- 6'—O"
3/4" CPVC -- 5'-6"
HANGERS MUST BE LOCATED WITHIN 6" OF EACH DROP.
5 ADEQUATE HEAT AND INSULATION PROVIDED BY OTHERS OWNER TO MANTAIN NEAT AND
ISULATION TO PREVENT FREEZING OF WET PIPE SPRINKLER SYSTEM.
6 f ! ALL CASES INSULATION MUST BE PLACED SO THE HEAT FROM INSIDE THE UNITS CAN
?EACH THE WET PIPE INSULATE ONLY ABOVE PIPE IN ATTIC, OUTSIDE ONLY OF PIPE IN
EXTERIOR WALLS
7 A►LL AREAS INSIDE UNITS TO HAVE SPRINKLERS EXCEPTIONS AS NOTED, PER N F P A. #13D
;SECTION 4-6
A) SPRINKLERS ARE NOT REQUIRED IN BATHROOMS 55 SQ FT AND LESS
8) SPRINKLERS SPRINKLERS ARE NOT REQUIRED IN CLOTHES CLOSETS, LINEN CLOSETS, AND PANTRIES
WHERE THE AREA OF THE SPACE DOES NOT EXCEED 24 SQ. FT. AND THE LEAST DIMENSION
DOES NOT EXCEED 3 FT AND WALLS AND CEILINGS ARE SURFACED WITH NONCOMBUSTIBLE
OR LIMITED COMBUSTIBLE MATERIALS AS DEFDIND IN NFPA 220, STANDARDS OF BUILDING
A CONSTRUCTION
C) SPRINKLERS MAY BE OMITTED FROM GARAGES, OPEN ATTACHED PORCHES, CARPORTS, AND
SIMILAR STRUCTURES
b) SPRINKLERS MAY BE OMITTED FROM ATTICS, CRAWL SPACES, AND OTHER CONCEALED SPACES
THAT ARE NOT USED OR INTENDED FOR LMNG PURPOSES OR STORAGR.
UNDERGROUND NOTES
1 _ UNDERGROUND SHOWN HERE FOR REFERENCE AND HYDRAVLIC CALCULATIONS ONLY
2 ALL UNDERGROUND SUPPLY PIPING TO BE INSTALLED IN ACCORDANCE WITH N F P.A.
#24, TUKWILA BUILDING AND WATER DEPARTMENTS STANDARDS AND SPECIFICATIONS.
31, UNDERGROUND TO BE TESTED AND FLUSHED PRIOR TO THE INSTALLATION OF ABOVE -
ACCEPTED
Without Comments
As Noted In Red
Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current city
ztandards Acceptance is subject to errors and
Jrnisslons which do no
:.ndards and ordina
'1eauacy of design rests totally with tete designer
tilt ,ns, deletions or revisions to these drawings after
LI1}s state will void this acceptance and will require a
resubmittal of revFtIi awinz2r subsequent approv'
+nal accepts celis subject to field test and inspection by
The Tukwila ire - revention Bureau
TUKWILA FIRE DEPARTMENT
Please call 575.4407
end give this job
No97--
and exact address for shut"
down or restoration approval.
P.V.C. PLASTIC PIPE
FIG. 22 FIG.23 FIG.14
WI. HANGER
SPACING
FASTENER
HDHEAD
SET
APPRDx
WEIGHT
PER 1OQ
NORTH
pgMETIM
DEC 2 9 1997
RODGER LACY
THE SAFETY TEAM, INC.
670 SOUTH LUCILE STREET P.O. BO)c, 81246 SEATTLE, WA. 98108
(206) 762-1450
RODGER LACY
SAFETY TEAM INC
HANGERS FOR CPVC PLASTIC PIPE
UNDERGROUND NOTES