PP - 4708 SOUTHCENTER BLVD BLDG B - THE BOULEVARD AT SOUTH STATION - PERMITS AND PLANS
4708 SOUTHCENTER BLVD BLDG B ASSOCIATED PERMITS 08-F-142 FIRE DEPARTMENT FIRE ALARM PLAN REVIEW COMMENTS Project Name: Park Place By The Woods Bldg. B 4708 Southcenter BI Permit No.: 08-F-142 Date: April 28, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • When the control panel is located inside a room, the door to the room shall have a sign with one -inch letters, which reads "Fire Alarm" or "Fire Alarm Control". • Install smoke detectors as shown in red on the plans within 5 ft. of the door opening for magnetic door holder operation. • Heat detectors installed in the dwelling units to be 135 degree rate of rise. • Heat detectors installed in the attic areas to be 194 degree fixed temp. • Dedicated fire alarm system circuit breakers shall be equipped with lockout devices. • If reset code is employed, reset code to be 1-2-3-4-5. • An electrical permit from the city of Tukwila Building Department permit center . • The Tukwila Fire Department has changed keybox manufacturers, from Supra to Knox. Install a fire department Knox Keybox. Contact the Tukwila Fire Prevention Office at 206-575-4407 for ordering information. I IPARK PLACE BY THE WOODS ii 14/2/2008 1 2 3 4 5 6 7 8 9 10 B C D E F G H J FIRE ALARM WIRE LEGEND DESIG. DESCRIPTION A 16/2 FPLR INITIATING CIRCUIT WIRING B 14/2 FPLR INDICATING CIRCUIT WIRING C 18/4 FPLR ANNUNCIATOR CiRCUIT WIRING 0 14/2 FPLP DUCT DETECTOR OR DOOR HOLDER POWER WIRING E AWG-16-THHW FOR DIRECT BURY/WET LOCATION ci 'VT Without CommenS As -Noted in --Red Per The Attached 1 IT 1 uI(WILA FiRE DEPARTMENT, Please call: 575.0.•407, and give this job No.0 F- ani exact address for shut down or restoration aDr rovat3 i nese plartStave been re'lawedTf7 1kti1la Preventia a.Bure Bureau for c n fcr mance with current l r standards. Acceptance is uhiectto errors and omissions which do violations oat4zr stanaaros and or t°na: es. • !,ti . ,3,;. xCfr .ti t- ti, adequacy of si;u i r grre Additions, . ,i..> of . Dc t.lt:` c draw.^ s rear this date will 'Joie } 7 c r } i require resubmittal of revised t?: " „ ..,... for , uli3. wquent a" " ' 1.. Final accelptance is subject to fled test and inspection by The Tukwila Fire Prevention Bure'u. Date: a.5—Ob By: ( NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. KEY LEGEND N D COMPONENT LIST SYMBOL DESCRIPTION QTY PART # MANUFACTOR MOUNTING SPEC FIRE ALARM CONTROL PANEL 1 FX -350 -DDR MIRCOM WALL TOP @ 66' Mal FIRE SIGNAL EXPANDER 1 BPS -6 MIRCOM WALL TOP @ 66' 1 FSE J ANNUNCIATOR 1 RAM-300LCDR MIRCOM WALL TOP @ 66' UM ///////// ///// TRANSMITTER FIELD VERIFY 1 TRAM J SUBSCRIBER TERMINAL UNIT FIELD VERIFY I STu I D❑ HORN WALL @ 80'-96' L�. 1♦ MINI -HORN 38 MH -25W MIRCOM WALL @ 80'-96' l_.1__..I BELL 1 MB -G10 -24R WHEELOCK OUTSIDE WALL @ 10' STROBE 1 ZRS-MCW-FR WHEELOCK _ WALL @ 80'-96° X WEATHER PROOF STROBE 1 RSSP-2475-FR WHEELOCK WALL @ 80'-96' WP ) ( D® HORN -STROBE 7 ZNS-MCW-FR WHEELOCK WALL @ 80'-96' M CEILING MOUNTED HORN/STROBE CEILING aCEIUNG MOUNTED STROBE CEILING CHIME FIELD VERIFY C O SPEAKER WALL @ 90' OJ JUNCTION BOX FIELD VERIFY DOOR HOLDER 6 DH24120SPC MIRCOM FIELD VERIFY CM DOOR STRIKE FIELD VERIFY EDI MANUAL PULL STATION 7 MS -701 DU MIRCOM WALL @ 48' F ®AB SMOKE DETECTOR ABOVE CEILING ABOVE CEILING OR IN DUCT 2) SMOKE DETECTOR 16 MIX -3100 MIRCOM CEILING - 3' FROM AIR DEFUSER ® BL SMOKE DETECTOR BELOW FLOOR BELOW FLOOR CO 194° FIXED TEMP HEAT DETECTOR 4 MIX -3300 MIRCOM CEILING ®R 194° RATE OF RISE HEAT DETECTOR 26 MIX -3300 MIRCOM CEIUNG ®R 135° RATE OF RISE HEAT DETECTOR CEIUNG 194°® 194° FIXED TEMP HEAT DETECTOR CEIUNG LINE TYPE HEAT DETECTOR FIELD VERIFY WF WATERFLOW SWITCH RISER PIPE PS PRESSURE SWITCH RISER PIPE TS TAMPER SWITCH GATE VALVE JB JUNCTION BOX ALONGSIDE DEVICE FIELD VERIFY M MONITOR MODULE FIELD VERIFY R ADDRESSABLE RELAY FIELD VERIFY 77e,8 FILE COPY Luse of increased demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4407 or email fireinsoregue. c ci.tulbwila.wa.us to schedule your inspections a minimum of 45 hours in advance of the date you want an inspection. General Note NPPA72-2002 Edition AA 1 -sec 5.63.1 „heat- eensing fire ddedord shall be located on the ■ ceiling not less than lOOnn (4 in) Iron the sidewall or on the sidewalls between /0Omm and 300nn (4ia and 12in.) from the ceiling. See figure F.5.63.1 A-sec. 5.732.1...smoke ddedors shall be located on the ceiling not less than lOOmm (4 in.) fron a sidewall to the near edge or, if on a sidewa(l, bdween lOOnn and 30044 (4 -in and 12in) down from the ceiling to the lop of the ddedor.See figure F.5.1.3.2.1 A3 -`Sec. /i5.7.4./ Deledors should not be located in a direct airflow or / \ closer than In (' ft.) from an air Supply diffuser or return air opening. Supply or return sources larger than /host commonly found in residential and anal/ commercial ealablidhments can require greater deararre to awoke detector. Similarly, smoke defector s should be located farther away from high velocity air supplied. -Sec 5.12.4 The operable part of each nonfat fire alarm box dial/ be ■ not less than 1./n (34 ft. and not none than 13TH (4 %Z fl.) above floor level. See figure F.5.IZ.4 4\5 -Sec. 75.4 Wall mounted appliances shall be mounted .rch that the / • \ entire /errs id not less than Zn (80 in) and not greater than 2.4m (96 in.) above the finished floor, 5ce figure !'.75.4 6 -Sec. 4.4.1.4.1 Dedicated branch circuit. A dedicated bunch circuit of one of the following shall supply prinary power (1) Commercial light and power. (2) An ergine -driven generator or equivalent in accordance with 4.4.1,92, where a person specifically trained in ifs operation id on duty of all tinea (3) An ergine -driven generator or equivalent arranged for cogeneration with commercial light and power in accordance with 4.4.1.92, where a person specifically trained in its operation is on duly al all tinea K L M N Ceiling 100 mm (4 in.) ///////f ////// Acceptable here Note: Measurements shown are to the closest edge of the detector. Never here • Top of detector / acceptable here / ,x,73,2,1 / A 103 mm (tut.) rum 300 mm (12 in.) maximum Sidewall MAP OF LOCATION FX-350-126DR ELECTRICAL ROOM 4/2/2008 Addrsbl SLC Devices RAM-300LCDR Other Other 0.220 > 0.380 0.040 0.040! 0.000 -- 0.000 0.000 : fl 000:: 0.000:- ; 0.000 0.000- fl 000 Q 000 :. < 0:000:: 0018 0.016 0.000 . 0.000 Notification Appl Circuit Notification Appl Circuit Notification Appl Circuit Notification Appl Circuit D.000. 0.000:': 0,000 0.000 0.000 0.000 0.075:;. 2. .......... 0.444.' #14 Solid #16 Solid 10 1 # of NAC's Used 0 000- 0.000 _............... )t.iESs7kfi%t#E1X&:i�$tjiift�¥ Project Infarmatim Command Shortcuts Configure Circuits Print Page Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4/2(2008 18 MH -25W Unused Unused Unused Notification Appl Circus Totals -0 000 20 MH -25W Unused Unused Unused amo Totals 0.000 8.540 Not!tcatbn Appl Circuit 6 ZNS-MCW-FR 1d Unused Unused Unused .. ................. Totals Notifcation Appl Circuit LB 1 BPS -602 Unused Unused Unused ODD Totals 0.075 J BPS -6 BPS -6 ELECTRICAL ROOM • 5495(1) Circuit 1 545(1) Circuit 2 5495(1) Circuit 3 5495(1) Circuit 4 0. X20 0000 0.000 E7.D00 0.000 n000> #14 Sdid #18 Sdid #14 Sdid #14 Sdid 560 150 1.66% 3 23% 5495 1 Aux Power Out Arra;i5iMiftell : 0.000: 0.000 #14 Sdid 4 0.00% 0.00% 0 00% �3E1? 6 k3:: iIltIf ittr�cl � Wre resistarces are based upm an arrbient temperature of 72 degrees F. Became of the minirrel difference between solid and sura ed wire no differential was made. Project Information Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4/2/2008 6 DH24120SPC Unused Unused Unused Totals 0.120 I x0.000: 1 1 1 1 MB -G10 -24R RSSP-2475-FR ZRS-MCW-FW 30cd ZNS-MCW-FW 15cd Lr:', 1 2008 Tukwila Fire ..4t-'&) 0 300 ( z 0 to ISSUED FOR APPROVAL z 0 U z w 0z W ct LL ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. B 4708 SOUTH CENTER BLVD. ILA WA, 98188 H RISER/BOM - FIRE ALARM PLAN APPROVED BY : ER DRAWN BY: RG DATE: 4-15-08 JOB# 87474 DWG. NO.: FA -01 Lil:d lila(_ Operable Part 1.1 (334 min V 1.37 (4) maximum m f .) mum m R) ,12,4 Finished floor — Sidereal ///////// ///// MAP OF LOCATION FX-350-126DR ELECTRICAL ROOM 4/2/2008 Addrsbl SLC Devices RAM-300LCDR Other Other 0.220 > 0.380 0.040 0.040! 0.000 -- 0.000 0.000 : fl 000:: 0.000:- ; 0.000 0.000- fl 000 Q 000 :. < 0:000:: 0018 0.016 0.000 . 0.000 Notification Appl Circuit Notification Appl Circuit Notification Appl Circuit Notification Appl Circuit D.000. 0.000:': 0,000 0.000 0.000 0.000 0.075:;. 2. .......... 0.444.' #14 Solid #16 Solid 10 1 # of NAC's Used 0 000- 0.000 _............... )t.iESs7kfi%t#E1X&:i�$tjiift�¥ Project Infarmatim Command Shortcuts Configure Circuits Print Page Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4/2(2008 18 MH -25W Unused Unused Unused Notification Appl Circus Totals -0 000 20 MH -25W Unused Unused Unused amo Totals 0.000 8.540 Not!tcatbn Appl Circuit 6 ZNS-MCW-FR 1d Unused Unused Unused .. ................. Totals Notifcation Appl Circuit LB 1 BPS -602 Unused Unused Unused ODD Totals 0.075 J BPS -6 BPS -6 ELECTRICAL ROOM • 5495(1) Circuit 1 545(1) Circuit 2 5495(1) Circuit 3 5495(1) Circuit 4 0. X20 0000 0.000 E7.D00 0.000 n000> #14 Sdid #18 Sdid #14 Sdid #14 Sdid 560 150 1.66% 3 23% 5495 1 Aux Power Out Arra;i5iMiftell : 0.000: 0.000 #14 Sdid 4 0.00% 0.00% 0 00% �3E1? 6 k3:: iIltIf ittr�cl � Wre resistarces are based upm an arrbient temperature of 72 degrees F. Became of the minirrel difference between solid and sura ed wire no differential was made. Project Information Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4/2/2008 6 DH24120SPC Unused Unused Unused Totals 0.120 I x0.000: 1 1 1 1 MB -G10 -24R RSSP-2475-FR ZRS-MCW-FW 30cd ZNS-MCW-FW 15cd Lr:', 1 2008 Tukwila Fire ..4t-'&) 0 300 ( z 0 to ISSUED FOR APPROVAL z 0 U z w 0z W ct LL ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. B 4708 SOUTH CENTER BLVD. ILA WA, 98188 H RISER/BOM - FIRE ALARM PLAN APPROVED BY : ER DRAWN BY: RG DATE: 4-15-08 JOB# 87474 DWG. NO.: FA -01 A B 1 2 3 4 5 6 7 8 9 10 M N P 825 SIFT 2 BEDROOM 1 BATH WING ROOM DINING BEDROOM EOL CLOSET 00 Co KITCHEN FROM 2ND FL DINING LIVING ROOM KITCHEN 00 0 0 825 SIFT 2 BEDROOM 1 BATH CLOSET 01:050 NI. BEDROOM A R 01:019 FROM 2ND FL CLOSET STORAGE BATH ROOM BEDROOM TO ATTIC CLOSET BATH ROOM 0 625 SIFT 1 BEDROOM 1 BATH WING ROOM 625 SOFT 1 BEDROOM 1 BATH WING ROOM BEDROOM STORAGE r 106 r dr J BEDROOM TO ATTIC 0 CLOSET BATH ROOM a � BEDROOM STORAGE 102 FROM 2ND FL CLOSET 825 SIFT 2 BEDROOM 1 BATH 00 0 CI WING ROOM KITCHEN DINING 01:049 01:048 11 I I i 5Cd V • _.1;1 - • 15cd FROM I _, EOL 1_1 • 2ND FL fes' D" 01:033 EOL BEDROOM STORAGE A BATH ROOM 0 CLOSET FROM 2ND FL BEDROOM 01 01:002 ELECTRICAL ROOM 2C STORAGE BATH ROOM 105) KITCHEN TO FACP 75cd WP & FSE CKT.#2 EOL WING ROOM J 0 00 625 SIFT 1 BEDROOM 1 BATH KITCHEN 00 Co 103 DN UP TO 01:047 FROM D FL 101 01:025 TO ATTIC LIVING ROOM 625 SIFT 1 BEDROOM 1 BATH O STORAGE A IMO BATH ROOM CLOSET FROM 2ND FL BEDROOM 1 ST FLOOR — BLDG. B 1/8"_1'-0" BATH ROOM STORAGE P BEDROOM BEDROOM DINING LIVING ROOM 825 SIFT 2 BEDROOM 1 BATH z 0 Tn ISSUED FOR APPROVAL d z 0 ci z W z 0 W I ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. B 4708 SOUTH CENTER BLVD. TUKWILA WA, 98188 CC w CC U— 1ST FLOOR - FIRE ALARM PLAN APPROVED BY : ER DRAWN BY: RG DATE: 4-15-08 JOB# 87474 DWG. NO.: FA -02 A B C D E F H J K L M 1 2 3 4 5 6 7 8 9 10 UP B FROM 3RD FL DINING FROM 3RD FL 825 SQFT 2 BEDROOM 1 BATH LMNG ROOM BEDROOM DOWN TO 1ST FL. BEDROOM FROM 3RD FL BEDROOM DOWN TO 1ST FL 625 SIFT 1 BEDROOM 1 BATH A,B A,B A,B CLOSET O 0o DINING KITCHEN 01:040 LMNG ROOM 01:041 DOWN TO 1ST FL 209 OiNN TO 1ST FL KITCHEN 00 o0 825 SIFT 2 BEDROOM 1 BATH 208 A,B A CLOSET CLOSET 01:018 STORAGE LIVING ROOM FROM 3RD FL 01:015 R BATH ROOM 01:042 15cd FROM 3RIl FI 01:032 STORAGE BATH ROOM C BEDROOM CLOSET FROM 3RD FL BEDROOM 00 00 DN A11 625 SIFT 1 BEDROOM 1 BATH LIVING ROOM DOWN TO 1ST FL G 0 0 O 00 OCi KITCHEN KITCHEN LIVING ROOM 425 SIFT STUDIO 1 BATH STORAGE CLOSET BEDROOM BATH ROOM CLOSET DOWN TO 1ST FL BEDROOM STORAGE N U 205 KITCHEN BEDROOM BEDROOM DOWN TO 1ST FL A,B CLOSET BATH ROOM BEDROOM FROM 3RD FL. A,B A STORAGE 01:09 R KITCHEN LMNG ROOM 00 00 00 00 625 SOFT 1 BEDROOM 1 BATH 01:043 202 825 SOFT 2 BEDROOM 1 BATH 00 00 LMNG ROOM KITCHEN DINING 15cd 01:044 UP FROM ATTIC DOWN TO 1ST FL 201 BATH ROOM 3 0 CLOSET AB DOWN TO 1ST. FL LIVING ROOM AB CLOSET DOWN TO 1ST FL AB 01:021 FROM1 3RD FL KITCHEN O0 00 A/ AB CLOSET 625 SQFT 1 BEDROOM 1 BATH FROM 3RD FL BEDROOM BEDROOM FROM 3RD FL BEDROOM B DIWNTO 1ST FL LMNG ROOM 825 SIFT 2 BEDROOM 1 BATH 2ND FLOOR - BLDG. B 1/8"=1'-0" N z 0 CC ISSUED FOR APPROVAL d z CC 0 U Z W Z 0 ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. B 4708 SOUTH CENTER BLVD. TUKWILA WA, 98188 0 CC CC w CC w LL CC LI. CC 00 U- N APPROVED BY: ER DRAWN BY: RG DATE: 4-15-08 JOB# 87474 DWG. NO. FA -03 1 2 3 4 5 825 SIFT 2 BEDROOM 1 BATH 6 UP DOWN TO 2ND FL. J I T F LIVING ROOM DINING 01:03 FROM ATTIC DINING 7 LIVING ROOM DOMAIN O 2ND FL. KITCHEN 00 00 825 SIFT 2 BEDROOM 1 BATH BEDROOM DOWN TO 2ND FL 00 00 KITCHEN 01:038 CLOSET 2ND FL DOWN TO AB A 1111 FROM DN ATTIC I1 BATH ROOM 0 CLOSET AB BEDROOM FROM ATTIC BEDROOM 8 9 10 1 A 1 2N DOWN TO R 01:029 BEDROOM DOWN TO 2ND FL CLOSET 625 SOFT 1 BEDROOM 1 BATH BATH ROOM STORAGE rh 01:037 WING ROOM FROM ATTIC 306 00 00 KITCHEN 307 0 BATH ROOM B B 00 00 I FRO1M Ara. LIVING ROOM 425 SOFT STUDIO 1 BATH 1 STORAGE CLOSET BEDROOM STORAGE CLOSET 2ND FL DOWN TO AB 0,1 4 BEDROOM 305 01:026 AB FROM ATTIC 625 SOFT 1 BEDROOM 1 BATH LANG ROOM DOWN TO 2ND FL 00 00 KITCHEN C BEDROOM FROM ATTIC KITCHEN 0 0 00 WING ROOM 625 SOFT 1 BEDROOM 1 BATH KITCHEN 00 00 01:036 303 2ND FL DOWN TO BEDROOM DOWN TO 2ND FL CLOSET JBATH ROOM BEDROOM STORAGE -11111--,- O SDN DOWN TO 2ND FL 302 FROM ATTIC CLOSET 825 SIFT 2 BEDROOM 1 BATH 00 00 LIVING ROOM KITCHEN DINING 15cd 01:035 FROM ATTIC 01:023 OI AB LIVING ROOM 625 SOFT 1 BEDROOM 1 BATH STORAGE BATH ROOM C- CC BATH ROOM CLOSET AB FROM ATTIC BEDROOM C STORAGE CLOSET AB 2ND FL DOWN TO BEDROOM 01:020 R A 301 UP -01:052 A FROM ATTIC FROM ATTIC KITCHEN 00 00 CLOSET AB FROM ATTIC BEDROOM DOWN TO 2ND FL WING ROOM 825 SQFT 2 BEDROOM 1 BATH 3RD FLOOR - BLDG. B 1/8"=I-0" M N Z U Z w z 0 ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. B 4708 SOUTH CENTER BLVD. TUKWILA WA, 98188 3RD FLOOR - FIRE ALARM PLAN APPROVED BY: ER DRAWN BY: RG DATE: 4-15-08 JOB# 87474 DWG. NO.: FA -04 A II II II II II 11 A,B If�I— 1 II 11 II II 11 I I II II II IL J� — L 01:007 A,B JL A,B Li 01:008 I— J1 I I I I I I i1 I I I CKT. #3 Jv41 FSE CKL__#1_ A,3B:11 ® 01:005 A,2B A,3B —� II II 11 11 i FROM FACP SMOKE FACP CKT.#1,2,3 AND FSE CKT.# 1 2B B CKT. #2 A,B I I I 1 I I I I Il A,41311 A,B 11 I I I I I I 11 I I 11 I F- CKT. #3 FSE CKT. #1 p—A,B II it FSE CKT. #1 ATTIC - BLDG. B 1/8"=1'-0" M N CIRCUIT DISCRIPTIONS: CKT.#1 - ROOM NOTIFICATION WEST. CKT.#2 - ROOM NOTIFICATION EAST. CKT.#3 - CORRIDOOR NOTIFICATION. CKT.#4 - TRIGGER FIRE SIGNAL EXPANDER (FSE). FSE CKT.#1 - DOOR HOLDERS NORTH AND SOUTH. FSE CKT.#2 - OUTDOOR BELL & STROBE & EAST CORRIDOR. NOTE: DASHED UNE INDICATES WALL BELOW ATTIC. 2 O 0 a cc O LL 0 w U) y O 206-575-0311 PARK PLACE BY THE WOODS BLDG. B 4708 SOUTH CENTER BLVD. TUKWILA WA, 98188 CC w CC LL ATTIC - FIRE ALARM PLAN APPROVED BY: ER DRAWN BY: RG DATE: 4-15-08 JOB# 87474 DWG. NO. : FA -05 2 1 2 3 5 6 7 8 9 10 A ATTIC B C D E F H 01:007 01:006 01:005 J K L M N #16/2 & #14/2 #16/2 & #14/4 #16/2 & #14/4 0--#16/2 & #14/4 #14/4 #14/2 #16/2 -0 #14/4 #16/2 & #14/4 -7:7 #16/2 & #14/4 #16/2 -4:1 CT #14/2 #14/2 .015ma 3RD FLOOR 15cd .074ma 01:053 0- #14/2 0- #14/2 01:039 .015ma 2ND FLOOR 15cd .074ma #16/2 #16/2 01:038 01:017 .027ma .027ma 01:014 CD .027ma 01:011 CO .027ma 01:037 #16/2 01:008 .027ma .027ma #14/2 #16/2 & #14/4 #16/2 & #14/4 #16/2 & #14/2 #14/2 Q-#16/2 & #14/2 0-#16/2 & #14/4 t:7-- #16/2 & #14/4 #16/2 01:018 .027ma .027ma #16/2 #16/2 CI b 01:041 b 01:040 0- #14/2 0- #14/2 #16/2 0-- #16/2 & #14/4 #14/4 01:020 .027ma .027ma #16/2 & #14/4 -0 01:023 .027ma 01:026 .027ma 01:036 CD #16/2 01:029 .027ma #16/2 #16/2 & #14/4 -0 #16/2 & #14/4 -0 #16/2 & #14/4 -0 #16/2 & #14/2 01:031 .027ma .027ma 01:035 01:034 #16/2 #16/2 01:052 #14/4 -Iv #14/2 15cd .074ma #14/4 -0 #14/2 01:015 .027ma 01:012 .027ma 01:042 01:009 .027ma .027ma #16/2 0-#16/2 & #14/2 -#16/2 & #14/4 -#16/2 & #14/4 0-#16/2 & #14/4 01:021 .027ma .027ma 01:024 .027ma #16/2 CD #16/2 /4-0 01:027 #16/2 & #14/4 -0 #16/2 & #14/4 -0 01:030 .027ma .027ma #16/2 °® 01:032 1/4-014-101-0 .027ma .027ma #16/2 & #14/2 - #16/2 01:04 4 01:❑045 F .015ma 15cd .074ma #14/4 -0 #14/2 .015ma .015ma 1ST FLOOR 15cd EOL .074ma 01:051 01:050 D 4 #16/2 01:019 EOL 01:016 01:013 CD , ■ CD .027ma .027ma .027ma .027ma 01:049 #16/2 01:010 .027ma .027ma 01:004 01:003 01:002 01:001 #16/2 01:022 .027ma .027ma 01:025 .027ma CO 01:028 EOL 01:033 .027ma .027ma .027ma #16/2 30cd WEST REMOTE ANNUNCIATOR LIOCEL 13,111-310.20 FACP #18/4 MIRCOM FX -350 -126 -DR CENTRAL -PHONE LINE #1 DI STATION Uff PHONE LINE #2 DIALER 120 VAC S (DEDICATED CKT.) I NAC -1 #16/2 NAC -2 NAC -3 NAC -4 #18/4 .092ma P #18/4 15cd 01:048 01:047 (2' #92 9 / #16/2 t"-- #16/2 a 01:046 15cd .074ma .015ma WP-75cd BELL .074ma FIRE ALARM SIGNAL EXPANDER BPS -6 INPUT #14/2 NAC -1 BATTERY BATTERY 12V-12AH 12V-12AH #14/2 RISER DIAGRAM #18/4 NAC -2 NAC -3 NAC -4 BATTERY 1 BATTERY 12V-7AH 12V-7AH 120 VAC (DEDICATED CKT.) EAST #18/4 CIRCUIT DISCRIPTIONS: CKT.#1 - ROOM NOTIFICATION WEST. CKT.#2 - ROOM NOTIFICATION EAST. CKT.#3 - CORRIDOOR NOTIFICATION. CKT.#4 - TRIGGER FIRE SIGNAL EXPANDER (FSE). FSE CKT.#1 - DOOR HOLDERS NORTH AND SOUTH. FSE CKT.#2 - OUTDOOR BELL & STROBE & EAST CORRIDOR. EOL .138ma .040ma #18/4 - z 0 a. a O U- 0 w cow 0 w z 0 ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. B 4708 SOUTH CENTER BLVD. TUKWILA WA, 98188 CC e1 CC LL BUILDING RISER DIAGRAM APPROVED BY : ER DRAWN BY: RG DATE: 4-15-08 JOB# 87474 DWG. Na FA -06 1 2 3 4 5 6 7 8 9 10 FIRE ALARM WIRE LEGEND DESIG. DESCRIPTION A 16/2 FPLR INITIATING CIRCUIT WIRING B 14/2 FPLR INDICATING CIRCUIT WIRING C 18/4 FPLR ANNUNCIATOR CIRCUIT WIRING D 14/2 FPLP DUCT DETECTOR OR DOOR HOLDER POWER WIRING E AWG-16-THHW FOR DIRECT BURY/WET LOCATION KEY LEGEND AND COMPONENT LIST SYMBOL DESCRIPTION QTY PART # MANUFACTOR MOUNTING SPEC FIRE ALARM CONTROL PANEL 1 FX -350 -DDR MIRCOM WALL TOP @ 66' FACP I FIRE SIGNAL EXPANDER 1 BPS -6 MIRCOM WALL TOP @ 66' I FSE I ANNUNCIATOR 1 RAM-300LCDR MIRCOM WALL TOP @ 66' I ANN I TRANSMITTER FIELD VERIFY I TRAN I SUBSCRIBER TERMINAL UNIT FIELD VERIFY I STU I HORN WALL @ 80'-96' Pap MINI -HORN 38 MH -25W MIRCOM WALL @ 80'-96' w BELL 1 MB -G10 -24R WHEELOCK OUTSIDE WALL @ 10' STROBE 1 ZRS-MCW-FR WHEELOCK _ WALL @ 80'-96' jr( WEATHER PROOF STROBE 1 RSSP-2475-FR WHEELOCK — WALL @ 80'-96' WP( ISI HORN -STROBE 7 ZNS-MCW-FR WHEELOCK WALL @ 80'-96' 0 CEILING MOUNTED HORN/STROBE CEILING 0 CEILING MOUNTED STROBE CEILING C CHIME FIELD VERIFY O SPEAKER WALL @ 90' 0 JUNCTION BOX FIELD VERIFY DOOR HOLDER 6 DH24120SPC MIRCOM FIELD VERIFY m DOOR STRIKE FIELD VERIFY COI F MANUAL PULL STATION 7 MS -701 DU MIRCOM WALL @ 48' ®AB SMOKE DETECTOR ABOVE CEILING ABOVE CEILING OR IN DUCT ® SMOKE DETECTOR 22 MIX -3100 MIRCOM CEILING - 3' FROM AIR DEFUSER ® BL SMOKE DETECTOR BELOW FLOOR BELOW FLOOR © 194° FIXED TEMP HEAT DETECTOR 4 MIX -3300 MIRCOM CEILING ©R 194° RATE OF RISE HEAT DETECTOR 26 MIX -3300 MIRCOM CEILING ®R 135° RATE OF RISE HEAT DETECTOR CEILING 1941) 194° FIXED TEMP HEAT DETECTOR CEILING lD/> LINE TYPE HEAT DETECTOR FIELD VERIFY wF WATERFLOW SWITCH RISER PIPE PS PRESSURE SWITCH RISER PIPE TS TAMPER SWITCH GATE VALVE JB JUNCTION BOX ALONGSIDE DEVICE FIELD VERIFY M MONITOR MODULE FIELD VERIFY R ADDRESSABLE RELAY FIELD VERIFY General Notes NPPA. 72-2002 Edition 1 -Scc 5.63,1,,.heat-sensirg fire detectors ehall be located on the ceiling not less than lOOrn (4 in) Iron the sidewall or on the sidewolls between100m and 500m (4 -in. and /2in.) from the ceiling. See figure F.5.63.1 A•, -Sec. 5.7J 2,1.,.snoke detectors shall be located on the ceiling not less than lOOnn (4 in) lion a 5idewall to the near edge or, if on o sidewall, between IOOmn and 3OOnn (oin. and 12in.) down fron the ceiling to the lop of the detector. See figure !=.5,732.1 A -Sec. h5,7.4./ De/cc/ors should not be located in a direct airflow or closer than In (3 ft.) Iron an air supply diffuser or rdum air opening. Supply or return sources larger than thox con nonly found in residential and small connercial establishments can require greater clearance to smoke de%lora Sinilarly, smoke detectors should be located farther away from high velocity air supplies. n4 -Sec. 5.12.4 The operable part of each manual fire alarn box shall be / 11\ not less than lin (34 ft) and not more than 137n (4 %Z ft.) above floor level See figure P.5.12.4 /1\5 -Sec. 7,5.4 Wall nounled appliances shall be mounted such that the • , entire lens is not less than 2n 030 in) and not greater than 2.4n 06 in,) above the finished floor. See figure f,75,4 n6 -sec. 4.4.1.4.1 Pedleafed branch circuit. A dedicated branch circuit of ■ \ one of the following shall supply primary power (I) Connercial light and power. (2) An engine -driven generator or equivafen/ in accordance with 4.4.1.9.2, where a person specifically trained in its operation is on duty at all tires. (3) An engine -driven generator or equivalent arranged for cogeneration with connercial light and power in accordance with 4.4,1.92, where a person specifically trained in its operation is on duty at all fines. Ceiling 100 mm (4 in.) a s r///////f//////J Acceptable here Note: Measurements shown are to the closest edge of the detector. Never here Top of detector acceptable here / (11 mm (4n1n.) minimum ,x,73,2,1 300 mm (12 in.) maximum V / Sidewail !ALLA orlori A 1.1 m (3)ft) min mum 1.37 m (47z R) maximum Operable pad Finished floor ////////////// Sidewall MAP OF LOCATION FX -350 CTRL Panel Addrsbl SLC Devices RAM-300LCDR 0:220 0:018 0.016' 0.000 0.000 0.000 Command Shortcuts Configure Circuits Print Page Project Info-ma5m F Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4/212008 18 MH -25W Unused �t DrawItNiittaM Unused Unused Totals 0.000 0:486 20 MH -25W Unused fit Unused Unused 6 ZNS-MCW-FR 15cd Totals 0.000 0.540 Notficatbn Appl Circuit "-tpRRBIRR Unused Unused Unused Totals .000 0444 rE BPS -602 Unused Unused 1 Unused Totals 0:075 0.150 BPS -es F'o =r <ir l.li i -,ns BPS -6 ELECTRICAL ROOM 5495(1)Circuit 1 0.120 0.000 #14 Sdid 560 5495(1) Circuit 2 0.000 0.344 - #18 Sdid 150 3:23% 5495(1) Circuit 3 £1.000 0.030 #14 Sdid .52 0.00% 5495(1) Circuit 4 0.000 0.000 #14 Sdid 0.00°10 5495(1) Aux Power Out 0.000 . 0000 #14 Sdid X00 0.00% OW>>s 3s; Wre resistances am based upm an ambient temperature of 72 de3rees F Becarse of the minimal difference between solid and se -acted wire no differential was grade. Project Information Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4/2/2008 6 DH24120SPC Unused Unused Unused #Fent. Totals 0.120 0.000: €Ta MB -G10 -24R RSSP-2475-FR ZRS-MCW-FW 30cd ZNS-MCW-FW 15cd Totals 0.000... 0.344. AS -BUILT 9-25-08 z 0 ISSUED FOR APPROVAL O z ci 0 cc 8 or 0) z W z o O ccW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 m c� 0 conft >04 W V a Et a d -a- 0 0 d CD CO CC LLI a) I— C) z v� g 0 N ~ RISER/BOM - FIRE ALARM PLAN APPROVED BY : ER DRAWN BY: RG DATE: 4-15-08 JOB# 87474 DWG. NO.: FA -01 0 A B H J K L 1 2 3 4 5 6 7 8 9 10 UP 825 SQFT 2 BEDROOM 1 BATH LMNG ROOM BEDROOM CLOSET 00 00 DINING KITCHEN BEDROOM 01:019 FROM 2ND FL STORAGE 108 01: 50 01:051 15cd FROM EOL 2ND FL FROM 2ND FL DINING LIVING ROOM KITCHEN 00 o0 825 SOFT 2 BEDROOM 1 BATH CLOSET 01:033 BEDROOM GE A CLOSET CL BATHROOM -w®1-1- ON BATH ROOM CLOSET FROM 2ND FL BEDROOM LA ROOM 0 BEDROOM 625 SIFT 1 BEDROOM 1 BATH WING ROOM BATH ROOM STORAGE U 106 01:004 15cd A 01:049 625 SIFT 1 BEDROOM 1 BATH 0 0 Oo KITCHEN 2C 30cd ELECTRICAL ROOM ANN 2C R L01:002 r TO FACP 75cd & FSE CKT.#2 WP BATH ROOM CLOSET TO ATTIC BEDROOM EOL STORAGE 0 UI 105 01:028 R AB 0 0 LIVING ROOM BEDROOM FROM 2ND FL. ATC-IEN ciD L STORAGE KITCHEN 00 00 FROM 2ND FL WING ROOM 625 SIFT 1 BEDROOM 1 BATH KITCHEN 00 0o BATH ROOM Car s 01:04. 103 BEDROOM TO ATTIC BEDROOM CLOSET I BATH ROOM STORAGE FROM 2ND FL CLOSET 135R01:010 O 102 825 SQFT 2 BEDROOM 1 BATH 0o 00 KITCHEN WING ROOM DINING 15cd 01:047 DN UP TO ATTIC 01:025 TO ATTIC LIVING ROOM 625 SOFT 1 BEDROOM 1 BATH STORAGE BATH ROOM AB CLOSET FROM 2ND FL BEDROOM 1ST FLOOR - BLDG. B 1 /8"= 1'-0' 01:055 01:046 FROM 2ND FL BATH ROOM STORAGE CLOSET TO ATTIC 3 U 01:022 A 101 UP F' ' M 2ND L. ROM 2ND FL KITCHEN 00 00 CLOSET PEDROOM FROM 2ND FL BEDROOM DINING LIVING ROOM 825 SIFT 2 BEDROOM 1 BATH M N AS -BUILT 9-25-08 Z 0 Dl 0 m w z Lu O 0 w L U Lu J w 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. B 4726 SOUTH CENTER BLVD. TUKWILA WA, 98188 CC LU CC LL 1ST FLOOR - FIRE ALARM PLAN APPROVED BY: ER DRAWN BY: RG DATE: 4-15-08 JOB# 87474 DWG. NO. : FA -02 H J K 1 2 3 4 5 6 7 8 9 10 UP B FROM 3RD FL. 825 SQFT 2 BEDROOM 1 BATH LIVING ROOM DINING BEDROOM DOWN TO 1ST FL BEDROOM A,B CLOSET 00 00 KITCHEN 01:057 01:040 FROM 3RD FL DINING LIVING ROOM 209 O 1ST FL KITCHEN 00 00 825 SQFT 2 BEDROOM 1 BATH 01:041 208 A,B A 01:018 FROM 3RD FL CLOSET STORAGE BATH ROOM BEDROOM DOWN TO 1ST FL 625 SOFT 1 BEDROOM 1 BATH CLOSET II 0 BATH ROOM A— STORAGE U LIVING ROOM FROM 3RD FL 01:015 R DOWN TO� E15cd FROM 1ST FL. • q q 03RD Fl CLOSET STORAGE AB DOWN TO 1ST FL BEDROOM 01:042 DN BATH ROOM CLOSET FROM 3RD FL BEDROOM 00 00 TO ATTIC 207 01:030 R 206 0 0 00 KITCHEN 625 SQFT 1 BEDROOM 1 BATH LIVING ROOM DOWN TO 1ST FL 00 C0 CTCHEN BEDROOM FROM 3RD FL A,B 01:012 204 A,B A L U TORAGE BATH ROOM BEDROOM DOWN TO 1ST FL. BEDROOM A,B CLOSET BATH ROOM STORAGE A i1/4:16 01:09 L � 01:043 A,B FROM 3RD FL CLOSET 202 825 SQFT 2 BEDROOM 1 BATH 00 00 KITCHEN WING ROOM DINING 15cd 01:044 BATH ROOM B LIVING ROOM 425 SOFT STUDIO 1 BATH STORAGE AB FROM IcLosEpRD FL. BEDROOM TORAGE CLOSET DOWN TO 1ST FL. BEDROOM AB A 205 01:027 R AB KITCHEN 00 00 FROM 3RD FL ININGROOM 625 SQFT 1 BEDROOM 1 BATH KITCHEN 00 00 203 I ON DOWN ND FL 01:024 Ni STORAGE oI BATH ROOM DOWN TO A B 1ST. FL. LIVING ROOM AB 625 SQFT 1 BEDROOM 1 BATH CLOSET FROM 3RD FL BEDROOM 0 2ND FLOOR - BLDG. B 1 /8"=1' 0" BATH ROOM 01:056 01:045 FROM ATTIC STORAGE N 01:021 CLOSET A 201 UP DOWN TO 1ST FL B L—FROM; D S WN TO 1ST FL. 3RD FL KITCHEN 00 Co CLOSET DOWN TO A B 1ST FL AB BEDROOM FROM 3RD FL BEDROOM LIVING ROOM 825 SOFT 2 BEDROOM 1 BATH L M N AS -BUILT 9-25-08 z m Ix co m m ci z LU 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. B 4726 SOUTH CENTER BLVD. TUKWILA WA, 98188 z 0 CC LLI ccc U- 0 0 —J LL CV APPROVED BY: ER DRAWN BY: RG DATE: 4-15-08 JOB# 87474 DWG. NO.: FA -03 1 2 3 4 5 6 UP DOWN TO 2ND FL. 825 SOFT 2 BEDROOM 1 BATH WING ROOM BEDROOM DOWN TO 2ND FL. CLOSET O Q 00 DINING KITCHEN A 01:053—A 01:059 01:038 F 01:039 FROM ATTIC DINING 7 WING ROOM DODO 2ND FL. KITCHEN 00 0 0 825 SIFT 2 BEDROOM 1 BATH DOWN TO 2ND FL. 309 BEDROOM DOWN TO 2ND FL CLOSET 625 SIFT 1 BEDROOM 1 BATH WING ROOM 308 STORAGE BATH ROOM STORAGE C., 306 15cd FAIR' I — I i I DN 01:031 R CLOSET 2ND FL DOWN TO AB STORAGE A BAN ROOM CLOSET AB BEDROOM FROM ATTIC BEDROOM 8 9 10 g 0 0 00 307 01:029 R 01:037 00 00 KITCHEN 625 SOFT 1 BEDROOM 1 BATH WING ROOM DOWN TO 2ND FL 00 00 KITCHEN o BATH ROOM STORAGE AB " AB 2ND FL, DOWN TO LMNG ROOM 425 SOFT STUDIO 1 BATH ROM - ATTIC CLOSET BEDROOM BATH ROOM STORAGE 9 305 AB FROM ATTIC 2ND FL DOWN TO BEDROOM AB 01:011 304 BEDROOM FROM ATTIC AB CLOSET STORAGE BAN ROOM a` BEDROOM DOWN TO 2ND FL. BEDROOM A,B CLOSET BATH ROOM STORAGE A,B 01:008 R 01:036 KITCHEN 00 00 LIVING ROOM 625 SOFT 1 BEDROOM 1 BATH 303 KITCHEN 0 Q 0 0 2ND FL DOWN TO FROM ATTIC CLOSET 302 DN DOWN TO 2ND F 825 SQFT 2 BEDROOM • 1 BATH 00 00 KITCHEN WING ROOM DINING 15cd 01:°35 STORAGE a BATH ROOM LING ROOM 625 SOFT 1 BEDROOM 1 BATH CLOSET FROM ATTIC BEDROOM 3RD FLOOR - BLDG. B 1/8"=1'-0" P 01:058 1:052 A FROM ATTIC BAN ROOM CLOSET 2ND FL DOWN TO AB 01:020 R A 301 01:034 tI : • �--FROM DO N TO FROM ATTIC ATTIC KITCHEN 00 00 CLOSET AB BEDROOM FROM ATTIC BEDROOM 2ND FL LIVING ROOM 825 SIFT 2 BEDROOM 1 BATH AS -BUILT 9-25-08 2 0 a- a ad O LL W V) ci z W z a 0 0 -1 LU L_ 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. B 4726 SOUTH CENTER BLVD. TUKWILA WA, 98188 3RD FLOOR - FIRE ALARM PLAN APPROVED BY: ER DRAWN BY: RG DATE: 4-15-08 JOB# 87474 DWG. NO. : FA -04 A B M N 1 2 3 4 5 6 7 8 9 10 I I I I I I I I I I I L- — I I I I I I I I FROM FACP SMOKE I I FACP CKT.#1,2,3 I I I I I I I I AND FSE CKT.# 1 II II I II II 1 111 A,4B _IL JL --L L_ 01:007 FSE FSE CKT. #1 7---- SIL NAC EOL A,B 01:006 I I I I I I I I I I I LI A,B A,B II I I I I I I I I I I I CKT. #3 O FSE _CKT._#1_ A,3B 1 J C) 01:005 A,3B—� Lr = — I I I I I I I I I 1 I I li II A,B 2B A,4B A,B V A,2B b NAC EOL CKT. #2 11 I I I I I I I I I I I I A,B I I I I CKT. #3 FSE CKT. #1 1TA, B J FSE CKT. #1 ATTIC - BLDG. B 1/8"= I-DII CIRCUIT DISCRIPTIONS: CKT.#1 - ROOM NOTIFICATION WEST. CKT.#2 – ROOM NOTIFICATION EAST. - — CKT.#3 – 1ST FLOOR NOTIFICATION. CKT.#4 – TRIGGER FIRE SIGNAL EXPANDER (FSE). FSE CKT.#1 – HALL WAY NOTIFICATION. FSE CKT.#2 – OUTDOOR BELL & STROBE & EAST CORRIDOR. FSE CKT. #3 – DOOR HOLDERS NORTH AND SOUTH. NOTE: DASHED LINE INDICATES WALL BELOW ATTIC. AS -BUILT 9-25-08 z 0 N cC ISSUED FOR APPROVAL m ch 0 2 U) N 0) ci z w 0 w ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. B Ea co w co I- C) z U 'S - cv0 CO I— ATTIC - FIRE ALARM PLAN APPROVED BY : ER DRAWN BY: RG DATE: 4-15-08 JOB# 87474 DWG. NO.: FA -05 A 1 2 3 4 5 6 7 8 9 10 M .015ma 1ST FLOOR 01:007 01:006 01:005 CD N V- #16/2 #16/2 & #14/2 #16/2 & #14/4 #14/2 1y- #14/2 15cd .074ma 01:053 01:056 01:039 01:038 #14/2 Kv-- #14/2 15cd .074ma e9e #16/2 #16/2 r #16/2 01:017 .027ma .027ma 01:018 .027ma .027ma 01:014 .027ma #16/2 & #14/4 #16/2 & #14/4 #14/4 01:011 W .027ma 01:037 #16/2 #16/2 a 01:055 b 01:041 01:040 #1412 #14/2 15cd EOL �--� .074ma 01:051 01:052 ci #16/2 #16/2 01:008 .027ma .027ma #14/2 #16/2 - #14/4 #16/2 & #14/4 #16/2 & #14/4 #16/2 -0 #14/2 #16/2 #16/2 & #14/4 #16/2 & #14/4 #16/2 & #14/2 #14/2 #16/2 & #14/2 K:7-#16/2 & #14/4 - #16/2 & #14/4 01:015 .027ma 01:012 a .027ma 01:042 01:009 .027ma .027ma #16/2 #16/2 & #14/2 -#16/2 & #14/4 cr--#16/2 & #14/4 01:019 EOL0®6 01:013 010 .027ma .027ma .027ma 01:010 b #16/2 #16/2 & #14/4 .027ma .027ma .027ma 01:050 01:049 #16/2 #16/2 #16/2 & #14/4 01:004 01:003 01:002 01:001 #16/2 #14/4 01:020 .027ma .027ma #16/2 & #14/4 - 7 01:023 .027ma CD 01:026 .027ma 01:036 CD #16/2 01:029 .027ma #16/2 #16/2 & #14/4 #16/2 & #14/4 -,D #16/2 & #14/4 -o #16/2 & #14/2 -0 01:021 .027ma .027ma 01:024 .027ma #16/2 CD #16/2 & #14/4 -0 01:027 01:030 .027ma .027ma #16/2 O1:Q43 01:031 .027ma .027ma 01:035 01:057 01:034 #16/2 #16/2 01:052 #14/4 - #14/2 -,0 15cd .074ma .0DH15ma #14/4 #14/2 - 01:032 .027ma .027ma #16/2 & #14/4 - #16/2 & #14/4 - #16/2 & #14/2 - 01:022 .027ma .027ma 01:025 .027ma 01:028 .027ma #18/2 WEST REMOTE ANNUNCIATOR 1100EL RAM -3501M #18/4 FACP MIRCOM FX -350.126 -DR TO CENTRAL PHONE LINE #1 DUAL STATION UNE ALER PHONE LINE #2 120 VAC S (DEDICATED CKT.) SLC NAC -1 #16/2 NAC -2 NAC -3 NAC -4 30cd 15cd PD EOL 092ma r .074ma #18/4 #18/4 CD #16/2 01:044 b 01:054 01045 EOL 01:033 .027ma .027ma 01:048 01:047 01:053 #16/2 #16/2 KIT- #16/2 U 01:046 15cd D .074ma .01H5ma #14/4 -ou #14/2 - FIRE ALARM SIGNAL EXPANDER BPS -6 INPUT #14/2 NAC -1 BATTERY I BATTERY 12V-12AH 12V-12AH #14/2 RISER DIAGRAM #18/4 NAC -2 #14/2 NAC -3 NAC -4 BAIIEJY 12V -7A11 BATTERY 12V-7AN �I 120 VAC (DEDICATED CKT.) EAST #18/4 15cd .074ma .015ma WP-75cd BELL D EOL .138ma .040ma CIRCUIT DISCRIPTIONS: CKT.#1 - ROOM NOTIFICATION WEST. CKT.#2 - ROOM NOTIFICATION EAST. CKT.#3 - 1ST FLOOR NOTIFICATION. CKT.#4 - TRIGGER FIRE SIGNAL EXPANDER (FSE). FSE CKT.#1 - HALL WAY NOTIFICATION. FSE CKT.#2 - OUTDOOR BELL & STROBE & EAST CORRIDOR. FSE CKT. #3 - DOOR HOLDERS NORTH AND SOUTH. #18/4 - AS -BUILT 9-25-08 z O ED w cc 0 0 O ¢ 0 ca w 5 m 0 rn V 2 w z 0 w LL ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. B 4726 SOUTH CENTER BLVD. TUKWILA WA, 98188 C W CC LL BUILDING RISER DIAGRAM APPROVED BY : ER DRAWN BY: RG DATE: 4-15-08 J0B# 87474 DWG. NO.: FA -06