FIRE ALARM WIRE LEGEND
DESIG.
DESCRIPTION
A
16/2 FPLR INITIATING CIRCUIT WIRING
B
14/2 FPLR INDICATING CIRCUIT WIRING
C
18/4 FPLR ANNUNCIATOR CIRCUIT WIRING
D
14/2 FPLP DUCT DETECTOR OR DOOR HOLDER POWER WIRING
E
AWG-18-THHW FOR DIRECT BURY/WET LOCATION
KEY LEGEND AND COMPONENT LIST
SYMBOL
DESCRIPTION
QTY
PART #
MANUFACTOR
MOUNTING SPEC
FIRE ALARM CONTROL PANEL
1
FX -350 -DDR
MIRCOM
WALL TOP @ 68'
I FACP I
FIRE SIGNAL EXPANDER
JH—Operable
WALL TOP @ 66'
I FSE I
ANNUNCIATOR
1.1
(3.i
minimum
1.37
maximum
m
R)
m
%
2,4
F,,12,4-
Finished floor
WALL TOP @ 66'
I ANN I
7/7///////////
TRANSMITTER
FIELD VERIFY
SUBSCRIBER TERMINAL UNIT
FIELD VERIFY
I an, I
HORN
WALL @ 80'-96'
MINI -HORN
48
MH -25W
MIRCOM
WALL @ 80'-96'
CO
BELL
1
MB -G10 -24R
WHEELOCK
OUTSIDE WALL @ 10'
STROBE
WALL @ 80'-96'
x(
WEATHER PROOF STROBE
1
RSSWP-2475-FR
WHEELOCK
WALL @ 80'-96'
WP ) (
IBJ
HORN -STROBE
WALL @ 80'-96'
0
CEILING MOUNTED HORN/STROBE
CEILING
0
CEILING MOUNTED STROBE
CEILING
CHIME
FIELD VERIFY
C
O
SPEAKER
WALL @ 90'
Q
JUNCTION BOX
FIELD VERIFY
DOOR HOLDER
FIELD VERIFY
im
DOOR STRIKE
FIELD VERIFY
UM
F
MANUAL PULL STATION
WALL @ 48'
0 AB
SMOKE DETECTOR ABOVE CEILING
ABOVE CEILING OR IN DUCT
®
SMOKE DETECTOR
CEILING - 3' FROM AIR DEFUSER
® BL
SMOKE DETECTOR BELOW FLOOR
BELOW FLOOR
a)
194° FIXED TEMP HEAT DETECTOR
8
MIX -3300
MIRCOM
CEILING
®R
194° RATE OF RISE HEAT DETECTOR
CEILING
®R
135° RATE OF RISE HEAT DEI ECTOR
16
MIX -3300
MIRCOM
CEILING
194°®
194° FIXED TEMP HEAT DETECTOR
CEILING
LINE TYPE HEAT DETECTOR
FIELD VERIFY
WF
WATERFLOW SWITCH
RISER PIPE
Ps
PRESSURE SWITCH
RISER PIPE
TS
TAMPER SWITCH
GATE VALVE
JB
JUNCTION BOX ALONGSIDE DEVICE
FIELD VERIFY
[T]
MONITOR MODULE
FIELD VERIFY
R
ADDRESSABLE RELAY
FIELD VERIFY
Genera/ Notes NP.PA 72-2002 Clition
1 -sec. 5.63.1...heal-eensinq fire detectors shall be located on the
ceiling not less than lOOnn (4 in) Iron the sidewall or on the
sidewalls between lOOnm and 300m (4/n and 12/n) Iron the
ceiling. See figure F.5.63.1
A -Sec. 5132.1 ...enoke defectors shall i e located on the ceiling not
less than lOOnn (4 in) Iron a sidewall lo the near edge or, if on a
sidewa/l, between IOOnn and 300m (4/n. and /2in) down front the
ceiling to the lop of the defector. See figure F.5132.1
^3 sec.175.7.4./ Defedors should not be located in a direct airflow or
f■, \ closer than In (3 ft.) Iron on air supply diffu cr or return air opening.
Supply or return sources larger than those cornody found in
residential and small connercial eslablidinede can require greater
clearance to snoke de/cc-torn Similarly, smoke ddedore should be
located farther away Iron high velocity air supplies.
n4 -sec. 5.12.4 The operable par! of each (larval fire darn box shall be
/ ■• no! less than 1.1(104 ft.) and not nore than 137n (4 %2 ft) above
floor level, See figure 1=.5.12.4
li\5 -Sec 7.5.4 Wall mounted appliances shall be mounted such that the
/ ■ \ entire lens is not less than Zn (8O in.) and not greater than 2.4n (96
in) above the finished floor. See figure F.7.5.4
/*T -Sec. 4.4.1.4.1 Dedicated branch circuit. A dedicated branch circuit of
is one of the follo.4ing 517011 supply primary power:
(l) Gonnercial light and power.
(2) An ergine -driven generator or equivalent in accordance with
4.4.1,92, where a person specifically trained in its operation i5 on
duty at all linen
(3) An engine -driven generator or equivalent arranged for cogeneration
with connercial light and power in accordance with 4.4.1.92, where a
person specifically trained in it operation is on duty at dl tires.
Ceiling
100 mm (4 in.)
Acceptable here
Note: Measurements shown are to
the closest edge of the detector.
Never here
Top of detector
acceptable here
300 mm
(12 in.)
maximum
x,5,75,2,/
Side 11
ire• f�1' /,
7i
N
MAP OF LOCATION
FX-350-60DR
outside
0220
0.006
0.000
iI.:LRttrft
0.000
0.000
0.000:
0.000
0.380
0:100
0.000
0>000'_
D.
0.000::
0.000:::
0.000
0:000:
Other
Other
Notification Appl Circuit
Notification Appl Circuit
Notification Appl Circuit
Notification Appl Circuit
1 # of NAC's Used
0.000-:.
0;000
0.000
0.000
<0.000
0.000
0,000
0.000
0000<
0;000
0:000::
0.000
0:486 #14 Solid
0.486
14 Solid
0.324.: #14 Solid
0:168 #18 Solid
iia>I iris ire tlfgittEAW
450
450
550
65
Command Shortcuts
Configure Circuits
R• -
4,40°la:.
Print Page
Project Information
Project Name: PARK PLACE BY THE WOODS
Prepared By: NELS
Project ID: 87474
Date: 5/8/2008
men.
Notification Appl Circuit
far
3.
ani
18
MH -25W
Unused
Unused
Unused
Totals
18
MH -25W
Unused
Unused
Unused
Totals
0486
Notification Appl Circuit
Unused
Unused
Unused
Totals
0:000
0.324
Notification Appl Circuit
rren
1
MB -G10 & RSSP
Unused
Unused
Unused
tibd
Totals
0.000
-:0168
a
[] Without Comments
As Noted In Red
Per The Attached Letter
I nese plans have hnei1 reviewed by The Tukwila Fire
Prevention Bureau for cor:fo ril•.',tice wiLfi current city
standards. Acccetitance is yuu;c:.•;,t to errors and
omissions which do not authorize vHations of adopted
standards and ci 1iila (Ices. responsibility for the
adequacy of desin rests total+; with the designer.
Additions, deletions or revisions to these drawings atter
this date will void th-s-acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to fietd test and inspection by
The Tukwila Fire, Prevention Bureau.
Date: S _ I — off' ay:
—T>1si( wthfa,(
4s ;hOki Ca,kcill •
s44—ms CO- COQ t•w'' e):14-5
970
NOTICE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate must be presented
to the Inspector prior to
Commencement of Acceptance
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
termination of the testing.
TUKWILA FIRE DEPARTMENT.
Please call: 575-440Z
and give this job
ig
and exact address for shut
down or restoration approval;
:. 2008
Tukwila Fire
ISSUED FOR APPROVAL
d
z
ci
0
C)
z
W
Z
0
ELECT. FIREOI*099KW
206-575-0311
107 WASHINGTON BLVD. ALGONA WA, 98001
PARK PLACE BY THE WOODS BLDG. I
4708 SOUTH CENTER BLVD.
TUKWILA WA, 98188
CC
w
CC
U -
RISER/BOM - FIRE ALARM PLAN
APPROVED BY :
ER
DRAWN BY:
RG
DATE:
5-6-08
JOB#
87474
DWG. NO. :
FA -01
Y/
GED
,
MIMI
Operable
WI
JH—Operable
1.1
(3.i
minimum
1.37
maximum
m
R)
m
%
2,4
F,,12,4-
Finished floor
4—Sldewall
7/7///////////
ire• f�1' /,
7i
N
MAP OF LOCATION
FX-350-60DR
outside
0220
0.006
0.000
iI.:LRttrft
0.000
0.000
0.000:
0.000
0.380
0:100
0.000
0>000'_
D.
0.000::
0.000:::
0.000
0:000:
Other
Other
Notification Appl Circuit
Notification Appl Circuit
Notification Appl Circuit
Notification Appl Circuit
1 # of NAC's Used
0.000-:.
0;000
0.000
0.000
<0.000
0.000
0,000
0.000
0000<
0;000
0:000::
0.000
0:486 #14 Solid
0.486
14 Solid
0.324.: #14 Solid
0:168 #18 Solid
iia>I iris ire tlfgittEAW
450
450
550
65
Command Shortcuts
Configure Circuits
R• -
4,40°la:.
Print Page
Project Information
Project Name: PARK PLACE BY THE WOODS
Prepared By: NELS
Project ID: 87474
Date: 5/8/2008
men.
Notification Appl Circuit
far
3.
ani
18
MH -25W
Unused
Unused
Unused
Totals
18
MH -25W
Unused
Unused
Unused
Totals
0486
Notification Appl Circuit
Unused
Unused
Unused
Totals
0:000
0.324
Notification Appl Circuit
rren
1
MB -G10 & RSSP
Unused
Unused
Unused
tibd
Totals
0.000
-:0168
a
[] Without Comments
As Noted In Red
Per The Attached Letter
I nese plans have hnei1 reviewed by The Tukwila Fire
Prevention Bureau for cor:fo ril•.',tice wiLfi current city
standards. Acccetitance is yuu;c:.•;,t to errors and
omissions which do not authorize vHations of adopted
standards and ci 1iila (Ices. responsibility for the
adequacy of desin rests total+; with the designer.
Additions, deletions or revisions to these drawings atter
this date will void th-s-acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to fietd test and inspection by
The Tukwila Fire, Prevention Bureau.
Date: S _ I — off' ay:
—T>1si( wthfa,(
4s ;hOki Ca,kcill •
s44—ms CO- COQ t•w'' e):14-5
970
NOTICE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate must be presented
to the Inspector prior to
Commencement of Acceptance
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
termination of the testing.
TUKWILA FIRE DEPARTMENT.
Please call: 575-440Z
and give this job
ig
and exact address for shut
down or restoration approval;
:. 2008
Tukwila Fire
ISSUED FOR APPROVAL
d
z
ci
0
C)
z
W
Z
0
ELECT. FIREOI*099KW
206-575-0311
107 WASHINGTON BLVD. ALGONA WA, 98001
PARK PLACE BY THE WOODS BLDG. I
4708 SOUTH CENTER BLVD.
TUKWILA WA, 98188
CC
w
CC
U -
RISER/BOM - FIRE ALARM PLAN
APPROVED BY :
ER
DRAWN BY:
RG
DATE:
5-6-08
JOB#
87474
DWG. NO. :
FA -01
Y/
0
E
F
G
H
J
K
L
M
N
1
2
3
4
5
7
8
10
DINING
1050 SQFT 2 BEDROOM
1.25 BATH
O0
0°
KITCHEN
y
01
0
FROM
2ND FL
A,B
01
LMNG ROOM
BATH ROOM
O
FROM 0 B
2ND FL
BEDROOM
TO
ATTIC
STORAGE
LMNG ROOM
1050 SOFT 2 BEDROOM
1.25 BATH
STORAGE
101
W/O HOOK UP
CLOSET
EOL
BEDROOM
DN
102
FROM
2ND FL
A,B
1
DINING
0 o I
0I
KITCHEN
CLOSET
0
BATH ROOM
GI
gi
DINING
1050 SOFT 2 BEDROOM
1.25 BATH
00
0 O
KITCHEN
- FROM
2ND FL
A,B
0
01
1;
BATH ROOM
WING ROOM
I,
TO
ATTIC
BEDROOM
STORAGE
L ING ROOM
1050 SQFT 2 BEDROOM
1.25 BATH
STORAGE
105
W/D HOOK UP
CLOSET
EOL
BEDROOM
DN
UP
106
FROM
2ND FL
A,B
DINING
Do
O Q
KITCHEN
0
J
BATH ROOM
W/D HOOKUP
1050 SQFT 2 BEDROOM
1.25 BATH
DINING
00
0
KITCHEN
LIVING ROOM
FROM
2ND FL
A,B
01 :OW
STORAGE
1050 SQFT 2 BEDROOM
1.25 BATH
LIVING ROOM DINING
STORAGE
BEDROOM
BEDROOM
WP
ON
1
UP
W/ D HOOK UP
CLOSET
FROM
2ND FL
A,B
8
ATTIC
0
o0
KITCHEN
0
U
1ST FLOOR - BLDG. I
1 /811 _ 11 -oil
1050 SQFT 2 BEDROOM
1.25 BATH
DINING LMNG ROOM
foo
0
KITCHEN
0
FROM
2ND FL
A,B
0
BATH ROOM
TO
ATTIC
STORAGE
113
LMNG ROOM
1050 SQFT 2 BEDROOM
1.25 BATH
STORAGE
W/D HOOK UP
CLOSET
BEDROOM
TO ATTIC
BEDROOM
1
DN
114
UP
W/D HOOKUP
CLOSET
FROM
2ND FL
A,B
4
EOL
BEDROOM
TO
ATTIC
DINING
po
GO
KITCHEN
0
l J
BATH ROOM
D
GENERAL NOTES:
1. HEAT DETECTORS IN UNITS SHALL BE 135° RATE OF RISE.
2. HEAT DETECTORS IN THE ATTIC SPACE SHALL BE 194° FIXED TEMPERATURE.
3. DEDICATED FIRE ALARM SYSTEM CIRCUIT SHALL BE EQUIPPED WITH LOCKOUT DEVICES.
4. CONTROL PANEL RESET CODE SHALL BE 1-2-3-4-5
5. INSTALL THE FIRE ALARM CONTROL PANEL IN A U.L. LISTED HOFFMAN
HEATED INCLOSURE (NEMA 3 RATED).
z
w
0
LU
11
ELECT. FIREOI*099KW
206-575-0311
107 WASHINGTON BLVD. ALGONA WA, 98001
PARK PLACE BY THE WOODS BLDG.
d
Co 03
Er 1—
CO CO
z
U 'S
=g
VJ n
0
N-
1ST FLOOR - FIRE ALARM PLAN
APPROVED BY:
ER
DRAWN BY:
RG
DATE:
5-6-08
JOB#
87474
DWG. NO. :
FA -02
H
J
K
L
M
1
2
3
4
5
6
7
8
9
10
1050 SQFT 2 BEDROOM
1.25 BATH
DINING WING ROOM
00
00
KITCHEN
FROM
ATTIC
FROM
ATTIC
STORAGE
CLOSET
BEDROOM
TO 2ND
FLOOR
BEDROOM
1050 SQFT 2 BEDROOM
1.25 BATH
WING ROOM DINING
STORAGE
ON
104
FROM
ATTIC
A,B
0
00
00
KITCHEN
W/O HOOK UP
CLOSET
l )
C)
BATH Roots
TO 2ND
FLOOR
o �
9
U
TO 2ND
FLOOR
BEDROOM
1050 SOFT 2 BEDROOM
1.25 BATH
DINING
0 0
lO
J
KITCHEN
FROM
ATTIC
LIVING ROOM
O
TO 2ND
FLOOR
STORAGE
107
W/ D HOOK UP
CLOSET
BEDROOM
TO 2ND
FLOOR
BEDROOM
LIVING ROOM
1050 SQFT 2 BEDROOM
1.25 BATH
STORAGE
FROM
ATTIC
A,B
4
DINING
00
0 0
KITCHEN
TO 2ND
FLOOR
FROM
ATTIC
BEDROOM
TO 2ND
FLOOR
BEDROOM
DINING
1050 SOFT 2 BEDROOM
1.25 BATH
00
00
KITCHEN
LI
- FROM
ATTIC
A,B
0
LIVING ROOM
BATH ROOM
FROM
ATTIC
TO 2ND
FLOOR
STORAGE
1050 SOFT 2 BEDROOM
1.25 BATH
LIVING ROOM DINING
STORAGE
111
W/D 1100K UP
CLOSET
TO 2ND
FLOOR
DN
112
0o
00
KITCHEN
TO 2ND
FLOOR
W/ D HOOK UP
CLOSET
TO 2ND
FLOOR
BEDROOM
N
9
2ND FLOOR- BLDG.
1/8"_11-OII
1050 SOFT 2 BEDROOM
1.25 BATH
DINING LIVING ROOM
00
00
KITCHEN
FROM
ATTIC
0
B
FROM
ATTIC
A,B
0
STORAGE
BATH ROOM
TO 2ND
FLOOR
W/DHOOKUP
CLOSET
BEDROOM
TO 2ND
FLOOR
BEDROOM
1050 SOFT 2 BEDROOM
1.25 BATH
LIVING ROOM DINING
STORAGE
ON
116
00
oO
KITCHEN
TO 2ND
FLOOR
FROM
ATTIC
BEDROOM
TO 2ND
FLOOR
BEDROOM
w
9
GENERAL NOTES:
N
1. HEAT DETECTORS IN UNITS SHALL BE 135° RATE OF RISE.
2. HEAT DETECTORS IN THE ATTIC SPACE SHALL BE 194° FIXED TEMPERATURE.
3. DEDICATED FIRE ALARM SYSTEM CIRCUIT SHALL BE EQUIPPED WITH LOCKOUT DEVICES.
4. CONTROL PANEL RESET CODE SHALL BE 1-2-34-5
5. INSTALL THE FIRE ALARM CONTROL PANEL IN A U.L LISTED HOFFMAN
HEATED INCLOSURE (NEMA 3 RATED).
z
0
¢
ISSUED FOR APPROVAL
ci
z
0
C)
2
•
W
z
0
W
ctrr
ELECT. FIREOI*099KW
206-575-0311
107 WASHINGTON BLVD. ALGONA WA, 98001
PARK PLACE BY THE WOODS BLDG. 1
4708 SOUTH CENTER BLVD.
TUKWILA WA, 98188
cc�y�yr
LLI
CC
LL
CI -
CC
LIJLL
LL
CC
0
0
J
LL
CV
APPROVED BY:
ER
DRAWN BY:
RG
DATE:
5-6-08
JOB#
87474
DWG. NO.:
FA -03
D
E
F
H
J
K
M
N
1
2
3
24013
A,B
4
5
6
7
8
9
10
01 A B
�
d r�
A,23 01:007
A,2B
0-A,B
A,2B-p
01:006 A'2B
(o d��
ita--A,213
FIA'2B01:001
I I
FROM CONTROL
PANEL
A,2B 3B,A
d-A,2B A,2B-p
ATTIC - BLDG. I
1/8"=1'-0"
01:016 Acei
� I
A,B
bn
01:021
0
A,B
A,B-p
01:022 A1
CD Dv
B-
CIRCUIT DESCRIPTIONS:
CKT.#1 - ROOM NOTIFICATION WEST.
CKT.#2 - ROOM NOTIFICATION EAST.
CKT.#3 - ROOM NOTIFICATION WEST.
CKT.#4 - OUTDOOR BELL & STROBE.
GENERAL NOTES:
1. HEAT DETECTORS IN UNITS SHALL BE 135° RATE OF RISE.
2. HEAT DETECTORS IN THE ATTIC SPACE SHALL BE 194° FIXED TEMPERATURE.
3. DEDICATED FIRE ALARM SYSTEM CIRCUIT SHALL BE EQUIPPED WITH LOCKOUT DEVICES.
4. CONTROL PANEL RESET CODE SHALL BE 1-2-3-4-5
5. INSTALL THE FIRE ALARM CONTROL PANEL IN A U.L LISTED HOFFMAN
HEATED INCLOSURE (NEMA 3 RATED).
Z
O
0
a.
a
O
LL
0
w
m
C/)
LU
z
0
W
I�-
1�
ELECT. FIREOI*099KW
206-575-0311
107 WASHINGTON BLVD. ALGONA WA, 98001
PARK PLACE BY THE WOODS BLDG. I
4708 SOUTH CENTER BLVD.
TUKWILA WA, 98188
ATTIC - FIRE ALARM PLAN
APPROVED BY :
ER
DRAWN BY:
RG
DATE:
5-6-08
JOB#
87474
DWG. NO.:
FA -04
H
J
K
L
M
N
1
2
3
#14/2
#16/2 & #14/4
01:013
#16/2 & #14/4 #16/2 & #14/4 #16/2 & 2 #14/4 #16/2 & 2 #14/4 #16/2 & 2 #14/4
01:012
#16/2 & #14/4
ATTIC
#16/2 & 2 #14/4 #16/2 & 2 #14/4
#16/2 & 2 #14/4 #16/2 & 2 #14/4
01:007
01:006
#16/2 & 2 #14/4
01:001
qc
#16/2
#16/2 & 2 #14/4
#16/2
T -TAP L
01:016
#16/2 & #14/4
#16/2 &
#14/4
#16/2 & #14/4
#16/2 & #14/4 #16/2 & #14/4
#16/2 & #14/4
CD b o b
01:021 01:022
#16/2 & #14/4
#14/2
L7-#14/2 #16/2 & #14/4 -#16/2 & #14/4 :7-#16/2 & #14/4 #16/2 & #14/2 :7-#16/2 & #14/4
4
.027ma
.027ma
01:014
.027ma
UNIT 103
2ND FLOOR
01:010
.027ma .027ma " .027ma
UNIT 104
.027ma .027ma
01:008
.027ma
UNIT 107
Q-#16/2 & #14/4 0-#16/2 & #14/4 0-#16/2 & #14/4 :7-#16/2 & #14/4
.027ma
.027ma
01:004
.027ma
UNIT 108
#14/2 0-#16/2 & #14/4#16/2 & #14/4 0-#16/2 & #14/4#16/2 & #14/2#16/2 & #14/4
.027ma
.027ma
01:002
.027ma
UNIT 110
#16/2 & #14/4 0-#16/2 & #14/4 #16/2 & #14/4 :7-#16/2 & #14/4
#16/2 & #14/4 #16/2 & #14/4 - #16/2 & #14/4 -0 #16/2 & #14/4
#16/2 & #14/4 #14/2
01:017
.027ma
UNIT 113
.027ma
•
.027ma
01:019
.027ma
UNIT 114
R
.027ma
.027ma
#16/2 & #14/4 - #16/2 & #14/4 -V #16/2 & #14/4 -0 #16/2 & #14/4
ATTIC
01:023
.027ma .027ma
UNIT 116
.027ma
#16/2 & #14/4 - #14/2-1:7
5
EOL
.027ma
.027ma
01:015
R
.027ma
UNIT 101
6
1ST FLOOR
01:011
.027ma .027ma .027ma
UNIT 102
EOL
.027ma .027ma
01:009
.027ma
UNIT 105
� r
•
.027ma
.027ma
01:005
R
.027ma
L_ UNIT 106
EOL CO
#18/2
d 75cd
.027ma
.027ma
01:003
.027ma
UNIT 109
#18/2
.040ma .138ma
WEST
7
8
9
10
TO CENTRAL
STATION
PHONE LINE #1
FACP
MIRCOM
FX356£DDDR
CU
DALER
PHONE LINE #2
120 VAC
(DEDICATED CKr.)
NAC -1
#16/2
2#14/4
NAC -2
C-3
NAC -4
14/4
I1._f
BATTERY
12V7AR
BIM!t
RISER DIAGRAM
#18/2
✓ -1-
01:018
r
01:018
.027ma " .027ma .027ma
UNIT 111
01:020
F
.027ma .027ma .027ma
L UNIT 112
J
�I r
2ND FLOOR
01:024
R
\--04 EOL
.027ma .027ma .027ma
UNIT 115
1ST FLOOR
EAST
CIRCUIT DESCRIPTIONS:
CKT.#1 - ROOM NOTIFICATION WEST.
CKT.#2 - ROOM NOTIFICATION EAST.
CKT.#3 - ROOM NOTIFICATION WEST.
CKT.#4 - OUTDOOR BELL & STROBE.
GENERAL NOTES:
1. HEAT DETECTORS IN UNITS SHALL BE 135° RATE OF RISE.
2. HEAT DETECTORS IN THE ATTIC SPACE SHALL BE 194° FIXED TEMPERATURE.
3. DEDICATED FIRE ALARM SYSTEM CIRCUIT SHALL BE EQUIPPED WITH LOCKOUT DEVICES.
4. CONTROL PANEL RESET CODE SHALL BE 1-2-3-4-5
5. INSTALL THE FIRE ALARM CONTROL PANEL IN A U.L. LISTED HOFFMAN
HEATED INCLOSURE (NEMA 3 RATED).
2
O
W
Z
0
LU
ELECT. FIREOI*099KW
206-575-0311
107 WASHINGTON BLVD. ALGONA WA, 98001
PARK PLACE BY THE WOODS BLDG. 1
4708 SOUTH CENTER BLVD.
TUKWILA WA, 98188
CC
Q
LLI
CC
LL
APPROVED BY :
ER
DRAWN BY:
RG
DATE:
5-6-08
JOB#
87474
DWG. NO.:
FA -05