HomeMy WebLinkAboutPP - 4708 SOUTHCENTER BLVD BLDG C - THE BOULEVARD AT SOUTH STATION - PERMITS AND PLANS4708 SOUTHCENTER BLVD BLDG C ASSOCIATED PERMITS 08-F-143 FIRE DEPARTMENT FIRE ALARM PLAN REVIEW COMMENTS Project Name: Park Place By The Woods Bldg. C 4708 Southcenter BI Permit No.: 08-F-143 Date: April 28, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • When the control panel is located inside a room, the door to the room shall have a sign with one -inch letters, which reads "Fire Alarm" or "Fire Alarm Control". • Install smoke detectors as shown in red on the plans within 5 ft. of the door opening for magnetic door holder operation. • Heat detectors installed in the dwelling units to be 135 degree rate of rise. • Heat detectors installed in the attic areas to be 194 degree fixed temp. • Dedicated fire alarm system circuit breakers shall be equipped with lockout devices. • If reset code is employed, reset code to be 1-2-3-4-5. • An electrical permit from the city of Tukwila Building Department permit center . • The Tukwila Fire Department has changed keybox manufacturers, from Supra to Knox. Install a fire department Knox Keybox. Contact the Tukwila Fire Prevention Office at 206-575-4407 for ordering information. fNELS A 2 3 4 5 6 7 8 9 10 B C FIRE ALARM WIRE LEGEND DESIG. DESCRIPTION A 16/2 FPLR INITIATING CIRCUIT WIRING B 14/2 FPLR INDICATING CIRCUIT WIRING C 18/4 FPLR ANNUNCIATOR CIRCUIT WIRING D 14/2 FPLP DUCT DETECTOR OR DOOR HOLDER POWER WIRING E AWG-16-THHW FOR DIRECT BURY/WET LOCATION KEY LEGEND AND COMPONENT LiST SYMBOL DESCRIPTION QTY PART # MANUFACTOR MOUNTING SPEC 3 FIRE ALARM CONTROL PANEL 1 FX -350 -DDR MIRCOM WALL TOP @ 66° FACP I FIRE SIGNAL EXPANDER 1 BPS -6 MIRCOM WALL TOP @ 66' FSE I /////////z//// ANNUNCIATOR 1 RAM-300LCDR MIRCOM WALL TOP @ 66° NMI TRANSMITTER FIELD VERIFY TRAN J SUBSCRIBER TERMINAL UNIT FIELD VERIFY ® HORN WALL @ 80'-96' too MINI -HORN 50 MH -25W MIRCOM WALL @ 80'-96' CI:1 BELL 1 MB -G10 -24R WHEELOCK OUTSIDE WALL @ 10' X STROBE 4 ZRS-MCW-FR WHEELOCK WALL @ 80'-96' WP k( WEATHER PROOF STROBE 1 RSSP-2475-FR WHEELOCK - WALL @ 80'-96' G® HORN -STROBE 7 ZNS-MCW-FR WHEELOCK WALL @ 80'-96' CEILING MOUNTED HORN/STROBE CEILING 0 CEILING MOUNTED STROBE CEILING C CHIME FIELD VERIFY Q SPEAKER WALL@ 90° JO JUNCTION BOX FIELD VERIFY DOOR HOLDER 6 DH24120SPC MIRCOM FIELD VERIFY En DOOR STRIKE FIELD VERIFY MI F MANUAL PULL STATION 7 MS -701 DU MIRCOM WALL @ 48° m AB SMOKE DETECTOR ABOVE CEILING ABOVE CEILING OR IN DUCT mSMOKE DETECTOR 19 MIX -3100 MIRCOM CEILING - 3' FROM AIR DEFUSER el BL SMOKE DETECTOR BELOW FLOOR BELOW FLOOR ® 194° FIXED TEMP HEAT DETECTOR 5 MIX -3300 MIRCOM CEILING ©R 194° RATE OF RISE HEAT DETECTOR 38 MIX -3300 MIRCOM CEILING ©R 135° RATE OF RISE HEAT DETECTOR CEILING 194°© 194° FIXED TEMP HEAT DETECTOR CEILING iD---> LINE TYPE HEAT DETECTOR FIELD VERIFY WF WATERFLOW SWITCH RISER PIPE PS PRESSURE SWITCH RISER PIPE TS TAMPER SWITCH GATE VALVE JB JUNCTION BOX ALONGSIDE DEVICE FIELD VERIFY M MONITOR MODULE FIELD VERIFY R ADDRESSABLE RELAY FIELD VERIFY General Notes IVPPA72-2002 Edition 1 '5ec. 5.63.1 „heal -sensing fire detectors shall be located on the ceiling not less than lOOnn (4 in) from the sidewall or on the sidewalls between100m and 300rin Coin and 12/n.) from the ceiling, See figure F.5.63.1 �2 5ec. 5.732.1 ...smoke defectors shall be located on the ceiling not / ,■ less than lOOnn (4 in.) from a sidewall to the near edge or, if on a sidewall, between100m and 300nh (4in, and 12in) down Iron the ceiling to the lop of the deledor. 5ec figure E,5.732,1 5cc. / .14.I Petector5 should not be located in a direct airflow or • \ do cr than In (3 fl.) Iron an air supply diffuser or return air opening. Supply or return sources larger than lho c connor>,y found in residential and snail connercial e,/ab/ietirserl, can require greater clearance to smoke detectors. 5inilarly, smoke detectors should be located farther away Iron high velocity air supplies /1\4 -ec. 5.12.4 The operable part of each marual fire alarn box shall be •• \ not less than 1Jn (3%2 II.) and not more than 137n (4 %Z ft.) above floor level. ee figure F.5.12.4 4\5 -Sec. 7.5.4 Wall mounted appliances shall be mounted such that the / ■ \ entire lens is not less than 2n (80 int and not greater than Z.4n (96 in.) above the finished floor. 5ec figure F.7..4 4.4.1.4/ Dedicated branch circuit. A dedicated brandy circuit of ■ one of the following shall supply primary power, (1) Conmercial light and power. (2) An engine -driven generator or equivalent in accordance with 4.4.1.9.2, where a person specifically trained in its operation is on duly al all lines. (3) An engine -driven generator or equivalent arranged for cogererafion with connercial light and power in accordance with 4.4.1.92, where a person specifically trained in its operation is on duly at all lines. O Z O Ceiling r//////y// Acceptable here Note: Measurements shown are to the closest edge of the detector. 100 mm (4 in.) //J, Never here • ,+ Top of detector / acceptable here/ 1t0 mm (4 in.) rum 300 mm (12 in.) maximum Sidewall MAP OF LOCATION ci z w z 0 BPS -6 Power Expander Calculations BPS -6 BPS -6 ELECTRICAL ROOM 5495(1) Circuit 1 5495(1) Circuit 2 5495(1) Circuit 3 PARK PLACE BY THE WOODS I 87474 4/2/2008 5495(1) Circuit 4 5435(1) Aux Power Out 5495 PowerrEx renter:; Tstal Stathdby`Currentf: tri 0.120 =0.000 0.000_` 0.344 0.000 0000:: #14 Solid #18 Solid #14 Solid 560 150 0 1.66%.' 3.23% 0.00% 0.00%, 0 two 0 000 lade #31951' 0.00% 0:464 Mt& iutesf60< Wire resistances are based upon an ambient tempera ure of 72 degrees F. Because of the minimal difference between solid and stranded wi e no differential was made. Command Shortcuts Configure Circuits #1. Note: A value msut be entered if you have selected any NAC circuits as AUX Power. Project Information Circuit Configuration Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4/2/2008 24 MH -25W Unused Unused Unused €s Notification Appl Circuit Totals rf 0.000 7.iintatin 0.648. f Notification Appl Circuli i Unused Unused Unused 3 ZRS-MCW-FR 15cd ................. Totals . may..:. ::- 0.702 FX-3501126.DR Notification Appl Circuit 1. 6 ZNS-MCW-FR 15cd Unused Unused Totals 0.000 0.624 j.:. 1 BPS -602 Unused Unused Unused Totals 0.075 0:150 Project Information Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4/2/2008 6 DH24120SPC >:,LIa020 0 Unused Unused Unused 0 a 0001> Totals 0120 0.000 1 1 1 MB -G10 -24R RSSP-2475-FR ZRS-MCW-FW 30cd 0. i 1 ZNS-MCW-FW 15cd 3074_` Totals 0.000 0.344 APPROVED BY : ER DRAWN BY: RG DATE: 3-25-2008 AS -BUILT 9-17-08 DWG. NO.: FA -01 3 Operable 11011•Part 1.1 (3)4 min 1.37 (4)4 maximum m fl.) mum m R) ,,1.2,-4- '12,-4-Finished floor Finished *—Sidewall /////////z//// MAP OF LOCATION ci z w z 0 BPS -6 Power Expander Calculations BPS -6 BPS -6 ELECTRICAL ROOM 5495(1) Circuit 1 5495(1) Circuit 2 5495(1) Circuit 3 PARK PLACE BY THE WOODS I 87474 4/2/2008 5495(1) Circuit 4 5435(1) Aux Power Out 5495 PowerrEx renter:; Tstal Stathdby`Currentf: tri 0.120 =0.000 0.000_` 0.344 0.000 0000:: #14 Solid #18 Solid #14 Solid 560 150 0 1.66%.' 3.23% 0.00% 0.00%, 0 two 0 000 lade #31951' 0.00% 0:464 Mt& iutesf60< Wire resistances are based upon an ambient tempera ure of 72 degrees F. Because of the minimal difference between solid and stranded wi e no differential was made. Command Shortcuts Configure Circuits #1. Note: A value msut be entered if you have selected any NAC circuits as AUX Power. Project Information Circuit Configuration Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4/2/2008 24 MH -25W Unused Unused Unused €s Notification Appl Circuit Totals rf 0.000 7.iintatin 0.648. f Notification Appl Circuli i Unused Unused Unused 3 ZRS-MCW-FR 15cd ................. Totals . may..:. ::- 0.702 FX-3501126.DR Notification Appl Circuit 1. 6 ZNS-MCW-FR 15cd Unused Unused Totals 0.000 0.624 j.:. 1 BPS -602 Unused Unused Unused Totals 0.075 0:150 Project Information Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4/2/2008 6 DH24120SPC >:,LIa020 0 Unused Unused Unused 0 a 0001> Totals 0120 0.000 1 1 1 MB -G10 -24R RSSP-2475-FR ZRS-MCW-FW 30cd 0. i 1 ZNS-MCW-FW 15cd 3074_` Totals 0.000 0.344 APPROVED BY : ER DRAWN BY: RG DATE: 3-25-2008 AS -BUILT 9-17-08 DWG. NO.: FA -01 1 2 3 4 5 6 7 8 9 10 UP 825 SIFT 2 BEDROOM 1 BATH LMNG ROOM DINING BEDROOM CLOSET 00 Co KITCHEN FROM 2ND FL B DINING LIVING ROOM KITCHEN 00 825 SQFT 2 BEDROOM 1 BATH CLOSET 112 BEDROOM A 01:026 FROM 2ND FL CLOSET STORAGE BATH ROOM BEDROOM 625 SQFT 1 BEDROOM 1 BATH LMNG ROOM 15cd FROM DN 2ND FL I 2B STORAGE BATH ROOM r -- Qi BEDROOM BEDROOM O 15cd 109 KITCHEN 00 Co TO ATTIC LMNG ROOM 01:043 065 625 SIFT 1 BEDROOM 1 BATH LIVING ROOM TO ATTIC O 0 Oo KITCHEN 00 OO KITCHEN LL BEDROOM 01:020 108 L U FROM 2ND FL CLOSET STORAGE BATHROOM BEDROOM 425 SOFT STUDIO 1 BATH LIVING ROOM I' BATH ROOM) �IAATH ROOM 107 01:040 g STORAGE AB 425 SIFT STUDIO 1 BATH cLosE2ND FL. T BEDROOM BEDROOM KITCHEN 00 00 TO ATTIC LMNG ROOM 425 SOFT STUDIO 1 BATH 01:064 TO ATTIC O0 Co KITCHEN 425 SIFT STUDIO 1 BATH LIVING ROOM TO ATTIC 00 00 KITCHEN BEDROOM `CLOSET -FROM A,B STORAGE BEDROOM TO ATTIC BEDROOM CLOSET R LAUNDRY ROOM 01:014 BATH ROOM STORAGE FROM 2ND FL CLOSET 104 ®01:063 01:002L"1 ELECTRICAL ROOM KITCHEN LIVING ROOM Oo 00 625 SIFT 1 BEDROOM 1 BATH 1ST FLOOR - BLDG. C 1 /8" =1' -all KITCHEN 00 00 825 SOFT 2 BEDROOM 1 BATH Oo 00 KITCHEN LIVING ROOM DINING 15cd 01:071 P 103 01:032 TO ATTIC LIVING ROOM STORAGE o—A BATH ROOM CLOSET AB 625 SIFT 1 BEDROOM 1 BATH FROM 2ND FL BEDROOM DN UP TO BATH ROOM 0 STORAGE FROM D FL 101 F• L'M 2ND L BEDROOM —F6 OM 2ND FL KITCHEN OD Oo CLOSET FROM 2ND FL BEDROOM UP TO B ATTIC DINING LIVING ROOM 825 SQFT 2 BEDROOM 1 BATH AS -BUILT 9-17-08 Z O m a z W Z 0 W ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. C 4722 SOUTH CENTER BLVD. TUKWILA WA, 98188 CC ©c w CC U_ 1ST FLOOR - FIRE ALARM PLAN APPROVED BY: ER DRAWN BY: RG DATE: 3-25-2008 JOB# 87474 DWG. NO.: FA -02 A B H J K L M N 1 2 3 4 5 6 UP B FROM• 3RD FL 825 SQFT 2 BEDROOM 1 BATH LIVING ROOM DINING BEDROOM DOWN TO 1ST FL BEDROOM A,B CLOSET 00 Oo KITCHEN 01:073 01:054 FROM 3RD FL. DINING LIVING ROOM OWIATO 1ST FL. KITCHEN 00 00 825 SIFT 2 BEDROOM 1 BATH 01:055 DOWN TO 1ST FL. • 213 CLOSET J N r— 01:045 n R A� DOWN TO 1ST FL. BEDROOM 212 A,B U FROM 3RD FL CLOSET STORAGE BEDROOM DOWN TO 1ST FL AB CLOSET BATH ROOM _S)BATH ROOM STORAGE 625 SIFT 1 BEDROOM 1 BATH A,B U LIVING ROOM FROM 3RD FL. 01:022 R 01:056 210 00 00 KITCHEN 625 SIFT 1 BEDROOM 1 BATH LIVING ROOM DOWN TO 1ST FL 00 KITCHEN BEDROOM FROM 3RD FL A,B 01:019 208 AB CLOSET BEDROOM FROtesET RD FL A,B STORAGE A 425 SIFT STUDIO 1 BATH LIVING ROOM 9 U STORAGE BATH ROOM O ID BATH ROOM ° 01:057 01:016 206 DOWN TO 1ST FL 00 00 KITCHEN 425 SIFT STUDIO 1 BATH BEDROOM LIVING ROOM DOWN TO 1ST FL 00 00 KITCHEN R 01:058 FROM 3RD FL. 01:013 204 A,B STORAGE O I° BATH ROOM BEDROOM DOWN TO 1ST FL CLOSET BATH ROOM BEDROOM STORAGE 202 FROM 3RD FL. CLOSET 825 SIFT 2 BEDROOM 1 BATH 00 00 KITCHEN WING ROOM DINING 15cd 01:059 15cd FROM (1 3RD STORAGE A BATH ROOM CLOSET AB FROM 3RD FL. BEDROOM 7 8 9 10 H DN 6115c d KITCHEN 00 00 DOWN TO 1ST FL. 211 DN DOWN TO 2ND FL 01:042 ° BATH ROOM) a LIVING ROOM 425 SOFT STUDIO 1 BATH BEDROOM CRATH ROOM ° ID STORAGE AB FRO 3RD. CLOSET 209 01:039 R BEDROOM 00 00 00 00 DOWN TO DOWN TO 1ST FL 1ST FL LIVING ROOM 425 SIFT STUDIO 1 BATH 207 01:037 IO BATH ROOD LIVING ROOM 425 SOFT STUDIO L 205 203 N 9 STORAGE KITCHEN KITCHEN BATH ROOM BATH ROOM ID STORAGE 00 00 00 00 0 AB n ROM - 3RD. FL IiCLOSET BEDROOM 1 BATH 01:031 CLOSET CLOSET CLOSET DOWN TO 1ST FL BEDROOM FROM 3RD FL LIVING ROOM 625 SIFT 1 BEDROOM 1 BATH 2ND FLOOR - BLDG. C 1/8"=1'-0" DOWN TO A B 1ST. FL LMNGROOM AB DOWN TO 1ST FL 625 SIFT 1 BEDROOM 1 BATH FROM 3RD FL BEDROOM BEDROOM CLOSET UP DOWN TO 1ST FL ROM; DOWN TO 3RD FL 1ST FL. KITCHEN 00 00 FROM 3RD FL BEDROOM LIVING ROOM 825 SOFT 2 BEDROOM 1 BATH AS -BUILT 9-17-08 z O E6 W ISSUED FOR APPROVAL d W 0 ci z w 0z w LL ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. C 4722 SOUTH CENTER BLVD. TUKWILA WA, 98188 2ND FLOOR - FIRE ALARM PLAN APPROVED BY: ER DRAWN BY: RG DATE: 3-25-2008 JOB# 87474 DWG. NO. : FA -03 A B 0 H J K L M N 1 2 3 4 5 6 7 8 9 10 I UP DOWN TO 2ND FL. 825 SQFT 2 BEDROOM 1 BATH LIVING ROOM DINING BEDROOM DOWN TO 2ND FL BEDROOM 00 00 KITCHEN A 01:069—LA 01:075 01:052 01:053 B FROM ATTIC DINING LIVING ROOM r OWILTO 2ND FL KITCHEN 0 0 825 SIFT 2 BEDROOM 1 BATH DOWN TO 2ND FL 313 CLOSET 2ND FL DOWN TO BATH ROOM 15 d 1 FROM ATTIC I � N 01:044 R AB STORAGE A L BATH ROOM CLOSET AB BEDROOM FROM ATTIC BEDROOM BEDROOM DOWN TO 2ND FL. CLOSET 625 SOFT 1 BEDROOM 1 BATH A,B LIVING ROOM FROM ATTIC A,B BATH ROOM J v STORAGE J r 01:021 R 01:051 310 00 00 KITCHEN 625 SIFT 1 BEDROOM 1 BATH LIVING ROOM DOWN TO 2ND FL 00 o0 KITCHEN DN KITCHEN 0 0 00 DOWN TO 2ND FL. 15cd 311 01:041 R BATHROOM) ac STORAGE AB ROM- I�CEATTIC LMNG ROOM 425 SIFT STUDIO 1 BATH BEDROOM CATH ROOM 309 BEDROOM 00 00 DOWN TO 2ND FL LMNG ROOM 425 SIFT STUDIO 1 BATH BEDROOM FROM ATTIC A,B 01:018 A,B CLOSET 308 307 0 0 00 DOWN TO 2ND FL STORAGE BAIN ROOM BEDROOM FROI8gLc: ATTIC A,B STORAGE A 1 425 SIFT STUDIO 1 BATH LIVING ROOM (BATH ROOM o 01:036 0® R 01:015 306 DOWN TO 2ND FL. 00 00 KITCHEN 425 SOFT STUDIO 1 BATH LMNG ROOM BEDROOM DOWN TO 2ND FL 00 00 KITCHEN R 01:049 BATH ROOM) C STORAGE AB -ROM- ATTIC I C WING ROOM 425 SIFT STUDIO BEDROOM 1 BATH BATH ROOM STORAGE 0; CLOSET AB DOWN TO 2ND FL BEDROOM 305 01:033 R AB FROM ATTIC Cws FROM 01:012 304 KITCHEN 00 00 LIVING ROOM 625 SIFT 1 BEDROOM 1 BATH 3RD FLOOR - BLDG C 1/8"= 1 1.011 KITCHEN 00 00 A,B A STORAGE O o BATH ROOM BEDROOM DOWN TO 2ND FL BEDROOM A,B CLOSET 0 BATH ROOM STORAGE A,B A 01:009 R 303 FROM ATTIC CLOSET 302 825 SIFT 2 BEDROOM 1 BATH 0 0 00 KITCHEN LMNG ROOM DINING 1 sed 01:048 01:074 r40 01:030 DOWN TO 2ND FL LIVING ROOM STORAGE BATH ROOM A AB CLOSET AB 625 SIFT 1 BEDROOM 1 BATH FROM ATTIC BEDROOM BATH ROOM C) CLOSET 2ND FL. DOWN TO BEDROOM r,► ii v 4' ROM1 DOT N TO ATTIC 2ND FL KITCHEN 00 0o CLOSET FROM ATTIC BEDROOM LMNG ROOM 825 SOFT 2 BEDROOM 1 BATH I � I AS -BUILT 9-17-08 z 0 ccw ISSUED FOR APPROVAL O z w 0 cS z Lu z 0 Lu L� ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. C 4722 SOUTH CENTER BLVD. TUKWILA WA, 98188 3RD FLOOR - FIRE ALARM PLAN APPROVED BY: ER DRAWN BY: RG DATE: 3-25-2008 JOB# 87474 DWG. NO.: FA -04 H J K L M 1 2 3 4 5 6 7 8 9 10 B FSE AUX CKT. H If -II II 11 II II II II II II 01:008 A,B I I I I I I I I 01:007 JV - A,B L I I I I I I I I I I I I u A,B I II I II I II 1L -- J L A,B 01:006 tOxtO° I I EOL I I II r A,B II II II Il 0 (Al H ,BI i FROM FACP SMOKE FACP CKT.#1,2,3 AND FSE CKT! # 1 A,4B 9B IF __A_ co-A,B A,B-� FSE CKT.#2 A,3B� A,2B 01:005 A,3B-424 I I H H A,B I I I I I I I I I I 2B A,4BL A,B it I I I I I I I I I I IL F— I9 A,B U EOL_e:1-431_0 %It FSE AUX CKT. FSE CKT. #1 FSE AUX CKT. ATTIC - BLDG. C 1/8"=1I-0" CIRCUIT DISCRIPTIONS: CKT.#1 - ROOM NOTIFICATION WEST. CKT.#2 - ROOM NOTIFICATION EAST. CKT.#3 - OUTSIDE BELL & STROBE. CKT.#4 - TRIGGER FIRE SIGNAL EXPANDER (FSE). FSE CKT.#1 - HALLWAY NOTIFICATION. FSE CKT.#2 - HALLWAY NOTIFICATION FSE AUX. CKT. - DOOR HOLDERS. NOTE: DASHED LINE INDICATES WALL BELOW ATTIC. N AS -BUILT 9-17-08 z 0 ISSUED FOR APPROVAL 0 v z LU z 0 W ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. C 4722 SOUTH CENTER BLVD. TUKWILA WA, 98188 Cc ac w c LL ATTIC - FIRE ALARM PLAN APPROVED BY: ER DRAWN BY: RG DATE: 3-25-2008 JOB# 87474 DWG. NO. : FA -05 1 2 EOL EOL 01:008 01:007 EOL 01:006 CD EOL 01:005 -#16/2 #16/2 & #14/2 #16/2 & #14/4 ATTIC #16/2 & #14/4 #16/2 & #14/4 #16/2 & #14/4 0-#16/2 & #14/4 #14/4 #14/2 r #16/2 #14/4 #16/2&#14/4 -00 #16/2 & #14/4 #16/2 3 .015ma 4 3RD FLOOR #14/2 10- #14/2 EOL 15cd 15cd .060ma .074ma 01:024 .027ma .027ma 01:069 01:053 10- #14/2 #14/4 01:021 .027ma 01:052 01:018 .027ma #16/2 & #14/2- #16/2 & #14/4 01:015 01:012 CD .027ma .027ma 01:051 #16/2 #16/2 & #14/4 rf-r#16/2 & #14/4 01:009 .027ma .027ma #16/2 #16/2 & #14/4 #14/2 #16/2 & #14/4 #16/2 V- #16/2 & #14/4 #14/2 #16/2 & #14/4 #16/2 & #14/4 #16/2 & #14/4 #16/2 & #14/2 01:027 .027ma .027ma 01:050 #16/2 & #14/4 #16/2 01:030 .027ma CD 01:033 .027ma 01:049 #16/2 01:036 .027ma 01:038 .027ma 01:048 CD #16/2 01:041 .027ma CD #14/2 -V #14/2 -V 01:044 .027ma .027ma #16/2 & #14/4 - #16/2 & #14/4 -m #16/2 & #14/4 - #16/2 & #14/4 -V #16/2 & #14/4 -V #16/2 & #14/2 - 01:068 15cd .074ma l I T .015ma #14/2 -V #14/2 -V 5 .015ma 2ND FLOOR 15cd 15cd .060ma .074ma V--#16/2 01:025 .027ma .027ma V--#14/2 Q-#14/4 01:022 .027ma #16/2 01:055 V 01:054 Krr- #16/2 & #14/2 01:019 CD .027ma #16/2 #16/2 & #14/4 6 I 01:016 .027ma #16/2 & #14/4 01:013 CD .027ma 01:056 01:010 .027ma .027ma #16/2 #16/2 & #14/4 #16/2 & #14/4 6 #16/2 & #14/4 #16/2 & #14/4 -10 01:028 .027ma .027ma 01:057 01:031 .027ma #16/2 b #16/2 & #14/4 -ID #16/2 & #14/4 -up, 01:034 01:037 .027ma .027ma #16/2 0®8 CD 01:039 .027ma 01:059 #16/2 & #14/4 01:042 .027ma #16/2 6 01:045 .027ma .027ma 01:060 #16/2 & #14/4 - #16/2 & #14/2 15cd .074ma #14/2- #14/2 DH .015ma 7 15cd 15cd OH 1 EOL ® pH .015ma .060ma .074ma 8 1ST FLOOR 01:026 EOL 01:023 .027ma .027ma 01:020 CD .027ma .027ma 01:067 01:066 01:017 0 ® ®4 .027ma 000 .027ma 01:065 #16/2 #16/2 01:011 .027ma .027ma 01:004 01:003 01:002 01:001 WEST 9 10 L. REMOTE ANNUNCIATOR FACP #16/2 TO CENTRAL PHONE LINE #1 STATION PHONE LINE #2 120 VAC S (DEDICATED CKT.) MIRCOM FX -350 -126 -DR DUAL LIE DIALER #16/2 SLC 01:029 01:032 01:035 .027ma .027ma .027ma .027ma 01:064 01:040 01:043 .027ma .027ma 01:063 01:062 #16/2 NAC -1 #16/2 NAC -2 NAC -3 #16/2 3® i1:0<1 P .092ma P .074ma #14/4 #14/4 w-- #16/2 EOL 01:046 .027ma 01:061 #16/2 #16/2 .027ma EOL .074ma DH .015ma WP-75cd BELL EOL .138ma P ED .040ma NAC -4 FIRE ALARM SIGNAL EXPANDER BPS -6 INPUT #14/2 NAC -1 1E7. ,).. BATTERY 12V-12AH BA11 tf{Y 12V-12AH #14/2 SPARE SPARE l RISER DIAGRAM #14/2 NAC -2 NAC -3 NAC -4 #14/2 AUX BATTERY BATTERY 12V-7AH 12V-7AH 2 120 VAC (DEDICATED CKT.) EAST CIRCUIT DISCRIPTIONS: CKT.#1 - ROOM NOTIFICATION WEST. CKT.#2 - ROOM NOTIFICATION EAST. CKT.#3 - OUTSIDE BELL & STROBE. CKT.#4 - TRIGGER FIRE SIGNAL EXPANDER (FSE). FSE CKT.#1 - HALLWAY NOTIFICATION. FSE CKT.#2 - HALLWAY NOTIFICATION FSE AUX. CKT. - DOOR HOLDERS. #18/4 - AS -BUILT 9-17-08 z 0 wcr ISSUED FOR APPROVAL 0 z w 0 w 0 U z W Z 0 W ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. C 4722 SOUTH CENTER BLVD. TUKWILA WA, 98188 BUILDING RISER DIAGRAM APPROVED BY : ER DRAWN BY: RG DATE: 3-25-2008 JOB# 87474 DWG. NO.: FA -06 H 1 2 3 4 5 6 7 8 9 10 FIRE ALARM WIRE LEGEND DESIG. DESCRIPTION A 16/2 FPLR INITIATING CIRCUIT WIRING B 14/2 FPLR INDICATING CIRCUIT WIRING C 18/4 FPLR ANNUNCIATOR CIRCUIT WIRING D 14/2 FPLP DUCT DETECTOR OR DOOR HOLDER POWER WIRING E AWG-16-THHW FOR DIRECT BURY/WET LOCATION 0 Without Comments As Noted In Red Per TJ Attached Letter X41 J K L M !nese pans have been reviewed by The Thi The Tiikvilia 5.re Preventionr:•ure:~1F :r.<U!.:'Orrn ?ice with cure/cal g standards. 1 to errors and :JrnisSiens t Ills . _ ,L. i^ ._ V, _ICtiCnS of •aLrop st,^ u , ., „Li .--:-.,...s. i-, onsibta ty for the Ad.(2!M '.. these drawings attery this . ... :iCe^:nil-willrequirea res#ub .a1 r :r sir .:. s for sub.=,.pquentapproval Finale an -;, to field tested inspection by The Tukwila Fire :Pr`uealian Bureau_ Because of increased demand our inspectors` schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4407 or email aeins e-- eg@ci.t ila,wa.us (, schedule your inspections a minimum of 48 hours- in advance of the date you want an inspection. KEY LEGENDAND D C® POE T LIST DESCRIPTION MY Y PART # MANUFACTOR MOUNTING SPEC FIRE ALARM CONTROL PANEL 1 FX -350 -DDR MIRCOM WALL TOP @ 66' ( FACP ( IMO FIRE SIGNAL EXPANDER 1 BPS -6 MIRCOM WALL TOP ©66' I FSE i ANNUNCIATOR 1 RAM-300LCDR MIRCOM WALL TOP @ 66' ( ANN ( TRANSMITTER FIELD VERIFY IRAN l SUBSCRIBER TERMINAL UNIT FIELD VERIFY ® HORN WALL @ 80'-96' PCI MINI -HORN 50 MH -25W MIRCOM WALL @ 80'-96' CO BELL 1 MB -G10 -24R WHEELOCK OUTSIDE WALL @ 10' X STROBE 4 ZRS-MCW-FR WHEELOCK WALL @ 80'-96' WEATHER PROOF STROBE 1 RSSP-2475-FR WHEELOCK WALL @ 80'-96' WP ) IBJ HORN -STROBE 7 ZNS-MCW-FR WHEELOCK WALL @ 80--96' H CEILING MOUNTED HORN STROBE CEILING CEIUNG MOUNTED STROBE CEIUNG C CHIME FIELD VERIFY O SPEAKER WALL @ 90' Q JUNCTION BOX FIELD VERIFY DOOR HOLDER 6 DH24120SPC MIRCOM FIELD VERIFY m DOOR STRIKE FIELD VERIFY m F MANUAL PULL STATION 7 MS -701 DU MIRCOM WALL @ 48' ® AB SMOKE DETECTOR ABOVE CEILING ABOVE CEILING OR IN DUCT SMOKE DETECTOR 19 MIX 3100 MIRCOM CEILING - 3' FROM AIR DEFUSER ® BL SMOKE DETECTOR BELOW FLOOR BELOW FLOOR ® 194° FIXED TEMP HEAT DETECTOR 5 MIX -3300 MIRCOM CEILING (DR 194° RATE OF RISE HEAT DETECTOR 38 MIX -3300 MIRCOM CEILING ®R 135° RATE OF RISE HEAT DETECTOR CEILING 194°® 194° FIXED TEMP HEAT DETECTOR CEILING LINE TYPE HEAT DETECTOR FIELD VERIFY WF WATERFLOW SWITCH RISER PIPE PS PRESSURE SWITCH RISER PIPE TS TAMPER SWITCH GATE VALVE JB JUNCTION BOX ALONGSIDE DEVICE FIELD VERIFY M MONITOR MODULE FIELD VERIFY R ADDRESSABLE RELAY FIELD VERIFY NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. TUKWILA FIRE DEPARTMENZ Please call: 575.4407 and give this job No. and exact address for shut. down or restoration approval; gariltax447- `37171 FILE COPY General Notes NPPA 72-2002 Edition n 1 Sec 5,63.1..heat-cenging fire defectors shall be located on the ■' ceiling not less than lOOnn (4 in.) Iron the sidewall or on the sidewolls bdween /OOnn and 300nn (4in, and 12in) from the ceiling. See figure P.5.63.1 A-Sec.5.7.5.2.1 ...smoke ddedore shall be located on the ceiling not less than lOOnn (4 in.) from a sidewall to the near edge or, if on a sidewall, between /O0nn and 300rrn (4in and l2/n) dawn from the ceiling to the lop of the defector, See figure F5,732,1 /f\3 -Sec A.5.7.4.1Defectors should not be located in a direct airflow or , ■ , loser than In (3 fl.) from an air supply diffuser or rdurn air opening. Supply or return sources larger than those cor•Irlor>'y found in residential andalcommercial sr, l a ' est bGshrxrd can c n r uire greater e4 clearance to spoke detectors. Sinllady, spoke detectors should be located farther away Iron high velocity air supplies. ^4 -sec. 5.12.4 The operable part of each manual fire darn box hall be ■ , not less thanlin (34 ft.) and not none than 137n (4 %Z fI) above floor level. See figure F.5.12.4 ^5 -Sec. 7.5.4 Wall nounled appliances shall be nounled such that the / • \ entire lens is not less than Zn (80 in) and not greater than 2.4n (96 in.) above the finished floor, See figure P'.75.4 6 Sec. 4.4.1.41 Dedicated d bran ch circuit. uit. / dedicated icofe d biarh circuit of one of the followingshall eupply pr/nary power: (1) Connercial light and power. (2) An engine -driven generator or equivalent in accordance with 4.4.1.92, where a person specifics/ly trained in ifs operdion is on duty at al/ tires (3) An engine -driven generator or equivaled arranged for cogeneration with corrnercial light and power in accordance with 4.4,1.9.2, where a person specifically trained in its operation is on duty al all tines, Ceiling 100 mm (4 in.) Acceptable here Note: Measurements shown are to the closest edge of the detector. 100 mm (4 in.) m'nimum Never here Top of detector acceptable here ,�,7, ,2,1 300 mm (12 in.) maximum idewafl MAP OF LOCATION !PARK PLACE BY THE WOODS 87474 3'J FX-350-126DR .ELECTRICAL ROOM FX -350 CTRL Panel Addrsbl SLC Devices RAM-300LCDR 0000:: 0 000:: 0.000 fl 000: Notification Appl Circuit Notification Appl Circuit o.000 U 000 0.648: #14 Solid 4 7.20% 0 702 : #14 Solid 8.67%...; Notification Appl Circuit 0624 #14 Solid Notification Appl Circuit 0075: 0 150 #16 Solid 10 '7.71°l0: 0;06% 1 # of NAC's Used :0.000< 0.000.;: BPS -6 ation k :BPS:6 ELECTRICAL ROOM Int, N ',PARK PLACE BY THE WOODS l 87474 4/2/2008 t 1 rfr.!'1 �11 5495(1) Circuit 1 0.-120 0:000 #14 Solid 560 5495(1) Circuit 2 0;000 0;344 #18 Solid 150 5495(1) Circuit 3 0.000 0.000 #14 Solid :2. 5495(1) Circuit 4 0.000. #14 Solid 1.66% 3.23°.6 0:00% 5495(1) Aux Power Out 0:000 0.000 #14 Solid 2 52...', 0.454 0.00% >I yG�iret{Fi�zlAs� . fl 7't xx „n, „ nr tzi Itp 11.ryAtil 14tiee E„,# Wire resistances are based upon an ambient tempera ure of 72 degrees F. Because of the minimal difference between solid and stranded wi a no differential was made. Et�t3 Command Shortcuts Configure Circuits #1. Note: A value msut be entered if you have selected any NAG circuits as AUX Power. Project Information Print Page Project Information Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4/2/2008 Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4/2/2008 6 DH24120SPC Unused Unused Unused :tom Totals 0 120 NotificationAppl Circuit 26 MH -25W bba Unused Unused Unused Totals 0;702 .:>I Notification Appl Circuit 3 ZRS-MCW-FR 15cd 6 ZNS-MCW-FR 15cd , , r:frr;r Unused ffittitid Unused Totals 0.000 0.624 : Notification Appl Circuit 1 BPS -602 flEt75:'/s. Unused Unused Unused Totals >0 075 0.150 1 1 1 1 MB -G10 -24R RSSP-2475-FR ZRS-MCW-FW 30cd ZNS-MCW-FW 15cd Totals /MIT IT I.k1j:;> 0.000 0.344 'Mid Tukwila Fire I�,3Yy 0 cc ISSUED FOR APPROVAL 0 z cr 0 C) z Lu 0z ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. C d i^1] co /yam co LLT w co I—• O) z U 'S Fig CA � c0 O N. d' LL RISER/BOM - FIRE ALARM PLAN APPROVED BY: ER DRAWN BY: RG DATE: 3-25-2008 JOB# 87474 DWG. NO.: FA -01 L11i� lin 14-- Operable IMO Part lt 1.1 (a) minimum 1y 1.37 Mt) maximum m t) m FI"1 X7'4 Finished floor 4—Sidewall .////////////// MAP OF LOCATION !PARK PLACE BY THE WOODS 87474 3'J FX-350-126DR .ELECTRICAL ROOM FX -350 CTRL Panel Addrsbl SLC Devices RAM-300LCDR 0000:: 0 000:: 0.000 fl 000: Notification Appl Circuit Notification Appl Circuit o.000 U 000 0.648: #14 Solid 4 7.20% 0 702 : #14 Solid 8.67%...; Notification Appl Circuit 0624 #14 Solid Notification Appl Circuit 0075: 0 150 #16 Solid 10 '7.71°l0: 0;06% 1 # of NAC's Used :0.000< 0.000.;: BPS -6 ation k :BPS:6 ELECTRICAL ROOM Int, N ',PARK PLACE BY THE WOODS l 87474 4/2/2008 t 1 rfr.!'1 �11 5495(1) Circuit 1 0.-120 0:000 #14 Solid 560 5495(1) Circuit 2 0;000 0;344 #18 Solid 150 5495(1) Circuit 3 0.000 0.000 #14 Solid :2. 5495(1) Circuit 4 0.000. #14 Solid 1.66% 3.23°.6 0:00% 5495(1) Aux Power Out 0:000 0.000 #14 Solid 2 52...', 0.454 0.00% >I yG�iret{Fi�zlAs� . fl 7't xx „n, „ nr tzi Itp 11.ryAtil 14tiee E„,# Wire resistances are based upon an ambient tempera ure of 72 degrees F. Because of the minimal difference between solid and stranded wi a no differential was made. Et�t3 Command Shortcuts Configure Circuits #1. Note: A value msut be entered if you have selected any NAG circuits as AUX Power. Project Information Print Page Project Information Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4/2/2008 Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4/2/2008 6 DH24120SPC Unused Unused Unused :tom Totals 0 120 NotificationAppl Circuit 26 MH -25W bba Unused Unused Unused Totals 0;702 .:>I Notification Appl Circuit 3 ZRS-MCW-FR 15cd 6 ZNS-MCW-FR 15cd , , r:frr;r Unused ffittitid Unused Totals 0.000 0.624 : Notification Appl Circuit 1 BPS -602 flEt75:'/s. Unused Unused Unused Totals >0 075 0.150 1 1 1 1 MB -G10 -24R RSSP-2475-FR ZRS-MCW-FW 30cd ZNS-MCW-FW 15cd Totals /MIT IT I.k1j:;> 0.000 0.344 'Mid Tukwila Fire I�,3Yy 0 cc ISSUED FOR APPROVAL 0 z cr 0 C) z Lu 0z ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. C d i^1] co /yam co LLT w co I—• O) z U 'S Fig CA � c0 O N. d' LL RISER/BOM - FIRE ALARM PLAN APPROVED BY: ER DRAWN BY: RG DATE: 3-25-2008 JOB# 87474 DWG. NO.: FA -01 A B C 0 E H J K L M N 1 2 3 4 UP 6 825 SIFT 2 BEDROOM 1 BATH LIVING ROOM BEDROOM EOL CLOSET 00 0 O DINING KITCHEN Yl 01:067 01:066 112 BEDROOM STORAGE FROM 2ND FL CLOSET O CC - BATH ROOM C �l BEDROOM TO ATTIC CLOSET 625 SIFT 1 BEDROOM 1 BATH LMNG ROOM BATH ROOM JD STORAGE 15cd FROM 2ND FL FROM 2ND FL B DINING 7 LIVING ROOM KITCHEN 00 00 825 SQFT 2 BEDROOM 1 BATH CLOSET 111 STORAGE --011111F-1- DN BATH ROOM a BEDROOM BEDROOM C 8 9 10 EOL 15cd TO ATTI KITCHEN 0 00 110 0 0o KITCHEN `.t 625 SIFT 1 BEDROOM 1 BATH 0 0 CO LIVING ROOM BEDROOM FROM 2ND FL KITCHEN 108 STORAGE CLOSET BATH ROOM NDRY ROOM 1:60)) � , 1 1:004 WING ROOM 425 SIFT STUDIO 1 BATH STORAGE CLOSET CLOSET BEDROOM BEDROOM LIVING ROOM 425 SIFT STUDIO 1 BATH HEATED WEATHER PROOF ENCLOSURE. 30cd A-41 01:002 ELECTRICAL ROOM TO FACP & FSE CKT.#2 2C C BEDROOM CLOSET 425 SIFT STUDIO 1 BATH LIVING ROOM 425 SIFT STUDIO 1 BATH LIVING ROOM BEDROOM CLOSET BATH ROOM STORAGE IA CLOSET I\ TO ATTIC BEDROOM 105 01:035 R AB 01:063 KITCHEN 00 00 FROM 2ND FL. LMNG ROOM 625 SOFT 1 BEDROOM 1 BATH 75cd 1_1 WP .r" C • EOL 1 ST FLOOR - BLDG. C 1/8"=1'_0" KITCHEN 00 0 0 103 BEDROOM TO ATTIC 0 CLOSET BATH ROOM BEDROOM STORAGE 01:032 TO ATTIC LIVING ROOM 625 SIFT 1 BEDROOM 1 BATH N STORAGE A BATH ROOM CLOSET FROM 2ND FL BEDROOM I 102 FROM 2ND FL CLOSET 825 SIFT 2 BEDROOM 1 BATH 00 00 LIVING ROOM KITCHEN DINING 15cd BATH ROOM a 0 01:062 FROM 2ND FL UP CLOSET TO ATTIC 101 BEDROOM FROM 2NDDFL OM 2ND FL KITCHEN 00 00 CLOSET FROM 2ND FL BEDROOM UP TO B ATTIC DINING LIVING ROOM 825 SIFT 2 BEDROOM 1 BATH z 0 iL ISSUED FOR APPROVAL 0 z 0 U Z w z 0 LTJ ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. C 4708 SOUTH CENTER BLVD. TUKWILA WA, 98188 CC w Is LL 1ST FLOOR - FIRE ALARM PLAN APPROVED BY: ER DRAWN BY: RG DATE: 3-25-2008 JOB# 87474 DWG. NO.: FA -02 J 2 3 4 5 6 7 8 9 10 UP T J FROM 3RD FL 01 825 SIFT 2 BEDROOM 1 BATH LIVING ROOM BEDROOM DOWN TO 1ST FL BEDROOM A,B CLOSET o0 0 0 DINING KITCHEN 0 FROM 3RD FL. DINING LIVING ROOM O N 1ST FL KITCHEN oQ 825 SIFT 2 BEDROOM 1 BATH 01:055 %212 (; DOWN TO`v gThed FROM 1ST FL • Q + O 3Rl FII A,B A (1501:025 FROM 3RD FL CLOSET STORAGE BATH ROOM BEDROOM DOWN TO 1ST FL AB CLOSET BATH ROOM 625 SIFT 1 BEDROOM 1 BATH A,B LIVING ROOM FROM 3RD FL 01:022 R STORAGE -� I I DN 213 CLOSET 01:045 •+ R AB DOWN TO 1ST FL STORAGE A BATH ROOM CLOSET AB BEDROOM FROM 3RD FL BEDROOM 210) 0® Jj15cd BATH ROOM (BATH ROOM 0 \� FROM FRIM 3RD: Ft 3RD. FL KITCHEN o 00 LIVING ROOM 425 SOFT STUDIO 1 BATH STORAGE CLOSET BEDROOM 209 0 0 0o KITCHEN 625 SQFT 1 BEDROOM 1 BATH LIVING ROOM DOWN TO 1ST FL. 00 0 KITCHEN STORAGE CLOSET 00 0 0 BEDROOM LIVING ROOM 425 SIFT STUDIO 1 BATH t 0 00 00 A,B 01:019 208 Go U A,B BEDROOM FROM 3RD FL CLOSET STORAGE BEDROOM CLOSET STORAGE 425 SIFT STUDIO 1 BATH LIVING ROOM OQ 00 0 425 SIFT STUDIO 1 BATH LIVING ROOM BEDROOM 00 c0 KITCHEN DOWN TO 1ST F CLOSET 01:013 R STORAGE ;B 204 204 01:U58 LIVING ROOM 425 SIFT STUDIO STORAGE CLOSET BEDROOM 1 BATH BEDROOM KITCHEN KITCHEN 1 0 0 Q O ■ FROM= 3 D L BATH ROOM BEDROOM DOWN TO 1ST FL 0 CLOSET BATH ROOM BEDROOM STORAGE 203 01:031 DOWN TO 1ST. FL LIVING ROOM LIVING ROOM �I AB STORAGE •1 BATH ROOM C CLOSET AB 625 SIFT 1 BEDROOM 625 SIFT 1 BEDROOM 1 BATH 1 BATH 2ND FLOOR - BLDG. C 1/811=1I-0" FROM 3RD FL BEDROOM 202 FROM 3RD FL CLOSET 825 SQFT 2 BEDROOM 1 BATH Q0 00 LIVING ROOM KITCHEN DINING lS? 15cd 01:059 UP FROM IC DOWN TO 1ST FL CLOSET DOWN TO 1ST FL BEDROOM CLOSET FROMI D•WN TO 3RD FL KITCHEN 00 0 o FROM 3RD FL BEDROOM 1ST FL LIVING ROOM 825 SIFT 2 BEDROOM 1 BATH M N z 0 ISSUED FOR APPROVAL d z Kx 0 W z o� 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. C 4708 SOUTH CENTER BLVD. TUKWILA WA, 98188 CC w CC LLLL 0 CC LLI CCU- 0 0 —J LL CI N APPROVED BY: ER DRAWN BY: RG DATE: 3-25-2008 JOB# 87474 DWG. NO.: FA -03 A B C D 2 3 4 6 7 8 9 10 GP 1 DOWN TO 2ND FL B H 825 SQFT 2 BEDROOM 1 BATH LMNG ROOM DINING BEDROOM DOWN TO 2ND FL CLOSET 00 OO KITCHEN 2 01:069-A F 01:053 01:052 FROM ATTIC DINING WING ROOM Ola 2ND FL KITCHEN DOWN TO 2ND FL • 313 BEDROOM CLOSET 312 00 00 825 SIFT 2 BEDROOM 1 BATH CLOSET 2ND FL DOWN TO 01:044 [ 1 1 R AB STORAGE A STORAGE a a BATH ROOM O BEDROOM DOWN TO 2ND FL A,B CLOSET BATH ROOM 0 625 SIFT 1 BEDROOM 1 BATH STORAGE WINO ROOM FROM ATTIC A,B O 01:021 R 15id FROM 0 ATTIC i BATH ROOM CLOSET BEDROOM FROM ATTIC BEDROOM 01:051 310 00 00 KITCHEN 625 SIFT 1 BEDROOM 1 BATH LMNG ROOM DOWN TO 2ND FL 00 o0 KITCHEN A,B 01:018 (308 WING ROOM 425 SIFT STUDIO 1 BATH CLOSET BEDROOM STORAGE CLOSET BEDROOM 0 CO LIVING ROOM 425 SQFT STUDIO 1 BATH UI A,B BEDROOM FROM ATTIC CLOSET STORAGE BATH R3OM BEDROOM CLOSET STORAGE 425 SIFT STUDIO 1 BATH WING ROOM 01:015 00 Co KITCHEN DOWN TO ND FL 01:050 3 305 00 Co 01:036 STORAGE CLOSET LIVING ROOM BEDROOM 425 SIFT STUDIO 1 BATH 2ND FL DOWN TO BEDROOM KITCHEN LMNG ROOM 425 SIFT STUDIO 1 BATH BEDROOM LIVING ROOM 0 O OO CLOSET STORAGE L M N BEDROOM DOWN TO 2ND FL BEDROOM A,B CLOSET 0 a JBATH ROOM A,B 01:009 a I STORAGE FROM ATTIC CLOSET 302 825 SIFT 2 BEDROOM 1 BATH 00 oO KITCHEN WING ROOM DINING 01:049 303 STORAGE a fBBAATHH ROOM BATH ROOM 00 00 625 SQFT 1 BEDROOM 1 BATH 3RD FLOOR - BLDG. C 1/8"_11-O" R CLOSET A AB CLOSET Lai �FROMI DOT N TO ATTIC 2ND FL KITCHEN 00 Co AB FROM ATTIC 2ND FL DOWN TO BEDROOM BEDROOM LIVING ROOM 825 SIFT 2 BEDROOM 1 BATH 2 0 0 C) z z 0 ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. C 4708 SOUTH CENTER BLVD. TUKWILA WA, 98188 0 LLI CC w LL CC CC 0 0 CC C) APPROVED BY: ER DRAWN BY: RG DATE: 3-25-2008 JOB# 87474 DWG. NO.: FA -04 1 2 3 4 5 6 7 8 9 10 I I I 11 I I I 1 11 I I 1 1 II I A,B II 1 1 11 LI- =—_- u------� 111 1111 1 1 il II 111 II II 1 JL_ _ _lL 01:008 I I I I I I I I II I I Ii 01:007 7II-====== I1 I- A,B I I I I 11 1 I I I I I A,B I I) I 11 I II 1L__� 01:006 A,B J 11 11 11 I 1 1 J� I ICKT. #3 J L - O FSE CKTr#a_ A,3B� ®01:006 E I1 A,3B-41 - U - I II J II I I I A'B I A,B FROM FACP SMOKE FACP CKT.#1,2,3 AND FSE CKT.# 1 A,4B 28 A,2B b CKT. #2 A,B I 1 I I I I I I A,4Bp A,B I 1 I I 11 11 I I I I I I A,B CKT. #3 FSE CKT. #1 II I I cr-A,B II FSE CKT. #1 ATTIC - BLDG. C 1 /8" =1 '-0" N CIRCUIT DISCRIPTIONS: CKT.#1 - ROOM NOTIFICATION WEST. CKT.#2 - ROOM NOTIFICATION EAST. CKT.#3 - CORRIDOOR NOTIFICATION. CKT.#4 - TRIGGER FIRE SIGNAL EXPANDER (FSE). FSE CKT.#1 - DOOR HOLDERS NORTH AND SOUTH. FSE CKT.#2 - OUTDOOR BELL & STROBE & EAST CORRIDOR. NOTE: DASHED LINE INDICATES WALL BELOW ATTIC. z 0 rn ISSUED FOR APPROVAL z 0 v z W z 0 W W !L 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. C ATTIC - FIRE ALARM PLAN APPROVED BY : ER DRAWN BY: RG DATE: 3-25-2008 JOB# 87474 DWG. NO.: FA -05 2 1 2 3 4 6 7 8 9 10 N 01:008 01:007 01 006 01:005 - #16/2 #16/2 & #14/2 #16/2 & #14/4 ATTIC #16/2 & #14/4 #16/2 & #14/4 #16/2 & #14/4 0-#16/2 & #14/4 #14/4 c -#14/2 -#14/2 .015ma 3RD FLOOR 15cd cd� .060ma .074ma - #14/2 01:024 .027ma .027ma 01:069 01:053 #16/2 01:021 .027ma 01:052 01:018 CD .027ma z3--#14/2 #16/2 & #14/2 01:015 CD .027ma 01:012 .027ma 01:051 #16/2 01:009 .027ma .027ma #14/2 #16/2 - #14/4 #16/2 & #14/4 - P #16/2 & #14/4 #16/2 -1:1 #16/2 & #14/4 c7- #16/2 & #14/4 -#16/2 & #14/4 -#16/2 & #14/4 #16/2 #16/2 & #14/4 P #14/4 #16/2 & #14/4 #14/2 , P #16/2 r #16/2 & #14/4 #16/2 & #14/4 #16/2 & #14/4 #16/2 & #14/2 • 1 01:027 .027ma .027ma 01:050 #16/2&#14/4v #16/2 01:030 .027ma .027ma 01:049 01:033 #16/2 .027ma 01:036 CD 01:038 .027ma 01:048 #16/2 01:041 .027ma #14/4 -10 #14/2 01:044 .027ma .027ma 01:068 15cd .074ma #16/2 & #14/4 -w #16/2 & #14/4 - #16/2 & #14/4 - #16/2 & #14/4 - #16/2 & #14/4 v #16/2 & #14/2 -0 #14/4 #14/2 .015ma .015ma 2ND FLOOR 15cd 15cd 1)021 .060ma .074ma -#16/2 01:025 .027ma .027ma 01:054 01:022 .027ma #16/2 01:055 ® 01:019 CD .027ma #16/2 b 01:016 .027ma 01:013 CD .027ma 01:056 01:010 .027ma .027ma #16/2 #14/2 #14/2 0-#16/2 & #14/2 #16/2 & #14/4 0-#16/2 & #14/4 -#16/2 & #14/4 Q-#16/2 & #14/4 b #16/2 & #14/4 #16/2&#14/4- 01:028 .027ma .027ma 01:057 01:031 .027ma #16/2 #16/2 & #14/4 -0 #16/2 & #14/4 -v .027ma 01:058 01:034 CD1/4-D1 .027ma 01:037 #16/2 CD 01:039 .027ma 01:059 01:042 .027ma #16/2 6 CD 01:045 .027ma .027ma 01:060 #16/2 & #14/4 -0 #16/2 & #14/4 #16/2 & #14/2 -- v a .074ma #14/4 #14/2 .015ma 15cd 15cd m EOL .015ma .060ma .074ma 1ST FLOOR 01:026 EOL .027ma .027ma 01:023 01:020 01:017 CD 01:014 01:011 .027ma .027ma .027ma .027ma .027ma .027ma 01:067 01:066 o Q #16/2 01:065 #16/2 01:004 01:003 01:002 01:001 WEST REMOTE ANNUNCIATOR TO CENTRAL STATION RW • #18/4 PHONE LINE #1 PHONE LINE #2 120 VAC S (DEDICATED CKr.) #16/2 01:029 .027ma .027ma .027ma 01:064 01:032 © .027ma 01:035 .027ma 01:040 01:063 01:062 #16/2 30cd #16/2 #14/2 l #18/4 .092ma P #18/4 #16/2 15cd .074ma CD 0'1:043 .027ma t:7- #16/2 EOL 01:046 .027ma .027ma #16/2 #16/2 121 01:061 .074ma .015ma WP-75cd BELL FIRE ALARM SIGNAL EXPANDER BPS -6 INPUT #14/2 NAC -1 RISER DIAGRAM #18/4 NAC -2 NAC -3 NAC -4 BATTERY I BATTERY 12V-7AH 12V-7AH 120 VAC (DEDICATED CKE.) EAST #18/4 .138ma CIRCUIT DISCRIPTIONS: CKT.#1 - ROOM NOTIFICATION WEST. CKT.#2 - ROOM NOTIFICATION EAST. CKT.#3 - CORRIDOOR NOTIFICATION. CKT.#4 - TRIGGER FIRE SIGNAL EXPANDER (FSE). FSE CKT.#1 - DOOR HOLDERS NORTH AND SOUTH. FSE CKT.#2 - OUTDOOR BELL & STROBE & EAST CORRIDOR. EOL .040ma #18/4 - ( 2 0 C'u ISSUED FOR APPROVAL d z U Z w z0 LU ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. C 4708 SOUTH CENTER BLVD. TUKWILA WA, 98188 BUILDING RISER DIAGRAM APPROVED BY : ER DRAWN BY: RG DATE: 3-25-2008 JOB# 87474 DWG. NO.: FA -06 2