HomeMy WebLinkAboutPP - 4708 SOUTHCENTER BLVD BLDG G - THE BOULEVARD AT SOUTH STATION - PERMITS AND PLANS4708 SOUTHCENTER BLVD BLDG G ASSOCIATED PERMITS 08-F-144 , FIRE DEPARTMENT FIRE ALARM PLAN REVIEW COMMENTS Project Name: Park Place By The Woods Bldg. G 4708 Southcenter BI Permit No.: 08-F-144 Date: April 29, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • When the control panel is located inside a room, the door to the room shall have a sign with one -inch letters, which reads "Fire Alarm" or "Fire Alarm Control". • Install smoke detectors as shown in red on the plans within 5 ft. of the door opening for magnetic door holder operation. • Heat detectors installed in the dwelling units to be 135 degree rate of rise. • Heat detectors installed in the attic areas to be 194 degree fixed temp. • Dedicated fire alarm system circuit breakers shall be equipped with lockout devices. • If reset code is employed, reset code to be 1-2-3-4-5. • An electrical permit from the city of Tukwila Building Department permit center . • The Tukwila Fire Department has changed keybox manufacturers, from Supra to Knox. Install a fire department Knox Keybox. Contact the Tukwila Fire Prevention Office at 206-575-4407 for ordering information. ]MELS ELECTRICAL ROOM i I A B C D E F G H J K 1 2 3 4 5 6 7 8 9 10 Without Comments As Noted In Red Per The Attached Letter i nese plans have been reviewed by The Tukwila Fire Prevention Bureau for confor mv'i,ce with current city 4.ndards. Acceptance is wL hiect to errors and c nissions which do not autllorize violations of adopted -macros and orvincnces. The ret onsibi1,?iy for the qua c`y' of desion jn rests tottePy with the designer. .;tcns, deletions or revisions to these drawings atter ,k dat3 will void trs acceptance 9.nd will require a - ubmittal of revised drawings for subsequent approval. nal acceptance is subject to field test and inspection by -i Tukwila FirePrevention Bureau. Date: 17-A 91 -0g By: TUKWILA FIRE DEPARTMEN Please call: 575-440Z and give this job end exact address for shuti down or restoration approval; FIRE ALARM WIRE LEGEND DESIG. DESCRIPTION A 1612 FPLR INITIATING CIRCUIT WIRING B 14/2 FPLR INDICATING CIRCUIT WIRING C 18/4 FPLR ANNUNCIATOR CIRCUIT WIRING D 14/2 FPLP DUCT DETECTOR OR DOOR HOLDER POWER WIRING E AWG-16-THHW FOR DIRECT BURY/WET LOCATION KEY LEGEND AND COMPONENT LIST SYMBOL DESCRIPTION QTY PART # MANUFACTOR MOUNTING SPEC FIRE ALARM CONTROL PANEL 1 FX -350 -DDR MIRCOM WALL TOP @ 66' 1 FACP I FIRE SIGNAL EXPANDER 1 BPS -6 MIRCOM WALL TOP @ 66' FSE ¢8idewalt ANNUNCIATOR 1 RAM-300LCDR MIRCOM WALL TOP @ 66' ANN TRANSMITTER FIELD VERIFY I Tamil SUBSCRIBER TERMINAL UNIT FIELD VERIFY STU CO HORN WALL @ 80'-96' MINI -HORN 38 MH -25W MIRCOM WALL @80'-96' CD BELL 1 MB -G10 -24R WHEELOCK OUTSIDE WALL @ 10' X STROBE 1 ZRS-MCW-FR WHEELOCK WALL @ 80'-96' WP ) ( WEATHER PROOF STROBE 1 RSSP-2475-FR WHEELOCK WALL @ 80'-96' CO HORN -STROBE 7 ZNS-MCW-FR WHEELOCK WALL @ 80'-96' -C CEILING MOUNTED HORN/STROBE CEIUNG aCEILING MOUNTED STROBE CEIUNG c CHIME FIELD VERIFY ® SPEAKER WALL @ 90' 0 JUNCTION BOX FIELD VERIFY DOOR HOLDER 6 DH24120SPC MIRCOM FIELD VERIFY m DOOR STRIKE FIELD VERIFY m F MANUAL PULL STATION 7 MS -701 DU MIRCOM WALL @ 48' AB SMOKE DETECTOR ABOVE CEILING ABOVE CEILING OR IN DUCT ® SMOKE DETECTOR 15 MIX -3100 MIRCOM CEILING - 3' FROM AIR DEFUSER BL SMOKE DETECTOR BELOW FLOOR BELOW FLOOR ® 194° FIXED TEMP HEAT DETECTOR 4 MIX -3300 MIRCOM CEIUNG (DR 194° RATE OF RISE HEAT DETECTOR 27 MIX -3300 MIRCOM CEILING (DR 135° RATE OF RISE HEAT DETECTOR CEILING 1941:D 194° FIXED TEMP HEAT DETECTOR CEILING Q)--> LINE TYPE HEAT DETECTOR FIELD VERIFY WF WATERFLOW SWITCH RISER PIPE PS PRESSURE SWITCH RISER PIPE TS TAMPER SWITCH GATE VALVE JB JUNCTION BOX ALONGSIDE DEVICE FIELD VERIFY M MONITOR MODULE FIELD VERIFY R ADDRESSABLE RELAY FIELD VERIFY NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. Because of increased demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4407 or email fireinsprequest(@ci.tukwila.wa.us to schedule your inspections a minimum of 48 hours in 'advance of the date you want an inspection. FILE COPY General Notes NEPA 72-2002 Edition A-sec. „hecif--ening fire (le/cc/ore :;hall be located on the • ceiling not less Than leen (4 in) from The eidewall or on the sidewalls between lOOnn and 300m (4in and IZin) Iron the ceiling. See figure F.5,G3.1 A2 -sec. 51.52.1...enoke de/cc/ore dhall be localed on the ceiling not / ■ \ less Than leen (4 in,) iron a sidewall to the rear edge or, if on a eidewoll, between lOOnn and 3OOnn (4in and I2in) down Iron the ceiling to the lop of the defector. See figure F5.732./ 3 -see. A51.4-.1 Defectors Should not he located in a direct airflov or • doses than In (3 ft.) Iron an air Supply diffuser or return air opening Supply or rdurn sources larger than those connody found in residential and small commercial establishrerla can require greater clearance to spoke deledore.. Similarly, spoke detectors should be located farther away iron high velocity air supplies. 4 -5cc. 5.12.4 The operable part of each manual fire darn box shop be / • \ not less than I.ln (3%2 ft.) and not nore than 137n (4 4 ft.) above floor level. See figure i.5.1Z.4 n5 -Sec 7.5.4 Wall mounted appliances shill be no unted such that the / •■ \ entire lens is not fess than 2n (80 in) and not greater than 2.4n (9G in.) above the finished floor, 5ce figure F.7.5.4 6 / 1-5ec. 4.4.1.4.1 Dedicated brands circuit. A dedicated brarch circuit of • one of the following shall supply primary power: (I) Gonnercial light and power. (2) An ergine -driven generator or equivalent in accordance with 4.4./.92, where a pereon specifically trained in its operation is on duty at dl /ince. (3) An ergine -driven generator or equivalent arranged for cogen ration with commercial light and power in accordance with 4.4,1.92, where a pereon specifically trained in ifs operation is on duty at dl lilies Ceiling / / / / / / /f// )17 100 mm (41n.) Acceptable here Note: Measurements shown are to the closest edge of the detector. Never here Top of detector acceptable here /1% mm (4 in.) m'nimum 300 nun (12 in.) maximum e Sidewau MAP OF LOCATION PARK PLACE BY THE WOODS FX -350 CTRL Panel Addrsbl SLC Devices /T1• : 0.220 0.380:: 83i.: 0.018 0.040 0.000 0.000 0.000 0.000. 0.000 0.000.: 0.000 0.000: 0.000 0.000: RAM-300LCDR Other Other 0.(300: 0.000: 0.000 0.000 0.000: 0.000: Notification Appl Circuit 0.000' 0.486 #14 Solid 450 Notification Appl Circuit 0.000 0.486 #14 Solid 500 Notification Appl Circuit 0.000 0.444:: #14 Solid 500 5.40% 6 00% 548% Notification Appl Circuit 0.075: 0,150<' #16 Solid 10 zei "1 # of NAC's Used 0.000 0.000`:': i3v:��ar�1 ?sl;atr'�ti1 S iter(: Project Infom ati_n Command Shortcuts Configure Circuits Print Page Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4''212008 Unused #(30> E Unused Unused 0 Totals 0.000 0 486 Notification Appl Circuit Unused Unused Unused 6 ZNS-MCW-FR 15cd Totals 0.000 Notification Appl Circuit .............................. Unused Unused Unused OW I Totals 2r.... st............................ Notification Appl Circuit Unused Unused Unused Totals 0.075: 0.150- L 1 M I BPS -6 • N I 14/2/2008 ............... 5495(1) Circuit 1 0.00T- #14 Solid 560 5495(1) Circuit 2 0.000. 0:344 #18 Solid 150 5495(1) Circuit 3 O>000 #14 Solid 5495(1) Circuit 4 5495(1) Aux Power Out Its Q 0.000 0:000 0,000 0`000 < Si #14 Solid #14 Solid 0.454 1�ut 1xor �i>reci ;'. Aff 1 66% 3.23% 0.00% 0.00% 0;00% Wee resistances are based upm an ambient temperature of 72 degees F. Because of the mhimal dii%,rsice between solid and stranded wee no differential was made. Circuit Configuration Project Information Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4/2/2008 3s> ,i.ITent raw E; tj culr 6 DH24120SPC 11 Unused Unused Unused Totals 0.120 0.000 1 1 1 MB -G10 -24R RSSP-2475-FR ZRS-MCW-FW 30cd 1 ZNS-MCW-FW 15cd Totals ........................ ........................ 0.000 0.344 44 0 i 1°1 . 2008 Tukwila Fire ( ISSUED FOR APPROVAL d z C Ui z w 0 ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. G d CO co CC n— w c0 I— CJ) Z U S' i— O co '- 0 .t' RISER/BOM - FIRE ALARM PLAN APPROVED BY : ER DRAWN BY: RG DATE: 4-17-08 JOB# 87474 DWG. NO.: FA -01 ® tii•i� �@— Operable — 1593.1 part 1.1 (31i minimum 1.37 (4.l maximum m R) m ft) 5,12,..1- G,12,4Finished floor Finished ¢8idewalt //.//////////./7 MAP OF LOCATION PARK PLACE BY THE WOODS FX -350 CTRL Panel Addrsbl SLC Devices /T1• : 0.220 0.380:: 83i.: 0.018 0.040 0.000 0.000 0.000 0.000. 0.000 0.000.: 0.000 0.000: 0.000 0.000: RAM-300LCDR Other Other 0.(300: 0.000: 0.000 0.000 0.000: 0.000: Notification Appl Circuit 0.000' 0.486 #14 Solid 450 Notification Appl Circuit 0.000 0.486 #14 Solid 500 Notification Appl Circuit 0.000 0.444:: #14 Solid 500 5.40% 6 00% 548% Notification Appl Circuit 0.075: 0,150<' #16 Solid 10 zei "1 # of NAC's Used 0.000 0.000`:': i3v:��ar�1 ?sl;atr'�ti1 S iter(: Project Infom ati_n Command Shortcuts Configure Circuits Print Page Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4''212008 Unused #(30> E Unused Unused 0 Totals 0.000 0 486 Notification Appl Circuit Unused Unused Unused 6 ZNS-MCW-FR 15cd Totals 0.000 Notification Appl Circuit .............................. Unused Unused Unused OW I Totals 2r.... st............................ Notification Appl Circuit Unused Unused Unused Totals 0.075: 0.150- L 1 M I BPS -6 • N I 14/2/2008 ............... 5495(1) Circuit 1 0.00T- #14 Solid 560 5495(1) Circuit 2 0.000. 0:344 #18 Solid 150 5495(1) Circuit 3 O>000 #14 Solid 5495(1) Circuit 4 5495(1) Aux Power Out Its Q 0.000 0:000 0,000 0`000 < Si #14 Solid #14 Solid 0.454 1�ut 1xor �i>reci ;'. Aff 1 66% 3.23% 0.00% 0.00% 0;00% Wee resistances are based upm an ambient temperature of 72 degees F. Because of the mhimal dii%,rsice between solid and stranded wee no differential was made. Circuit Configuration Project Information Project Name: PARK PLACE BY THE WOODS Prepared By: NELS Project ID: 87474 Date: 4/2/2008 3s> ,i.ITent raw E; tj culr 6 DH24120SPC 11 Unused Unused Unused Totals 0.120 0.000 1 1 1 MB -G10 -24R RSSP-2475-FR ZRS-MCW-FW 30cd 1 ZNS-MCW-FW 15cd Totals ........................ ........................ 0.000 0.344 44 0 i 1°1 . 2008 Tukwila Fire ( ISSUED FOR APPROVAL d z C Ui z w 0 ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. G d CO co CC n— w c0 I— CJ) Z U S' i— O co '- 0 .t' RISER/BOM - FIRE ALARM PLAN APPROVED BY : ER DRAWN BY: RG DATE: 4-17-08 JOB# 87474 DWG. NO.: FA -01 1 2 3 4 5 6 7 8 9 10 825 SOFT 2 BEDROOM 1 BATH LIVING ROOM DINING FROM 2ND FL BEDROOM EOL CLOSET 00 00 KITCHEN CF+- \ o1:os 1 \ F 108 625 SQFT 1 BEDROOM 1 BATH ICING ROOM 01:050 II II 625 SQFT 1 BEDROOM 1 BATH WING ROOM TO ATTIC KITCHEN KITCHEN CD C 00 00n KITCHEN KITCHEN 01:049 • 15cd FROM EOL ill • 2ND FL. I UP DINING WING ROOM KITCHEN 00 00 825 SQFT 2 BEDROOM 1 BATH 107 CLOSET D J NI 0' OI 01:033 EOL BEDROOM A BATH ROOM CLOSET FROM 2ND FL BEDROOM 01:015 104 LI 9 1 A,B BEDROOM FROM 2ND FL EOL STORAGE CLOSET BATH ROOM 01:002 HEATED WEATHER PROOF ENCLOSURE. ELECTRICAL ROOM KITCHEN LIVING ROOM 0 0 00 625 SOFT 1 BEDROOM 1 BATH LI] KITCHEN 00 00 01:048 01:004 LAUNDRY ROOM BEDROOM TO ATTIC BEDROOM CLOSET BATH ROOM 01:010 Co R STORAGE DN 103 01:027 TO ATTIC WNG ROOM 625 SQFT 1 BEDROOM 1 BATH u STORAGE a OI r BATH ROOM CLOSET AB FROM 2ND FL BEDROOM UP TO ATTIC STORAGE CLOSET TO ATTIC nl 15cd 01:024 FROM 2ND FL CLOSET 102 825 SQFT 2 BEDROOM 1 BATH 00 00 01:047 FROM `�✓ 2ND FL KITCHEN ID 0 00 BEDROOM CLOSET FROM 2ND FL BEDROOM KITCHEN FROM 2ND FL O WING ROOM DINING DINING LMNG ROOM 825 SQFT 2 BEDROOM 1 BATH 1 ST FLOOR - BLDG. G 1 /8" = 11-0" FROM 2ND ft. 0 Z W Z 0 W C ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. G 4708 SOUTH CENTER BLVD. TUKWILA WA, 98188 1ST FLOOR - FIRE ALARM PLAN APPROVED BY: ER DRAWN BY: RG DATE: 4-17-08 JOB# 87474 DWG. NO.: FA -02 CD C 01:049 • 15cd FROM EOL ill • 2ND FL. I UP DINING WING ROOM KITCHEN 00 00 825 SQFT 2 BEDROOM 1 BATH 107 CLOSET D J NI 0' OI 01:033 EOL BEDROOM A BATH ROOM CLOSET FROM 2ND FL BEDROOM 01:015 104 LI 9 1 A,B BEDROOM FROM 2ND FL EOL STORAGE CLOSET BATH ROOM 01:002 HEATED WEATHER PROOF ENCLOSURE. ELECTRICAL ROOM KITCHEN LIVING ROOM 0 0 00 625 SOFT 1 BEDROOM 1 BATH LI] KITCHEN 00 00 01:048 01:004 LAUNDRY ROOM BEDROOM TO ATTIC BEDROOM CLOSET BATH ROOM 01:010 Co R STORAGE DN 103 01:027 TO ATTIC WNG ROOM 625 SQFT 1 BEDROOM 1 BATH u STORAGE a OI r BATH ROOM CLOSET AB FROM 2ND FL BEDROOM UP TO ATTIC STORAGE CLOSET TO ATTIC nl 15cd 01:024 FROM 2ND FL CLOSET 102 825 SQFT 2 BEDROOM 1 BATH 00 00 01:047 FROM `�✓ 2ND FL KITCHEN ID 0 00 BEDROOM CLOSET FROM 2ND FL BEDROOM KITCHEN FROM 2ND FL O WING ROOM DINING DINING LMNG ROOM 825 SQFT 2 BEDROOM 1 BATH 1 ST FLOOR - BLDG. G 1 /8" = 11-0" FROM 2ND ft. 0 Z W Z 0 W C ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. G 4708 SOUTH CENTER BLVD. TUKWILA WA, 98188 1ST FLOOR - FIRE ALARM PLAN APPROVED BY: ER DRAWN BY: RG DATE: 4-17-08 JOB# 87474 DWG. NO.: FA -02 H J K L 1 2 3 4 5 6 7 M N 825 SOFT 2 BEDROOM 1 BATH LMNG ROOM DINING BEDROOM DOWN TO 1ST FL BEDROOM A,B— CLOSET O 0 Co KITCHEN FROM DOWN TO 3RD FL 1S 01:040 F AB tv—A I 21:020 R FROM 3RD FL. CLOSET STORAGE BATH ROOM C BEDROOM 625 SIFT 1 BEDROOM 1 BATH WING ROOM DOWN TO FROM 1ST FL D"'1-03RD FL. A,B A,B CLOSET BATH ROOM STORAGE 4) 01:017 U R 01:041 DINING WING ROOM DOWN TO 1ST FL. ( 208 00 00 KITCHEN 625 SIFT 1 BEDROOM 1 BATH WING ROOM DOWN TO 1ST FL 00 00 KITCHEN 01:042 15cd FROM L... Pro - • 3RD FL. KITCHEN 00 0 J 825 SQFT 2 BEDROOM 1 BATH 207 CLOSET DOWN TO 1ST FL DN A,B 01:014 206 U A,B BEDROOM FROM 3RD FL CLOSET STORAGE BA -111 ROOM 425 SOFT STUDIO 1 BATH WING ROOM BEDROOM 00 00 KITCHEN DOWN TO CLOSET 01:012 R B 01:043 204 STORAGE FROM) 1D 3Df L. --BATHROOM A.B \ o BATH ROOM) BEDROOM DOWN TO 1ST FL CLOSET BEDROOM STORAGE 01:032 AB STORAGE O BATH ROOM CLOSET AB BEDROOM FROM 3RD FL BEDROOM C. 0 BATH ROOM STORAGE CLOSET DOWN TO 1ST FL B 205 N n 01:029 A—e BEDROOM AB rn KITCHEN 00 00 FROM 3RD FL LIVING ROOM 625 SIFT 1 BEDROOM 1 BATH 8 KITCHEN 00 Oo I I I —i DN 15cd DOWN TO 1ST FL 203 I 01:026 DOWN TO 1ST. FL LIVING ROOM AB STORAGE C BATH ROOM 0 CLOSET AB 625 SIFT 1 BEDROOM 1 BATH FROM 3RD FL BEDROOM 2ND FLOOR - BLDG. G 1/811_11-0" 9 10 ED BATH ROOM STORAGE CLOSET 01:023 DOWN TO A B 1ST FL 202 FROM 3RD FL CLOSET 01:044 FROM D FL 201 KITCHEN 0 0 Co CLOSET AB BEDROOM FROM 3RD FL BEDROOM 825 SIFT 2 BEDROOM 1 BATH 0 0 00 LIVING ROOM DINING KITCHEN FROM DOWN TO 39D -F 1ST FL 01:045 F (1 • DOWN TO r f 1ST—FL--- LMNG ROOM 825 SOFT 2 BEDROOM 1 BATH LIP z 0 0) W cc ISSUED FOR APPROVAL O z 0 0 ci z 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. G 4708 SOUTH CENTER BLVD. TUKWILA WA, 98188 APPROVED BY: ER DRAWN BY: RG DATE: 4-17-08 JOB# 87474 DWG. NO.: FA -03 1 2 3 4 5 6 7 8 9 10 825 SQFT 2 BEDROOM 1 BATH LMNG ROOM DINING FROM ATTIC BEDROOM DOWN TO 2ND FL BEDROOM FROM ATTIC A,B CLOSET r J 00 0 KITCHEN DOWN TO 2Nu I -L 309 A,B A 01:019 01.038 STORAGE BEDROOM DOWN TO 2ND FL A,B CLOSET BATH ROOM 0 DN DINING LMNG ROOM KITCHEN 00 00 825 SQFT 2 BEDROOM 1 BATH STORAGE 625 SQFT 1 BEDROOM 1 BATH LNINO ROOM FROM ATTIC A,B a L n 01:016 R BATH ROOM Cs_ CLOSET 2 CLOSET AB DOWN TO 2ND FL BEDROOM BEDROOM 308 0 0 00 KITCHEN 625 SQFT 1 BEDROOM 1 BATH LNING ROOM DOWN TO 2ND FL 0 0 OO KITCHEN 00 oO 425 SQFT STUDIO 1 BATH LMNG ROOM BEDROOM CLOSET STORAGE (306H 01`037 D BATH ROOM STORAGE CLOSET DOWN TO 2ND FL BEDROOM AB 305 01:028 R AB FROM ATTIC 0 0 O STORAGE KITCHEN 00 00 LMNG ROOM 625 SQFT 1 BEDROOM 1 BATH KITCHEN 00 00 01:036 FREW A,B 0 BATH ROOM BEDROOM DOWN TO 2ND FL BEDROOM A,B CLOSET 0 BATH ROOM FD STORAGE A A,B 01:008 R L_I DN DOWN TO 2ND FL AB DOWN TO 2ND FL LMNG ROOM 625 SIFT 1 BEDROOM 1 BATH BEDROOM BATH ROOM CLOSET DOWN TO 2ND FL STORAGE U 15cd 301 BEDROOM FROM ATTIC CLOSET 302 825 SQFT 2 BEDROOM 1 BATH 00 00 KITCHEN FROM LIVING ROOM DINING DOWN TO 2ND FL. 01:035 Di + FROM A KITCHEN 00 00 CLOSET FROM ATTIC BEDROOM LIVING ROOM 825 SQFT 2 BEDROOM 1 BATH 3RD FLOOR - BLDG. G 1 /8"=11-0" z 0 w U Z w 0z W C t ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. G 4708 SOUTH CENTER BLVD. TUKWILA WA, 98188 CC w CC LL 3RD FLOOR - FIRE ALARM PLAN APPROVED BY: ER DRAWN BY: RG DATE: 4-17-08 JOB# 87474 DWG. NO.: FA -04 A B C D E F G H J K L M N 1 3 4 5 II I I I I I I II II II II II II I L J LL JI ---- -1 A,B I I I I I I I I I 11 I I 7 A,B d I I I I I I I I I 0 I FROM C#33 ' I AND FSE CKTI# 1 A,4B II II II II II A,B B 01:007 FSE CKT. #1 -1 I- 01:006 I I I I I I I I I I I -JL A,B- 3 rH IA,B II I I I I I I I I A,B I I I I I I I I I I II 2B I I I I I I I I ‘1:1 CKT. #3 FSE CKT. #1 I I I I I I I I I I A,2B b. Q01:005 b o r -SE OKTr# i w 0 O u.... CKT. #3 FSE CKT. #1 CKT. #2 A,B -Tv ATTIC - BLDG. G 1/8"_1'-0" 8 9 10 CIRCUIT DISCRIPTIONS: CKT.#1 - ROOM NOTIFICATION WEST. CKT.#2 - ROOM NOTIFICATION EAST. CKT.#3 - CORRIDOOR NOTIFICATION. CKT.#4 - TRIGGER FIRE SIGNAL EXPANDER (FSE). FSE CKT.#1 - DOOR HOLDERS NORTH AND SOUTH. FSE CKT.#2 - OUTDOOR BELL & STROBE & EAST CORRIDOR. NOTE: DASHED UNE INDICATES WALL BELOW ATTIC. z 0 C ISSUED FOR APPROVAL 0 z w z 0 w ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. G 4708 SOUTH CENTER BLVD. TUKWILA WA, 98188 ATTIC - FIRE ALARM PLAN APPROVED BY : ER DRAWN BY: RG DATE: 4-17-08 JOB# 87474 DWG. NO.: FA -05 H J K L M 2 3 4 5 7 8 9 10 01:007 01:006 01:005 ri1 1 i1 t1' N #16/2 & #14/2 #16/2 & #14/4 #16/2 & #14/4 ATTIC #16/2 & #14/4 #16/2 & #14/4 #14/4 #14/2 #16/2 -1p #14/4 #16/2&#14/4 #16/2 & #14/4 #16/2 -4:1 C7-- #14/2 Q- #14/2 .015ma 3RD FLOOR 15cd .074ma 01:053 01:019 .027ma .027ma 01:039 01:038 #16/2 #16/2 01:016 CD .027ma 01:013 .027ma 01:011 .027ma 01:037 #16/2 #16/2 & #14/2 Q-#16/2 & #14/4 , #16/2 & #14/4 01:008 .027ma .027ma #14/2 #16/2 & #14/4 #16/2 0-#16/2 & #14/4 P #14/4 #16/2 & #14/4 #16/2 & #14/2 #14/2 01:022 .027ma .027ma #16/2 & #14/4 -� 01:025 .027ma 01:028 .027ma 01:036 CD #16/2 #16/2 & #14/4 -o #16/2 & #14/4 -� #16/2 & #14/8 01:031 .027ma .027ma 01:035 01:034 01:052 #14/4 v #14/2 v 15cd .074ma #14/4 v #14/2 -v .015ma .015ma 2ND FLOOR 15cd .074ma 01:020 01:017 0 .. .027ma .027ma #16/2 0 b 01:040 - #14/2 v- #14/2 01:041 .027ma #16/2 , #16/2 & #14/2 6 01:014 01:012 .027ma .027ma 01:042 01:009 .027ma .027ma #16/2 0-#16/2 & #14/4 I, #16/2 & #14/4 6 v-#16/2 & #14/4 01:023 L-11114-1110141- .027ma .027ma 01:026 L-01 CD .027ma #16/2 #16/2 & #14/4 #16/2&#14/4v 01:029 .027ma 01:043 01:032 .027ma .027ma #16/2&#14/4-w #16/2&#14/2v #16/2 #16/2 b °® b °o F 15cd .074ma #14/4 -z7 #14/2 v .015ma .015ma 1ST FLOOR 15cd EOL -0' .074ma 01:051 0 01:021 EOL 0 • .027ma .027ma 01:018 01:015 01:010 ® 0 ■ .027ma .027ma .027ma .027ma 01:050 01:049 #16/2 #16/2 01:004 01:003 01:002 01:001 WEST REMOTE ANNUNCIATOR • • #18/4 #16/2 FACP 1414Lr OM MIRCOM FX -150 -126 -DR TO CENTRAL- PHONE LINE #1 DUAL STATION PHONE LINE #2 DIALER --s 120 VAC S (DEDICATED CKr.) 01:024 01:027 01:030 401 -1101141-0 .027ma .027ma .027ma .027ma 0 #1612 3® 15cd NAC -1 #16/2 NAC -2 NAC -3 NAC -4 BAS Irxr BATTERY 12V -12M 12V-12AH #14/2 RISER DIAGRAM #18/4 .092ma P #18/4 EOL 01:033 Dol .027ma .027ma 01:048 01:047 #16/2 #16/2 .074ma FIRE ALARM SIGNAL EXPANDER BPS -6 INPUT #14/2 NAC -1 NAC -2 NAC -3 NAC -4 BATTERY 1 BATTERY 12V-7AH 12V•7AH ammogb a) 120 VAC (DEDICATED CKT.) EAST P #18/4 0 01:046 #16/2 15cd .074ma WP-75cd .138ma CIRCUIT DISCRIPTIONS: CKT.#1 - ROOM NOTIFICATION WEST. CKT.#2 - ROOM NOTIFICATION EAST. CKT.#3 - CORRIDOOR NOTIFICATION. CKT.#4 - TRIGGER FIRE SIGNAL EXPANDER (FSE). FSE CKT.#1 - DOOR HOLDERS NORTH AND SOUTH. FSE CKT.#2 - OUTDOOR BELL & STROBE & EAST CORRIDOR. P .015ma BELL ED EOL .040ma #18/4 - z O w ISSUED FOR APPROVAL 0 z 0 C) 2 LiJ z 0 ELECT. FIREOI*099KW 206-575-0311 107 WASHINGTON BLVD. ALGONA WA, 98001 PARK PLACE BY THE WOODS BLDG. G 4708 SOUTH CENTER BLVD. TUKWILA WA, 98188 BUILDING RISER DIAGRAM APPROVED BY: ER DRAWN BY: RG DATE: 4-17-08 JOB# 87474 DWG. NO.: FA -06