CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Project: �� ��
fC
Fire Alarm:
Type offI�Inspect'on:
rlti
Address:Contact
Suite #: /�V7?
5-7
/fre
Person:
Special Instructions:
Phone No.:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
aci4veriai 01'2 Se,664--df
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Inspector: -,
M/6-
Date: eV/ W / i
Hrs.:
/- o
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Pro' :
PilTr4CC(.._ tG
T P -E3'
Type of Inspection:
co (lam-/vd—r
Address:
Suite #:
S 4v-6-5
Contact Person:
Special Instructions:
Occupancy Type:
Phone No.:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Inspector: flA4
c
Date: h
h
Hrs.: (
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
Sheet
Helton Fire
1
Date 05/17/17
Job: PATRICKK
PROJECT INFORMATION
Job Patrick Kent Res
14479 57th Ave So Tukwila WA
Occupancy
Area per Sprinkler
Sprinklers
Number of Sprinklers Calculated:
Authority having Jurisdiction
System type Wet
Water Supply 60.00 psi Static,
Light Hazard
256 sq ft 1616 Coverage
Tyco LF -2 Concealed 4.9K
2 heads
Tukwila Fire Dept
55.00 psi Residual @ 26.0
gpm
Demand
CALCULATION SUMMARY
22.74 psi @ 26.0 gpm @ B.O.R.
34.91 psi @ 26.0 gpm @ Supply
55.00 psi available @ 26.0 gpm
Below curve by 20.09 psi
PROGRAM: 'HydroCalc' by Micro Space Systems
www.microspacesystems.com
Pete Helton
1390-0601-A Level 1
lelton Fire Protection
��I,yy1FP965NC
ea: Dat.
PAID
MAY 13 2017
TUKWILA FIRE
cc ?.-0
0
o-
0
Of
S
3 w
3c 3a
a .
�
w a.
Qaxl
a- 11 11
gQi ?N O
p i
K O o
a.52
0 col
fA (A
co
C N N
0).7 WO)
O O
0 O
(PZ)
tQ
w
=ma
Pressure (PSI)
o 0 O Q
I I I I I
0
Sheet 2
8
m
w
Patrick Kent Res Sheet 3
Helton Fire
Description of Fitting abbreviations
Code Description
PE Plastic 90 degree Elbow
PTR Plastic Tee flow thru run
BKF Backflow preventor
MTR Meter Loss
Description of Other abbreviations
Code Description
DR
BL
PT
PE
PF
A.5
L
F
T
Drop
Branch Line
Total pressure
Pressure loss due
Pressure loss due
Raised to the power
Actual pipe length
Fitting equivalent pipe
Total pipe length
to elevation
to friction
of .5
changes
(Square
length
Root)
PATRICKK 05/17/17 0:45am Sheet 4
Helton Fire
Srinkler Systems Hydraulic Flow Calculations
Patrick Kent Res
14479 57th Ave So Tukwila WA
Raw data previous to any calculations
No. Code Diam Length Kfacl Kfac2 Press Elev Hose HW
1 DR1 1.109
2 DR2 1.109
3 BL1 1.109
4 RI1 1.109
5 UG1 1.109
0.50 4.9 7.000 -0.500 0.0 150
0.50 4.9 7.000 -0.500 0.0 150
27.00 DR1 DR2 0.000 -0.500 0.0 150
5.00 BL1 -4 0.000 12.000 0.0 150
60.00 RI1 -3 0.000 -0.500 0.0 150
Vel Fittings
32 1PE
32 1PE,1PTR
32 1PE,6PTR
32 2PE,4PTR,1BKF
32 4PE,1MTR
PATRICKK 05/17/17 0:45am Sheet 5
Helton Fire
Srinkler Systems Hydraulic Flow Calculations
Patrick Kent Res
14479 57th Ave So Tukwila WA
Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Notes
Drop 1 C = 150
L 0.5 PT 7.00 1
13.0=4.90(7.00)^.5 F 7.0 PE -0.22 (EL= -0.5 ft)
1 13.0 1.109 1PE T 7.5 0.02945 PF 0.22 4.3
PT 7.00 3 Bl Jct
K -factor for drop 1 = 13.0/(7.00)".5 = 4.91
Drop 2
L 0.5 PT 7.00 2
13.0=4.90(7.00)^.5 F 8.0 PE -0.22
2 13.0 1.109 1PE 1PTR T 8.5 0.02945 PF 0.25
PT 7.03 3
K -factor for drop 2 = 13.0/(7.03)".5 = 4.90
4.3
C = 150
(EL= -0.5 ft)
B1 Jct
PATRICKK 05/17/17 0:45am Sheet 6
Helton Fire
Srinkler Systems Hydraulic Flow Calculations
Patrick Kent Res
14479 57th Ave So Tukwila WA
Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps)
Notes
Branchline No. 1 C = 150
-_____= K=9.81=4.91+4.90 L 27.0 PT 7.03 3 DR1 + DR2
26.0=9.81(7.03)^.5 F 13.0 PE -0.22 (EL= -0.5 ft)
3 26.0 1.109 1PE 6PTR T 40.0 0.10688 PF 4.28 8.6
PT 11.09 4 Top of Riser
K -factor for branchline no. 1 = 26.0/(11.09)^.5 = 7.81
PATRICKK 05/17/17 0:45am Sheet 7
Helton Fire
Srinkler Systems Hydraulic Flow Calculations
Patrick Kent Res
14479 57th Ave So Tukwila WA
Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps)
Notes
Riser C = 150
____= L 5.0 PT 11.09 4 BL1
F 18.0 PE 5.20 (EL= 12.0 ft)
4 26.0 1.109 2PE 4PTR T 23.0 0.10673 PF 6.45 8.6 1BKF = 4.00#
1BKF PT 22.74 5 B.O.R.
K -factor for Riser = 26.0/(22.74)^.5 = 5.45
Under ground C = 150
__= L 60.0 PT 22.74 5 B.O.R.
F 28.0 PE -0.22 (EL= -0.5 ft)
5 26.0 1.109 4PE 1MTR T 88.0 0.10672 PF 12.39 8.6 1MTR = 3.00#
PT 34.91 6 Supply Jct
Available flow at 34.91 psi is 62.2 gpm which is 36.2 gpm from curve.
Supply pressure available with 26.0 gpm flowing is 55.00 psi,
thus system requirement is 20.09 psi below supply curve. (36.5%)
PATRICKK 05/17/17 0:45am Sheet 8
Supply Analysis
Node at Static Residual Available Total Required
Source Pressure Pressure Flow Pressure Demand Pressure
6 60.00
= _ = _ = _
55.00 26.0 55.00 26.0 34.91
Elevation Node
Node (ft) K -Value
Node Analysis
Type
Source
1 10.50 Orif= 4.90
2 10.50 Orif= 4.90
3 11.00
4 11.50
5 -0.50
6 0.00
_
Supply
Pressure
(psi)
7.00
7.00
7.03
11.09
22.74
34.91
Discharge
(gpm)
_
13.0
13.0
_
Notes
PATRICKK 05/17/17 0:45am
Pipe Information
Sheet 9
Nodel Elevl Kfactor Qadd Nominal Fittings L (ft) Cfac Total Pt
Pipe (ft) Hose ID F (ft) Vel Elev Pe
Node2 Elev2 Qtot Actual Length T (ft) Psi/Ft Fric Pf Notes
1
1 10.50 4.90
3 11.00
13.0 1" 1PE L 0.5 150 Pt 7.00
F 7.0 4.3 Pe -0.22
13.0 1.109 7.0 T 7.5 0.0295 Pf 0.22 DR1:K=4.91
2 10.50 4.90 13.0 1" 1PE 1PTR L 0.5 150 Pt 7.00
2 F 8.0 4.3 Pe -0.22
3 11.00 13.0 1.109 8.0 T 8.5 0.0295 Pf 0.25 DR2:K=4.90
3 11.00 9.81 [26.0] 1" 1PE 6PTR L 27.0 150 Pt 7.03 DR1 + DR2
3 F 13.0 8.6 Pe -0.22
4 11.50 26.0 1.109 13.0 T 40.0 0.1069 Pf 4.27 BL1:K=7.81
4
4 11.50 7.81
5 -0.50
[26.0] 1" 2PE 4PTR L 5.0 150 Pt 11.09 Top of Riser
1BKF F 18.0 8.6 Pe 5.20 1BKF = 4.00#
26.0 1.109 18.0 T 23.0 0.1067 Pf 6.45
5 -0.50 1" 4PE 1MTR L 60.0 150 Pt 22.74
5 F 28.0 8.6 Pe -0.22 1MTR = 3.00#
6 0.00 26.0 1.109 28.0 T 88.0 0.1067 Pf 12.39 Supply
O Without Comments
I(' As Noted in ReJ
�,
O Per The f';t�:ar�l . �d Letter
_ .er
These plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current City
standards. Acceptance is subject to errors and
omissions which do not authorize violations of adopted
5:andards and ordinances. The responsibility for the
adequacy of design rests totally with the designer.
Additions, deletions or revisions to these drawings after
this date will void this acceptance and will require a
resubmit'cai of revised drawings for subsequent approval.
Final acceptance is subject to field test and Inspection by
The Tukwila Fire Prevention Bureau.
Date: 5-- )--"S -1, By:
60 610 S.G.D.
S.G.
DINING RM.
7"
DOUBLE `r
2x4 WALL
LIMN RM.
42 Y
HALF
WALL
UKWIL.A FIRE DEPAR iTMENT
Please call 206-575-4407 and
give this Fire. Permit No.
/7- S- 091
and exact address for shut-
down or restoration approval.
EN
GE Wl
OD (VTO)
ROVIDE THUR WALL COMBUSTION AIR
VENTILATION
SOLID CORE 134" ° IN.
W/ WEATHER STRIP
URFACE WARM WA L
Y2G.W.B. WALLS
.W.B. TYPE X LID
FU L FURNACE & WAT R
H + TER. MIN. 18" ABC]
S "B
1
A/C PAD.I
J
TWO PERMANENT OPENINGS METHOD.
• PROVIDE 1 OPENING COMMENCING WITHIN 12" OF
THE TOP OF ENCLOSER & 1 OPENING COMMENCING
WITHIN 12" OF THE BOTTOM OF THE ENCLOSER.
rilt o . D S•
• f1 e,clC4 4
FOR HORTIZONTAL DUCTS EACH OPENING SHALL
HAVE A MIN. FREE AREA OF NOT LESS THAN 1 SQ.
IN. PER 2,000 BTU/H. OF TOTAL INPUT RATING OF
ALL APPLIANCE IN THE ENCLOSER.
ENERGY CREDITS TABLE R406.2:
4x4
POST
HIGH EFFICIENCY HVAC EQUIPMENT 38 AIR
SOURCE HEAT PUMP WI MIN. HSPF OF 8.5.
EFFICIENT WATER HEATING 5A - ELECTRIC
WATER HEATER W/ A MINIMUM EF OF 0.93.
AND ALL SHOWERHEAD AND KITCHEN SINK
FAUCETS INSTALLED IN THE HOUSE SHALL
BE RATED AT 1.75 GPM OR LESS. ALL OTHER
LAVATORY FAUCETS SHALL BE RATED AT 1.0
4'-1O"
AREA SUMMARY
........_..... .............
FIRST FLOOR AREA
SECOND FLOOR AREA
TOTAL FLOOR AREA
GARAGE
PORCH
= HOSE BIB
S.G. = SAFETY GLAZING
"
PAI''
MAY 18 2017
TUKWILA FIRE
7
M/
6x10 D.F. #2
EGRESS
BEDROOM 2
1',1 o„
DOUBLE
STUDS
00M 4 w
HANGER
1%1)(11
JOIST MUST LINE UP
D I R E CTLY ABOVE WALL
TO PROVIDE SHEAR
TRANSFER. FASTEN
JOISTS TO TOP PLATE
WF (2) 10d NAILS c 12
O.C. (SEE DETAIL 3 ON
liwomme IMINIIM =EP =filt C10201111 =I MOM imam MOM= Cellswil
TRIPLE
STUDS
6x6
POST
4x6
POST
MAST R B
DROOM
4x6
POST
5' TUB/
SHWR.
SECON
CANTILEVERED
JOISTS
FLOO "' RN