PP - 5951 S 180TH ST - BUILDING FILE - PERMITS AND PLANS
5951 S 180TH ST ASSOCIATED PERMITS 17-F-023 16-5-236 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Urban Interiors 5951 S. 180th St. Permit No.: 16-S-236 Date: November 16, 2016 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 "for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 21 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). 4 • Flexible sprinkler hose bends shall not exceed the maximum radius permitted by the listing. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • All valves controlling the water supply for automatic sprinkler systems and waterflow switches on all sprinkler systems shall be electrically supervised. • All interior control valves shall be readily accessible, labeled and located not more than 6 ft. above the floor. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more sprinkler heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2013 Edition. iN «A l�x`•t w� t 11;1 +Y 41, n.L Without Comments As Noted In Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance w;th current City standards. Acceptance is subject. to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer, Additions, deletions {:; ~evisions to these drawings after this date will void thisacceptance and will require a resubmittal of revise- drawings for subsequent approval. Final acceptance I' subject to field test and inspection by The Tukwila Fire Prevention Bureau. Gate: �-L(0 -f By:. ... IM:ILA FIRE DEPARTMENT ca; )$ 5A 5- Ci i and Ave thi a Fire Pern NO. (c� -S- 00.11041,1•S••••.0.11•1•111111.)_3 and exact d , ess for shut- down or restora,Uon approval. /3// rfPf ,ZZW/7 /j/ !,//' 1111 zA i�/ii/ri/iiriroiiioiii/ii/riiiuriiiiiiiiiiiisiiiii/iii/nuiiiiiiiuio/in/irru /iiiw.riiviQe�� $fr nr i_/i.,_ /i /i /i/ /i __.___ii.eii /i /i. / /i, /ice/,r /i�ii_•__s,. 1 IIiIn iil�lll ( ■ ■ ■ ■ '� ■ � IhIILE4/ e■�� 0 / / / yr :44A: / ;ter G/��, ;;ii � 0 4 / /,/(//, iiii%iii i! ® ■_■ ■S■ /r„�/a • 111 "1 IP!PIiIi.iih_"4" r • • MU 1110111011.111111 111111111 I 111111 10111 Ea1111111 1101111111111WAIIIIIIIIIINIIIIINIIII I-111111111111011 mominmegimI�- -r- r,- :. # 6 111011 •!!i - IPiiii- _ 11, II 11 111111111M 11111 111111111 111111 11111111111 1 f 1 f i t f 1 IIj •RE•ENT TIO g IN 111111.11119 --- J • WPC ifil r r KZ / ii i Pi '0. 44 11 0, �I ,,,,',,�,, ■■■ _� IIIiiiiiiiir III II III! 111111-------------- ■ III 111111111 ii I,■■■■■■■■ ■■■■■..■' r '% ■ r _ i5 111111.1111 � r 1111111111117 I1 [il Ilro II II t S! ci, NIA 1 i / ///,I„/,////// t4WWW/,/,///.//„/,I,//,/,,,I,/,,,,,,, i io OFFICE of �j-0 102 0 E -S I i IIIbAWIW..,//I//Io/II/.I/./I,///////./IW0W.IAWA r1========7 -amu ti) I 0 10 — 01 1” SLUG AT EXIS11NG WITHIN DEMO D a (SI MM. „ FIRE SPRINKLER FLOOR PLAN SCALE: Vae=1'-C" erN 4 EXIST. UPRIGHT \ SPRINKLER TO REMAIN \ 1 EXISTING EXIST. BRANCHLINE— C X U CY] C PER PLAN 7- NEW FLEXHEAD MODEL 2048, 1/2" W/ MOUNTING BRACKET CEILING TILE--"."" SPRINKLER HEAD FLEXIBLE SPRINKLER DROP DETAIL SCALE: NONE 2x JOIST 3/8" ALL THREAD ROD LENGTH PER PLAN 3/8" TOLCO FIG. 58 EYELET W/3/8" x2" LAG WITH 3/8" WASHER ANVIL FIG. 69 RING HANGER SIZE PER PLAN TYP. HANGER DETAILS SCALE: NONE GENERAL NOTES 1. — 2. DENOTES EXISTING FIRE SPRINKLER PIPING. DENOTES NEW FIRE SPRINKLER PIPING. 3. rcil DENOTES EXISTING PENDENT FIRE SPRINKLER TO REMAIN. 4. @ DENOTES EXISTING FIRE SPRINKLER TO RELOCATE. 5. DENOTES EXISTING UPRIGHT FIRE SPRINKLER TO REMAIN AT DECK. 6. it DENOTES 1" PLUG AT (E) DROP TO BE REMOVED. PLUG AT OVERHEAD BRANCHLINE. SCOPE OF WORK MODIFY EXISTING ARE SPRINKLER SYSTEM FOR TI WALLS & CEILINGS. VICINITY MAP HANGER LEGEND A "U" HOOK B _111\ D BM. CLAMP Vv/ "STRAP E EYELET F ' ig CEILING FLANGE H SIDE BEAM BRACKET K SHORT CLIP M ALL THREAD ROD N TOGGLE NUT ■ POWDER DRIVEN STUD R EXPANSION BOLT J:1_ U U = U V I STATE CERTIFICATION 1 t/4 an o�+ goto viz A nz co a R a s m oz Ai A R THRDS ,,-u•_0 z c� 0. n PENDENT TEE SIZE FIRE PTION f 2 107 O O0 1/2" threene 9-03C Level3 1 16 1 SPRAY _ 1 iot FProtection, Inc. i 3 17 ❑ 0 3/4" . 32 SPRAY o 1» Ez irea 1 371Qa1/2"10/j1�6 EA 8162SIDEWALL ® ® 1»(6late 12131118 2 DRY TYPE ,�1"1" v»• ® 1, - WAY EARTHQUAKE BRACE TEMP RATING SPRINKLERS UP AND DOWN OPENING N s a N UP m z BRACE 0 165° . 0WAYEARTHQUAKE o -e- 212° 1" UCTURE TO CENTER©286° OFPIPE IN INCHESVJING /� 1/2E LEGEND 3g= 350° a 1 500° CO 1/2" P PIPE -O -LET F PLAIN END FIT FITTING APPROVAL REQUIRED SN GROOVED SHAPED NIPPLE CITY OF TUKWILA TSN THREADED SHAPED NIPPLE SPRINKLER HEADS USED SYM MANUF MODEL TYPE THREAD SIZE ORIFICE SIZE HEAD FINISH ESCUTCH FINISH TEMP QTY \ REIJABLE F1FR 56 QR RECESSED 1h' K=5.6 , CHROME 155' 22 L, ,, L RELIABLE F1FR 56 QR UPRIGHT 1h' K=5.6 tie_ N/A 155 1 i rNa7(,� r:. ., : ,_ „..... 7r 4mire - - 01 -NI m_my .1 '- " IDEA OE\ITER TOTAL 23 QUALITY CONTROL BY CLINT CARR DATE 10/20/16 APPROVED FOR FABRICATION BY DATE GENERAL NOTES 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UL LISTED OR FM APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISERS AND DIMENSIONS SHOWN THUSLY (1-6) WHICH ARE END TO END. 3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 2010 EDITION. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 2010 EDITION. 5. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 2010 EDITION 6. JOINING OF PIPE AND FITTINGS, THREADED & WELDED, SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 2010 EDITION. 7. OWNER TO PROVIDE ADEQUATE HEAT IN AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM TO PREVENT WATER IN PIPES FROM FREEZING. 8. ALL WIRING OF ELECTRICAL DEVICES (IF REQUIRED) TO BE PROVIDED BY OTHERS 9. PAINTING OF PIPE & EQUIPMENT (IF REQUIRED) TO BE PROVIDED UMW 10. FURRING OF PIPE & EQUIPMENT (IF REQUIRED) TO BE PROVIDED BY OTHER DESIGN CRITERIA 1. DESIGNED PER NFPA 13, 2010 EDITION. PIPE NOTES 1. ALL THREADED PIPE TO BE SCH. 40 BLK. REVISIONS NO DATE I DESCRIPTION CONTRACT WITH: GOUDY CONSTRUCTION P.O. BOX 3028 BELLEVUE, WA 98009 PROJECT NAME: URBAN INTERIORS T.I. PAID 5951 S. 180TH STREET p _ 2 20Th TUKWILA, WA 98188 TUKWILA FIRE cc 'y-70 PATRIFP099CF ATRIOT WWW.PATRIOTFIRE.COM mattg@patriotfire.com FIRE PROTECTION, INC. 2707 70TH AVENUE EAST TEL: (253) 926-2290 TACOMA, WA 98424 FAX: (253) 922-6150 DESIGNER MATT GREENE 11111 Fp...1 DATE 10/31/16 1 OF 1 JOB NO. 12-19395 ,�'io�ica123• I . ■• ❑ a01 SHOWROOM D G+10,2'AFF , W e ACT _ _=-_") Y L ]i =� i r:l 1 ` L 1 r , '' OWROOM I TO BE REMO GENERAL 101 CE H . 1 LI OPEN OTS GRID -0 TO REM STR GT " N RE. 111 �MD 0 t I� �/ ■ . - = _1.1, c. I„ ERIN' '` ' w .11M-11 11 WA I � - � ,, _� _ ,. .i., "s — si L 0 G„, -■�, ,, . I■ STORAGE ii i Pi '0. 44 11 0, �I ,,,,',,�,, ■■■ _� IIIiiiiiiiir III II III! 111111-------------- ■ III 111111111 ii I,■■■■■■■■ ■■■■■..■' r '% ■ r _ i5 111111.1111 � r 1111111111117 I1 [il Ilro II II t S! ci, NIA 1 i / ///,I„/,////// t4WWW/,/,///.//„/,I,//,/,,,I,/,,,,,,, i io OFFICE of �j-0 102 0 E -S I i IIIbAWIW..,//I//Io/II/.I/./I,///////./IW0W.IAWA r1========7 -amu ti) I 0 10 — 01 1” SLUG AT EXIS11NG WITHIN DEMO D a (SI MM. „ FIRE SPRINKLER FLOOR PLAN SCALE: Vae=1'-C" erN 4 EXIST. UPRIGHT \ SPRINKLER TO REMAIN \ 1 EXISTING EXIST. BRANCHLINE— C X U CY] C PER PLAN 7- NEW FLEXHEAD MODEL 2048, 1/2" W/ MOUNTING BRACKET CEILING TILE--"."" SPRINKLER HEAD FLEXIBLE SPRINKLER DROP DETAIL SCALE: NONE 2x JOIST 3/8" ALL THREAD ROD LENGTH PER PLAN 3/8" TOLCO FIG. 58 EYELET W/3/8" x2" LAG WITH 3/8" WASHER ANVIL FIG. 69 RING HANGER SIZE PER PLAN TYP. HANGER DETAILS SCALE: NONE GENERAL NOTES 1. — 2. DENOTES EXISTING FIRE SPRINKLER PIPING. DENOTES NEW FIRE SPRINKLER PIPING. 3. rcil DENOTES EXISTING PENDENT FIRE SPRINKLER TO REMAIN. 4. @ DENOTES EXISTING FIRE SPRINKLER TO RELOCATE. 5. DENOTES EXISTING UPRIGHT FIRE SPRINKLER TO REMAIN AT DECK. 6. it DENOTES 1" PLUG AT (E) DROP TO BE REMOVED. PLUG AT OVERHEAD BRANCHLINE. SCOPE OF WORK MODIFY EXISTING ARE SPRINKLER SYSTEM FOR TI WALLS & CEILINGS. VICINITY MAP HANGER LEGEND A "U" HOOK B COACH SCREW ROD D BM. CLAMP Vv/ "STRAP E EYELET F HDIP G CEILING FLANGE H SIDE BEAM BRACKET K SHORT CLIP M ALL THREAD ROD N TOGGLE NUT P POWDER DRIVEN STUD R EXPANSION BOLT S PIPE SPIKE U V X Z STATE CERTIFICATION SPRINKLER LEGEND , an o�+ goto viz A nz co a R a s m oz Ai A R THRDS SPRINKLER ORIFICE SIZES AND TYPE z c� 0. n PENDENT TEE SIZE FIRE PTION f 2 8 6 2 O O0 1/2" threene 9-03C Level3 1 16 1 SPRAY 1 iot FProtection, Inc. i 3 17 ❑ 0 3/4" RIFCF _4 ::tur°F1:;relLYYEre:AAP8t7TLIPE;ENIK:" 32 SPRAY o 1» Ez irea 1 371Qa1/2"10/j1�6 8162SIDEWALL ® ® 1»(6late 12131118 2 DRY TYPE ,�1"1" v»• ® 1, - WAY EARTHQUAKE BRACE TEMP RATING SPRINKLERS UP AND DOWN OPENING N s a N UP m z BRACE 0 165° N 0WAYEARTHQUAKE o -e- 212° 1" UCTURE TO CENTER©286° OFPIPE IN INCHESVJING /� 1/2E LEGEND 3g= 350° a 1" 500° CO 1/2" P PIPE -O -LET F PLAIN END FIT FITTING APPROVAL REQUIRED SN GROOVED SHAPED NIPPLE CITY OF TUKWILA TSN THREADED SHAPED NIPPLE SPRINKLER HEADS USED SYM MANUF MODEL TYPE THREAD SIZE ORIFICE SIZE HEAD FINISH ESCUTCH FINISH TEMP QTY REIJABLE F1FR 56 QR RECESSED 1h' K=5.6 CHROME CHROME 155' 22 0 RELIABLE F1FR 56 QR UPRIGHT 1h' K=5.6 BRONZE N/A 155 1 TOTAL 23 QUALITY CONTROL BY CLINT CARR DATE 10/20/16 APPROVED FOR FABRICATION BY DATE GENERAL NOTES 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UL LISTED OR FM APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISERS AND DIMENSIONS SHOWN THUSLY (1-6) WHICH ARE END TO END. 3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 2010 EDITION. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 2010 EDITION. 5. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 2010 EDITION 6. JOINING OF PIPE AND FITTINGS, THREADED & WELDED, SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, 2010 EDITION. 7. OWNER TO PROVIDE ADEQUATE HEAT IN AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM TO PREVENT WATER IN PIPES FROM FREEZING. 8. ALL WIRING OF ELECTRICAL DEVICES (IF REQUIRED) TO BE PROVIDED BY OTHERS 9. PAINTING OF PIPE & EQUIPMENT (IF REQUIRED) TO BE PROVIDED UMW 10. FURRING OF PIPE & EQUIPMENT (IF REQUIRED) TO BE PROVIDED BY OTHER DESIGN CRITERIA 1. DESIGNED PER NFPA 13, 2010 EDITION. PIPE NOTES 1. ALL THREADED PIPE TO BE SCH. 40 BLK. REVISIONS NO DATE BY DESCRIPTION CONTRACT WITH: GOUDY CONSTRUCTION P.O. BOX 3028 BELLEVUE, WA 98009 PROJECT NAME: URBAN INTERIORS T.I. PAID 5951 S. 180TH STREET p _ 2 20Th TUKWILA, WA 98188 TUKWILA FIRE cc 'y-70 PATRIFP099CF ATRIOT WWW.PATRIOTFIRE.COM mattg@patriotfire.com FIRE PROTECTION, INC. 2707 70TH AVENUE EAST TEL: (253) 926-2290 TACOMA, WA 98424 FAX: (253) 922-6150 DESIGNER MATT GREENE SHEET Fp...1 DATE 10/31/16 1 OF 1 JOB NO. 12-19395 (5j -y,f_ ith d' o As r,,,ot.a'c, 0 Pet The t'1L}.dc plans ha" been reviewe.ef -a-Fire sO r Bu C C11 r1'ar Lorformarte with current aty „ y ACCeOtet)cl. 's subject to errors and ;:ons wrric:; a,o no, t -;prize v1i €atlons of adopted anc• Iurra;n noes. The (esponsWity for the ,.lacy of oesig:. Ct v. iotr'ly With tip designer. 2D .ons, c:eletior9s o.. e:`'`1sions to these drawings after 13.. 7aatF �Niii void this ^cceptaricc and will require '' (E) RECEMNG ite '6\ (EI'¢TORAGE) JANITOR' � I120 121 SF. 20SF _i (E) BREAK 119 120 SF resubrni tai of re'viSee drawings fA r subsequen p �rnlai. -lilac acceptance is subject to field test and inspection The Tukwila Fire Prevenz.ion Bur su. Date: 21 ',132,;____B -y. FP 16-71N' 7'-8" (E) WOMENS R I}: 54SF I 117 HALL 118 87 SF (E)MENS RR 1118 70SF F(tee Aerie. ►►� FC_,4o.) 8, ,4L-Fi �& /1/.' '7 .rr'/o ff 4:,I 0 M:1 3 P:.. - • J �}e uG- �I Wit , W4 4'8/ oct 6-T 13'-0" awl 20 11'-0 12" 0-- 11'-4 12" (FP -02 7tlKWILA FIRE LPARmf P €se mil 206-575-4407 give this Fire Permit No. 1"1 rte- �Z3 and endcdd 5 fix shut- down hutdown or retor opproval. ,I 4 01AL r J ' 1 X. s64em CONFIGURATOR 1123 I 813 SF 10-0" PRESENTATION 10'-4" 10,4" 10-4' (FP -02 ( FP -02 )-N 5-A 12" 6-8 12" M.01> 15 IDEA CENTER SHOWROOM I 101 12,091 SF FP -04 607 SF R d – OPP 4 M00, X 6'-3 12" 10' 4' 19-4' 12'-6 12" 6'-3 1/2" ' I A4.01` 6 6-07/16' ALIGN - STORAGE I 106 I 99 SF 4 4N MEM (FP-10 ),8%/:' W Fite— Mr,/ al evloogiq.�r�i Y_ ) 3 ' AA.000% \ A6AO ii OPP OPP "OPE ,-� 1 CAs.00./ C0° CD FLOOR PLAN A3.D2 Scale: 1/8" =1-0" FLOOR PLAN GENERAL NOTES 1. PATCH AND REPAIR GW9 AS REQUIRED TO ACCEPT NEW FINISH. 2. ALL DIMENSIONS ARE FROM FINISH FACE UNLESS NOTED OTNERNASE. 3. PRIOR TO COMPLETION OF CONSTRUCTION, CLEAN ALL SURFACES INCLUDING, BUT NOT LIMITED TO, SWITCH AND OUTLET PLATES, HVAC GRILLES, AND CEILING GRID. RESTORE ANY OF THE ABOVE AS TO LIKE -NEW GOOD WORKING CONDITION AS REQUIRED. 4 ALL MECHANICAL, ELECTRICAL, AND PLUMBING SYSTEMS TO BE BIDDER -DESIGNED. SUBCONTRACTOR SHALL BE RESPONSIBLE FOR PREPARATION OF DESIGN PLANS, ENGINEERING, AND PERMITS. 5. ALL DOOR HARDWARE TO MEET REQUIREMENTS OF 2012 IBC WITH WASHINGTON STATE AMENDMENTS 8 OWNER'S BUILDING REQUIREMENTS. 6. ALL LOCKSETS SHALL BE OPERABLE FROM EGRESS SIDE WITHOUT USE OFA KEY OR SPECIAL KNOWLEDGE. LOCKS ANLL RELEASE UPON PUSHING LEVER HARDWARE DOWNLWRD ON THE EGRESS OF EVERY DOOR. KEYNOTE LEGEND FP -01 FP -02 FP -03 FP -04 FP -05 FP -07 FP -10 FP -11 CHAIR WALL EXISTING SOFFIT ABOVE WORKCENTER CASEWORK PATCH AND FLOAT EXISTING CONCRETE SLAB ON GRADE TO ACCEPT NEW FLOOR FINISH WOOD FRAMED DISPLAY PLATFORM FINISH PER FINISH PLAN POINT OF SALE STATION: CASEWORK FDIC: PRONDE POWER AND DATA AT LOCATIONS NEW SIDE WALK TO AUGN WITH EXISTING JOINT UNES. FINISH TO MATCH EXISTING SIDEWALK CONDITION WRITABLE MIRROR, FOIC DOOR SCHEDULE DOORS 102A 106B 1078 109A DOOR TYPE A HEIGHT T O' T O' TO' WIDTH 61Y 6-0' T O' THK. HW 13/4' HW1 13/4' 17A2 13/4' HN2 13/4' HWl COMMENTS DOOR TYPES DOOR DOOR , DOOR WIDTH WIDTH DOOR Ii 0 4– ® BUILDING STANDARD GLASS WOOD DOOR SLIDING DOOR DOOR HARDWARE 1N1-1 WW2 1 12 PR BUTT HINGES SLIDING HARDWARE PER STOREFRONT MFR 1 SURFACE MOUNTED CLOSER DECORATIVE PULLS/PAIR EACH SIDE 1 LEVER LOCKSET 1 DOOR STOP 1 CLOSER I SET SILENCERS WALL SCHEDULE SYMBOL 02 03 04 05 20 DESCRIPTION SND- 5/8' GWB-3 5/8' STUD WALL -59' GWB STUD- 5/5 GWB-359' SND WALL SND- 5/8' GWB-359' SND WALL -59' GWB SND -59' GWB-3 5/8' STUD WALL -59' GWB SND - 5/8' GWB -6' SND WALL -59' GWB FLOOR PLAN LEGEND HEIGHT TO CEILING TO CEILING TO6' ABOVE CEIUNG 150' 9' 0' FIRE RATING NON -RATED NON -RATED NON -RATED NON -RATED NON -RATED NO WORK THIS AREA NEW CONSTRUCTION EXISTING TO REMAIN WALL TAG, SEE SCHEDULE NEW FIRE EXTINGUISHER C./Users`dthorlekson/O000ments%16-366 - 2015 - THOMASVILLE URBAN INTERIORS - 20160622_dthorlaksoh@hoarch.com.M PINTO FEB - F, 2017 TUKWILA FIRE Cc- #.z0v W F J F CO CO Q Wce Wm o� �z3 ;o 2 5 z� W o� Z J» iff aH al a cg 2 D r REV DESCRIPTION PREUMINARY PRICING SET PREUMINARY PRICING SET REVISION BUILDING PERMIT DOCUMENTS 1 BUILDING PERMIT RESUBMTTAL BI CONSTRUCTION ISSUE • DATE 06272016 07/01/2016 07292016 09'152016 10.062016 FLOOR PLAN A3.02