HomeMy WebLinkAboutPP - 6815 S 180TH ST - WELLS FARGO - PERMITS AND PLANS6815 5180TH ST ASSOCIATED PERMITS 09-F-006 BATTERY CALCULATIONS REVISED STANDBY DEVICES CURRENT CURRENT TOTAL (STANDBY) TOTAL (ALARM) STANDBY ALARM SK -5808 1 0.2 0.325 0.2 0.325 SK- SMOKE 32 0.055 0.055 1.76 1.76 15CD STROBE ONLY 5 0 0.066 0 0.33 P2R 75CD 9 0 0.176 0 1.584 P2R 110CD 4 0 0.212 0 0.848 SUM COLUMN FOR : TOTAL STANDBY LOAD (AMPS) ALARM LOAD (AMPS) LOAD 1.96 4.847 BATTERY AMP HOUR: 1.96 4.847 REQUIREMENTS TOTAL 24 0.0833 47.04 0.403755 47.44376 TOTAL AMP HOURS REQUIRED: 56.93251 BATTTERIES INSTALLED WILL BE TWO 12 VOLT 75 AMP HR BATTERIES. BATTERY CALCULATIONS STANDBY DEVICES CURRENT CURRENT TOTAL (STANDBY) TOTAL (ALARM) STANDBY ALARM SK -5808 1 0.2 0.325 0.2 0.325 SK- SMOKE 32 0.055 0.055 1.76 1.76 15CD STROBE ONLY 5 0 0.066 0 0.33 P2R 75CD 9 0 0.176 0 1.584 P2R 110CD 4 0 0.212 0 0.848 SUM COLUMN FOR : TOTAL STANDBY LOAD (AMPS) ALARM LOAD (AMPS) 1.96 4.847 LOAD REQUIREMENTS TOTAL 1.96 24 47.04 4.847 0.0833 0.403755 BATTERY AMP HOUR: 47.44376 TOTAL AMP HOURS REQUIRED: 56.93251 BATTTERIES INSTALLED WILL BE TWO 12 VOLT 36 AMP HR BATTERIES. electrician2.com voltage drop calculator Page 1 of 1 Voltage Drop Calculator by electrician2.com k=12.9 for copper or k=21.2 for aluminum Select Material Select Size Copper 14 AWG Select Voltage and Phase 24 DC or 1 -phase AC Enter 1 -way circuit Enter Load length in feet in amperes 205 1.5 Click to Calculate Voltage drop Voltage at load end of circuit 1.9 22.1 Per Cent cma of voltage drop conductor 7.9 4110 Last updated: 12/13/2006 http://www.electrician2.com/calculators/vd calculator initial.html 12/10/2008 electrician2.com voltage drop calculator Page 1 of 1 Voltage Drop Calculator by electrician2.com k=12.9 for copper or k=21.2 for aluminum Select Material Select Size Copper 14 AWG Select Voltage and Phase 24 DC or 1 -phase AC Enter 1 -way circuit Enter Load length in feet in amperes 175 1.2 Click to Calculate Voltage drop Voltage at load end of circuit 1.3 22.7 Per Cent cma of voltage drop conductor 5.4 4110 Last updated: 12/13/2006 http://www.electrician2.com/calculators/vd calculator initial.html 12/10/2008 11 0 0 ' / TRUCK BAY 1� TRANSFER CH 10'.0 i �i TRANSFER 2 1.1 ------ 1 ........ H 10'{1 - i Oil i •,,,,, I -Li (;) \\ C \ , LUNCHROOM CH 9..0.: WOMEN R.R. CH d'-0' 15 I i 75 75 E.O.L r1===="-' MEN: nn. CH 0:P 15 Li de ..... -- it 1 T000000R 1 CO 10',0' RECEDING CH 10',0' v GO 00' IANN] 1 `TO FACPi fO 6.0 BUNKER .- AJ,111 -- 115 15L ; %\ JAN TM CH 010 iiir FIRE ALARM PLAN STAFF LOCKERS CH 0'10 I S l C h4.ya. keictda+ SCALE: 1/8"=1'—O" 1 1 1 I I I\ / GUEST LOCKERS CH 0-0'' 1 I 5 CUSTOMER SERVICE GH 10',0' 7,1 i L4 / EYT VEST6ULE 1 lrr I I 1► II MANAGER CH 10'0" 1 a ti bS E.O.L I I 1 GONE CH 10-0' SERVER GO 10,0' O GHT MANAGER CH 10,0' 110 --------------------------- ' -----f r • MAO TRAP 1 CH 0, 1 �!"`` '- ------of E -a MDFI:DF CH 0,' MNER VAULT CH 9'-0' i E.O.Lr'=jam S t 0000/WORK AREA GO 10'-0 u STORAGE CH 10,w e 1 1 P • FACP P -- ---� • E:1IT VES173ULE CH 00' -PIV FIRE ALARM LEGEND SYMBOL DESCRIPTION A FIRE ALARM CONTROL PANEL WEI 16 GAUGE 2 CONDUCTOR C ANNUNCIATOR CM CIRCUIT NUMBER POST INDICATOR VALVE Iiill 0 FIRE ALARM MANUAL PULL STATION al FIRE ALARM HORN/STROBE # INDICATES CANDELA RATING © FIRE ALARM STROBE # INDICATES CANDELA RATING ,,Ty ANNUNCIATOR ea- WATERFLOW SWITCH 111 TAMPER SWITCH Q BELL pSMOKE DETECTOR pH HEAT DETECTOR E.O.L. END OF LINE RESISTOR WIRING LEGEND SYMBOL DESCRIPTION A 14 GAUGE 2 CONDUCTOR B 16 GAUGE 2 CONDUCTOR C 18 GAUGE 4 CONDUCTOR # CIRCUIT NUMBER NOTES 1. ALL HORN STROBES SHALL 2. SHELL ONLY CONSTRUCTION 3. CEILING TO BE T—BAR. BE 80" AFF. 75 75 75 75 75 75 75 75 11010 11011 110 110imir 218. III 13 15 © 0 0-0 FIRE ALARM RISER � -- SCALE: N.T.S. A 8 c D E NOTES: 1 SMOKE DETECTOR • 0 2 PULL STATION • • 3 WATER FLOW • • 4 TAMPERS • 5 PIV • 6 DUCT DETECTOR • • A B C D E FIRE ALARM SYSTEM MATRIX SCALE: N.T.S. Per kivS f elev¢. 0e4•e'4-s-o- uSecy -Co-•pee - 4 c,fl`ok see.;h Jyj%1.. C7 Without Comments TX As Noted in Red {� Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: By:� S! tUKWILA FIRE. DEPARTa:lzM. Please call: 575.4407 and give this job No. bq—F-00(0 and exact address for shuts dome Of restoration onarayst FILE -- PO + a otci v,efsa 01.4/ Yet *04 4# cep l S . SQ+C,LI Iockoc-tdeulce 0 ecl►ccva krec. err, 11 -CI clefs +. kh ole 00X • J -j.,1I ( c'F;r'-;c14,54-14404'4 e 11Iav,>^ Co`•-htil "si5�~4.t w1a✓�- woe.. --• f{ Ct e n c2 -�`c3 } -fo !-e cow• J c,t� J ; h Co�� v h �'i j o �, Pre 4414 -1.°1 seri', �C e S p40.— . NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result Irl a Reinspection Fee and termination of the testing. pi 00 r, IMPORTANT O1 C Because of increased demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4407 to schedule your inspections a minimum of 48 hours in advance of the date you want an inspection. NFRBY ELECTRICInc. COMMERCIAL- INDUSTRIAL www.kirbyelectric.com 4826 "B" St. NW Suite 102 Auburn, Washington 98001 (253) 859-2000 (FAX) 859-2363 'YELLS FARGO BANK WELLS FARGO BANK CV OPERATIONS SPERRY DRIVE TUKWILA, WA REVISIONS: 12-5-08 12-17-08 SCALE: 1 /8"=1'-0" DATE: 12-5-08 DRAWN BY: CHECKED BY: SHEET FA JOB NO.: OF