Loading...
HomeMy WebLinkAboutPP - 13355 56TH AVE S - CASTILLO RESIDENCE - PERMITS AND PLANS13355 56TH AVE S ASSOCIATED PERMITS 04-5-179 FIRE SYSTEMS WEST, INC. 219 FRONTAGE ROAD, NORTH SUITE B PACIFIC,WA 98047 HYDRAULIC CALCULATIONS FOR CASTILLO RESIDENCE 13355 56TH AVE SOUTH FILE NUMBER: CASTILLO DATE: 9/01/04 -DESIGN DATA - OCCUPANCY CLASSIFICATION: RESIDENTIAL NFPA-13D DENSITY: 20 GPM/SPRINKLER AREA OF APPLICATION: 256 sq. ft. COVERAGE PER SPRINKLER: 256 sq. ft. NUMBER OF SPRINKLERS CALCULATED: 2 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 40.6 gpm TOTAL WATER REQUIRED (including hose): 40.6 gpm FLOW AND PRESSURE (@ CITY): 40.6 gpm @ 60.5 psi SPRINKLER ORIFICE SIZE: K=4.1 inch NAME OF CONTRACTOR: FIRE SYSTEMS WEST DESIGN/LAYOUT BY: PAUL BOZE AUTHORITY HAVING JURISDICTION: TUKWILA FIRE DEPARTMENT CONTRACTOR CERTIFICATION NUMBER: FIRESWI140B1 • SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 9/2/2004 E:\HASSFILE\CASTILLO.SDF JOB TITLE: CASTILLO RESIDENCE WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. 8 PRESS. 8 DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) CITY 65.0 20.0 500.0 64.6 40.6 60.5 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 40.6 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 40.6 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 1 16.0 K= 4.10 23.8 20.0 2 16.0 K= 4.10 25.3 20.6 3 16.0 - - - - 32.6 4 8.0 41.4 5 8.0 45.9 6 8.0 44.4 7 8.0 43.8 TOR 8.0 46.5 BF1 2.0 49.5 BF2 2.0 53.5 BOR 0.5 55.6 CITY 0.0 SOURCE 60.5 40.6 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 9/2/2004 E:\HASSFILE\CASTILLO.SDF JOB TITLE: CASTILLO RESIDENCE PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -20.0 1.101 PL 14.00 PF 1.5 1 16.0 4.1 23.8 20.0 6.7 150 FTG 2E PE 0.0 2 16.0 4.1 25.3 20.6 0.068 TL 21.65 PV Pipe: 2 -40.6 1.101 PL 15.50 PF 7.3 2 16.0 4.1 25.3 20.6 13.7 150 FTG ET PE 0.0 3 16.0 0.0 32.6 0.0 0.252 TL 28.89 PV Pipe: 3 -40.6 1.101 PL 8.00 PF 5.4 3 16.0 0.0 32.6 0.0 13.7 150 FTG ET PE 3.5 4 8.0 0.0 41.4 0.0 0.252 TL 21.39 PV Pipe: 4 -27.2 1.101 PL 16.00 PF 4.5 4 8.0 0.0 41.4 0.0 9.2 150 FTG 3ET PE 0.0 5 8.0 0.0 45.9 0.0 0.120 TL 37.04 PV Pipe: 5 13.4 1.101 PL 25.00 PF 1.5 5 8.0 0.0 45.9 0.0 4.5 150 FTG 3ET PE 0.0 6 8.0 0.0 44.4 0.0 0.032 TL 46.04 PV Pipe: 6 6.7 1.101 PL 33.50 PF 0.5 6 8.0 0.0 44.4 0.0 2.3 150 FTG 4ET PE 0.0 7 8.0 0.0 43.8 0.0 0.009 TL 58.36 PV Pipe: 7 6.7 1.101 PL 33.50 PF 0.5 6 8.0 0.0 44.4 0.0 2.3 150 FTG 4ET PE 0.0 7 8.0 0.0 43.8 0.0 0.009 TL 58.36 PV Pipe: 8 13.4 1.101 PL 52.00 PF 2.4 7 8.0 0.0 43.8 0.0 4.5 150 FTG 6E PE 0.0 4 8.0 0.0 41.4 0.0 0.032 TL 74.95 PV Pipe: 9 -40.6 1.402 PL 3.00 PF 0.6 5 8.0 0.0 45.9 0.0 8.4 150 FTG E PE 0.0 TOR 8.0 0.0 46.5 0.0 0.078 TL 7.90 PV Pipe: 10 -40.6 1.402 PL 6.00 PF 0.5 TOR 8.0 0.0 46.5 0.0 8.4 150 FTG ---- PE 2.6 BF1 2.0 0.0 49.5 0.0 0.078 TL 6.00 PV Pipe: 11 FIXED PRESSURE LOSS DEVICE BF2 2.0 0.0 53.5 0.0 4.0 psi, 40.6 gpm BF1 2.0 0.0 49.5 0.0 Pipe: 12 -40.6 1.402 PL 3.00 PF 1.4 BF2 2.0 0.0 53.5 0.0 8.4 150 FTG ET PE 0.6 BOR 0.5 0.0 55.6 0.0 0.078 TL 17.69 PV Pipe: 13 -40.6 1.380 PL 30.00 PF 4.7 BOR 0.5 0.0 55.6 0.0 8.7 150 FTG ETCG PE 0.2 CITY 0.0 SRCE 60.5 (N/A) 0.084 TL 55.69 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 9/2/2004 E:\HASSFILE\CASTILLO.SDF JOB TITLE: CASTILLO RESIDENCE PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) NOTES: (1) Calculations were performed by the HASS 7.6 computer program under license no. 5009058210 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.013 gpm and a maximum imbalance at any node of 0.143 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 13.7 ft/sec at pipe 3. (4) PIPE FITTINGS TABLE Pipe Table Name: STANDARD.PIP PAGE: * MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatV1v AlmChk DPV1v NPTee 1.101 2.53 6.33 2.53 6.33 7.59 1.27 12.66 12.66 6.33 1.380 3.00 6.00 2.00 7.00 6.00 1.00 10.00 10.00 6.00 1.402 3.24 6.48 2.16 7.56 6.48 1.08 10.80 10.80 6.48 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 9/2/2004 E:\HASSFILE\CASTILLO.SDF JOB TITLE: CASTILLO RESIDENCE WATER SUPPLY ANALYSIS 500.0 gpm Static: 65.00 psi Resid: rl N O 0 O O —o 0 O — 0 CO r-1 N O O O O O O O O N t0 Lfl O O M O O N ri 0 0w a4 U) aw--a,U)---- O O b O — O 10 O — Lf1 O — O — M O — N N d4 ci FLOW (GPM) SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 9/2/2004 E:\HASSFILE\CASTILLO.SDF JOB TITLE: CASTILLO RESIDENCE WATER SUPPLY CURVE 72+ 66+ 0 1\ 60X\ I \ I \ I \ 54+ \ I \ I \ I \ P 48+ R I E I S, 1 S 42+ U I R 1 E 1 36+ ( 1 \ P I S 1 I 30+ ) I 24+ \ I \ I \ * <-20.0 psi @ 500 gpm 18+ Flow Test Point 12+ LEGEND I " I X = Required Water Supply 60.46 psi @ 40.6 gpm 6+ I 0 = Available Water Supply 64.57 psi @ 40.6 gpm I" 0++-+---+----+ + + + + + + 200 300 400 500 600 700 800 900 1000 FLOW (GPM) 174847 14- f 0 17 CPVC HANGERS/RESTRAINERS TYPICAL APPLICATIONS --- HANGER - APPLICATION 1RESTRAINER APPLICATION FIG 22 MAIN FL -00R FLA NJ -_ �'/S-" I, -Q FIG. 23 AL1 TOLCO HANGERS 1 RESTRAINER$ USED WITH CPVC PLASTIC PIPE CONFORMTO NFPA 13, 13R, $ 13D. APPROVED FASTENERS ARE FURNISHED BY MANUFACTURER WITH FIG. 22, FIG. 23 & FIG.24 SURGE RESTRAINER Fla 29 798 E. HARRISON STREET CORONA, CALIFORNIA 91719 (909) 737 5599 FAX (909) 737-0330 (510) 791 2832 G ELECTRIC BELL 0-300 Psi GAUGE --�. WAo-ERFLOW S wkTcr POTTE'2 VSR-SF r 1 PARTIAL SECTION eRIGHT 1 1 0- r � •'-0)' 0 e 4* n r err � 1 t MA1N1 FLOOR • t N. 0 2 N° FLOOR AIN e— 0 SPARE SPRINKLER 1= -ox. IS NOT REQUIRED 5y NrPA IBD r DRAIN LINE PIPE TO SAFE EDI SCHAP.CX OUTSIDE r1- ^MES 2O X) e Doc) BLE. GNEGiL BACrFLOW ASsEMeLY FIRE SYSTEMS WEST START- POINT ! s E R D ETA I L_ Notes: _ ACCEPTED ❑ Without Comments ❑ As Noted In Red ❑ Per The Attached Letter f These plans harp been reviewed by The Tukw la Fire Prevenuon Bureau for cor fcr Hance with currert coy -tandards Acceptance )1ECt to errors and omission's 41h eh ",o nG uJLhorl_e v'o1aLions of adop ed 1 standards arra c. _Iola ices 1 re re: onatbtl tJ for the rUCq.iacy of Gt2Y gn Jest's t -t: Ily With the des gior ,Additions o- r r ans ri these drawings after this date will Yo d trii5 acceptance and Will requ re a resubmittal of revised drawings for subsequent approval Final acceptance is subject to field test and inspect The Tukwila Fire Pre,rentronB�ureau Date c)/(q d`i By 02167° 1 Pipe and fittings are 1" CPVC plastic U N 0. 2. Hangers shall be installed a maximum of • 6'-0" apart for 1" CPVC. ■ _ 6'-6" apart for 1'/4" CPVC. • 12" from drop. 3. Piping shall run concealed. In attic or cold areas the insulation shalt be Installed over the piping 4. Sprinklers shall be installed in all rooms except clothes closets, linen closets and pantries where the area does not exceed 24 square feet and the least dimension does not exceed 3 feet and the watts and ceilings are surfaced with non-combustible or limited combustible matenais.' 12 f UKWILA FIRE L)EfA Y i v. i'l I Please call 575-4407 and give this job No O and exact address for shut- down or restoration approval. - 2wt0 F'RAM1Nt. ON GLB'S INsULATkan[ ovEe. Pi PE f A.RTIALL SEG -r, ON Vis-- 1 -o • • 5. The garage is exempt from sprinkler coverage except for a sprinkler above the CPVC spnnkler riser 6 Maximum coverage per sprinkler is 16 feet by 16 feet (20 gpm flowing per head), or 8'-0" from any wall Exclusions 1. Electrical or alarm wiring or installation 2 Underground water supply, tank or pump 1 CONTRACT NAME CASTILLU ESIbENCE 13355 5G,' AVE S TUKWILA , WA 98 17,5 Z000 - 8G9 - 4783 CONTRACT NATH 6 —SAME A5 ABOVE- 3111:75) BOVE— HANQER LEQEND SPRINKLER HEADS REVISIONS QENERAL NOTES A '"U' HOOK L "L ROD SYMBOL TYPE MFG MODEL SIZE TEMP FINISH CANOPY QUANTITY MK DATE BY DESCRIPTION B COACH SCREW ROD M MACHINE THREADED ROD 0 CONCEALED VIKING MIRAGE 14- 4 I T55° W H4 IT E W H ITE 14- c C` CLAMP N TOGGLE NUT 0 RECESSED VIKII'4G VK 430 4- 4,3 1551' WHITE WH TE 7 A D E TOP BEAM CLAMP EYE ROD P R POWDER DRIVEN STUD WEDGE ANCHOR 0 - RECESSED VIKING VK 43c, x_43 175° WHITE W141TE 3 A F FLUSH SHED. T APPROVALS REQUIRED G H J K CEILING FLANGE SIDE BEAM BRACKET "J' BOLT SHORT CLIP U W C ITY._ OF _TUKLc/ ILA 2 - V'S (Ai rsuv X Y TOTAL THS SHEET 24 1 ALL MATERIAL AND EQUIPMENT TO BE NEW AND UNDERWRITERS APPROVED 2 PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1-6) WHICH ARE END TO END 3 EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA PAMPHLET NO 13 4 PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA PAMPHLET NO 13 5 PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO 13 6 JOINING OF PIPE AND FITTINGS THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO 13 7 OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER W PIPES FROM FREEZING IN AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM.* 8 STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING I5 THE RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL REPRESENTATIVE, SEP - 2 2004 •3;t( A'7( Fire Systems west 219 Frontage Road North, Suite B Pacific, WA 98047 _ (253) 833-1248 fax(253)735-0113 - WA CL IFIRESWI 14081 WA ECL #F1RESWI 055LW 0 Ct FAB BY QC IESrALL BY / DESIGNER DATE JOB NO PAUL- Bd2E 8 -3I -a4 SHEET 2-I I- 9070 I OF=