HomeMy WebLinkAboutPP - 576 INDUSTRY DR - FIDELIS COMMUNICATIONS INC. - PERMITS AND PLANS576 INDUSTRY DR
ASSOCIATED PERMITS
14-F-142 93-F-308
MUM
SITE LOCATION
CITY OF TUKWILA
FIRE DEPARTMENT
444 Andover Park East
Tukwila, WA 98188
206-575-4407
Date application
accepted:
FIRE PROTECTION SYSTEMS PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
**PLEASE PRINT**
Site Address: 576 Industry Drive
Tenant Name: Fidelis Communications New Tenant? -Yes
❑ El- No
Property Owner's Name: Andover Executive Park
Mailing Address: POB 130940, Carlsbad, CA 92013
CONTACT PERSON -if there are questions about the submittal.
Name: Karina Veliz Day Telephone: 206.349.5889
Company Name: Guardian Security Systems
Mailing Address: 1743 First Ave South, Seattle, WA 98134
kveliz@guardiansecurity.com City State Zip
E-mail Address: Fax Number: 206.628.4990
Total number of new/relocated devices or sprinkler heads: 34
Valuation of Project (contractor's bid price): $ 5000.
Scope of Work (please provide detailed information):
Adding -devices to existing IFACP.
King Co. Assessor's Tax No.: 0223400010
Suite Number: Floor:
City State Zip
PERMIT APPLICATION NOTES
Value of Construction - In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules.
Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit
is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or
abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in
writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE
UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY
FOR THIS PERMIT.
BUILDING 0 ER O$ AUTHORI D GENT: f n
-12)
�
Signature: W' Date: AJC,
Print Name: Karina Veliz Day Telephone: 206.349.5889
Plan Permit App.doc
1/2/13 TFD FP Form 8
16'
ACCEPTED
&WITHOUT COM C; N.TS.j 350 f
❑ AS NOTED IN R•=J)
❑ PER THE ATTAC - ED LETTER
The drawings affixed heretd re$ 'ii
reviewed and accepte.1 by tI y oI.
Tukwila Fire De it. A :! 1i+i
or revisions to this, r i ;; aft v this
date will void thi.; n I hill
require a resubrlitt,J re.i� 1r. wings.
Final acceptance is subject to field -
inspection by a representative of this
department
DATE: ! if 7 53 ,BY:,_...101 S/t
CITY OF TUKWILA
575-4407
CtASE T
5 7 5
.L n1WAST2Y fl2
TUKWILA FIRE DEPARTMENT.
Please call: 575.4407
and give this job
No. ;SB 4
and exact address for shut-
down or restoration approval.
TE OP: RISC 14E -A -r 6Cr�..CTisP....
CYfSrNG HEA -r bETF:C.Tmftl, .ZNS1g.,
no
1993
C.�i3�ts
FIDELIS COMMUNICATIONS
FIRE ALARM SYSTEM ADDITION
TUKWILA, WASHINGTON
SHEET #
DESCIPTIO\
FA -01
SHEET INDEX, SY
v130L LIST,. WIRE DESIGNATIONS AND CALCULATIONS
FA -02
TYPICAL WRING AND MOUNTING DETAILS
FA -03
FI
RE ALAR
\1 PLAN AND NAC SINGLE LINE DIAGRAv
HEET INDEX
QUANTITY
EX
1
SYMBOL DESCRIPTION
MODEL
MANUFACTURER BACKBOX
MOUNTING HEIGHT
FACP
FIRE ALARM
CONTROL PANEL
(EXISTING)
D9112
BOSCH
EXISTING
VERIFY
IN FIELD
BPS
REMOTE BOOSTER
POWER SUPPLY
(NEW)
PAD -3
SIEMENS
PAD-3—ENCL
66" A.F.F.
TO TOP
SMOKE DETECTOR
17 ® PHOTOELECTRIC
(NEW)
EX
1
EX
EX
10
5
E
2W—B
SYSTEM
SENSOR
4—INCH
OCTAGONAL BOX
CEILING
OSA
ABOVE CEILING
SMOKE DETECTOR
(EXISTING)
EXISTING EXISTING
EXISTING
ABOVE
CEILING
HEAT DETECTOR
(NEW)
5601 P
SYSTEM
SENSOR
4—INCH
OCTAGONAL BOX
CEILING
HEAT DETECTOR
(EXISTING)
EXISTING EXISTING
EXISTING
CEILING
MANUAL PULL
STATION
(EXISTING)
EXISTING EXISTING
EXISTING
48" A.F.F.
TO CENTER
8
FIRE ALARM
HORN STROBE
(NEW)
ZH—MC—CW SIEMENS
4S BOX
CEILING
FIRE ALARM
STROBE
(NEW)
ZR—MC—CW SIEMENS
4S BOX
CEILING
PIEZOELECTRIC
V TRANSDUCER
(EXISTING)
EXISTING EXISTING
EXISTING
VERIFY
ON FIELD
END—OF—LINE
RESISTOR
N/A
N/A
N/A
N/A
EX
EXISTING DEVICE/
EQUIPMENT
N/A
N/A
N/A
N/A
A.F.F.
ABOVE FINISHED
FLOOR
N/A
N/A
N/A
N/A
EOL
END OF LINE
RESISTOR
N/A
N/A
N/A
N/A
F.B.O.
FURNISHED BY
OTHERS
N/A
N/A
N/A
N/A
RED
AS BUILT
ADD OR CHANGE
N/A
N/A
N/A
N/A
GREEN AS BUILT
REMOVE
N/A
N/A
N/A
N/A
BLUE
AS BUILT
NOTES TO CAD
N/A
N/A
N/A
N/A
WIRE DESIGNATION
FIRE ALARM BOOSTER POWER SUPPLY BATTERY CALCULATION
I Project:; FIDELIS COMMUNICATIONS
Panel ; PAD -3 BOOSTER POWER SUPPLY (ELECTRICAL ROOM)
Date: ;June 23, 2014
Module/Device
Qty
Standby Total Standby Alarm Total Alarm
(mA) (mA) (mA) (mA)
Power Module
1
ATOTAL FIRE ALARM POWER SUPPLY
30
30
0
30
30
30
0
30
B Auxiliary Device Current
0
0
C = Notification Appliance Load (Max. Total / mA)
0
1479
Total(A)
CALCULATION
D Total current ratings of all devices in system (line A + line B + line C)
30 Total(B)= 1509
30
1509
E Total current ratings converted to amperes (line D x .001)
0.03
1.509
F Number of standby hours (24 or 60 per NFPA 72, Chapter 1, 1-5.2.5).
24
G Multiply lines E and F
Total Standby AH
0.72
H Alarm sounding period in hours (5 mins+ .0833 hours)
0.0833
I Multiply lines E and H
Total Alarm AH
0.1256997
J Add lines G and I Total Standby and Alarm AH
0.8456997
K Multiply line J by 1.2 (20% extra insurance to meet desired performance)
1.01483964
12-V DC BATTERY SIZE RECOMMENDED (AMPERE -HOUR) 7
Notification Appliance Circuit Detail
PROJECT: FIDELIS COMMUNICATIONS
PAD -3 BOOSTER POWER SUPPLY (ELECTRICAL RM) ;Wire Resistance 2.58
June 23, 2014 CURRENT TOTAL=1 1479.00
ZR -MC -W @15cd
TOTAL mA=
CALCULATIONS
4
WISE SCHEDULE A\D CONDUIT FILL CHAT
O Without Comments
0 As Noted in Red
O Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current City
standards. Acceptance is subject to errors and
omissions which do not authorize violations of adopted
standards and ordinances, The responsibility for the
adequacy of des4p ;,:, s totally with the designer,
Additions, deietiony, 5 4. s-evisions to these drawing; after
tris date will void this acceptance and will requira a
resubmittal of revised drawings for subsequent approval,
Final acceptance is subject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Date: -.Z-r `( By: VIM s `(
C11 JuK. rek.of-e L .e.0 's 6t' 0,444. . oiSwe 64,+1 .
eNvt4- byredAtt- il4hdl-e etA H.� o►, a�c��� 1 c vc-.:
NOTICE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate must be presented
to the Inspector prior to
commencement of Acceptance
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
termination of the testing
TUKWILA FIRE DEPARTMENT
Nene call 206-575-4407 and
give this Fire Permit No.
:ld exact address for sliut-
;d wn or restor on approval.
WIRE DESIGNATION
PAD
,JUN ;?3 7It1la
i.,U"q lLA FIR
cc /-7.6'
Copyright 2014 by Guardian Security Systems, Inc. All Rights Reserved
co
z
0
z_
LLJ
w
cn0
(1)
1,0
Lv
FAX (206) 628-4990
TEL. (206) 622-6545
z
0
U)
w
w
U)
LU
J
LU
REV. BY:
D M G
WIRE DESIGNATION
SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE
I
S
INITIATION CIRCUIT TWO #16 FPLP
SIGNALING CIRCUIT TWO #14 FPLP
DESCRIPTION
0�
Z
CONDUIT FILL CHART
NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA
TWO 600V #12 AWG THHN/THWN .244 O.D. .0467
TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346
TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191
CONDUIT FILL
CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE
ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM
THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE.
CONDUIT SIZE MAXIMUM FILL
1/2" .12 SQUARE INCH
3/4" .21 SQUARE INCH
1" .34 SQUARE INCH
1-1/4" .60 SQUARE INCH
1-1/2" .82 SQUARE INCH
2" 1.34 SQUARE INCH
FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4.
O Without Comments
0 As Noted in Red
O Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current City
standards. Acceptance is subject to errors and
omissions which do not authorize violations of adopted
standards and ordinances, The responsibility for the
adequacy of des4p ;,:, s totally with the designer,
Additions, deietiony, 5 4. s-evisions to these drawing; after
tris date will void this acceptance and will requira a
resubmittal of revised drawings for subsequent approval,
Final acceptance is subject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Date: -.Z-r `( By: VIM s `(
C11 JuK. rek.of-e L .e.0 's 6t' 0,444. . oiSwe 64,+1 .
eNvt4- byredAtt- il4hdl-e etA H.� o►, a�c��� 1 c vc-.:
NOTICE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate must be presented
to the Inspector prior to
commencement of Acceptance
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
termination of the testing
TUKWILA FIRE DEPARTMENT
Nene call 206-575-4407 and
give this Fire Permit No.
:ld exact address for sliut-
;d wn or restor on approval.
WIRE DESIGNATION
PAD
,JUN ;?3 7It1la
i.,U"q lLA FIR
cc /-7.6'
Copyright 2014 by Guardian Security Systems, Inc. All Rights Reserved
co
z
0
z_
LLJ
w
cn0
(1)
1,0
Lv
FAX (206) 628-4990
TEL. (206) 622-6545
z
0
U)
w
w
U)
LU
J
LU
REV. BY:
D M G
DESCRIPTION
0�
Z
4
0
1
0
I
V)
DATE
a
:c.,
0
2a<aaa
N
�CALE: 1/4"=1'0"
DRAWN BY:
D. GARCIA
DESIGNED BY:
R. VEZZANI
DATE: 06/20/14
BACKROUND PLAN PROVIDED BY:
1.0B NUMBER:
SHEET
FA -0 1
JUNCTI❑N BOX
MOUNTED ON
CEILING FLEX
/
/
/
/
/
/
/
0 0
0 0
4S BOX W/ 1
MOUNTED AGA
CEILING SUPF
TO NEXT DEVICE
G MUD RING
INST
ORT
SMOKE/HEAT DETECTOR
SUSPENDED
ILLUMINATED CEILING
SMOKE/HEAT DETECTOR MOUNTING DETAIL
TRIGGER FROM
EXISTING BOSCH
CONTROL PANEL
0
GND N AC
TB1
0
0
11,d0
0
0
00
PAD -3
POWER SUPPLY
(ELECTRICAL ROOM)
0
INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX
1 + 1- 1 2+ 2- 2 NC C NO + - + - + - + - + -
0
0
0
0
0
3.6k EOL
0
0
0
0
0
0
0
0
0
0
0
PAD-3POWER SUPPLY
WIRING DETAIL
TB2
n__
S
HARD LID
CEILING
SPARE
SPARE
NAC CKT S2
NAC CKT S1
CADDY BAR
4" SQUARE DEEP BOX
7 WITH 1 -GANG RING
CEILING STROBE OR
HORN STROBE
HORN/STROBE & STROBE
MOUNTING DETAIL (DROP CEILING)
TO PAD -3
POWER SUPPLY
HARD ;LID
CEILIING
HORN
STROBE
TYPICAL WIRING AND MOUNTING DETAILS
STROBE
SUPPORT
BRIDGE
4N SQUARE
DEEP BOX
CEILING STROBE OR
HORN STROBE
HORN/STROBE & STROBE
MOUNTING DETAIL (HARD LID)
HORN
STROBE
TYPICAL NAC CIRCUIT WIRING DETAIL
STROBE
HORN
STROBE
EOL
Copyright 2014 by Guardian Security Systems, Inc. All Rights Reserved
'4
CC
1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134
FAX (206) 628-4990
TEL. (206) 622-6545
U)
z
0
U)
w
w
U)
a
w
J
W
REV. BY:
0
2
0
DESCRIPTION
0
Z
4
0
L
0
I
DATE
0
0
N
lD
0
2<<aaa
CD
Zne
F-
0o0o
z
DRAWN BY:
D. GARCIA
DESIGNED BY:
R. VEZZANI
DATE: 06/20/14
BACKROUND PLAN PROVIDED BY:
s0B NUMBER:
i
SHEET
FA -022
1E.
EXIST 1
\,
C)US
TO NEW SIEMENS PAD -3
BOOSTER POWER IN
ELECTRICAL ROOM
t��......X ...)I II,��.�
tAN,k ..I } 01.I ~I......
TO NEW SIEMENS PAD -3
BOOSTER POWER IN
ELECTRICAL ROOM
E)
o -S
\ EW
(:)3[::::..N OFF
S2-1
15Cd
o—S
l`.
r`\F\ E C..
i,;
OUSE
S1-1
15Cd
'1A
NV .............I
[1
N. S2-8
Lao1Cd
r-
S2-7
.30Cd
0
D _1\
_4N
of FIC
EIDE. ,
S2;
\-,d
,„ U,� ' b
yep
EXL)TI \
PREAKR0 ) v1
)-) CPT
cD—S
isk
STING
VV .)[\ <RC.) ..)M /
(N)
l
S2-2
30Cd
Ci
V S1-2
0 30Cd
SHOWER
_--5.5__
15Cd _,
EX STING
OFFICE
S1-3
15Cd
o -S
1J/
(L)
S2-5
15Cd
f �E.1f��
r
21—c
21
OFF
0
DOOR- 3E
LOC,[ LD O I.T.
S2-4
\/c"1 _ 7
EXISTING
(?F Lhi nF
s 1-6
30Cd
ri S1-7
15Cd
:r-
0 F-( I c
N - W
C, ... I... c 1
PROVO ROVI FO
1UIF._)I\J 3IANDARF)
i
M 1 N 31...1NDS
EW STOR.EF..
`.: Y s --1 _. [ _:: _ M
\J j
CONFER.
r
I1
EQL
{
FLAGNOTES:
EXISTING HEAT DETECTOR TO BE REPLACE WITH
NEW SYSTEM SENSOR 2WB SMOKE DETECTOR.
EXISTING HEAT DETECTOR TO BE REMOVE.
EXISTING PIEZOELECTRIC DEVICE TO BE REMOVE.
EXISTING MANUAL PULL STATION TO BE REMOVE.
S2-1
S2-2 S2-3
S2-4
S2-5
S2-6
S2-7 S2-8
15Cd 30Cd 15Cd 15Cd 15Cd 15Cd 30Cd 30Cd
FACP FH BPS
S1-1
30Cd
(ELECTRICAL ROOM)
S1-2
30Cd 15Cd 15Cd 15Cd 30Cd 15Cd
S1-3
S1-4
S1-5
S1-6
S1-7
) 120 VAC, DEDICATED
( BY OTHERS )
NAC SINGLE LINE DIAGRAM
SCALE: NONE
EOL
S1
Copyright 2014 by Guardian Security Systems, Inc. All Rights Reserved
EOL
S2
r
1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134
FAX (206) 628-4990
TEL. (206) 622-6545
z
0
w
w
0)
a
w
J
W
(REV. BY: '
0
2
0
DESCRIPTION
0
z
4
Ct
0
0.0
I
DATE
0
0
<aaa
DRAWN BY:
D. GARCIA
DESIGNED BY:
R. VEZZANI
DATE: 06/20/14
BACKROUND PLAN PROVIDED BY:
\0B NUMBER:
i
SHEET \
FA -03 J