Loading...
HomeMy WebLinkAboutPP - 636 INDUSTRY DR - SUPERIOR FIRE - PERMITS AND PLANS636 INDUSTRY DR ASSOCIATED PERMITS 11-F-170 00-F-001 PO Box 237011 Federal Way WA NINO 206-234-6700 Tel 263417-6776 Fax Fire Com NW, Inc. Battery Calculation Work Sheet Project: Comp View 11 Project 636 — Industry Drive Tukwila WA 98188 This project consists of a tenant improvement to an existing fire alarm system for a 'B' occupancy building that is NOT sprinklered. This scope of work will include installing a new signal expander power supply with new signaling devices and the relocation of existing smoke and heat detectors. This is the battery calculation worksheet is for the new signal expander power supply and the connected signaling devices. i Qty Part # and description Supervised Current mA Alarm Current mA 1 SK5495 power supply 75 205 1 GEC3 Hom strobes 15cd 0 58 2 GEC3 Hom strobes 75cd 0 206 1 GCC Hom strobe 15cd 0 105 1 GCC Hom strobe 30cd 0 124 5 GES3 Strobes 15cd 0 150 3 GES3 Strobes 30cd 0 105 1 GES3 Strobes 110cd 0 103 1 GCS Strobe 75cd 0 167 4,146 Subtotal 75 , 1223 Total hours X24 x083 Subtotal 1800 102 Safety Factor 10% +180 +10 Total 1980 112 Total Current Required 2092 mA or 2.4 amps Battery sized used - 2ea 7 amp batteries Note that the battery calculation for the FACP does not change because all of the smoke and heat detectors are existing devices that are relocated to accommodate the new floor plan. Cn d- N a� 0 E 0 LL -0 -0 0 0 a) 0_ E 0 0 z 0 J 00I rn 0 0 /4 ogre. Lt.. h, at,i-e ors -%o 0 6: 20: 40 PM ❑ Without Comments gAs Noted in Recd Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureat.' for conformance : tth current City standards. Acceptance is subject. tr.; errors and omissions which do not .wt:horize violations of adopted standards and ordinanc=e.. The E'e;oon sibiliiy for the adequacy of design rets ?totally with the designer. Additions, deletions or revisionis +o cl.ese drawings after this date will void this .Dc eptctnce ind Mil require a resubmittal of revised drawings ft ubse=quent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: 7- 7— I ( By: I w 0 kavt rewvote L..2•O. t TUKWILA, FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No. / - E__- leo _ and exact address kw shut- down down or restoration approval. orrs Cc:Y� 5 istlov.). NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. FIRE ALARM PLAN SCALE: 1/8"=1'-0" GENERAL NOTES: 1. ALL WORK IS TO CONFORM TO NATIONAL ELECTRIC CODE STANDARDS. 2. WIRING METHOD IS TO BE OPEN CABLING EXCEPT WHERE IT IS EXPOSED AND BELOW SEVEN FEET - THEN IT IS TO BE IN CONDUIT. 3. ALL JUNCTION BOXES, COVERS, AND BACK BOXES ARE TO BE PAINTED RED. 4. PULL STATIONS ARE TO BE MOUNTED AT 48" TO 53" ABOVE THE FLOOR. 5. ALL WALL MOUNT INDOOR HORNS, STROBES, HORN STROBES, AND SPEAKER STROBES ARE TO BE MOUNTED 80" ABOVE THE FLOOR OR 6' BELOW THE CEILING, WHICHEVER IS LOWER. 6. SMOKE DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE FOLLOWING: A) 36" INCHES AWAY FROM ANY AIR HANDLING SYSTEM DIFFUSER B) NOT IN CLOSE PROXIMITY TO ANY FLUORESCENT LIGHT FIXTURES 7. EXTERIOR HORN / STROBE SHALL BE MOUNTED ON THE TOP 2/3 OF THE OUTSIDE WALL OF THE BUILDING, AS HIGH AS POSSIBLE FOR MAXIMUM VISIBILITY FROM THE FIRE DEPARTMENT ACCESS ROADWAY. 8. ALL WIRING PENETRATING ANY FIRE RATED BARRIER SHALL BE SEALED WITH MATERIAL WHICH WILL PREVENT PASSAGE OF FLAME AND HOT GASES. 9. EXISTING HEAT DETECTORS IN WAREHOUSE AND ABOVE CEILING GRID TO REMAIN. 10. EXISTING PULL STATIONS TO REMAIN. 11. SMOKE DETECTORS AS SHOWN AND IN ALL ROOMS EXCEPT RESTROOMS AND BREAK ROOM. 12. HEAT DETECTORS IN RESTROOMS AND BREAKROOM. ROOF 30cd 15cd 15cd 15cd 15cd 15cd 15cd I.1 1.1 NI WI ►:► to ►:, EOL 15cd 15cd 75cd 75cd 30cd 30cd 30cd 75cd 1.1 1,1 101 161 ►•I 1.1 ►•I 161 FIRST FLOOR FACP 4 TO 120 VAC UNSWITCHED DEDICATED CIRCUIT TO TELCO ROOM FIRE ALARM RISE DIAGRAM SCALE: N.T.S. EQUIPMENT LEGEND DEVICE SYMBOL QUANTITY PART NUMBER DESCRIPTION BACKBOX Edcl; 1 D7412 FIRE ALARM CONTROL PANEL INCLUDED LANNJ 1 -- ANNUNCIATOR INCLUDED LFJ 7 270SP0 MANUAL PULL STATION SINGLE GANG ;s; 1 2W8 SMOKE DETECTOR 4 SQUARE X 1-7/8" DEEP ENi 1 GCC HORI'd STROBE — CEILING MOUNT 4 SQUARE X 1-7/8" DEEP ®4 # 4 GEC3 HORN STROBE — WALL MOUNT 4 SQUARE X 1-7/8" DEEP ®# C 1 GCS STROBE — CEILING MOUNT 4 SQUARE X 1-7/8" DEEP ® # 9 GES3 STROBE — WALL MOUNT 4 SQUARE X 1-7/8" DEEP OO 24 2WB SMOKE DETECTOR 4 SQUARE X 1-7/8" DEEP ❑D 1 WGEC WEATHERPROOF HORN STROBE INCLUDED (`) PROVIDED AND INSTALLED BY OTHERS EXISTING DEVICE TO REMAIN NEW OR EXISTING DEVICE RELOCATED INDICATES CANDELA INDICATES EXISTING INDICATES CEILING MOUNT WIRE LEGEND TYPE DESCRIPTION A 18 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE B 14 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE C 18 AWG, 4 CONDUCTOR 'FPLP' JACKETED CABLE 0 4' 8' 16' SCALE: 1/8"=1*— 0" FIRE COM NW «C Prf/r//i/l////////////////f. PO Box 23700 Federal Way WA 98093 206-234-5700 DATE: 06/27/11 DRAWN: CEA CHECKED: JD APPROVED BY: JD PROJECT NAME: COMP VIEW 636 Industry Drive Tukwila, WA 98188 SCALE: 1/8"=1'-0" NO. DATE REVISION BY SHEET TITLE: FIRE ALARM PLAN JOB NUMBER: 11-027 FA -1 of 1 PAID JUL 21 2011 TUKWILA FIRE ;f7 e/ 0,2,07' 0 r rn TUKWILA FIRE DEPART 'wa l_ Please call: 575.4407 and give this job No.®O—f CD/ and ,:t address for shut' dowit 4r restoration approval. ACCEPTED Without Comments As Noted In Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to tnese drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau./ Date: /�w o By: ,-/.5-(2—