Battery Calculation Work Sheet
Project: Comp View 11 Project
636 — Industry Drive
Tukwila WA 98188
This project consists of a tenant improvement to an existing fire alarm system for a 'B' occupancy
building that is NOT sprinklered. This scope of work will include installing a new signal expander
power supply with new signaling devices and the relocation of existing smoke and heat detectors.
This is the battery calculation worksheet is for the new signal expander power supply and the
connected signaling devices.
i
Qty Part # and description Supervised Current mA Alarm Current mA
1 SK5495 power supply 75 205
1 GEC3 Hom strobes 15cd 0 58
2 GEC3 Hom strobes 75cd 0 206
1 GCC Hom strobe 15cd 0 105
1 GCC Hom strobe 30cd 0 124
5 GES3 Strobes 15cd 0 150
3 GES3 Strobes 30cd 0 105
1 GES3 Strobes 110cd 0 103
1 GCS Strobe 75cd 0 167
4,146 Subtotal 75 , 1223
Total hours X24 x083
Subtotal 1800 102
Safety Factor 10% +180 +10
Total 1980 112
Total Current Required
2092 mA or 2.4 amps
Battery sized used - 2ea 7 amp batteries
Note that the battery calculation for the FACP does not
change because all of the smoke and heat detectors are
existing devices that are relocated to accommodate the
new floor plan.
Cn
d-
N
a�
0
E
0
LL
-0
-0
0
0
a)
0_
E
0
0
z
0
J
00I
rn
0
0
/4 ogre. Lt.. h, at,i-e ors -%o
0
6: 20: 40 PM
❑ Without Comments
gAs Noted in Recd
Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
Prevention Bureat.' for conformance : tth current City
standards. Acceptance is subject. tr.; errors and
omissions which do not .wt:horize violations of adopted
standards and ordinanc=e.. The E'e;oon sibiliiy for the
adequacy of design rets ?totally with the designer.
Additions, deletions or revisionis +o cl.ese drawings after
this date will void this .Dc eptctnce ind Mil require a
resubmittal of revised drawings ft ubse=quent approval.
Final acceptance is subject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Date: 7- 7— I ( By: I
w
0
kavt
rewvote L..2•O. t
TUKWILA, FIRE DEPARTMENT
Please call 206-575-4407 and
give this Fire Permit No.
/ - E__- leo _
and exact address kw shut-
down down or restoration approval.
orrs
Cc:Y� 5 istlov.).
NOTICE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate must be presented
to the Inspector prior to
commencement of Acceptance
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
termination of the testing.
FIRE ALARM PLAN
SCALE: 1/8"=1'-0"
GENERAL NOTES:
1. ALL WORK IS TO CONFORM TO NATIONAL ELECTRIC CODE STANDARDS.
2. WIRING METHOD IS TO BE OPEN CABLING EXCEPT WHERE IT IS EXPOSED AND BELOW SEVEN FEET - THEN IT IS TO BE IN CONDUIT.
3. ALL JUNCTION BOXES, COVERS, AND BACK BOXES ARE TO BE PAINTED RED.
4. PULL STATIONS ARE TO BE MOUNTED AT 48" TO 53" ABOVE THE FLOOR.
5. ALL WALL MOUNT INDOOR HORNS, STROBES, HORN STROBES, AND SPEAKER STROBES ARE TO BE MOUNTED 80" ABOVE THE FLOOR OR 6'
BELOW THE CEILING, WHICHEVER IS LOWER.
6. SMOKE DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE FOLLOWING:
A) 36" INCHES AWAY FROM ANY AIR HANDLING SYSTEM DIFFUSER
B) NOT IN CLOSE PROXIMITY TO ANY FLUORESCENT LIGHT FIXTURES
7. EXTERIOR HORN / STROBE SHALL BE MOUNTED ON THE TOP 2/3 OF THE OUTSIDE WALL OF THE BUILDING, AS HIGH AS POSSIBLE FOR
MAXIMUM VISIBILITY FROM THE FIRE DEPARTMENT ACCESS ROADWAY.
8. ALL WIRING PENETRATING ANY FIRE RATED BARRIER SHALL BE SEALED WITH MATERIAL WHICH WILL PREVENT PASSAGE OF FLAME AND HOT
GASES.
9. EXISTING HEAT DETECTORS IN WAREHOUSE AND ABOVE CEILING GRID TO REMAIN.
10. EXISTING PULL STATIONS TO REMAIN.
11. SMOKE DETECTORS AS SHOWN AND IN ALL ROOMS EXCEPT RESTROOMS AND BREAK ROOM.
12. HEAT DETECTORS IN RESTROOMS AND BREAKROOM.
ROOF
30cd 15cd 15cd 15cd 15cd 15cd 15cd
I.1 1.1 NI WI ►:► to ►:,
EOL
15cd 15cd 75cd 75cd 30cd
30cd 30cd 75cd
1.1 1,1 101 161 ►•I 1.1 ►•I 161
FIRST FLOOR
FACP
4
TO 120 VAC UNSWITCHED
DEDICATED CIRCUIT
TO TELCO ROOM
FIRE ALARM RISE DIAGRAM
SCALE: N.T.S.
EQUIPMENT LEGEND
DEVICE
SYMBOL
QUANTITY
PART NUMBER
DESCRIPTION
BACKBOX
Edcl;
1
D7412
FIRE ALARM CONTROL PANEL
INCLUDED
LANNJ
1
--
ANNUNCIATOR
INCLUDED
LFJ
7
270SP0
MANUAL PULL STATION
SINGLE GANG
;s;
1
2W8
SMOKE DETECTOR
4 SQUARE X 1-7/8" DEEP
ENi
1
GCC
HORI'd STROBE — CEILING MOUNT
4 SQUARE X 1-7/8" DEEP
®4 #
4
GEC3
HORN STROBE — WALL MOUNT
4 SQUARE X 1-7/8" DEEP
®#
C
1
GCS
STROBE — CEILING MOUNT
4 SQUARE X 1-7/8" DEEP
® #
9
GES3
STROBE — WALL MOUNT
4 SQUARE X 1-7/8" DEEP
OO
24
2WB
SMOKE DETECTOR
4 SQUARE X 1-7/8" DEEP
❑D
1
WGEC
WEATHERPROOF HORN STROBE
INCLUDED
(`)
PROVIDED AND INSTALLED BY OTHERS
EXISTING DEVICE TO REMAIN
NEW OR EXISTING DEVICE RELOCATED
INDICATES CANDELA
INDICATES EXISTING
INDICATES CEILING MOUNT
WIRE LEGEND
TYPE
DESCRIPTION
A
18 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE
B
14 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE
C
18 AWG, 4 CONDUCTOR 'FPLP' JACKETED CABLE
0 4' 8'
16'
SCALE: 1/8"=1*— 0"
FIRE COM NW «C
Prf/r//i/l////////////////f.
PO Box 23700 Federal Way WA 98093 206-234-5700
DATE:
06/27/11
DRAWN:
CEA
CHECKED:
JD
APPROVED BY:
JD
PROJECT NAME:
COMP VIEW
636 Industry Drive
Tukwila, WA 98188
SCALE:
1/8"=1'-0"
NO.
DATE
REVISION
BY
SHEET TITLE:
FIRE ALARM PLAN
JOB NUMBER: 11-027
FA -1 of 1
PAID
JUL 21 2011
TUKWILA FIRE
;f7 e/ 0,2,07'
0
r
rn
TUKWILA FIRE DEPART 'wa l_
Please call: 575.4407
and give this job
No.®O—f CD/
and ,:t address for shut'
dowit 4r restoration approval.
ACCEPTED
Without Comments
As Noted In Red
Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current city
standards. Acceptance is subject to errors and
omissions which do not authorize violations of adopted
standards and ordinances. The responsibility for the
adequacy of design rests totally with the designer.
Additions, deletions or revisions to tnese drawings after
this date will void this acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to field test and inspection by
The Tukwila Fire Prevention Bureau./
Date: /�w o By: ,-/.5-(2—