FIRE PROTECTION SYSTEMS PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
**PLEASE PRINT**
King Co. Assessor's Tax No.:
Site Address: 768 Industry Dr. Bldg 16, Tukwila, WA 98188 Suite Number: Floor:
Tenant Name: Healing Place International New Tenant? -Yes ❑ - No
Property Owner's Name: Industrial Park
Mailing Address: 800 Industry Dr 98188
City State Zip
2523049015
CONTACT PERSON -if there are questions about the submittal.
Name: Karina Veliz Day Telephone: 206-349-5889
Company Name: Guardian Security Systems
Mailing Address:1743 First Ave South, Seattle, WA 98134
kveliz@guardiansecurity.com City State Zip
E-mail Address: Fax Number: 206.374.2852
Total number of new/relocated devices or sprinkler heads: 10
Valuation of Project (contractor's bid price): $ 5,000'
Scope of Work (please provide detailed information): Add 10 devices to existing FACP.
PERMIT APPLICATION NOTES
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules.
Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit
is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or
abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in
writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE
UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY
FOR THIS PERMIT.
BUILDING0 NER OR AUTH IED AGENT:
Signature: (O
Date:
Print Name: Karina Veliz Day Telephone: 206.349.5889
Plan Permit App.doc 1/2/13 TFD FP Form 8
HEALING
PLACE INTERNATI0NAL T.I. ANDOVER EX
FIRE ALARM SYSTEM AD
TUKWILA, WASHINGTON
CUTIVE PARK BLDG. 16
I'IION
TUKWILA FIRE DEPARTMENT
Pl s!, call 206-575-4407 and
give this Fire Permit No.
and exact address for shut-
down
hutdown or restoration approval.
SHEET #
DESCRIPTION
FA -01
SHEET INDEX, SYIvBOL LIST, WIRE DESIGNATIONS, CALCULATIONS
AND FLOOR FIDE ALARM PLAN
SHEET INDEX
QUANTITY
EX
EX
2
6
2
EX
EX
EX
SYMBOL DESCRIPTION
MODEL MANUFACTURER BACKBOX
MOUNTING HEIGHT
FACP
EX
FIRE ALARM
CONTROL PANEL
(EXISTING)
EXISTING EXISTING EXISTING
66" A.F.F.
TO TOP
BPS
EX
REMOTE BOOSTER
POWER SUPPLY
(EXISTING)
FCPS-24 NOTIFIER EXISTING
66" A.F.F.
TO TOP
FIRE ALARM
STROBE
(NEW)
SCW SYSTEM SENSOR 4S BOX
CEILING
8N
FIRE ALARM
HORN STROBE
(NEW)
PC2W SYSTEM SENSOR 4S BOX
CEILING
8N
FIRE ALARM
HORN STROBE
(NEW)
P2W SYSTEM SENSOR 4S BOX
80" A.F.F.
TO BOTTOM
® EX
SMOKE DETECTOR
(EXISTING)
EXISTING EXISTING EXISTING
CEILING
®EX HEAT DETECTOR
(EXISTING)
EXISTING EXISTING EXISTING
CEILING
❑F EX MANUAL PULL STATION
(EXISTING)
EXISTING EXISTING EXISTING
48" A.F.F.
TO CENTER
EX
EXISTING
DEVICE
N /A
N/A N/A
N/A
A.F.F.
ABOVE FINISHED
FLOOR
N/A
N/A N/A
N/A
END OF LINE
RESISTOR
N/A
N/A N/A
N/A
F.B.O.
FURNISHED BY N/A
OTHERS
N/A N/A
N/A
I = INITIATION CIRCUIT = #16/2C FPLP WIRES
S = SIGNALING CIRCUIT = #14/2C FPLP WIRES
SYMBOLS LEGEND
1. ALL EQUIPMENT SHALL BE U.L. LISTED
2. ACCESS PANELS TO AREAS THAT REQUIRE SERVICING, TROUBLESHOOTING ETC.
PROVIDED BY OTHERS
3. DO NOT DEVIATE FROM CONDUIT RUNS AS SHOWN ON FLOOR PLANS WITHOUT PRIOR
APPROVAL FROM SYSTEM SUPPLIER (GUARDIAN SECURITY SYSTEMS, INC. TEL.
206-622-6545). FACTORS SUCH AS EXCESSIVE VOLTAGE DROP, ADDITIONAL PARTS,
ENGINEERING, ETC. THAT ARE A RESULT OF CONDUIT RUN DEVIATIONS SHALL BE
THE SOLE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
4. DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIRFLOW, NOR CLOSER THAN
3'-0" (900mm) FROM AN AIR SUPPLY DIFFUSER.
5. ALL 120VAC POWER REQUIREMENTS FOR THE FIRE ALARM SYSTEM SHALL BE
FURNISHED BY THE ELECTRICAL CONTRACTOR AND SHALL MEET ALL REQUIREMENTS
OF THE AUTHORITY HAVING JURISDICTION.
6. ALL FIRE ALARM DEVICE BACK BOXES, FIRE ALARM TERMINAL CABINETS, GUTTERS,
JUNCTION BOXES AND ASSOCIATED CONDUITS SHALL BE FURNISHED AND INSTALLED
BY THE ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. REFER TO FIRE
ALARM SYMBOL LIST AND/OR MOUNTING DETAILS FOR ADDITIONAL INFORMATION.
SYSTEM SUPPLIER PROVIDED BACK BOXES SHALL BE INSTALLED BY ELECTRICAL
CONTRACTOR UNLESS OTHERWISE NOTED.
7, DETECTOR TESTING SHALL BE ACCOMPLISHED PER THE MANUFACTURER'S
INSTRUCTIONS.
8. ALL WIRING SHALL BE CUT FOR IN AND OUT. WIRING SHALL NOT BE LOOPED
THROUGH DEVICES. ALL SPLICED WIRE POSSESSING SHIELDS SHALL HAVE SHIELDS
SPLICED AND TAPPED TO TAPED TO PREVENT GROUND FAULTS.
g, THE ALARM SYSTEM SHALL HAVE AN AUDIBILITY OF NOT LESS THAN 15dB ABOVE
AMBIENT NOISE LEVELS. TESTING SHALL BE ACCOMPLISHED WITH A dB METER.
10. INSTALLATION SHALL BE IN STRICT COMPLIANCE WITH NFPA, LOCAL AND STATE,
NEC AND. CONTRACT DRAWINGS.
11. ALL CONDUIT SIZING AND ROUTING BY ELECTRICAL CONTRACTOR PER NEC AND AHJ.
12. A SET OF INSTALLATION AS—BUILT DRAWINGS SHOWING ACTUAL CONDUIT AND
CONDUCTOR ROUTES SHALL BE KEPT BY PROJECT FOREMAN FOR USE BY G.S.S.
FIELD TECHNICIANS.
GENERAL NOTES
0
t r
Without Comments
As Noted in Rel
Per The Attached Letter
These plans have been revlewed by The Tukwila Fire
cvention Burct,t: for conformance with current City
TO EXISTING FCPS-24
POWER SUPPLY
FLAGNOTE:
1 REPLACE EXISTING WALL MOUNT HORN WITH
NEW SYSTEM SENSOR WALL MOUNT HORiV
STROBE.
A
FIRE ALARM BOOSTER
Project: HEALING PLACE INTERNATIONAL
Panel: EXISTING NOTIFIER FCPS-24
Date: January 14, 2016
Module/Device
POWER
Qty
SUPPLY
T.I.
POWER
Standby
(mA)
BATTERY
SUPPLY
Total Standby
(mA)
CALCULATION
Alarm
(mA)
Total Alarm
(mA)
Power Module
1
91
91
0
145
145
0
TOTAL FIRE ALARM POWER SUPPLY
91
145
B Auxiliary Device Current 0 0
C
Notification Appliance Load (Max. Total / mA) 0 3973
D
Total(A)= 91 Total(B)= 4118
CALCULATION
Total current ratings of all devices in system (line A + line B + line C)
91
4118
E
F
Total current ratings converted to amperes (line D x .001)
0.091
4.118
Number of standby hours (24 or 60 per NFPA 72, Chapter 1, 1-5.2.5).
24
DATE
G
Multiply lines E and F Total Standby AH
2.184
H
Alarm sounding period in hours (5 mins+ .0833 hours)
0.0833
I
J
Multiply lines E and H Total Alarm AH
0.3430294
Add lines G and I Total Standby and Alarm AH
2.5270294
K
Multiply line J by 1.2 (20% extra insurance to meet desired performance)
3.03243528
12-V DC BATTERY SIZE RECOMMENDED (AMPERE -HOUR)
7
Notification Appliance Circuit Detail
PROJECT: HEALING PLACE INTERNATIONAL T.I.
Panel: EXISTING NOTIFIER FCPS-24 POWER SUPPLY Wire Resistance 2.58
Date: January 14, 2016 CURRENT TOTAL= 3973.00
FULLY LOADED CKT
i00
Total Wire Resistance (R )z`I
Total Device Load, Amps (I)
Voltage Drop (E
EOL Voltage
1.50
FULLY LOADED Clt"
DEVICES 0 TOTAL mA='' 1500 14
Total Wire Resistance (R
Total Device Load, Amps (1
Voltage Drop ( E
EQLf Voltage
24.00'
WL"2)*(R/ft)
Total CctLoad)
Er I*R)
1500
0.00
0.00
79? 237!
107 428
1761 176;
132,
TOTAL mA=l 973' 14
22.60!
973
'Total Wire Resistance (R )
1 Device Load, Amps
`Voltage Drop (E)
IL Voltage'
CALCULATIONS
WL " 2) * (R/ft)
Total
Cot Load)
E-1 * R),.,
1.43
0 97
1.40
2.60',
•
S
15
HERBA
S3-1
15Cd ON
®EX
;-ndards. Acceptance is subject to errors and
:••c!Issions which co net authorize violations of adopted
::. r!dards and or(iinances. The responsibility for the
:adequacy of dee'>it: E e .totally wlth the designer.
ddiions, deletior.}, .; ;--.vis'ons to these drawings after
this date will vasa s-;_; .. ' e eptance. and will require a
i esubmittai r F { ,:irawiings-for-sub ent approval.
Final acceptance I . subject to fie'. est and Inspection by
The Tukwila Fire Prevention i3ure
Date: _ a (.0 -I By:
S3-2
30Cd
S3-3
30Cd
#.1_13N
o—S
®EX
GRINDING ROOIv
'M'4
PACKAGING
®EX
S3-4
10Cd
OFFICE 5
S3-7
15Cd
0
S3-6
37 30Cd
N
® EX
®EX
TO EXISTING
FCPS-24
POWER SUPPLY
®EX
STORAGE
N
A completed
Fire Depat
Certificate m
to the ins
commej (cern
ThStin Of F
and Diacc
Failure o^'t
in a Re-insp
termination
S3-9
75Cd
FIRE ALARM PLAN
SCALE:
3/16" = 1'0"
® EX
OFFICE 3
NORTH
NM—
N
S34 0--
15Cd
3N
S3-8
15Cd
OFFICE EX
HORN
STROBE
STROBE
HORN
STROBE
EX
EOL
TYPI A g /IR2� I Dy uua an Jecurity Systems,
O
igned, Tukwila
ent Pre-test
st be presented
,ctor prior to
t of Acceptance
ny Fre Alarm
Tori Systems.
st will result
don Fee and
f the testing
EOL
S3
PAID
JAN 1.9 2016
TUKWILA FIRE
cc
Inc. All Rights Reserved
FAX (206) 628-4990
TEL. (206) 622-6545
U)
z
0
U)
w
w
w
J
LU
IREV. BY: I
0
0
DESCRIPTION
0
z
4
t
0
1
0
'1
UI
DATE
:r
0
cc
0 >Oa
0
W 'Y
�CC
W m Z
cc
W Z �.
>ohm
o E ftZ
Z o1=
Q a
. W
Z
Q W M
w(�
fY
. 172z
CALE: 3/16"=1'0"
DRAWN BY:
D. GARCIA
DESIGNED BY:
F. PETRASKI
DATE: 01/14/16
BACKROUND PLAN PROVIDED BY:
\ 0B NUMBER: 14904-y
SHEET
FA -01