HomeMy WebLinkAboutPP - 887 INDUSTRY DR - CREATIVE ASSEMBLY SYSTEMS - PERMITS AND PLANS887 INDUSTRY DR
ASSOCIATED PERMITS
99-F-401
INITIATING CIRCUIT A
FROM FACP
INDICATING CIRCUIT
FROM FACP
F
V
A
b
>v
PARTIAL FLOOR PLAN SPACE 887 (../
SCALE: 1/4"=1'-0"OD
c>-- A
TO NEXT DEVICE
TO NEXT DEVICE
c --A
Symbols Legend
Symbol
QTY
Description
Mounting
Manufacturer
Part #
C
1
Fire Alarm System Control Panel
Existing
Silent Knight
5207
Control Panel & Modules
1
Photo Smoke Detector
4 Square Deep with 3" Round Ring
System Sensor
1400
0
Main Circuit Board(Existing)
Power Supply/Charger
Initiating Zone Module
Indicating Circuit Module
Masterbox/Line Reversal
Miscellaneous Module A
Miscellaneous Module B
4
Photo Smoke Detector (Existing)
-
System Sensor
2400
0.7
i
1
Heat Detector 135 Fixed Temp (Existing)
-
Fire Lite
HD601
2
Mini Horn -Strobe (Existing)
-
Wheelock
MIZ-FR
Wire Legend
Symbol
Description
Type of Circuit
A
2 14 AWG Solid Fire Rated
Conventional (IDC) Circuit
C
2 14 AWG Solid Fire Rated
Audible (NAC) Circuit
(Pacific Gulf Space #831)
Fire Alarm Systems Battery Calculation Chart
Transfer G & H from
above to complete
Battery Calculations
Total
Standby AH
(G)
A
B
C
D
E
F
Device/
Module
Model
Number
Quantity
of
Device/
Module
Standy
Current
(Amps)
Total
Standby
Current
(B x C)
Alarm
Current
(Amps)
Total
Alarm
Current
(B x E)
Control Panel & Modules
0
0
Main Circuit Board(Existing)
Power Supply/Charger
Initiating Zone Module
Indicating Circuit Module
Masterbox/Line Reversal
Miscellaneous Module A
Miscellaneous Module B
5207
1
0.12
0.12
0.7
0.7
0
0
0
0
0
0
0
0
0
0
0
0
Initiating Devices
0
0
Smoke Detector
Smoke Detector
Smoke Detector
Power Supervision Relay
1400
1
0.0001
0.0001
0.001
0.001
2400
4
0.0001
0.0004
0.067
0.268
0
0
0
0
Notification Appliances
0
0
Horn
Strobe
Horn/Strobe Combination
Bell
Sync Module
Miscellaneous
N/A
0
0
N/A
0
0
MIZ-2415FW
2
N/A
0
0.082
0.164
N/A
0
0
N/A
0
0
0
N/A
0
0
Sum Column for Standby Load (Amps)
Multiply by Required Standby Time (24 or 60 hours) x
Total Standby AH =
Sum Column
Multiply by Required Alarm
Multiply by Required Alarm
0.1205
G
(Amps)
= .083) x
= .167) x
Alarm AH =
24
2.892
for Alarm Load
Time (5 min.
Time (10 min.-
Total
1.133
0.083
0.094039
Transfer G & H from
above to complete
Battery Calculations
Total
Standby AH
(G)
Total
Alarm AH
(H)
Required
AH
(G + H)
Safety
Factor
(multiply)
Total System
Ampere -Hours
Required
2.892
0.094039
2.986039
1.2
3.5832468
NOTE: Always use a battery with a higher AH rating than required!
Battery AH used: 7AH
GENERAL NOTES
1. INSTALLATION SHALL BE ACCOMPLISHED IN STRICT COMPLIANCE WITH NFPA, LOCAL AND STATE AHJ'S,
NEC, AND CONTRACT DRAWINGS.
2. WIRE ROUTING IS DIAGRAMMATIC IN NATURE ONLY AND NOT INTENDED FOR ACTUAL CONDUIT ROUTING.
3. ALL CONDUIT SIZING AND ROUTING BY ELECTRICAL CONTRACTOR PER NEC AND AHJ.
4. THE SYSTEM SHALL BE MONITORED BY A UL LISTED MONITORING STATION BEFORE AHJ TEST.
5. VERIFY ALL LOCATIONS OF DEVICES WITH ELECTRICAL/ARCHITECTURAL PLANS. SCALE AND PLACE
ALL DEVICES PER ELECTRICAL/ARCHITECTURAL PLANS.
6. FIELD VERIFY WATER FLOW, SPRINKLER, SMOKE DAMPERS AND DUCT DETECTOR LOCATIONS.
7. FIELD VERIFY ALL WIRING LOCATIONS AND REQUIREMENTS FOR HVAC AND FAN CONTROL.
8. SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN 3'-0" OF AIR DIFFUSERS.
9. NFPA 5-3.6.1.3 REQUIRES THAT NO SMOKE DETECTORS ARE TO BE INSTALLED UNTIL AFTER FINAL
CONSTRUCTION CLEAN-UP. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO CLEAN-UP MUST
BE CLEANED OR REPLACED ACCORDING TO CHAPTER 7 AND WILL BE INVOICED ON A T&M BASIS.
10. FACP SHALL NOT BE ENERGIZED WITHOUT THE PRESENCE OF TECHNICIANS.
11. ALL CIRCUITS WILL BE PROPERLY TAGGED AND TESTED FOR OPENS, SHORTS, GROUNDS AND PROPER
END OF THE LINE RESISTANCE. EACH CIRCUITS METER READING MUST BE DOCUMENTED AND PRESENTE
TO FIELD TECHNICIAN UPON ARRIVAL ON SITE FOR CHECKOUT.
12. A SET OF INSTALLATION AS -BUILT DRAWINGS SHOWING ACTUAL CONDUIT AND CONDUCTOR ROUTES
SHALL BE KEPT BY PROJECT FOREMAN FOR USE BY FIELD TECHNICIANS.
13. AGREEMENT AND CONFIRMATION OF ALL MILESTONE EVENTS WILL BE MADE WITH PROJECT MANAGER.
SERVICES MUST BE SCHEDULED WITH PROJECT MANAGER WITH A MINIMUM OF TEN WORKING DAYS
NOTICE
ACC tPTED
DESCRIPTION
J
v
iu
Frontage Road North, Suite 9 Pacific, WA. 98047
N
FAX (253) 735-0113
AI Without Comments
O As Noted In Red
Q Per The Attached Letter
.lans have been reviewed by The Tukwila Fire
tion Bureau for cosfsubject to ermance rth rors ors andt city lit rds. Acceptance
ns which do not authorize violations of od rope'
rds and ordinances. The responsibility
finer.
acy of design rests totally
.ns, deletions or revisions
revstdrawings after
te will void eance and will requirea
mitta{ of ised drawings for subsequent appnva
l.
acceptance is subject to field test and inspecti m by
ukwila Fire Prevention Bureau. L�
These
Preve
stand
miss
stand
adeq
Addit
this
resu
14. NO TAPPING OF SIGNALING OR INITIATING ZONE CIRCUITS ARE ALLOWED. T -TAPPING OF STYLE 4
ADDRESSABLE CIRCUITS IS ALLOWED PROVIDING SPLICE IS PROFESSIONALLY INSTALLED, POLARITY IS
OBSERVED, SHIELDS ARE CONTINUOUS AND FREE OF GROUNDS. SHIELDS SHALL BE TERMINATED AT
FACP ONLY. "CABLE SHIELDS SHALL BE SPLICED TOGETHER AT EVERY JUNCTION BETWEEN THE FIRE
ALARM PANEL AND THE LAST DEVICE ON EACH CABLE RUN. SHIELDS AND OTHER FIRE ALARM
CONDUCTORS (EXCEPT POWER GROUNDS) SHALL BE INSULATED AND COMPLETELY FREE FROM CONDUIT
OR EARTH GROUNDS. SHIELDS WILL BE TIED TO GROUND ONLY AT THE FIRE ALARM PANEL BY THE
INSTALLING FIRE ALARM TECHNICIAN."
15. MOUNT AUDIBLE/VISUAL DEVICE BACKBOX AT 80" TO BOTTOM AFF OR 6" BELOW CEILING WHICH EVER
IS LOWER. SEE FLOOR PLANS FOR CANDELA RATING OF DEVICE BEING INSTALLED.
16. AS BUILTS ARE REQUIRED AT TIME OF AHJ ACCEPTANCE. PRECISION ALARM NEEDS RED LINE
AS BUILTS 2 WEEKS PRIOR TO AHJ TESTS.
Fina
The
Dat
W
IL D Q
�J3
0 Q
Fr<
Y. r§ -
z3
Ikt•
(1)