ASSOCIATED PERMITS
98-F-229
Table of Contents
Project Description
Battery Calculation Sheets
Fire Alarm Equipment
Model Description
BK -2400 Ionization Smoke Detectors
692-5A 15 Candela Horn/Strobe
Catalog Sheet
Attached: Fire Alarm System Plans
ACCEPTED
Without Comments
❑ As Noted In Red
❑ Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current city
standards. Acceptance is subject to errors and
omissions which do not authorize violations of adopted
standards and ordinances. The responsibility for the
adequacy of design rests totally "1h the designer.
Additions, deletions or revisions to these drawings after
this date will void this acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Date: /0" 5 V By: 4111 Sly
I(34 :TAIO 547
r ;Ne
TUKWILA FIRE DEPARTMENT.
Please call: 575.4407
and give this job
No. /8—f--,
and exact address for shut
down or restoration approval.
Total Standby
Current
Total Alarm
Current
A
Total supervicory current from the
attached calc sheet
0.12 A
B
Number of standby hours required (24 or
60) per NFPA 721-5.2.5
C
Multiply Lines A & B
24 H
2.8800 AH
D
E
Total alarm current from the attached
calc sheet
4.56 A
Alarm Sounding period (decimal eq)
0.084 H
F
Multiply Lines D & E
0.38304 AH
G
Add Lines C & F
3.2630 AH
H
Multiply G by 120% (Total aH req'd)
3.915648 AH
Minimum Battery Required —>
3.916
Pacific Gulf Properties
Building 1130
9/28/98
Decimel
Minutes Equivalent
4
0.067
5
0.084
6
0.1
10
0.167
BATTERY CALCULATION FORM
date:
Job Name:
Address:
9/28/98
Pacific Gulf Properties
Building 1130, Tukwilla
Device
Quantity
_STANDBY_ Current
per device
ALARM_ Current
Standby
Current
Alarm Current
per device
Silent Knight 5207 FACP
1
120 mA
400 mA
120
400
mA
mA
0
0
mA
mA
0
0
mA
mA
0
0
mA
mA
0
0
mA
mA
0
0
mA
mA
0
0
Current Subtotals (in mA)
120
400
Smoke Detectors
Quantity
STANDBY Current
per device
ALARM_ Current
Standby
Current
Alarm Current
per device
BRK-2400 Smoke Detector
29
0.12 mA
70 mA
3.48
2030
Heat Detector w/Remote
4
0 mA
44 mA
0
176
mA
rnA
0
0
mA
mA
0
0
mA
mA
0
0
mA
mA
0
0
mA
mA
0
0
Current Subtotals (in mA)
3.48
2206
Notification Appliances
Quantity
Current
Standby
Current
Alarm Current
_ALARM_
per device
Wheelock MIZ-24WM
9
127 mA
1143
Amseeco Bell
1
63 mA
63
Wheelock WS3T-24FR
1
115 mA
115
Wheelock Strobe
5
127 mA
635
,,,A
0
mA
0
mA
0
Current Subtotals (in rnA)
1956
Other I Additional Devices/
/ Quantity
STANDBY Current
per device
ALARM_ Current
Standby
Current
Alarm Current
per device
mA
mA
0
0
mA
mA
0
0
mA
mA
0
0
mA
mA
0
0
mA
mA
0
0
mA
mA
0
0
mA
mA
0
0
Current Subtotals (in mA) 4
0
0
Total Current Requirements
Standby
Current
Alarm Current
Current rating of all devices in rnA
123.48
4562
Current ratings converted to amperes (X .001)
0.12
4.56
Mounts to Sine Gang Ring
80" above the floor, 8" below the
ceiling, Which ever Isiower
Existing Unit
Mounts to 310 mud ring
900 Sq Foot spacing
HORN/STROBE
MANUAL PULL STATION
SMOKE DETECTOR
HORN/STROBE
HEAT DETECTOR
DESCRIPTION