HomeMy WebLinkAboutPP - 539 INDUSTRY DR - UNKNOWN - PERMITS AND PLANS539 INDUSTRY DR
ASSOCIATED PERMITS
D98-0020 99-F-265 00-F-377
1:;3WOWS L c -
ACCEPTED
fi
Without Comments
AsNotedlnRed
❑ Per The Attached Letter
These plans have been reviewed by The TukwildFire
Prevention Bureau for conformance with current City
standards. Acceptance is subject to errors and
omissions which do not authorize violations of adOpted
standards and ordinances. The responsibility forthe
adequacy of design rests totally with the designe .
Additions, deletions or revisions to these drawin9; after
this date will void this acceptance and will require a
resubmittal of revised drawings forsubsequent Vproval.
Final acceptance is subject to field test and inspection b�
The Tukwila Fire Prevention Bureau.
rata9/if/f 9 By:
TUKWILA FIRE DEPARTMENT
Please call: 575.4407
and give this job
No. Jia
and exact address for shut-
down or restoration apdroval.
1
c\V°
0
co
06eXP
sa4Esutokz kSkb
Nalc�c..
?.Gt : ac44,-1 Giag1,PPcicciP : fl 1
S394
FILE
Z.1 w,! Cp \- we Co�'cu9
2(4 2 I c ,A +,r.
twstLYe Ct co ,t
Figr@EWM D�1
Alit; ` 3 iggq
. mala
CT.+,T.C1 C nnnor 1HH:U l?1-1 Tc:TI F,f, ?t--nr
WIRE SCHEDULE AND CONDUIT FILL CHART
WIRE DESIGNATION
SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE
F INITIATING CIRCUIT TWO *18 FPL/THHN RED (JACKET)
S SIGNALING CIRCUIT - AUDI❑ TWISTED PAIR W/ SHIELD #14 FPL RED/BLACK
CONDUIT FILL CHART
NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA
TWO 600V #12 AWG THHN/THWN .244 0.D. .0467
TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346
TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191
CONDUIT FILL
CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE
ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM
THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE.
CONDUIT SIZE MAXIMUM FILL
1/2" .12 SQUARE INCH
3/4" .21 SQUARE INCH
1" .34 SQUARE INCH
1-1/4" .60 SQUARE INCH
1-1/2" .82 SQUARE INCH
2" 1.34 SQUARE INCH
FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4.
WIRE DESIGNATION
1. ALL WALL -MOUNTED AUDIBLE & VISUAL SIGNALING APPLIANCES SHALL HAVE
THEIR HEIGHTS ABOVE THE FINISHED FLOOR AT 80" TO BOTT❑M, NFPA 72,
1999 EDITION, ALLOWS 80"-96' FOR VISUAL DEVICES (CH. 4-4,4) AND
REQUIRES A MINIMUM OF 90" TO TOP FOR AUDIBLE DEVICES
OR 6" FROM CEILING, WHICHEVER IS LOWER (CH, 4-3.5).
FOR SLEEPING AREAS GREATER THAN 16' (LINEAR) VISIBLE N❑TIFICATI❑N SHALL BE
WITHIN 16' OF PILL❑W AND GREATER THAN OR EQUAL TO 24" FROM CEILING
TO TOP OF LENS FOR 110cd (CH. 4-4.4.3.2)
2. ALL EQUIPMENT SHALL BE U.L. LISTED.
3. ELECTRICAL CONTRACTOR SHALL FURNISH ACCESS PANELS TO AREAS THAT
REQUIRE SERVICING, TROUBLE SHOOTING, ETC.
4, DO NOT DEVIATE FROM CONDUIT RUNS AS SHOWN ON FLOOR PLANS WITHOUT
PRIOR APPROVAL FROM SYSTEM SUPPLIER (GUARDIAN SECURITY SYSTEMS, INC.,TEL
(206)622-6545). FACTORS SUCH AS EXCESSIVE VOLTAGE DROP, ADDITI❑NAL
PARTS, ENGINEERING, ETC., THAT ARE A RESULT OF CONDUIT RUN DEVIATIONS
SHALL BE THE SOLE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
5. DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIR -FLOW, NOR CLOSER THAN
3 FEET (900rmr1) FROM AN AIR SUPPLY DIFFUSER.
6. ALL FAN SHUTDOWN FUNCTIONS, DAMPER CLOSURES, AND ASSOCIATED
MECHANICAL SYSTEM FIRE ALARM INTERFACE SHALL BE BY MECHANICAL
CONTRACTOR.
7, ALL DUCT SMOKE DETECTORS SHALL BE MOUNTED BY THE MECHANICAL CONTRACTOR,
ALL AIR VEL❑CITY TESTING SHALL BE PERFORMED BY THE MECHANICAL CONTRACTOR.
8. ALL 120VAC POWER REQUIREMENTS FOR THE FIRE ALARM SYSTEM SHALL BE
FURNISHED BY THE ELECTRICAL CONTRACTOR AND SHALL MEET ALL REQUIREMENTS
OF THE AUTHORITIES HAVING JURISDICTION.
9. ALL FIRE ALARM DEVICE BACKB❑XES, FIRE ALARM TERMINAL CABINETS,
GUTTERS, JUNCTI❑N BOXES, AND ASSOCIATED CONDUITS SHALL BE FURNISHED
AND INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED, REFER
TO FIRE ALARM SYMBOL LIST AND/OR MOUNTING DETAILS FOR ADDITIONAL
INF❑RMATI❑N. SYSTEM SUPPLIER PROVIDED BACKBOXES SHALL BE INSTALLED
BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED.
10. SMOKE DETECTOR TESTING SHALL BE ACCOMPLISHED WITH TEST MAGNETS AS PER
THE MANUFACTURER'S INSTRUCTIONS.
11. ALL WIRING, INITIATING DEVICES AND ANNUNCIATOR PANEL SHALL BE
SUPERVISED TO THE PRINCIPAL POINT OF ANNUNCIATI❑N. THE FIRE ALARM
CONTROL PANEL TO SUPERVISE THE ANNUNCIATOR PANEL, ALL INITIATING
AND INDICATING DEVICE CIRCUITS.
12. ALL WIRING SHALL BE CUT FOR IN AND OUT. WIRING SHALL NOT BE
LOOPED THROUGH DEVICES. ALL SPLICED WIRE P❑SSESING SHIELDS SHALL HAVE
SHIELDS SPLICED AND TAPED TO PREVENT GROUND FAULTS.
13. P❑INT AND COMMON ANNUNCIATION AND T -TAPPING
(EXCEPT SLC LOOP) ARE PROHIBITED.
14, PROVIDE 3/4" CONDUIT FROM FIRE ALARM CONTROL PANEL TO TELEPHONE
BACKBOARD FOR OWNER PROVIDED CENTRAL STATI❑N M❑NIT❑RING.
15. THE ALARM SYSTEM SHALL HAVE AN AUDIBILITY OF NOT LESS THAN 15dB ABOVE
AMBIENT N❑ISE LEVELS. TESTING SHALL BE ACCOMPLISHED WITH A dB METER.'
16. ALL FLOW SWITCHES SHALL BE 2 WIRE WITH N❑N-ELECTR❑NIC RETARD TYPE
SIMILAR TO THE SYSTEM SENSOR MODEL "WFD SERIES" ONLY.
17. ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED
PER MANUFACTURER'S SPECIFICATIONS.
18. FIRE ALARM SYSTEM INSTALLATI❑N COMPANY SHALL BE UL LISTED (UUJS),
19. INSTALLATI❑N SHALL BE IN STRICT COMPLIANCE WITH NFPA, LOCAL AND STATE,
NEC AND CONTRACT DRAWINGS
20, ALL CONDUIT SIZING AND ROUTING BY ELECTRICAL CONTRACTOR PER NEC AND AHJ
21. THE FACP SHALL NOT BE ENERGIZED WITHOUT THE PRESENCE OF G.S.S. TECHNICIANS
22. A SET OF INSTALLATI❑N AS -BUILT DRAWINGS SHOWING ACTUAL CONDUIT AND
CONDUCTOR ROUTES SHALL BE KEPT BY PROJECT FOREMAN FOR USE BY G.S.S.
FIELD TECHNICIANS
i
35
r
/
15cd
2F
S
2F (,
2F ("
C
2F n
EXIST, TORE RM,
E
2F
2F ('
15cd
�1 S
2F
-2F
TRAINING RM.
15cd
j
NolpAfrE
2F (Th
-2S
339
(4C
USE IF NEEDED
OTHERWISE
DISREGARD 15cd
2F
TO NEAREST
EXISTING
MANUAL
PULL STATION
J\ -T
/13
15cd
s
IrJ
15cd
J
TO NEAREST
SIGNALING
POWER SOURCE
s
AREA OF WORK
BUILDING #3 FLOOR PLAN
BATTERY SIZING CALCULATION
NEWWWXX*NEWXWMENEXNEWXNEWX*NOC40100KWXIEWWAXNEWWWNEWWWWW*WWW*WWW*WWWWWWW*
Job Nave: HALLW❑OD BUILDING #3
Panel Location: BATTERY ADD-ON
Date Performed: 11-02-2001
QTY, DEVICE NAME
STD-BY(Amps) ALARM(Amps)
8 STR:
RSS( 15CD)
0. 0000
0, 4240
Stand -By Load =
Stand -By Time =
Totals = 0. 0000
0. 0000 Amps
24 Hrs.
Stand -By =
0. 00 Amp*Hrs
Total = Stand -By + Alarm
= 0. 00 + 0.04
= 0. 04 Amp*Hrs
0, 4240
Alarm Load = 0.4240 Amps
Alarm Time = 5/60 Hrs.
Alarm = 0.04 Amp*Hrs
Multiply by De -Rating Factor of 1. 25 ---> 0. 04 * 1. 25 = 0. 04
A( MINIMUM BATTEkY SIZE = 0.04 Anpere*Hours
IE
WWWWWWWXWAXWWWWXWWNEWWWWWWWWWWWNEWWWXWWWWNEWWWWWWWWWWWWWWWWWWWWWW
31(
WORST CASE VOLTAGE DROP CALCULATION
D
Job Name:
Circuit:
Date Performed:
HALLWO❑D BUILDING #3
STROBE CIRCUIT
11-01-2001
8 STR: RSS(15CD) at 0. 0530 Amps each = 0. 4240 Amps
Total = 0. 4240 Amps
Circuit Length = 261 Ft to End Wire Size = #14 AWG
Circuit Load =
0. 4240 Amps Voltage = 24. 0 Volts
(Ckt. Load) ) (Ckt. Length) * 21. 6
Voltage Drop = A 100%
(Circular Mils) NE (Volts)
( 0. 4240 ) * ( 261 ) N 21. 6
Voltage Drop = * 100%
( 4110 ) * ( 24. 0)
Voltage Drop = 2.42%
wmootExwwwwwwwxwwwwwwwwmolookwx
A( VOLTAGE DROP = 2. 42%
QUANTITY
1� 1
2
8
SYMBOL DESCRIPTION MODEL
MANUFACTURER
BACKBOX MOUNTING HEIGHT
12/24
REMOTE POWER SUPPLY PS -12/24-8 WHEELOCK
PROVIDED
66" AFF
TO TOP
F
MANUAL PULL STATION BNG-1
NOTIFIER
4S DEEP BOX W/ 48" AFF
SINGLE GANG RING TO CENTER
AREA HEAT DETECTOR HD -601
NOTIFIER
4S DEEP BOX W/ CEILING
3-0 RING
HEAT DETECTOR
C (ABOVE CEILING)
HD -601
NOTIFIER
4S DEEP BOX W/ ABOVE CEILING
3-0 RING
HEAT DETECTOR
E (EXISTING)
EXISTING
EXISTING
EXISTING EXISTING
FIRE ALARM
STROBE
RSS-2415W WHEELOCK
4S DEEP BOX
NO RING
80" A.F.F.
TO BOTTOM
FIRE ALARM N/A
JUNCTION BOX
BY ELECTRICIAN 4S BOX VERIFY IN
U.O.N. FIELD
FATC
FIRE ALARM N/A
TERMINAL CABINET
BY ELECTRICIAN 18 x 18 x 6 VERIFY IN
U.O.N. FIELD
A.F.F.
ABOVE FINISHED N/A
FLOOR
N/A
N/A N/A
EEL.
END OF LINE
RESISTOR
N/A
N/A
N/A N/A
EX
EXISTING
DEVICE
N/A
N/A
N/A N/A
F.B.O.
FURNISHED BY
OTHERS
N/A
N/A
N/A N/A
N/A
NOT
APPLICABLE
N/A
N/A
N/A N/A
U.D.N.
UNLESS OTHERWISE
NOTED
N/A
N/A
N/A N/A
VL
•
FAX (206) 628-4990
TEL. (206) 622-6545
VERIFY L❑CATI❑N
IN FIELD
N/A
N/A
N/A N/A
WP
WEATHERPROOF
DEVICE
N/A
N/A
N/A
N/A
SYMBOLS LEGEND
(+)
FROM
CONTROL
PANEL
(-)
(+)
FROM
FCPS
(
)
SMOKE/HEAT TDETECTORS
E❑LR
E❑LR
ALARM
WIRING DIAGRAMS
JUNCTION BOX
MOUNTED ON
CEILING SLAB
PREVI❑US DEVICE
11
0 0
0
F-'
EAT DETECTOR
JUNCTI❑N BOX
MOUNTED AGAINST
CEILING SUPPORT
lCDl
SMOKE/HEAT DETECfT❑R
TO N
SUSPENDED
ILLUMINATED CEILING
GOICE/HEAT MOUNTING DIAGRAM
4S DEEP BOX
W/ 4S
EXTENSION BOX
CFP
�j Without Comments
As Noted In Red
El Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current city
nrceptance is subject to errors and
is11-olieMich do not authorize violations of adopted
standards and ordinances. The responsibility for the
adequacy of design rests totally with the designer.
Additions, deletions or revisions to these drawings after
this date will void this acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Date: I /, 5y o ° By:
3eccev Cei/,A/ j 76---c7-CCs SHRH be smC..
-ePc/3-ca 411 H T (L's 6 .(c c&/' Lv,'1
Swn 0 Ice.
4" SQUARE DEEP
BACK BOX WITH
1G TRIM RING
fKWILA FIRE DEPARTMEN4
RI@ago call: 575-4407
Nid give this job
Na,aa -T377
qnd exact address for shut.
CiQ14Gr,1. Orr restoration approval,
HEIGHT REQUIREMENTS
PULL STATION - STROBE
WALL MOUNTED DEVICE MOUNTING ELEVATION
3 NOV ' 3 2000
GENERAL NOTES
SYSTEM CALCULATIONS
MOUNTING DIAGRAMS
Copyright 2000 by Guardian Security Systems, Inc. All Rights Reserved
z
0
uJ
Q
co
0
SCALE:
uJ
DESCRIPTION
O
z
EDEN SYSTEMS
w
J
F -
w
LL
DRAWN BY:
MSH
r4DESIGNED BY:
FRANK CLOSE
"DATE:
11/01/00
p OB NUMBER: 52780
SHEET
FA- 01