HomeMy WebLinkAboutPP - 571 INDUSTRY DR - UNKNOWN - PERMITS AND PLANS571 INDUSTRY DR ASSOCIATED PERMITS 01-F-138 1. ALL WALL -MOUNTED AUDIBLE & VISUAL SIGNALING APPLIANCES SHALL HAVE THEIR HEIGHTS ABOVE THE FINISHED FLOOR AT 80' TO BOTTOM, NFPA 72, 1999 EDITION, ALLOWS 80'-96' FOR VISUAL DEVICES (CR 4-4.4) AND REQUIRES A MINIMUM OF 90' TO TOP FOR AUDIBLE DEVICES OR 6' FROM CEILING, WHICHEVER IS LOWER (CH. 4-3.5). FOR SLEEPING AREAS GREATER THAN 16' (LINEAR) VISIBLE NOTIFICATION SHALL BE WITHIN 16' OF PILLOW AND GREATER THAN OR EQUAL TO 24' FROM CEILING TO TOP OF LENS FOR 110cd (CH. 4-4,4.3.2) 2. ALL EQUIPMENT SHALL BE U.L. LISTED. 3. ELECTRICAL CONTRACTOR SHALL FURNISH ACCESS PANELS TO AREAS THAT REQUIRE SERVICING, TROUBLE SH❑❑TING, ETC. 4. DO NOT DEVIATE FROM CONDUIT RUNS AS SHOWN ON FLOOR PLANS WITHOUT PRIOR APPROVAL FROM SYSTEM SUPPLIER (GUARDIAN SECURITY SYSTEMS, INC., TEL (206)622-6545). FACTORS SUCH AS EXCESSIVE VOLTAGE DROP, ADDITIONAL PARTS, ENGINEERING, ETC., THAT ARE A RESULT OF CONDUIT RUN DEVIATIONS SHALL BE THE SOLE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR, 5. DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIR -FLOW, NOR CLOSER THAN 3 FEET (900run> FROM AN AIR SUPPLY DIFFUSER. 6. ALL FAN SHUTDOWN FUNCTI❑NS, DAMPER CLOSURES, AND ASSOCIATED MECHANICAL SYSTEM FIRE ALARM INTERFACE SHALL BE BY MECHANICAL CONTRACTOR. 7. ALL DUCT SMOKE DETECTORS SHALL BE MOUNTED BY THE MECHANICAL CONTRACTOR. ALL AIR VELOCITY TESTING SHALL BE PERFORMED BY THE MECHANICAL CONTRACTOR. 8. ALL 120VAC POWER REQUIREMENTS FOR THE FIRE ALARM SYSTEM SHALL BE FURNISHED BY THE ELECTRICAL CONTRACTOR AND SHALL MEET ALL REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. 9. ALL FIRE ALARM DEVICE BACKBOXES, FIRE ALARM TERMINAL CABINETS, GUTTERS, JUNCTION BOXES, AND ASSOCIATED CONDUITS SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. REFER TO FIRE ALARM SYMBOL LIST AND/OR MOUNTING DETAILS FOR ADDITIONAL INFORMATION. SYSTEM SUPPLIER PROVIDED BACKBOXES SHALL BE INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. 10. SMOKE DETECTOR TESTING SHALL BE ACCOMPLISHED WITH APPROVED SMOKE AS PER THE MANUFACTURER'S INSTRUCTIONS. 11, ALL WIRING, INITIATING DEVICES AND ANNUNCIATOR PANEL SHALL BE SUPERVISED TO THE PRINCIPAL POINT OF ANNUNCIATION. THE FIRE ALARM CONTROL PANEL TO SUPERVISE THE ANNUNCIAT❑R PANEL, ALL INITIATING AND INDICATING DEVICE CIRCUITS. 12. ALL WIRING SHALL BE CUT FOR IN AND OUT. WIRING SHALL NOT BE LOOPED THROUGH DEVICES. ALL SPLICED WIRE POSSESING SHIELDS SHALL HAVE SHIELDS SPLICED AND TAPED TO PREVENT GROUND FAULTS. 13. POINT AND COMMON ANNUNCIATION AND T -TAPPING (EXCEPT SLC LOOP) ARE PROHIBITED. 14, PROVIDE 3/4" CONDUIT FROM FIRE ALARM CONTROL PANEL TO TELEPHONE BACKBOARD FOR OWNER PROVIDED CENTRAL STATION MONITORING. 15. THE ALARM SYSTEM SHALL HAVE AN AUDIBILITY OF NOT LESS THAN 15dB ABOVE AMBIENT NOISE LEVELS. TESTING SHALL BE ACCOMPLISHED WITH A dB METER. 16. ALL FLOW SWITCHES SHALL BE 2 WIRE WITH NON -ELECTRONIC RETARD TYPE SIMILAR TO THE SYSTEM SENSOR MODEL "WFD SERIES' ONLY. 17. ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED PER MANUFACTURER'S SPECIFICATIONS. 18. FIRE ALARM SYSTEM INSTALLATION COMPANY SHALL BE UL LISTED (UUJS). 19. INSTALLATION SHALL BE IN STRICT COMPLIANCE WITH NFPA, LOCAL AND STATE, NEC AND CONTRACT DRAWINGS 20. ALL CONDUIT SIZING AND ROUTING BY ELECTRICAL CONTRACTOR PER NEC AND AHJ 21. THE FACP SHALL NOT BE ENERGIZED WITH❑UT THE PRESENCE OF G.S.S. TECHNICIANS 22. A SET OF INSTALLATION AS -BUILT DRAWINGS SHOWING ACTUAL CONDUIT AND CONDUCTOR ROUTES SHALL BE KEPT BY PROJECT FOREMAN FOR USE BY G.S.S. FIELD TECHNICIANS QUANTITY 1 SYMBOL DESCRIPTION MODEL MANUFACTURER BACK BOX MOUNTING HEIGHT FACP FIRE ALARM CONTROL PANEL EX EX EX EX AREA HEAT DETECTOR HD 601 FIRELITE 4S DEEP BOX W/ CEILING 3-0 GANG RING A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EOL END OF LINE RESISTOR N/A N/A N/A N/A EOLP END OF LINE POWER MODULE N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.O.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A VL VERIFY LOCATION IN FIELD N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A PARTS LEGEND WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE I INITIATING CIRCUIT TWO #18 FPL RED/GRAY CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #16 AWG FPL TW CABLE .156 0.0. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. GENERAL NOTES WIRE LEGEND N 31E KNEWWWWWWWWWWWWWWWWWWWWWWMEWWWNEWNEWNEWNEWWWNEWWWWWWWWNEWNEWW*WWWWWWW NE E BATTERY SIZING CALCULATION »E WWWWWWWWWWWWWMWWWWWWWWWAMWXWWWWWWWWWWWWWWNEWWWWWWWWWWWWWWWWWWW E Job Name: APPERSON - BLDG 5 Panel Location: FACP BATTERY CALC ADD-ON Date Performed: 06-26-2001 QTY. DEVICE NAME STD-BY(Amps) ALARM(Amps) 1 HEAT: HD601 0.0000 0.0150 Totals = 0.0000 Stand -By Load = 0.0000 Amps Stand -By Time = 24 Hrs. Stand -By = 0.00 Amp*Hrs Total = Stand -By + Alarm = 0.00 + 0,00 = 0.00 Amp*EHrs Multiply 0.0150 Alarm Load = 0.0150 Amps Alarm Time = 5/60 Hrs. by De -Rating Factor of 1.25 ---> Alarm = 0.00 Amp*Hrs 0.00 * 1.25 = 0.00 W3 31EW31 WNE E3M W3EE31 WWWWW31 WWWW31 WWWWW31 WW31 W31 WNEWNENEWNEWAWNEW)K NE MINIMUM BATTERY SIZE = 0.00 Ampere*Hours CALCULATIONS F a ACCEPTS Without Comments As Noted In Red Per The Attached Letter I These plans have been reviav ed by The Tukwila Fire Prevention Bureau for confo,;7 ;.-:. ice with current city. standards. Acceptance is subject to errors and. .,rnissions which do not author ^ !ic! tions of adopted andards and ordinances ,. for the .dequacy of design reser r��r» � > r: _>. _ 6 3signer. d:iitions, deletions or revisions ;., the -Se .rewings after • ,is date will void this acceptance and Mil require a asubmittal of revised drawings tr subsequent approval. "incl acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. TUKWILA FIRE DEPARTMENT Please call: 575-4407 and give this job No. 0 I -F-/3� and exact address for shut- down or restoration approval. Copyright 2001 by Guardian Security Systems, Inc. r Loi z w crs zre 1. 1`r) c0 a' z O I- CD z Lu J F- F - LU Cl) C7 LL1 Q F- 1,0 FAX (206) 628-1+990 03 0 .} /(ALE: NTS rTh Z O O z w co W J f - F -- I -- w DRAWN BY: DEW DESIGNED BY: DEW DATE: 6/26/01 .1..0B NUMBER: SHEET All Rights Reserved FA- 01 REV. BY: 1 ) DESCRIPTION 5 5 7,1 Lu Q 1 •. / 03 0 .} /(ALE: NTS rTh Z O O z w co W J f - F -- I -- w DRAWN BY: DEW DESIGNED BY: DEW DATE: 6/26/01 .1..0B NUMBER: SHEET All Rights Reserved FA- 01