1. ALL WALL -MOUNTED AUDIBLE & VISUAL SIGNALING APPLIANCES SHALL HAVE
THEIR HEIGHTS ABOVE THE FINISHED FLOOR AT 80' TO BOTTOM, NFPA 72,
1999 EDITION, ALLOWS 80'-96' FOR VISUAL DEVICES (CR 4-4.4) AND
REQUIRES A MINIMUM OF 90' TO TOP FOR AUDIBLE DEVICES
OR 6' FROM CEILING, WHICHEVER IS LOWER (CH. 4-3.5).
FOR SLEEPING AREAS GREATER THAN 16' (LINEAR) VISIBLE NOTIFICATION SHALL BE
WITHIN 16' OF PILLOW AND GREATER THAN OR EQUAL TO 24' FROM CEILING
TO TOP OF LENS FOR 110cd (CH. 4-4,4.3.2)
2. ALL EQUIPMENT SHALL BE U.L. LISTED.
3. ELECTRICAL CONTRACTOR SHALL FURNISH ACCESS PANELS TO AREAS THAT
REQUIRE SERVICING, TROUBLE SH❑❑TING, ETC.
4. DO NOT DEVIATE FROM CONDUIT RUNS AS SHOWN ON FLOOR PLANS WITHOUT
PRIOR APPROVAL FROM SYSTEM SUPPLIER (GUARDIAN SECURITY SYSTEMS, INC., TEL
(206)622-6545). FACTORS SUCH AS EXCESSIVE VOLTAGE DROP, ADDITIONAL
PARTS, ENGINEERING, ETC., THAT ARE A RESULT OF CONDUIT RUN DEVIATIONS
SHALL BE THE SOLE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR,
5. DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIR -FLOW, NOR CLOSER THAN
3 FEET (900run> FROM AN AIR SUPPLY DIFFUSER.
6. ALL FAN SHUTDOWN FUNCTI❑NS, DAMPER CLOSURES, AND ASSOCIATED
MECHANICAL SYSTEM FIRE ALARM INTERFACE SHALL BE BY MECHANICAL
CONTRACTOR.
7. ALL DUCT SMOKE DETECTORS SHALL BE MOUNTED BY THE MECHANICAL CONTRACTOR.
ALL AIR VELOCITY TESTING SHALL BE PERFORMED BY THE MECHANICAL CONTRACTOR.
8. ALL 120VAC POWER REQUIREMENTS FOR THE FIRE ALARM SYSTEM SHALL BE
FURNISHED BY THE ELECTRICAL CONTRACTOR AND SHALL MEET ALL REQUIREMENTS
OF THE AUTHORITIES HAVING JURISDICTION.
9. ALL FIRE ALARM DEVICE BACKBOXES, FIRE ALARM TERMINAL CABINETS,
GUTTERS, JUNCTION BOXES, AND ASSOCIATED CONDUITS SHALL BE FURNISHED
AND INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. REFER
TO FIRE ALARM SYMBOL LIST AND/OR MOUNTING DETAILS FOR ADDITIONAL
INFORMATION. SYSTEM SUPPLIER PROVIDED BACKBOXES SHALL BE INSTALLED
BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED.
10. SMOKE DETECTOR TESTING SHALL BE ACCOMPLISHED WITH APPROVED SMOKE AS PER
THE MANUFACTURER'S INSTRUCTIONS.
11, ALL WIRING, INITIATING DEVICES AND ANNUNCIATOR PANEL SHALL BE
SUPERVISED TO THE PRINCIPAL POINT OF ANNUNCIATION. THE FIRE ALARM
CONTROL PANEL TO SUPERVISE THE ANNUNCIAT❑R PANEL, ALL INITIATING
AND INDICATING DEVICE CIRCUITS.
12. ALL WIRING SHALL BE CUT FOR IN AND OUT. WIRING SHALL NOT BE
LOOPED THROUGH DEVICES. ALL SPLICED WIRE POSSESING SHIELDS SHALL HAVE
SHIELDS SPLICED AND TAPED TO PREVENT GROUND FAULTS.
13. POINT AND COMMON ANNUNCIATION AND T -TAPPING
(EXCEPT SLC LOOP) ARE PROHIBITED.
14, PROVIDE 3/4" CONDUIT FROM FIRE ALARM CONTROL PANEL TO TELEPHONE
BACKBOARD FOR OWNER PROVIDED CENTRAL STATION MONITORING.
15. THE ALARM SYSTEM SHALL HAVE AN AUDIBILITY OF NOT LESS THAN 15dB ABOVE
AMBIENT NOISE LEVELS. TESTING SHALL BE ACCOMPLISHED WITH A dB METER.
16. ALL FLOW SWITCHES SHALL BE 2 WIRE WITH NON -ELECTRONIC RETARD TYPE
SIMILAR TO THE SYSTEM SENSOR MODEL "WFD SERIES' ONLY.
17. ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED
PER MANUFACTURER'S SPECIFICATIONS.
18. FIRE ALARM SYSTEM INSTALLATION COMPANY SHALL BE UL LISTED (UUJS).
19. INSTALLATION SHALL BE IN STRICT COMPLIANCE WITH NFPA, LOCAL AND STATE,
NEC AND CONTRACT DRAWINGS
20. ALL CONDUIT SIZING AND ROUTING BY ELECTRICAL CONTRACTOR PER NEC AND AHJ
21. THE FACP SHALL NOT BE ENERGIZED WITH❑UT THE PRESENCE OF G.S.S. TECHNICIANS
22. A SET OF INSTALLATION AS -BUILT DRAWINGS SHOWING ACTUAL CONDUIT AND
CONDUCTOR ROUTES SHALL BE KEPT BY PROJECT FOREMAN FOR USE BY G.S.S.
FIELD TECHNICIANS
QUANTITY
1
SYMBOL DESCRIPTION
MODEL MANUFACTURER BACK BOX
MOUNTING HEIGHT
FACP
FIRE ALARM
CONTROL PANEL
EX EX
EX
EX
AREA HEAT DETECTOR
HD 601 FIRELITE
4S DEEP BOX W/ CEILING
3-0 GANG RING
A.F.F.
ABOVE FINISHED
FLOOR
N/A N/A
N/A
N/A
EOL
END OF LINE
RESISTOR
N/A N/A
N/A
N/A
EOLP
END OF LINE
POWER MODULE
N/A N/A
N/A
N/A
EX
EXISTING
DEVICE
N/A N/A
N/A
N/A
F.B.O.
FURNISHED BY
OTHERS
N/A N/A
N/A
N/A
N/A
NOT
APPLICABLE
N/A N/A
N/A
N/A
U.O.N.
UNLESS OTHERWISE
NOTED
N/A N/A
N/A
N/A
VL
VERIFY LOCATION
IN FIELD
N/A N/A
N/A
N/A
WP
WEATHERPROOF
DEVICE
N/A N/A
N/A
N/A
PARTS LEGEND
WIRE SCHEDULE AND CONDUIT FILL CHART
WIRE DESIGNATION
SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE
I INITIATING CIRCUIT TWO #18 FPL RED/GRAY
CONDUIT FILL CHART
NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA
TWO 600V #12 AWG THHN/THWN .244 O.D. .0467
TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346
TWO CONDUCTOR 300V #16 AWG FPL TW CABLE .156 0.0. .0191
CONDUIT FILL
CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE
ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM
THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE.
CONDUIT SIZE MAXIMUM FILL
1/2" .12 SQUARE INCH
3/4" .21 SQUARE INCH
1" .34 SQUARE INCH
1-1/4" .60 SQUARE INCH
1-1/2" .82 SQUARE INCH
2" 1.34 SQUARE INCH
FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4.
GENERAL NOTES
WIRE LEGEND
N 31E KNEWWWWWWWWWWWWWWWWWWWWWWMEWWWNEWNEWNEWNEWWWNEWWWWWWWWNEWNEWW*WWWWWWW
NE
E
BATTERY SIZING CALCULATION
»E
WWWWWWWWWWWWWMWWWWWWWWWAMWXWWWWWWWWWWWWWWNEWWWWWWWWWWWWWWWWWWW E
Job Name: APPERSON - BLDG 5
Panel Location: FACP BATTERY CALC ADD-ON
Date Performed: 06-26-2001
QTY. DEVICE NAME
STD-BY(Amps) ALARM(Amps)
1 HEAT: HD601 0.0000 0.0150
Totals = 0.0000
Stand -By Load = 0.0000 Amps
Stand -By Time = 24 Hrs.
Stand -By = 0.00 Amp*Hrs
Total = Stand -By + Alarm
= 0.00 + 0,00
= 0.00 Amp*EHrs
Multiply
0.0150
Alarm Load = 0.0150 Amps
Alarm Time = 5/60 Hrs.
by De -Rating Factor of 1.25 --->
Alarm = 0.00 Amp*Hrs
0.00 * 1.25 = 0.00
W3 31EW31 WNE E3M W3EE31 WWWWW31 WWWW31 WWWWW31 WW31 W31 WNEWNENEWNEWAWNEW)K
NE MINIMUM BATTERY SIZE = 0.00 Ampere*Hours
CALCULATIONS
F
a
ACCEPTS
Without Comments
As Noted In Red
Per The Attached Letter
I These plans have been reviav ed by The Tukwila Fire
Prevention Bureau for confo,;7 ;.-:. ice with current city.
standards. Acceptance is subject to errors and.
.,rnissions which do not author ^ !ic! tions of adopted
andards and ordinances ,. for the
.dequacy of design reser r��r» � > r: _>. _ 6 3signer.
d:iitions, deletions or revisions ;., the -Se .rewings after
• ,is date will void this acceptance and Mil require a
asubmittal of revised drawings tr subsequent approval.
"incl acceptance is subject to field test and inspection by
The Tukwila Fire Prevention Bureau.
TUKWILA FIRE DEPARTMENT
Please call: 575-4407
and give this job
No. 0 I -F-/3�
and exact address for shut-
down or restoration approval.
Copyright 2001 by Guardian Security Systems, Inc.
r
Loi
z
w
crs
zre
1.
1`r)
c0
a'
z
O
I-
CD
z
Lu
J
F-
F -
LU
Cl)
C7
LL1
Q
F-
1,0
FAX (206) 628-1+990
03
0
.}
/(ALE: NTS
rTh
Z
O
O
z
w
co
W
J
f -
F --
I --
w
DRAWN BY:
DEW
DESIGNED BY:
DEW
DATE: 6/26/01
.1..0B NUMBER:
SHEET
All Rights Reserved
FA- 01
REV. BY:
1
)
DESCRIPTION
5
5
7,1
Lu
Q
1
•.
/
03
0
.}
/(ALE: NTS
rTh
Z
O
O
z
w
co
W
J
f -
F --
I --
w
DRAWN BY:
DEW
DESIGNED BY:
DEW
DATE: 6/26/01
.1..0B NUMBER:
SHEET
All Rights Reserved
FA- 01