HomeMy WebLinkAboutPP - 722 INDUSTRY DR - UNKNOWN - PERMITS AND PLANS722 INDUSTRY DR
ASSOCIATED PERMITS
00-F-063
AREA OF WORK
TO EXISTING CONVENTIONAL ALARM ZONE
TO EX
--P
STING INDICATING CIRCUIT
2S
2F -- .
75
T
r2F
2S
BLDG. 712
SYST y LAYOUT
JUNCTION BOX
MOUNTED ON
CEILING SLAB
n
0 0
JUNCTION BOX
MOUNTED AGAINST
CEILING SUPPORT
Il
HEAT DETECTOR J
TO NEXT DEVICE
`SUSPENDED
ILLUMINATED CEILING
NEAT DETECTOR MOUNTING
W31E 38EX M MOD* WWWW X( 3101( W NON *W)1E30EX***E3IE*39ENOK WWX WWW EXEWW 3K X01040101( )1010031(WWXE
)IE
BATTERY SIZING CALCULATION
30 EwwwwXE3003Yc30E39iw3rC#E3IE31EXE3Ycwi0E38EwXE31E31E31E3IE3lEwwww31Ew3IE3tEXE30E31E3fE3bEw31Ew3EE3iEw39E3IE3IE3iE3lEXEw30EwXE31Eww30Eww
Job Name'
Panel Locatlorn
Date Performed!
HALLWOOD #2
MAIN FIRE ALARM CONTROL PANEL ADD-ON
02-08-2000
QTY. DEVICE NAME
STD -BY( Amps) ALARM( Amps)
4 HEAT' HD602
0. 0000 0. 0600
Stand -By Load =
Stand -By Time =
Tota Is = 0. 0000
0. 0000 Amps
24 Hrs.
Stand -By =
0, 00 Amp*Hrs
Tota l = Stand -By +Alarm
= 0. 00 + 0, 00
= 0. 00 Amp*Hrs
Alarm Load =
Alarm Time =
0. 0600
0. 0600 Amps
5/60 Hrs.
A l arm =
Multiply by De -Rating Factor of 1.25 --->
0. 00
0. 00 Amp*Hrs
NE 1.25= 0.01
3IEXEXE3E3lE*31EXEW31E31E31E3EWWWW31E*30E*3IfWWWWXE31EWWWW*31E30EXEXEW31EXE3E31031E31E31E31 W
31E
39E MINIMUM BATTERY SIZE = 0. 01 Ampere*Hours
31E
30E
31E
XE'
31fW30EaWWWW31E E31Ei3E E3XW31E3k3iEr'Yc30E3. AEW3Yc31'c300XE3i3r'E3iEW C39EiPEW3 'E3YWWWW#iXEW39EWW
XEXE3fE3EXEXE31<3 XEXEXEXEXEXEXEXE30EWXE31EXE31EXEXE3 31;XE31fW3 WWNEX E3EE3 W34E30E3 W30EW31EXE31E3IEWWXEWXE3IE3iE3 31E31E31EXE3i W
31E 30E
31E
WORST CASE VOLTAGE DROP CALCULATION
* XE
E31EWMMXENEXE 3# W M MWitiNENEX tEXE 3IE OKNE 3iE EWMW E3f AMO X31; XE MEXEXOXXE38E31f31E3101E
Job Name'
CIrcuItl
Date Performed!
HALLWOOD #2
STROBE ADD-ON TO EXISTING CIRCUIT
02-08-2000
1 H/S= NS -2475W at
1 SIR' RSS( 75CD) at
0. 1640 Amps each = 0. 1640 Amps
0. 1400 Amps each = 0. 1400 Amps
Circuit Length =
Circuit Load =
Voltage Drop =
Voltage Drop =
Total = 0.3040 Amps
300 Ft to End Wire Size = #14 AWG
0. 3040 Amps Voltage = 24. 0 Volts
(Ckt. Load) A (Ckt. Length) 3 21. 6
(Circular Mils) X( (Volts)
( 0. 3040) 31(
300 ) * 21. 6
4110 ) *( 24.0)
Voltage Drop = 2. 00%
WWWKW30EW30E3Y)KX X XWX(X0KWWX(MOIE31E3KWNEW
31E 31(
VOLTAGE DROP = 2. 00% A
349K i1EWWWW !EXE 'XE3IEWWWWWWWW3I;X WWWW
SYST CULATIONS
4S DEEP BOX
EXTENSION BOX
4' SQUARE DEEP
BACK BOX WITH
1G TRIM. RING
HEIGHT REQUIREMENTS
A 100%
A.100%
100%
ALL WALL -MOUNTED AUDIBLE & VISUAL SIGNALING APPLIANCES SHALL HAVE
THEIR HEIGHTS ABOVE THE FINISHED FLOOR AT 90' TO BOTTOM. NFPA 72,
1996 EDITION, ALLOWS 80'-96' FOR VISUAL DEVICES (CH, 6-4.4) AND
REQUIRES A MINIMUM OF 90' TO TOP FOR AUDIBLE DEVICES
OR 6' FROM CEILING, WHICHEVER IS LOWER (CH. 6-3.5).
FOR SLEEPING AREAS GREATER THAN 16' (LINEAR) VISIBLE NOTIFICATION SHALL BE
WITHIN 16' OF PILLOW AND GREATER THAN OR EQUAL TO 24' FROM CEILING
TO TOP OF LENS FOR 110cd (CH. 6-4.4.3.2)
2. ALL EQUIPMENT SHALL BE U.L. AND C.S.F.M. LISTED.
3. ELECTRICAL CONTRACTOR SHALL FURNISH ACCESS PANELS TO AREAS THAT
REQUIRE SERVICING, TROUBLE SHOOTING, ETC.
4. DO NOT DEVIATE FROM CONDUIT RUNS AS SHOWN ON FLOOR PLANS WITHOUT
PRI❑R APPROVAL FROM SYSTEM SUPPLIER (GUARDIAN SECURITY SYSTEMS, INC., TEL
(206)622-6545). FACTORS SUCH AS EXCESSIVE VOLTAGE DROP, ADDITIONAL
PARTS, ENGINEERING, ETC.;; THAT ARE A RESULT OF CONDUIT RUN DEVIATIONS
SHALL EE THE SOLE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
5. DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIR -FLOW, NOR CLOSER THAN
3 FEET (900rw) FROM AN AIR SUPPLY DIFFUSER.
6. ALL FAN SHUTDOWN FUNCTIONS, DAMPER CLOSURES, AND ASSOCIATED
MECHANICAL SYSTEM FIRE ALARM INTERFACE SHALL BE BY MECHANICAL
CONTRACTOR.
7. ALL DUCT SMOKE DETECTORS SHALL BE MOUNTED BY THE MECHANICAL CONTRACTOR.
DUCT SMOKE DETECTORS EXPOSED TO THE WEATHER SHALL BE WEATHER
PROTECTED BY THE MECHANICAL CONTRACTOR, ALL AIR VELOCITY TESTING
SHALL BE PERFORMED BY THE MECHANICAL CONTRACTOR.
8. ALL 120VAC POWER REQUIREMENTS FOR THE FIRE ALARM •SYSTEM SHALL BE
FURNISHED BY THE ELECTRICAL CONTRACTOR AND SHALL MEET ALL REQUIREMENTS
OF THE AUTHORITIES HAVING JURISDICTION.
9. ALL FIRE ALARM DEVICE BACKBOXES, FIRE ALARM TERMINAL CABINETS,
GUTTERS, JUNCTION BOXES, AND ASSOCIATED CONDUITS SHALL BE FURNISHED
AND INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. REFER
TO FIRE ALARM SYMBOL LIST AND/DR MOUNTING DETAILS FOR ADDITIONAL
INFORMATION. SYSTEM SUPPLIER PROVIDED BACKBOXES SHALL BE INSTALLED °
BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED,
10. SMOKE DETECTOR TESTING SHALL BE ACCOMPLISHED WITH TEST MAGNETS AS PER
THE MANUFACTURER'S INSTRUCTIONS.
11. ALL WIRING, INITIATING DEVICES AND ANNUNCIATOR PANEL SHALL BE
SUPERVISED TO THE PRINCIPAL POINT DF ANNUNCIATION. THE FIRE ALARM
CONTROL PANEL TO SUPERVISE THE ANNUNCIAT❑R PANEL, ALL INITIATING
AND INDICATING DEVICE CIRCUITS.
12. ALL WIRING SHALL BE CUT FOR IN AND OUT. WIRING SHALL NOT BE
LOOPED THROUGH DEVICES.
13. POINT AND COMMON ANNUNCIATION AND T -TAPPING
(EXCEPT SLC LOOP) ARE PROHIBITED.
14. PROVIDE 3/4' CONDUIT FROM FIRE ALARM CONTROL PANEL TO TELEPHONE
BACKBOARD FOR OWNER PROVIDED CENTRAL STATION MONITORING.
15. THE ALARM SYSTEM SHALL HAVE AN AUDIBILITY OF NOT LESS THAN 15dB ABOVE
AMBIENT NOISE LEVELS. TESTING SHALL BE ACCOMPLISHED WITH A dB METER.
16. ALL FLOW SWITCHES SHALL BE 2 WIRE WITH NON -ELECTRONIC RETARD TYPE
SIMILAR TO THE SYSTEM SENSOR MODEL 'WFD SERIES' ONLY.
17. ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED
PER MANUFACTURER'S SPECIFICATIONS.
18. SYSTEM SHALL BE FURNISHED AND INSTALLED BY A NESCO AFFILIATE AND
AUTHORIZED NOTIFIER DISTRIBUTOR.
19. FIRE ALARM SYSTEM INSTALLATION COMPANY SHALL BE UL LISTED (UUJS).
20. INSTALLATION SHALL BE IN. STRICT COMPLIANCE WITH NFPA, LOCAL AND STATE,
NEC AND CONTRACT DRAWINGS
21. ALL CONDUIT SIZINGAND ROUTING BY ELECTRICAL CONTRACTOR PER NEC AND AHJ
22. THE FACP SHALL NOT BE EERGIZED WITHOUT THE PRESENCE OF G.S.S. TECHNICIANS
23. A SET OF INSTALLATION AS -BUILT DRAWINGS SHOWING ACTUAL CONDUIT AND
CONDUCTOR ROUTES SHALL BE KEPT BY PROJECT FOREMAN FOR USE BY G.S.S.
FIELD TECHNICIANS
44S/ DEEP BOX
WEXTENSION BOX
4' SQUARE DEEP
BACK BOX WITH
1G TRIM RING
HEIGHT REQUIREMENTS
PULL STATION - STROBE PULL STATION - HORN/STROBE
WALL MOUNTED FIRE ALARM
EV1CF MOUNTING ELEVATIONS
NOTES
QUANTITY
1
SYMBOL DESCRIPTION
MODEL
MANUFACTURER BACKBOX
MOUNTING HEIGHT
Ufl AREA HEAT DETECTOR HD -602 NOTIFIER
4S DEEP BOX W/
3-0 RING
CEILING
FIRE ALARM
75 HORN/STROBE
NS -2475W WHEELOCK
RED
4S DEEP BOX
NO RING
80" A.F.F.
TO BOTTOM
gpFIREOBE ALARM
STR
RSS-2415W WHEELOCK
RED
4S DEEP BOX
NO RING
80" A.F.F.
TO BOTTOM
aFIRE ALARM
JUNCTION BOX
N/A
BY ELECTRICIAN 4S BOX
U.O.N.
VERIFY IN
FIELD
FATC
FIRE ALARM
TERMINAL CABINET
N/A
BY ELECTRICIAN 18 x 18 x 6
U.O.N.
VERIFY IN
FIELD
A.F.F.
ABOVE FINISHED
FLOOR •
N/A
N/A
N/A
N/A
EOL
END OF LINE
RESISTOR
N/A
N/A
N/A
N/A
END OF LINE
POWER MODULE
N/A
N/A
N/A
N/A
EX
EXISTING
DEVICE
N/A.
N/A
N/A
N/A
F.B.O.
FURNISHED BY
OTHERS
N/A
N/A
N/A
N/A
N/A
NOT
APPLICABLE
N/A
N/A
N/A
N/A
U.O.N. UNLESS OTHERWISE N/A
NOTED
N/A
N/A
N/A
VL
VERIFY LOCATIDN N/A
IN FIELD
N/A
N/A
N/A
WP
WEATHERPROOF
DEVICE
N/A
N/A
N/A
N/A
SYMBOL LIST
WIRE SCHEDULE AND CONDUIT FILL CHART
- WIRE DESIGNATION •
SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE
F INITIATING CIRCUIT TWO #18 FPL/THHN RED (JACKET)
S SIGNALING CIRCUIT - AUDIO TWISTED PAIR V/ SHIELD #14 FPL RED/BLACK
CONDUIT FILL CHART
NO. OF CONDUCTORS VOLTS WERE SIZE TYPE DIMENSIONS AREA
TWO 600V 112 AWG THHN/THWN .244 O.D. .0467
TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346
TWO CONDUCTOR 300V ,.18 AWG FPL TW CABLE .158 O.D. .0191
CONDUIT FILL
CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE
ABOVE CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM ALL DIMENSION FROM
THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE.
CONDUIT SIZE MA4MUM FILL
- 1/2" .12 SQUARE INCH
r 3/4' .21 SQUARE INCH
1' .34 SQUARE INCH
1-1/4' .60 SQUARE INCH
1-1/2' .82 SQUARE INCH
2 1.34 SQUARE INCH
FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9. TABLE 4.
RETURN TO
EXISTING ZONE
(+)
WIRE DESIGNATIONS
FROM
EXISTING ZONE.
(-)
RETURN TO
EXISTING
CIRCUIT
(+)
FROM
EXISTING
CIRCUIT
(-)
4EAT DETECTORS
ALARM ST%OE3ES AND I -4O N/STROE3FS
TUKWILA FIRE DEPARTMENT
Please call: 575-4407
and give this job
No. 00--r' O(o3
and exact address for shut'
down or restoration approval,.
L
Without comments
As Noted in Red
Per The Attached Letter
These plans have bean reviawod by The Tukwila Fire
Prevention Bureau for conte r:nen e tvith current city
standards. Acceptance is subject to errorand
omissions whichd!o not authorize vl at.ion
standards and ordinances. The Ie pc ° i i - ler the
adequacy of design rests totally with
Additions, deletions or revisions these di awing, after
this date will void this acceptance and will require a
resubmittal of revised drawings for subsequent approval
Final acceptance is subject to fle1d test and inspection ,y
The Tukwila Fire Prcvontion Cureeu.
Date: 2 -/_7- Oct By;
s1/
CZS
11mm
M_
00
rn
0
0
0
co
to
U5
0
N
z
O
0n
W
0Y
DESCRIPTION
ISSUED FOR PLAN CHECK
0
A
0
co
tU
O
z
J
F
>21
O
2
W
9JJ
1
O
z
�w[:,] 'mu\! ,,/
1/8" = 1'
DRAWN BY:
JJD
DESIGNED BY:
FRANK CLOSE
DATE: 2/8/00
\ OB NUMBER: 52567
MOUNTING DIAG
S
-: AMS
Copyright 2000 by Guardian Security Systems, Inc. All Rights Reserved
J
SHEET
FAO19
WE
FF_B 14 2000
C1