FIRE PROTECTION SYSTEMS PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
**PLEASE PRINT**
site Address: 14418 44th Lane S.
Tenant Name: Foster Plat lot 2
Property Owner's Name: Soundbuilt Homes
King Co. Assessor's Tax No.:
Suite Number: Floor:
New Tenant? 0 - Yes ❑ - No
Mailing Address:
City State Zip
CONTACT PERSON -if there are questions about the submittal.
Name: Mike Hutchinson Day Telephone:
Company Name: Evergreen Fire Protection
Mailing Address: PO BOX 998 Puyallup 98371
City State Zip
E-mail Address: Evergreenfirepro@msn.com Fax Number: 253-252-7943
Valuation of Project (contractor's bid price): $ 4100.00
Scope of Work (please provide detailed information): new NFPA 13D fire sprinkler system
PERMIT APPLICATION NOTES
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules.
Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit
is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or
abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in
writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE
UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY
FOR THIS PERMIT.
BUILDING OWNER OR AUTHORIZED AGENT:
Signature:
Print Name: Mike Hutchinson
Plan Permit App.doc 5/14/10
Date: 10/15/2015
253-381-4456
TFD FP Form 8
Z
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
1>C-012.3
/s 11 -
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Project:iy
iir, ' Pst
.7.- 2—
Type of Inspection:
Ar
Address:
Suite #: /g is
YVA Ln
Contact Person:
Special Instructions:
Occupancy Type:
Phone No.:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
-"Rc7/ s613s
f;/f—Pis
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
i
Inspector(.. Aii,
Date:L46// 6,
Hrs.: J o
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
1
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
Di5_Oia3
A --s- /77
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Project:Type
-65
Pin- f. Z
of Inspection:
SPcoP liii0,6 th<-
Address: it/yl U
Suite #: �l
t4 ti LNS
Contact Person:
Permits:
Special Instructions:
Phone No.:
4..Approved per applicable codes.
riCorrections required prior to approval.
COMMENTS:
cA.Ju T -- 3 b G- f
T:04-Cni$ -- olL
0
— To Co U
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Inspector: i,.1 fvz.•(-2___
Date: 4/7427),(0
Hrs.: 1
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
BATE: '10/15/2015 C:\PROGRAM FILES\HRS SYSTEMS\HHOUSE34\2603.rdf Page 1
EVERGREEN FIRE PROTECTION, INC.
10509 64th AVENUE E
PUYALLUP,WA 98373
RESIDENTIAL SPRINKLER SYSTEM
HYDRAULICS CALCULATION REPORT
FOR
Foster Plat lot 2
Tukwilla
14418 44th Lane S.
Date: 10/15/2015
File No:
Data File Name: 2603.rdf
SPRINKLER SPACING
256.0 sq. ft./spklr.(max) Max. Dist. Bet. Spklrs: 16.0 ft.
Min. Dist. Bet. Spklrs: 8.0 Max. Dist. Spklr. to Wall: 8.0 ft.
SPRINKLER SPECIFICATIONS
Mfr: RASCO Descr: RA0612 RFC43 Fl Conc .Pend.(16x16) K=4.30
Calculated K Factor for Arm -Overs & Drops:
1.0 ft. x 1.101 in. Drop: K=4.26 (Incl. 1 Tee)
0.0 ft. x 1.101 in. Arm -Over: K=4.25 (Incl. 1 Tee & 1 Ell)
PIPE SPECIFICATIONS
Type: CPVC S-40 HWC: 150
WATER SUPPLY
Source: Public Test Date: By:
Static: 60.0 psi Resid: 0.0 psi Flow: 0.0 gpm
Public Main Size: 0 in
Domestic Demand: 0.0 gpm at node number 0
SPRINKLER DEMAND
No.Spklrs. Min Spklr. Press. Node Total Avail. Req'd
Flowing Flow (psi) No. Flow Press. Press.
1 13.0 9.3 1 13.0 60.0 33.6
2 13.0 9.3 1 26.4 60.0 46.5
REVIEWING AUTHORITY
City of Tukwilla
•
1A3ZNOTON STATE
CERTIFICATE OF COMPETENCY
FIRE PROTECTION SPRINKLER SYSTEMS
Michael D. Hutchinson
1166.0599 -BG Level 2
Evergreen Fire Protection, Inc.
•
•
E rE: '10/15/2015 C:\PROGRAM FILES\HRS SYSTEMS\HHOUSE34\2603.rdf Page 2
PIPE & NODE DATA
P # END LEN FIT.
HWC NOD DIA EQV.LN
RESULTS OF ANALYSIS
FIXD
LOSS EL SP
PUMP (FT) (K)
* FLOW ANALYSIS
* 1 sprinkler flowing * 2 sprinklers flowing
* *
*DISCH FLOW PF PT *DISCH FLOW PF PT
* (GPM) FL/FT PE (PSI)*(GPM) FL/FT PE (PSI)
* *
1 1 13.00 2LB ---- 20.0 4.26 13.0 -13.0 0.86 9.3 13.0 -13.0 0.86 9.3
150 3 1.101 15.0 ---- 20.0 ---- ---- -0.03 0.00 10.2 ---- -0.03 0.00 10.2
2 2 2.00 B ---- 20.0 4.26 ---- 0.0 0.00 10.2 13.4 -13.4 0.23 9.9
150 3 1.101 5.0 ---- 20.0 ---- ---- 0.00 0.00 10.2 ---- -0.03 0.00 10.2
3 3 37.00 2L2B4R ---- 20.0 ---- ---- -13.0 1.87 10.2 ---- -26.4 6.95 10.2
150 4 1.101 24.0 ---- 20.0 ---- ---- -0.03 0.00 12.0 ---- -0.11 0.00 17.1
4 4 10.00 B ---- 20.0 ---- ---- -13.0 0.46 12.0 ---- -26.4 1.71 17.1
150 5 1.101 5.0 ---- 10.0 ---- ---- -0.03 4.33 16.8 ---- -0.11 4.33 23.2
5 5 30.00 2L5R ---- 10.0 ---- ---- -13.0 1.38 16.8 ---- -26.4 5.13 23.2
150 6 1.101 15.0 ---- 10.0 ---- ---- -0.03 0.00 18.2 ---- -0.11 0.00 28.3
6 6 10.00 4R ---- 10.0 ---- ---- -13.0 0.43 18.2 ---- -26.4 1.60 28.3
150 7 1.101 4.0 ---- 0.0 ---- ---- -0.03 4.33 23.0 ---- -0.11 4.33 34.2
7 7 1.00
150 8 1.101
-5.0
0.0 ----
8 8 80.00 4L ----
150 9 1.598 28.0 ----
9 9 1.00
150 10 1.101
-5.0
0.0 ----
0.0 ---- ---- -13.0 0.03 23.0 ---- -26.4 0.11 34.2
0.0 ---- ---- -0.03 0.00 28.0 ---- -0.11 0.00 39.3
0.0 ---- ---- -13.0 0.54 28.0 ---- -26.4 2.01 39.3
0.0 ---- ---- 0.00 0.00 28.5 ---- -0.02 0.00 41.3
0.0 ---- ---- -13.0 0.03 28.5 ---- -26.4 0.11 41.3
0.0 SRCE ---- -0.03 0.00 33.6 ---- -0.11 0.00 46.5
Legend:
P - Pipe #
DIA - Pipe Diameter
EQV. LN - Pipe Equivalent Length
PUMP - Pump Pressure
SP - K -Factor
FLOW - Flow Rate
PF - Pressure Loss due to Friction
PT - Total Pressure at Node
Node Notes
Pipe Notes
LEN - Pipe Length
FIT. - Pipe Fittings
FIXD LOSS - Fixed Loss Device
EL - Node Elevation
DISCH - Discharge in gpm
FL/FT - Friction Loss per Foot
PE - Pressure Loss due to Elevation
Fitting Code Letters:
E=45 Ell, L=90 Ell, B=TeeBch, R=TeeRun, C=Couplg, S=SwgChk, G=GatV1v, X= X,
Y=
DTE:'10/15/2015 C:\PROGRAM FILES\HRS SYSTEMS\HHOUSE34\2603.rdf Page 3
The maximum velocity of water flow occurs in pipe 7
at 4.38 ft/s with 1 sprinkler flowing.
The maximum velocity of water flow occurs in pipe 4
at 8.91 ft/s with 2 sprinklers flowing.
PIPE FITTINGS TABLE
Pipe Table Name: standard.npt
PAGE: C MATERIAL: CPVC S-40 HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E L B R C S G X Y Z
45 Ell 90 Ell TeeBch TeeRun Couplg SwgChk GatV1v X Y Z
1.101 1.00 5.00 5.00 1.00 1.00 8.00 2.00 0.00 0.00 0.00
1.598 2.00 7.00 8.00 1.00 1.00 14.00 3.00 0.00 0.00 0.00
Sprinkler system has been hydraulically calculated with the
HASS HOUSE 3.4 computer program (License No. R609099990)
to provide an average imbalance of 0.010 gpm at each node and
a maximum imbalance of 0.10 gpm with one sprinkler
flowing, and 0.010 gpm at each node and maximum imbalance
of 0.06 gpm with 2 sprinklers flowing in accordance
with NFPA 13 and 13D or 13R.
The minimum source pressure is 20.0 psi with a minimum required pressure
of 46.5 psi and a 7 minute flow of 185 gal. and a 10 minute flow of 264.3 gallons.
The minimum pressure at any node is 9.3 psi at node 1.
Under full flow conditions the minimum source pressure is 20.0 psi with a minimum
of 60.0 psi and a 7 minute flow of 224 gal. and a 10 minute flow of 320.0 gallons.
The minimum pressure at any node is 14.2 psi at node 1.
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
ATE: C:\PROGRAM FILES\HRS SYSTEMS\HHOUSE34\2603.rdf Page 4
P
R
E
S
S
U
R
E
P
S
I
WATER SUPPLY CURVE
60.0 0A CC
54.0
48.0
42.0
36.0
30.0
24.0
18.0
12.0
6.0
CB
0.0 1 1 1 1 1 I
04 8 12 16 20 24
28
I I I
32 36 40
FLOW (GPM)
Static = 60.0 psi (fixed pressure)
(1 sprinkler flowing) (2 sprinklers flowing)
A = Available Water Supply
60.0 psi @ 13.0 gpm
B = Required Water Supply
33.6 psi @ 13.0 gpm
C = Available Water Supply
60.0 psi @ 26.4 gpm
D = Required Water Supply
46.5 psi @ 26.4 gpm
V
AI\
COV'D PATIO
FAVILY 00M
13-2 X 15-0
NOOK
T
L_
TO UPPER FLOOR
SPRINKLER RISER
PWD��
TILITY
ALL
3 CA
GARAGE
KITCHEN
—6 X 15-0
PANT
ARCH
DINING ROOM
11-0 x 11-6
COFFERED CLG.
ARCH
FOYER
COV'D
POACH
FLOOR A\
LIVING ROM
14-0 x 11-6
1 /4" = 1'-0"
ALL PIPE TO 3E 1"CDVC
U\LESS OTHERWISE \OTE3.
6" 120v Eell to be located on
the exterior approach to
home.
General Notes
1. OWNER TO PROVIDE ADEQUATE HEAT (40'F. MIN) TO PREVENT
SPRINKLER PIPES FROM FREEZING.
2. OWNER TO PROVIDE HARD WIRED HOME SMOKE DETECTION SYSTEM.
3. CPVC PIPE SHALL HAVE HANGERS 6'-0" c\c AND NOT MORE THAN
6" FROM ANY SPRINKLER HEAD.
4. ALL ATTIC PIPING TO BE TENTED WITH BATT INSULATION TO PREVENT
FREEZING.
5. ALL PIPING TO BE 1" C.P.V.C. U.N.O.
6. A 6" BELL TO BE LOCATED ON THE EXTERIOR APPROACH TO HOME IF
REQUIRES BY THE LOCAL A.H.J.
7. IF A OUTLET FOR A FUEL FIRED APPLIANCE IS PIPED ON AN EXTERIOR
COVERED DECK A INTERMEDIATE TEMP. DRY SPRINKLER WILL BE
INSTALLED.
111111111111111.
SYM
STATIC WATER PRESSURE 80 pal
TO SYSTE
DRAIN VALVE
DRAIN PIPED TO EXTERIOR —
1" AMES 2000B BACKFLOW PREVENTERS
1" WATER METER 10
Sprinkler Symbol Legend
SPRINKLER ORIFICE SIZE, TYPE & FINISH
RELIABLE RFC 43 16'x16' 2 head flow requirement 26 GPM ® 9.6 psi
RELIABLE F1 RES 49 16'x16' FLOW REQUIREMENT 26 GPM ® 9.6 psi
RELIABLE F1 RES 44 SIDEWALL 16' X 20'
VICTAULIC DRY UPRIGHT
Reliable F 3 QR DRY Sidewall
TOTAL
To domestic piping
WATER FLOW
INDICATOR
• PRESSURE
GAUGE
1.5"
80'
SPRINKLER RISER
QUAN TEMP K FACTOR
21
3
24
155' 4.9
155'
155'
200'
155'
4.3
4,3
5.6
5.6
NTS
�EDRO0v 3
9-6 09 0
BEDROOM 2
10-5 X 10-.7
CD 41 UP FROM MAIN FLOOR
CLOSET
CLOSET
CLOSET
OPE\ TO
BELOW
CONED,
LOFT
BEDROOM 4
11-0 X 13-5
ONU ROOM
-0 X 13-7
AULT D CLG.
TEST H
ER FLOOR
D
LA\
1 /4" = 1-0
INSULATION
DATE: 10/15/2015
//
0 V / / 4
PIPE
INSULATION TENTING DETAIL
V=GEE\ FRE R OTECTIO\
PO BOX 998
Puyallup, WA 98371
EVERGFP967LZ
Phone: (253) 252-7942
' REV:
I DRAWN: MH
' SHEET:
\C.
1 OF1
❑ Without Comments
As Noted in Red
❑ Per The Attathed Letter
,"h., -.,se plans have been reviewed by The Tukwila Fire
"revention Bureau for conformance with current City
r andards. Acceptance is subject to errors and
omissions which do not authorize violations of adopted
standards and ordinances. The responsibility for the
adequacy of design rests totally with the designer.
Additions, deletions or revisions to these drawings after
this date will void this acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance Is subject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Date: / O L?j. By:
TUKWI A FIRE DEPARTMENT
Newt t call 206-575-V107 O7 and
gin this Fire Permit No.
/42S2_L27
.,
and exact °y� es 3 for shut-
down or E. c ',jen {af:orov 1a
,
Sheet Title
6.5.3 A warning sign, with minimum 'As inch letters, shall be affixed
adjacent to the main shutoff valve and shall state the following:
WARNING: The water system for this home supplies fire
sprinklers that require certain flows and pressures to fight a
fire. Devices that restrict the flow or decrease the pressure or
automatically shut off the water to the fire sprinkler system,
such as water softeners, filtration systems, and automatic shut-
off valves, shall not be added to this system without a review
of the fire sprinkler system by a fire protection specialist. Do
not remove this sign.
FIL
OPY
Stamp
1YASHIMOTON !.TATE
CERTIFICATE OF COMPETENCY
FIRE PROTECTION SPRINKLER SYSTEMS
Michael D. Hutchinson
1166 -0599 -BG Level 2
Ever er;'n ; rotection, Inc.
a.
\PA 133 FIDE
26C3 7L Foster
SLA\
tot7
1V18 /I/Ith Lcne S.
Tu<wi c, WA 98168
PAID
aPl
cc 7/'"
5
RE
STh'/Yk4 ,17;A/