Fire Department Review
Control #B94-0305
(510)
Re: McNett, David - 4652 South 160th
Dear Sir:
The attached set of building plans have been reviewed by
The Fire Prevention Bureau and are acceptable with the
following concerns:
1. Every building shall be accessible to Fire Department
apparatus by way of access roadways with all-weather
driving surface of not less than 20' wide and 13'6"
vertical clearance. Access roads in excess of 150' shall
be provided with an approved turn -around area. Access
shall be within 150' of all portions of the buildings.
(UFC 10.203,204 as amended)
All required hydrants and surface access roads shall
be installed and made serviceable prior to and during
the time of construction. (UFC 10.203, 204 as
amended)
2. For short plat development (four single family homes
or less), hydrants shall be placed so that a hydrant is
within 250 feet of a building. Distance from a hydrant to
a building is measured along the path of vehicular travel.
Fire hydrants shall conform to American Water Works
Association specifications C-502-54; it shall be
compression type, equipped with two 2 1/2" N.S.T. hose
ports and one 5" Storz pumper discharge port, and
shall have a 1 1/4" Pentagon open -lift operating nut.
3. An approved residential fire sprinkler system may be
installed when vehicular travel distance from the nearest
hydrant exceeds maximum distance allowed.
City of Tukwila
FIRE DEPARTMENT
444 Andover Park East
Tukwila, Washington 98188-7661
(206) 575-4404
John W. Rants, Mayor
Page number 2
All new sprinkler systems and all modifications to
existing sprinkler systems shall have fire department
review and approval of drawings prior to installation
or modification. New sprinkler systems and all
modifications to sprinkler systems involving more than
50 heads shall have the written approval of the
W.S.R.B., Factory Mutual, Industrial Risk Insurers,
Kemper or any other representative designated and/or
recognized by The City of Tukwila, prior to submittal
to the Tukwila Fire Prevention Bureau. No sprinkler
work shall commence without approved drawings. (City
Ordinance #1646)
Acceptance of residential fire sprinkler systems shall
include field verification of GPM and residual
pressures meeting or exceeding the listing for the
sprinkler type.
4. Your street address must be conspicuously posted on
the building and shall be plainly visible and legible from
the street. Numbers shall contrast with their background.
(UFC 10.301(a))
This review limited to speculative tenant space only -
special fire permits may be necessary depending on detailed
description of intended use.
Any overlooked hazardous condition and/or violation of the
adopted Fire or Building Codes does not imply approval of
such condition or violation.
Yours truly,
The Tukwila Fire Prevention Bureau
cc: T.F.D. file
ncd
City Of�x�� BILE
AUG 4 1993
John W. Rants, Mayor
Fire Department Thomas P. Keefe, Fire chief
Project Name
TUKWILA FIRE DEPARTMENT
FINAL APPROVAL FORM
/?kA/T7 4J-
Address Y65 / i
Permit No.229___V_:_(23_651-_
Retain current inspection schedule
Needs shift inspection
Suite #
Approved without correction notice
Approved with correction notice issued
Sprinklers:
Fire Alarm:
Hood & Duct:
Halon:
Monitor:
Pre -Fire:
Permit=:
5 /3 b
ik) .572 -
Authorized Sig ature
FINALAPP.FRM T.F.D. Form F.P. 85
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone (206) 575.4404 • Far (206) 575-4439
Cascade A/armf
P.O. Box 7459 - Kent, Washington 98042
Ph: 206-767-5800 EXT # 2
Fax: 253-630-4851
www.cascadealarm.com
WET - AUTOMATIC SPRINKLERS
(One Systemper Report)
1CONFIDENCE TEST
Location of System
Design Density 0.00/ft2 Lexamrle.495/2000 ft):
REPAIRS
Occupancy Name: Ramos Residence
Occupancy Address: 4652 S. 160th
Fire Department / Confidence Test Report
City of
RED
Certification Given
YELLOW LWHITE
Contact Name: Steve
Phone Number: 206-419-7798
City, State, Zip: Tukwila, WA 98188 Bldg Owner/Agent: Same
Building Owner Address:
Date of Inspection: 12/12/07 Inspection Type: Annual Quarterly Acceptance
Testers Name
(Please Print): Ronald E. Bennett SFD Certification Number: FSCC-5073
Central station monitoring? Yes
Monitoring company name:
Control panel manufacturer: Model Number:
Problems Found: (if additional room is needed, please add a separate sheet)
• Corrections Made:
Date Corrected: Corrected By:
This certifies that this fire and life safety system has been properly inspected for reliability to cover the
Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that
discrepancies are noted and have been reported to the building Owner/Manager for corrective action.
Signature of Tester:, ( /,j1 /4 Phone # 206-767-5800
Testing Agency: Cascade Alarm, LLC
Mailing Address: P.O. Box 7459
Kent, WA 98042
Building Representive
CTF-13
(signature)
Page 1 of 2
The items on the checklists below shall be inspected and tested. This list does not constitute all of
the required inspecting and testing of the fire and life safety system. Refer to the Seattle Fire
Department Fire Code for inspecting and testing requirements.
Flow test conducted?
Static pressure: 9 d psi Flow pressure: 50 psi
2 -inch drain?
Flow switches, supervisory switches and alarm bells tested?
Alarm bell operates?
System inspected and lubricated?
Pressure regulating valves tested? M\A
Valves are sealed or supervised? NI A
Signs are provided on valves?
Pumper connections and clapper valves unobstructed and turn freely? y . NAA Yes
Wet type sprinkler heads replaced or successfully sample tested in last 50 Yes
years? Dry heads tested or replaced every 10 years?
Sprinkler coverage is acceptable?
Proper number of spare sprinkler heads available?
System left in service?
System gauges replaced or calibrated every 5 years?
Sprinkler heads free of corrosion, paint, obstructions and/or physical dams e?
(FDC)? N
�thr IL"
N/A
N/A
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Was debris found in the Fire Department Connection
( ) ' es No
Was the Fire Department Connection (FDC) back flushed? Date [)f i A, Yes No
Was an internal pipe and valve inspection performed every 5 years? Date1M-tNts. No
Sprinkler wrench available for each type of sprinkler? Yes ) No
CTF-13
Page 2 of 2
CONTRACTOR: ROBINSON PLUMBING INC.
607 S.E. EVERETT MALL WAY, SUITE 26
EVERETT. WA 98208
STATE OF WASHINGTON SPRINKLER LICENSE #RO-BI-NP-*272C2 LEVEL 2
682-0895 355-6171
DESIGNER: REGINA L. ROBINSON - ELMSLIE
STATE OF WASHINGTON CERTIFICATE OF COMPETANCY #537-64-7117 LEVEL 2
BUILDER: D.L. MCNETT CONSTRUCTION
PROPERTY ADDRESS: 4652 S. 160TH. TUKWILA
TOTAL NUMBER OF SPRINKLER HEADS: 20
FIRE SPRINKLER SYSTEM NOTES:
* FIRE SPRINKLER SYSTEM DESIGN PER N.F.P.A. STANDARD 13D
* SPRINKLER SYSTEM TO BE WATER PRESSURE TESTED & FLOW TESTED
* SPRINKLER PIPING AND FITTINGS TO BE C.P.V.C. "EXTINGUISH SURE" BY R & G
SLOANE CO. EXPOSED PIPING AND FITTINGS SHALL BE C.P.V.C. "EXTINGUISH SURE"
UNDER SMOOTH CEILING CONSTRUCTION AS PER U.L. LISTING
* UNDERGROUND WATER SERVICE TO BE COMBINATION DOMESTIC AND FIRE SPRINKLER
* INSTALLATION OF C.P.V.C. PIPE AND FITTINGS TO BE DONE BY MANUFACTUROR
CERTIFIED INSTALLERS
* FLOW SWITCH TO BE WIRED TO ALARM BELL (WIRING BY OTHERS)
* THREE SPARE SPRINKLER HEADS TO BE PROVIDED ALONG WITH INSTRUCTIONS TO
HOMEOWNER / TENANT
* SPRINKLER HEADS TO BE CENTRAL "GBR" PENDANT RESIDENTIAL QUICK RESPONSE WITH
CONCEALED ESCUTCHEONS AS PER LISTING
* LINES IN ATTIC TO BE PROTECTED FROM FREEZING WITH INSULATION OVER THE TOP
OF TIIE PIPING (BY INSULATION CONTRACTOR)
* ALL PIPES ARE 1" DIAMETER UNLESS OTHERWISE MARKED ON DESIGN DRAWINGS
* DESIGN SPACING IS 16' X 16'
* DESIGN AREA IS FOR 2 HEAD FLOW
* MINIMUM FLOW REQUIREMENTS FOR HEADS ARE: (1) HEAD FLOW = PSI
(2) HEAD FLOW = 4._WM4AdAJPSI
MAR �,�
JOB: D.L. MCNETT CONSTRUCTION
ADDRESS: 4652 S. 160TH, TUKWILA
DESIGNER: REGINA L. ROBINSON-ELMSLIE
CALCULATIONS FOR 19 GPM FLOW (1 HEAD) IND. LOSS NET TOTAL
A. WATER PRESSURE IN STREET
B. ARBITRARY SELECT PIPE SIZE:
C. DEDUCT METER LOSS (1")
D. DEDUCT HEAD LOSS FOR
ELEVATION SYSTEM CONTROL VALVE
HEIGHT= 15.00 X 0.434
DEDUCT LOSS FROM BACKFLOW DEVICE
80.00
2.00 78.00
6.51 71.49
4.00 67.49
E. DEDUCT PRESSURE LOSS FROM CITY MAIN
TO SPRINKLER (1-1/2" WATER SERVICE)
ITEM QUANTITY EQUIV FT. TOTAL FT.
PIPE: 225.00 1.00 225.00
VALVES:2.00 2.00 4.00
ELBOWS:2.00 3.00 6.00
TEES: 1.00 2.00 2.00
TOTAL: 237.00
TOTAL EQUIVALENT FT X .015 PSI/FT = 3.56 63.94
F, DEDUCT PRESSURE LOSS FOR 1" PIPING
CONTROL VALVE TO FARTHEST SPRINKLER
ITEM QUANTITY EQUIV FT. TOTAL FT.
PIPE: 67.00
ELBOWS:9.00
R-TEES:8.00
B-TEES:2.00
TOTAL: 0.00
1.00 67.00
7.00 63.00
1.00 8.00
5.00 10.00
148.00
TOTAL EQUIVALENT FT X .0597 PSI/FT = 8.84 55.10
REMAINING PRESSURE FOR SPRINKLER OPERATION 55.10
CALCULATIONS PER NFPA 13D A-4-4.3(1)
Regina L. Robinson-Elrnslic
537-64-7117
JOB: D.L. MCNETT CONSTRUCTION
ADDRESS: 4652 S. 160TI1, TUKWILA
DESIGNER: REGINA L. ROBINSON-ELMSLIE
CALCULATIONS FOR 28 GPM FLOW (2 HEADS) IND. LOSS NET TOTAL
A. WATER PRESSURE IN STREET 80.00
B. ARBITRARY SELECT PIPE SIZE:
C. DEDUCT METER LOSS (1") 3.50 76.50
D. DEDUCT HEAD LOSS FOR
ELEVATION SYSTEM CONTROL VALVE
HEIGHT= 15.00 X 0.434
DEDUCT LOSS FROM BACKFLOW DEVICE
6.51 69.99
4.00 65.99
E. DEDUCT PRESSURE LOSS FROM CITY MAIN
TO SPRINKLER (1-1/2" WATER SERVICE)
ITEM QUANTITY EQUIV FT. TOTAL FT.
PIPE: 225.00 1.00 225.00
VALVES:2.00 2.00 4.00
ELBOWS:2.00 3.00 6.00
TEES: 1.00 2.00 2.00
TOTAL: 237.00
TOTAL EQUIVALENT FT X .026 PSI/FT = 6.16 59.83
F.
DEDUCT PRESSURE LOSS FOR 1" PIPING
CONTROL VALVE TO FARTHEST SPRINKLER
ITEM QUANTITY EQUIV FT. TOTAL FT.
PIPE: 67.00
ELBOWS:9.00
R-TEES:8.00
B-TEES:2.00
TOTAL:
1.00
7.00
1.00
5.00
67.00
63.00
8.00
10.00
148.00
TOTAL EQUIVALENT FT X .1224 PSI/FT = 18.12 41.71
REMAINING PRESSURE FOR SPRINKLER OPERATION 41.71
CALCULATIONS PER NFPA 13D A-4-4.3(1)
Regina L. Robinson-Etrnstie
537-64-7117
-1 -
sv ie' -i
64116E 2
`L J�
t'
of/r.....2064.1 SW/resl
)`D 8 eat,
/y
ooRE G.lc,GC
vAL✓C
SYS7&"-1 doAnzOG. VALVE
Sep vice
Z+"r ert r __
VAL PE 4.SSEA/B4Y "IDer 1ILL
1.�,,. ;CT- S
�ll,l
Lott -vg
V1IMoifll 3O 1110
difc y14(.A8 -.SOYA-31W
aue_4aedep
le =,rurtTaedsul
I r+,�„'C,I s F ui3
_VC.I •dI nO/J'Sulil�n rig^ rcEI 1J IC 1-1:11.,i- ^^! G' cAnbaJ
"al+ir ;l;' IC" Ii, ei.ep
t i J. c_`- l ifY d, CLCislAaJ J0
p 'SUCIiIr E " T eG aal3 e11nn)1n1
/ 0 eq iSq K eleac.ae rue rennet/Nal
ueeq anew oleieq pexl}fie S UIMeJp eqi
2131131 C3"3Vlld 3H1 213d 0
G321 NI a310N SV -131
'91N31/111A100 1flOHIIM
L
A - • ,DQYr deiJOdd r sPet.oKLC72 (SCS s1a S)
�O PxS�P6.vriN4_ a . P )t,, JT t�SJ
✓CSIo�/ P+ I. J CS )
D - ciP Oe ,b N Ve-72 7I 4L P9)6
- t -No,. 'zow'r4G P/s%E
Alvee3c,L/G CALd( 4Al /OrJ .vo
v4Lv(
A ssem BLY7
t e F -06,e PON/
141I /—D
-
1! .
r I i M
!vKo��urcrb«.,Irrr�.mn+�r.r,ma';a1'i�ti Myp ro 1 . r 6
jy',Ydd tiWnl l��.
7
�j(py •
riobinson PIumbirlo Inc.
_ k
a i 'A 1 -
A 3 -
v
2 o -
2
4.' ..)Q
„iS
i
De* 3,4Z
.Shoot w
• FP/
>.,., _ ..
1
141.
7--v "C4, I/EA D .6E734 /LS
/t/0 .S 1..(
D/N/N&
1
o-
11/ r tied
•
n /'
Ntsr ea €)r"t
N Sr
ates/6"0
F4 /may
//1
0,4
Ce.0.S£r
/• 1v
MA/,
- ge-D2ocri4
'4 P-0"
•
0
L
64-7,1
G -A ,se 46-�
Shoo nns foo no.
„
F,e SPQti
,,Ccr a /la�sE
,¢ FOO /14c111e71
S/r p D,e+wm165 C3•J,STeuc,io/.1
Fc.00c fir/ .41-6.5-2. S /foo n 1 j '
TVCc414-.4 '
De" 71r►14.
,
Pals 3/LL
•-
Ib.. Ho
Pl- -
`' I