Fire Department Review
Control #B94-0275
Re: Vandenberg - 4650 South 160th Street, Lot B
Dear Sir:
The attached set of building plans have been reviewed by
The Fire Prevention Bureau and are acceptable with the
following concerns:
1. City Ordinance #1626 requires a fire hydrant to be
within 250' of the nearest point of the building in the
route of vehicular travel. Your site plan indicates the
nearest hyrant to be 370' away.
Installation of a fire hydrant to meet the
requirements of City Ordinance #1626 shall be required
for this project.
2. In lieu of the hydrant requirement, you may install an
automatic residential sprinkler system.
All new sprinkler systems and all modifications to
existing sprinkler systems shall have fire department
review and approval of drawings prior to installation
or modification. New sprinkler systems and all
modifications to sprinkler systems involving more than
50 heads shall have the written approval of the
W.S.R.B., Factory Mutual, Industrial Risk Insurers,
Kemper or any other representative designated and/or
recognized by The City of Tukwila, prior to submittal
to the Tukwila Fire Prevention Bureau. No sprinkler
work shall commence without approved drawings. (City
Ordinance #1646)
Contact The Tukwila Fire Prevention Bureau to witness
all required inspections and tests. (UFC 10.503) (City
Ordinance #1646)
City of Tukwila
FIRE DEPARTMENT
444 Andover Park East
Tukwila, Washington 98188-7661
(206) 575-4404
Page number 2
John W. Rants, Mayor
3. All electrical work and equipment shall conform
strictly to the standards of The National Electrical Code.
(NFPA 70)
4. Required fire resistive construction, including
occupancy separations, area separation walls, exterior
walls due to location on property, fire resistive
requirements based on type of construction, draft stop
partitions and roof coverings shall be maintained as
specified in the Building Code and Fire Code and shall be
properly repaired, restored or replaced when damaged,
altered, breached, penetrated, removed or improperly
installed. (UFC 10.601)
Your street address must be conspicuously posted on
the building and shall be plainly visible and legible
from the street. Numbers shall contrast with their
background. (UFC 10.301(a))
Any overlooked hazardous condition and/or violation of the
adopted Fire or Building Codes does not imply approval of
such condition or violation.
Yours truly,
The Tukwila Fire Prevention Bureau
cc: T.F.D. file
ncd
City of Tukwila
FIRE DEPARTMENT
444 Andover Park East
Tukwila, Washington 98188-7661
(206) 575-4404
Fire Department Review
Control #B94-0276
(512)
FILE
John W. Rants, Mayor
July 29, 1994
Re: Vandenberg - 4650 South 160th Street, Lot C
Dear Sir:
The attached set of building plans have been reviewed by
The Fire Prevention Bureau and are acceptable with the
following concerns:
1. City Ordinance #1626 requires a fire hydrant to be
within 250' of the nearest point of the building in the
route of vehicular travel. Your site plan indicates the
nearest hydrant to be 370' away.
Installation of a fire hydrant to meet the
requirements of City Ordinance #1626, shall be
required for this project.
2. In lieu of the hydrant requirement, you may install an
automatic residential sprinkler system.
All new sprinkler systems and all modifications to
existing sprinkler systems shall have fire department
review and approval of drawings prior to installation
or modification. New sprinkler systems and all
modifications to sprinkler systems involving more than
50 heads shall have the written approval of the
W.S.R.B., Factory Mutual, Industrial Risk Insurers,
Kemper or any other representative designated and/or
recognized by The City of Tukwila, prior to submittal
to the Tukwila Fire Prevention Bureau. No sprinkler
work shall commence without approved drawings. (City
Ordinance #1646)
Contact The Tukwila Fire Prevention Bureau to witness
all required inspections and tests. (UFC 10.503) (City
Ordinance #1646)
City of Tukwila
FIRE DEPARTMENT
444 Andover Park East
Tukwila, Washington 98188-7661
(206) 575-4404
Page number 2
John W. Rants, Mayor
3. All electrical work and equipment shall conform
strictly to the standards of The National Electrical Code.
(NFPA 70)
4. Require fire resistive construction, including
occupancy separations, area separation walls, exterior
walls due to location on property, fire resistive
requirements based on type of construction, draft stop
partitions and roof coverings shall be maintained as
specified in the Building Code and Fire Code and shall be
properly repaired, restored or replaced when damaged,
altered, breached, penetrated, removed or improperly
installed. (UFC 10.601)
Your street address must be conspicuously posted on
the building and shall be plainly visible and legible
from the street. Numbers shall contrast with their
background. (UFC 10.301(a))
Any overlooked hazardous condition and/or violation of the
adopted Fire or Building Codes does not imply approval of
such condition or violation.
Yours truly,
The Tukwila Fire Prevention Bureau
cc: T.F.D. file
ncd
Retain current inspection schedule
Needs shift inspection
Approved without correction notice
Approved with correction notice issued
fpr. lers:
Fire Alarm:
Hood & Duct:
Halon:
Monitor
Pre -Fire:
Permits: l
Authoriz' d Signatu e
FINALAPP.FRM
T.F.D. Form
P. 85
Headquarters Station: 444 Ando er Park East • Tukwila, Washington 08188 • Phone (2157$4404 • Soy (206) 5754439
CONTRACTOR: ROBINSON PLUMBING INC.
607 S.E. EVERETT MALL WAY, SUITE 26
EVERETT, WA 98208
STATE OF WASHINGTON SPRINKLER LICENSE #RO-BI-NP-*272C2 LEVEL 2
682-0895 355-6171
DESIGNER: REGINA L. ROBINSON - ELMSLIE
STATE OF WASHINGTON CERTIFICATE OF COMPETANCY #537-64-7117 LEVEL 2
BUILDER: GREG VANDENBERG
PROPERTY ADDRESS: 4650 S. 160TH ST., TULWILA
PARCEL: 222304-9104
TOTAL NUMBER OF SPRINKLER HEADS: 17
FIRE SPRINKLER SYSTEM NOTES:
* FIRE SPRINKLER SYSTEM DESIGN PER N.F.P.A. STANDARD 13D
* SPRINKLER SYSTEM TO BE WATER PRESSURE TESTED & FLOW TESTED
r
* SPRINKLER PIPING AND FITTINGS TO BE C.P.V.C. "EXTINGUISH SURE" BY R & G
SLOANE CO. EXPOSED PIPING AND FITTINGS SHALL BE C.P.V.C. "EXTINGUISH SURE"
'UNDER SMOOTH CEILING CONSTRUCTION AS PER U.L. LISTING
* UNDERGROUND WATER SERVICE TO BE COMBINATION DOMESTIC AND FIRE SPRINKLER
* INSTALLATION OF C.P.V.C. PIPE AND FITTINGS TO BE DONE BY MANUFACTUROR
CERTIFIED INSTALLERS
* FLOW SWITCH WIRED TO ALARM BELL @ EXTERIOR
* THREE SPARE SPRINKLER HEADS TO BE PROVIDED ALONG WITH INSTRUCTIONS TO
HOMEOWNER / TENANT
* SPRINKLER HEADS TO BE CENTRAL "R1M" PENDANT RESIDENTIAL QUICK RESPONSE AS
PER LISTING
* LINES IN ATTIC TO BE PROTECTED FROM FREEZING WITH INSULATION OVER THE TOP
OF THE PIPING (BY INSULATION CONTRACTOR)
* DESIGN SPACING IS 16' X 16'
* DESIGN AREA IS FOR 2 HEAD FLOW
* MINIMUM FLOW REQUIREMENTS FOR HEADS ARE: (1) HEAD FLOW = 14 GPM @ 12.9 PSI
(2) HEAD FLOW = 11 GPM @ 8.0 PSI
JOB: VANDENBERG SPRINKLER
ADDRESS: 4650 S. 160TH, TUKWILA
DESIGNER: REGINA L. ROBINSON-ELMSLIE
CALCULATIONS FOR 14 GPM FLOW (1 HEAD) IND. LOSS NET TOTAL
A. WATER PRESSURE IN STREET 80.00
B. ARBITRARY SELECT PIPE SIZE:
C. DEDUCT METER LOSS (1") 2.00 78.00
D. DEDUCT HEAD LOSS FOR
ELEVATION SYSTEM CONTROL VALVE
HEIGHT= 20.00 X 0.434
8.68 69.32
E. DEDUCT PRESSURE LOSS FROM CITY MAIN
TO SPRINKLER (1-1/2" WATER SERVICE)
ITEM QUANTITY EQUIV FT. TOTAL FT.
PIPE: 210.00 1.00 210.00
VALVES:2.00 2.00 4.00
ELBOWS:4.00 3.00 12.00
TEES: 1.00 2.00 2.00
TOTAL: 228.00
. TOTAL EQUIVALENT FT X .01 PSI/FT = 2.28 67.04
F: DEDUCT PRESSURE LOSS FOR 1-1/2" PIPING
• CONTROL VALVE TO FARTHEST SPRINKLER
ITEM QUANTITY EQUIV FT. TOTAL FT.
PIPE: 24.00 1.00 24.00
ELBOWS:2.00 7.00 14.00
R-TEES:1.00 1.00 1.00
B-TEES:0.00 5.00 0.00
DCHECK:1.00 196.00 196.00
VALVE: 0.00 1.00 0.00
TOTAL: 235.00
TOTAL EQUIVALENT FT X .0057 PSI/FT = 1.34 65.70
DEDUCT PRESSURE LOSS FOR 1" PIPING
CONTROL VALVE TO FARTHEST SPRINKLER
ITEM QUANTITY EQUIV FT. TOTAL FT.
PIPE: 71.00 1.00 71.00
ELBOWS:9.00 7.00 63.00
R-TEES:8.00 1.00 8.00
B-TEES:1.00 5.00 5.00
TOTAL: 0.00 147.00
TOTAL EQUIVALENT FT X .0340 PSI /FT = 5.00 60.70/;;='``
REMAINING PRESSURE FOR SPRINKLER OPERATION 60
CALCULATIONS PER NFPA 13D A-4-4.3(1)
Regina l . :<i+yen-trro�lie
57-64-7117
JOB: VANDENBERG SPRINKLER
ADDRESS: 4650 S. 160TH, TUKWILA
DESIGNER: REGINA L. ROBINSON-ELMSLIE
CALCULATIONS FOR 22 GPM FLOW (2 HEADS) IND. LOSS NET TOTAL
A. WATER PRESSURE IN STREET
B. ARBITRARY SELECT PIPE SIZE:
C. DEDUCT METER LOSS (1")
D. DEDUCT HEAD LOSS FOR
ELEVATION SYSTEM CONTROL VALVE
HEIGHT= 20.00 X 0.434
E. DEDUCT PRESSURE LOSS FROM CITY MAIN
TO SPRINKLER (1-1/2" WATER SERVICE)
ITEM QUANTITY EQUIV FT. TOTAL FT.
PIPE: 210.00
VALVES:2.00
ELBOWS:4.00
TEES: 1.00
TOTAL:
1.00 210.00
2.00 4.00
3.00 12.00
2.00 2.00
228.00
80.00
3.00 77.00
8.68 68.32
TOTAL EQUIVALENT FT X .015 PSI/FT = 3.42 64.90
F: DEDUCT PRESSURE LOSS FOR 1-1/2" PIPING
CONTROL VALVE TO FARTHEST SPRINKLER
ITEM QUANTITY EQUIV FT. TOTAL FT.
PIPE: 24.00
ELBOWS:2.00
R-TEES:1.00
B-TEES:0.00
DCHECK:1.00
VALVE: 0.00
TOTAL:
1.00 24.00
7.00 14.00
1.00 1.00
5.00 0.00
196.00 196.00
1.00 0.00
235.00
TOTAL EQUIVALENT FT X .0131 PSI/FT = 3.08 61.82
DEDUCT PRESSURE LOSS FOR 1" PIPING
CONTROL VALVE TO FARTHEST SPRINKLER
ITEM QUANTITY EQUIV FT. TOTAL FT.
PIPE: 71.00
ELBOWS:9.00
R-TEES:8.00
B-TEES:1.00
TOTAL:
1.00 71.00
7.00 63.00
1.00 8.00
5.00 5.00
147.00
TOTAL EQUIVALENT FT X .0783 PSI/FT = 11.51
REMAINING PRESSURE FOR SPRINKLER OPERATION
CALCULATIONS PER NFPA 13D A-4-4.3(1)
tie
/
r
A
J
PATIO
NGO
FSD M-#
T
4ITCtEL
L N/ING-7 ThV
VA t-ve
t Dc-%, /4.)
LAND/
5C./6, L % 1/4"
1
ACCEPTED
WITHOUT COMMENTS.
AS NOTED IN RED
PER THE ATTACHED LETTER
The drawings affixed hereto have been
reviewed and accepted by the City of
Tukwila Fire Dept Additions, deletions
or revisions to these drawings after this
date will void thi3 acceptance and will
require a resubmittal of revised drawings.
Final acceptance is subject to field -
inspection by a representative of this
department
DATE.IA r_BY,_
CITY OF TUKWILA
5/5-4407
Q - JT/.0 L G? Z P�JLig AJT (scc --.%t -s
"4"
)
- Jt.S/o"/
- c/P c) e "Dau/'/ V' 7 ,Gi t. P',C
i
NO/Z,ZO.✓%At. P,AJE
.41V0,24u4./G CALa11 ,4 /O/.% .JO4.)k.
CoN fy %,v e
'= -
TUKWILA FIRE OEPM fiVIENT
Please call: 575-4407
and give this job
No. %S rfo ° IF
and exact address for shut-
down or restoration approval.
lrCC�?l/� �6e�ZL�
\!
Ps 5e7-1 p6,-74 N IsA Fr7.
F' ° -Iasi st44 t rz. eerbult2b
9 - 02-7/0
i obinson Plumbing inc_
03
!.
11 `7
443 0et 43
h N "1
g 1/2b X
?
a
Job no 3-0/o3
D.1. / 212,9/4$34
D..*n 11 see F .
0,...N.
Ff/
11,
1
/ "DA✓
84 sill
J PER FL
OO;=
SCA
t 4
1 0'
"/0 JC4[6
N=,r1- i3
Fr7 v n?L h -2_--2-(A)
FrtT
F
W
/
11 Robinson
h
b Al
aO Q
V)Q W _
� W� � 0 3
tv
Q A
II
r
2
J
A* p 2.0 /03
Da" i z /3//0/4':<
D.M. ey zAzi
Sn..i N.
SPP