HomeMy WebLinkAboutPP - 4343 S 160TH ST - LANDFAIR - PERMITS AND PLANS4343 S 160TH ST
ASSOCIATED PERMITS
14-S-210 D14-0140
IMAM
SITE LOCATION
CITY OF TUKWILA
FIRE DEPARTMENT
444 Andover Park East
Tukwila, WA 98188
206-575-4407
Date application
accepted:
FIRE PROTECTION SYSTEMS PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Site Address: 4343 S 160th ST
Tenant Name: New Tenant? ❑ - Yes ❑ - No
Property Owner's Name: Sound Built Homes
Mailing Address: 12815 Canyon Rd E Puyallup,WA 98373
City State Zip
CONTACT PERSON -if there are questions about the submittal.
Name: Mike Hutchinson Day Telephone: 253-252- 71 2
**PLEASE PRINT**
King Co. Assessor's Tax No.:
Suite Number: Floor:
Company Name:
Evergreen Fire Protection
Mailing Address: PO BOX 998 Puyallup 98371
City State Zip
E-mail Address: Evergreenfireproamsn.com Fax Number: 253-252-7943
Valuation of Project (contractor's bid price): $ 4161.00
Scope of Work (please provide detailed information): new NFPA 13D fire sprinkler system
PERMIT APPLICATION NOTES
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules.
Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit
is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or
abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in
writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE
UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY
FOR THIS PERMIT.
BUILDING OWNER OR AUTHORIZED AGENT:
Signature: Date: 9/10/2014
Print Name: Mike Hutchinson Day Telephone: 253-3814456
Plan Permit App.doc
5/14/10 TFD FP Form 8
AIWZORMT
SITE LOCATION
CITY OF TUKWILA
FIRE DEPARTMENT
444 Andover Park East
Tukwila, WA 98188
206-575-4407
Date application
accepted:
FIRE PROTECTION SYSTEMS PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
**PLEASE PRINT**
King Co. Assessor's Tax No.:
4343 S 160th st
Site Address: Suite Number: Floor:
Tenant Name: New Tenant? E- Yes ❑ - No
Property Owner's Name:
Sound Built Homes
Mailing Address: 12815 Canyon rd. E Puyallup WA 98373
City State Zip
CONTACT PERSON -if there are questions about the submittal.
Mike Hutchinson
Name:
253 252 7942
Day Telephone:
Company Name:
Evergreen Fire Protection
PO Box 998 Puyallup WA
Mailing Address:
E-mail Address: evergreenfirepro@msn.com
City State Zip
Fax Number:
Total number of new/relocated devices or sprinkler heads: 24
Valuation of Project (contractor's bid price): $ 4161.00
Scope of Work (please provide detailed information): New 13 D fire system
PERMIT APPLICATION NOTES
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules.
Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit
is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or
abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in
writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE
UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY
FOR THIS PERMIT.
BUILDING OWNER OR AUTHED AGENT:
Signature: i _
Print Name: R
Plan Permit App.doc
Date:
Day Telephone:
1/2/13 TFD FP Form 8
3
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
pit( - o/90
PERMIT NUMBERS
CITY OF TUKVVILA FIRE DEPARTMENT
206-575-4407
Project:
Geti. ,-,
2f—a,--'
Type o Insp ion:
Hood & Duct:
Address: 43 y3
Suite #:
s /60
Contact P rson:
Special Instructions:
Phone No.:
` Npproved per applicable codes.
Corrections required prior to approval.
COMMENTS:
se
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Inspector: !---)
„s ----d____
Date: -7 /j //
Hrs.:
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F.. D. Form F.P. 113
1
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Project: �/„J���/'/�/�/�
Type off�Inspection:
Address: //
Suite #: y3y3 S. /60`
Contact Person:
Special Instructions:
Phone No.:
Approved per applicable codes.
,4o/s;
Corrections required prior to approval.
�rs —
Arc
— oK G>va.i-
3a/A
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Inspector: XI-
07
Date: 51,z 05
Hrs.:
/.01
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
DATE: 40/10/2014 C:\program files\HRS Systems\hhouse34\2603aa.rdf Page 1
EVERGREEN FIRE PROTECTION, INC.
10509 64th AVENUE E
PUYALLUP,WA 98373
RESIDENTIAL SPRINKLER SYSTEM
HYDRAULICS CALCULATION REPORT
FOR
Landfair lot 2
Tukwila, WA
4343 S 160th st
Date: 9/10/2014
File No:
Data File Name: 2603aa.rdf
SPRINKLER SPACING
256.0 sq. ft./spklr.(max) Max. Dist. Bet. Spklrs: 16.0 ft.
Min. Dist. Bet. Spklrs: 8.0 Max. Dist. Spklr. to Wall: 8.0 ft.
SPRINKLER SPECIFICATIONS
Mfr: 1 Reliable Descr: RA0612 RFC43 F1 Conc. Pend. (16x16) K=4.30
Calculated K Factor for Arm -Overs & Drops:
1.0 ft. x 1.101 in. Drop: K=4.26 (Incl. 1 Tee)
0.0 ft. x 1.101 in. Arm -Over: K=4.25 (Incl. 1 Tee & 1 Ell)
PIPE SPECIFICATIONS
Type: CPVC S-40 HWC: 150
WATER SUPPLY
Source: Public Test Date: By:
Static: 60.0 psi Resid: 0.0 psi Flow: 0.0 gpm
Public Main Size: 0 in
Domestic Demand: 0.0 gpm at node number 0
SPRINKLER DEMAND
No.Spkirs. Min Spklr. Press. Node Total Avail. Req'd
Flowing Flow (psi) No. Flow Press. Press.
1 13.0 9.3 1 13.0 60.0 33.4
2 13.0 9.3 1 26.1 60.0 46.8
`,VIEWING AUTHORITY
City of Tukwila
DATE:49/10/2014 C:\program files\HRS Systems\hhouse34\2603aa.rdf Page 2
P
R
E
S
S
U
R
E
P
S
I
WATER SUPPLY CURVE
60.0 A QC
54.0
48.0
42.0
36.0
CB
30.0
24.0
18.0
12.0
6.0
0D
0.0 I I 1 I 1 1
04 8 12 16 20 24 28
32
I I
36 40
FLOW (GPM)
Static = 60.0 psi (fixed pressure)
(1 sprinkler flowing) (2 sprinklers flowing)
A = Available Water Supply
60.0 psi @ 13.0 gpm
B = Required Water Supply
33.4 psi @ 13.0 gpm
C = Available Water Supply
60.0 psi @ 26.1 gpm.
D = Required Water Supply
46.8 psi @ 26.1 gpm
DATE:49/10/2014 C:\program files\HRS Systems\hhouse34\2603aa.rdf Page 3
RESULTS OF ANALYSIS
NFPA NODE & PIPE DATA
1 Sprinkler Flowing
Node Tag Elevation Node Type Pressure Discharge Notes
(FT) (PSI) (GPM)
1 20.0 K= 4.26 9.3 13.0
2 20.0 9.7
3 20.0 9.7
4 20.0 11.7
5 10.0 16.5
6 0.0 22.6
7 0.0 22.9
8 0.0 27.9
9 0.0 28.4
10 0.0 SOURCE 33.4
Pipe Tag K-fac AF AF to L C (Pt)
Frm Node El (ft) PT (q) node/ Nom ID Fit F (Pe) Notes
To Node El (ft) PT TF(Q) disch Act ID T FL/FT (Pf)
Pipe: 1 4.26 7.00 150 0.4
3 20.0 9.7 13.0 Disch 1.000 B: 5 5.00 0.0
1 20.0 9.3 13.0 1.101 12.00 0.031 0.4
Pipe: 2 0.00 3.00 150 0.0
3 20.0 9.7 0.0 1.000 B: 5 5.00 0.0
2 20.0 9.7 0.0 1.101 8.00 0.000 0.0
Pipe: 3 0.00 B: 5 51.00 150 2.1
4 20.0 11.7 13.0 1 1.000 L: 5 16.00 0.0
3 20.0 9.7 13.0 1.101 6R: 6 67.00 0.031 2.1
Pipe: 4 0.00 10.00 150 4.8
5 10.0 16.5 13.0 3 1.000 L: 5 5.00 4.3
4 20.0 11.7 13.0 1.101 15.00 0.031 0.5
Pipe: 5 0.00 3B:15 34.00 150 6.0
6 0.0 22.6 13.0 4 1.000 L: 5 22.00 4.3
5 10.0 16.5 13.0 1.101 2R: 2 56.00 0.031 1.7
Pipe: 6 0.00 5.00 150 0.3
7 0.0 22.9 13.0 5 1.000 4R: 4 4.00 0.0
6 0.0 22.6 13.0 1.101 9.00 0.031 0.3
Pipe: 7 0.00 1.00 150 5.0
8 0.0 27.9 13.0 6 1.000 0.00 0.0
7 0.0 22.9 13.0 1.101 1.00 0.031 5.0
Fixed Pressure Loss Device: 5.00 psi
Pipe: 8 0.00 79.00 150 0.5
9 0.0 28.4 13.0 7 1.500 4L:28 28.00 0.0
8 0.0 27.9 13.0 1.598 107.00 0.005 0.5
Pipe: 9 SOURCE 1.00 150 5.0
10 0.0 33.4 13.0 8 1.000 0.00 0.0
9 0.0 28.4 13.0 1.101 1.00 0.031 5.0
DATE:,9/10/2014 C:\program files\HRS Systems\hhouse34\2603aa.rdf Page 4
Fixed Pressure Loss Device: 5.00 psi
RESULTS OF ANALYSIS
NFPA NODE & PIPE DATA
2 Sprinklers Flowing
Node Tag Elevation Node Type Pressure Discharge Notes
(FT) (PSI) (GPM)
1 20.0 K= 4.26 9.3 13.0
2 20.0 K= 4.26 9.4 13.1
3 20.0 9.7
4 20.0 17.1
5 10.0 23.1
6 0.0 33.7
7 0.0 34.7
8 0.0 39.8
9 0.0 41.7
10 0.0 SOURCE 46.8
Pipe Tag K-fac AF AF to L C (Pt)
Frm Node El (ft) PT (q) node/ Nom ID Fit F (Pe) Notes
To Node El (ft) PT TF(Q) disch Act ID T FL/FT (Pf)
Pipe: 1 4.26 7.00 150 0.4
3 20.0 9.7 13.0 Disch 1.000 B: 5 5.00 0.0
1 20.0 9.3 13.0 1.101 12.00 0.031 0.4
Pipe: 2 4.26 3.00 150 0.2
3 20.0 9.7 13.1 Disch 1.000 B: 5 5.00 0.0
2 20.0 9.4 13.1 1.101 8.00 0.031 0.2
Pipe: 3 0.00 13.1 2 B: 5 51.00 150 7.4
4 20.0 17.1 13.0 1 1.000 L: 5 16.00 0.0
3 20.0 9.7 26.1 1.101 6R: 6 67.00 0.111 7.4
Pipe: 4 0.00 10.00 150 6.0
5 10.0 23.1 26.1 3 1.000 L: 5 5.00 -4.3
4 20.0 17.1 26.1 1.101 15.00 0.111 10.3
Pipe: 5 0.00 3B:15 34.00 150 10.6
6 0.0 33.7 26.1 4 1.000 L: 5 22.00 -4.3
5 10.0 23.1 26.1 1.101 2R: 2 56.00 0.111 14.9
Pipe: 6 0.00 5.00 150 1.0
7 0.0 34.7 26.1 5 1.000 4R: 4 4.00 0.0
6 0.0 33.7 26.1 1.101 9.00 0.111 1.0
Pipe: 7 0.00 1.00 150 5.1
8 0.0 39.8 26.1 6 1.000 0.00 0.0
7 0.0 34.7 26.1 1.101 1.00 0.111 5.1
Fixed Pressure Loss Device: 5.0 psi
Pipe: 8 0.00 79.00 150 1.9
9 0.0 41.7 26.1 7 1.500 4L:28 28.00 0.0
8 0.0 39.8 26.1 1.598 107.00 0.018 1.9
Pipe: 9 SOURCE 1.00 150 5.1
DATE: .0/10/2014 C:\program
•
files\HRS Systems\hhouse34\2603aa.rdf
10 0.0 46.8 26.1 8 1.000 0.00
9 0.0 41.7 26.0 1.101 1.00 0.111
Fixed Pressure Loss Device: 5.0 psi
Legend:
PT - Total Pressure at Node
Fl - Flow rate (gpm)
L - Pipe Length
F - Fitting Length
T - Total Length of Pipe
C - Hazen -Williams Coefficient
FL/FT - Friction Loss per Foot
Pt - Total Pressure Loss
Pe - Elevation Pressure Loss
Pf - Friction Pressure Loss
Page 5
0.0
5.1
Fitting Code Letters:
E=45 Ell, L=90 Ell, B=TeeBch, R=TeeRun, C=Couplg, S=SwgChk, G=GatV1v, X= X, Y=
The maximum velocity of water flow occurs in pipe 7
at 4.38 ft/s with 1 sprinkler flowing.
The maximum velocity of water flow occurs in pipe 5
at 8.79 ft/s with 2 sprinklers flowing.
PIPE FITTINGS TABLE
Pipe Table Name: standard.npt
PAGE: C MATERIAL: CPVC S-40 HWC: 150
Diameter Equivalent Fitting Lengths
(in) E L B R C
45 Ell 90 Ell TeeBch TeeRun Couplg
1.101 1.00 5.00 5.00 1.00 1.00
1.598 2.00 7.00 8.00 1.00 1.00
in Feet
S G X Y Z
SwgChk GatV1v X Y Z
8.00 2.00 0.00 0.00 0.00
14.00 3.00 0.00 0.00 0.00
A negative value for flow rate indicates the direction of flow is from the second pipe nc
A Fixed Pressure Loss Device calcualtes as a positive friction loss
A Fire Pump calculates as a negative friction loss
Sprinkler system has been hydraulically calculated with the
HASS HOUSE 3.4 computer program (License No. R609099990)
to provide an average imbalance of 0.010 gpm at each node and
a maximum imbalance of 0.09 gpm with one sprinkler
flowing, and 0.015 gpm at each node and maximum imbalance
of 0.15 gpm with 2 sprinklers flowing in accordance
with NFPA 13 and 13D or 13R.
The minimum source pressure is 20.0 psi with a minimum required pressure
of 46.8 psi and a 7 minute flow of 183 gal. and a 10 minute flow of 260.8 gallons.
The minimum pressure at any node is 9.3 psi at node 1.
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
a'
0
N
0
ciao
QJ
O 0
-11E
Em
Z
1
QN
2
D
0
2
z
0
lD
ui
1
D�
O
0
a
z
-121
o�
(E
cm
!Ay
Z
tJ
(
m
pA
2
1
9
Re
n
LAWN & IRRIGATION
CENTRIFUGAL SELF -PRIMING SPRINKLER PUMPS
APPLICATIONS
Ideal for both residential and commercial lawn and turf sprinkling systems.
FEATURES & BENEFITS
• Rugged cast iron casing and pump base
• High efficiency thermoplastic impeller and diffuser
• BI models are configured with a brass impeller which is
recommended for more demanding applications such
as weir feeders*
• 2" NPT suction and 1-1/2" NPT discharge
• Self -priming to 25'
• Maximum pressure to 47 psi
• Flow rates to 89 U.S. gpm
• RLSP Series can be set for use with 115 Volts or 230 Volts
Model
Item
Number
UPC
Vons
Amps
Intake
Discharge
Discharge Pressure
PSI at 5' Lift
10
20
30
40
Gallons Per Minute
RLSP-75 614670 010121 124851 3/4 115/230 12.6 A @ 115 V/ 6.3 A @ 230 V 2" NPT 1-1/2" NPT 58
RLSP4101 614671 0 10121 12486 8 1 115/230 16.4 A @ 115 V / 8.2 A @ 230 V 2" NPT 1-1/2" NPT 63
RLSP-150 614672 010121 12487 5 1-1/2 115/230 17.4 A @ 115 V/ 8.7 A @ 230 V 2" NPT 1-1/2" NPT 71
RLSP-200 614673 010121 12488 2 2 115/230 20 A @ 115 V/ 10 A @ 230 V 2" NPT 1-1/2" NPT 89
*RLSP-150-BI 614675 010121 14089 9 1-1/2 115/230 17.4 A @ 115 V/ 8.7 A @ 230 V 2' NPT 1-1/2" NPT 71
*RLSP-200-BI 614676 010121 14090 5 2 115/230 20 A @ 115 V / 10 A @ 230 V 2" NPT 1-1/2" NPT 89
Carton Specifications
Model
Length
Width
RLSP-75 11.5" 20.5"
RLSP-100 11.5" 20.5"
RLSP-150 11.5" 20.5"
RLSP-200 11.5' 20.5"
RLSP-150-BI 11.5" 20.5°
RLSP-200-BI 11.5" 20.5"
Height
13"
13"
13"
13"
13"
13"
Weight
(lbs)
54
57
60
63
61
64
Carton Cubes
(cu ft)
1.77
1.77
1.77
1.77
1.77
1.77
Pallet
Quantity
18
18
18
18
18
18
Qty. per
Layer
6
6
6
6
6
6
Layers per
Pallet
Centrifugal Self -Priming Sprinkler Pumps
3
3
3
3
3
3
80
10 20 30 40 50
Capacity - US gpm
60
70
80
90
46
54
60
75
60
75
29
38
44
60
44
60
7
11
15
36
15
36
Max
Pressure
PSI
43
45
44
47
41
45
Max
Flow
GPM
58
63
71
89
71
89
RedLionPraducts.com I Hotline: 1.888.956.0000
s.
PLAN VIEW
-
IDCVA)
DOUBLE CHECK
VALVE
- TYPE COPPER PIPE
PVC
- POLY ETHYLENE
FIRE
TO SERVICE
THE WATER METER IS INSTALLED BY CITY STAFF
I' COUPLING MUELLER 110 X ANGLE STOP BALI. VALVE
8-24258 / 1" MUELLER 300 BALL CURB VALVE FULL PORT
TO MAIN
t 8.20205
THIS VALVE IS ROTATED TO A VERTICAL POSI�ON
a METER 1
THIS VALVE IS TO BE SEALED INA OPEN POSITION
1" MUELLER RESID. FIRE SERVICE CONNECTION
TYPE K COPPER
- W1TH F.I.P. CONNECTIONS
8 LOCKABLE ANGLE BALL VALVE
THIS VALVE IS IN A HORIZONTAL POSTION
DOMESTIC
TO SERVICE
- TYPE K COPPER PIPE
- PVC
-POLYETHYLENE
FITIINGS USED ON THE PIPES LEADING TO THE HOUSE FROM THE MUELLAR TEE SHALL BE
MUELLER 110 TYPE FITTINGS OR EQUAL.
METER INSTALLED 8Y CITY
FINISHED GROUND LINE SECTION MUELLER RES. FIRE SERVICE CONNECTION
--
24'
1.
, J lt -• iv
TO MAIN
GRAVEL
TO SERVICE
!
I
I
I
TYPE K COPPER - TYPE K CCPPER PIPE
-PVC
- POLY ETHYLENE
1" FIRE SERVICE PARTS LIST:
1-B-24258 - 1" COUPLING MUELLER 110 XANGLE STOP - BALL
1-B-25028 - 1" CORP STOP - BALL
1 - TAILPIECE WITH FEMALE IRON PIPE THREADS
NOTES:
"
1. NO METER BOXES IN SIDEWALKS AND DRIVEWAYS WHERE POSSIBLE.
2. USE CLEAN 5/8" MINUS CRUSHED ROCK TO BACKFILL AROUND CORP STOP AND
SERVICE LINE.
3. THE FIRE SPRINKER SYSTEM SHALL BE DESIGNED PER APPENDIX R AND
NFPA 13D
4.THE DOUBLE CHECK VALVE SHALL BE INSTALLED WITHIN 5' OF THE WATER METER.
5. THE DOUBLE CHECK VALVE SHALL BE INSTALLED TO PROTECT FROM FREEZING.
NOT TO SCALE
1" FIRE / DOMESTIC SERVICE
`
�at1514
o 0
X
fie, /oy
1YOe
City of
Tukwila
SHEET: X)( -XX
REVISION #1: 1-11-2012
LAST REVISION:
APPROVAL:
I
3EDROON 2
10-5 X 10-7
UP FROM MAIN FLOOR
0
BEDROOM 4
11-0 X 13-5
OPEN TO
BELOW
BONUS ROOIv
19-OX13-
VPULTE CLL
C
D
E� FL0ICH PLA\
PIPE
INSULATION
INSULATION TENTING DETAIL
1/4" = 1'-0"
•
COV'D PATIO
�.�,.AL:, FIRE DEPARTMENT
I-'Hist
E ARTj --
I-'Hist call 2067575-1107 and
this Fire Permit No.
d ex ct�'—
for shut
ez wn or rzIorwon epproval
TO UPPER FLOOR
KITCHEN
0
DINING R ON
11-0 x 11-6
COFFERED CLO
UTILIT
0—
FOYER
3 CAR GARAGE
LIVING ROOM
COV'D
PORCH
WATER FLOW
INDICATOR
PRESSURE
GAUGE
STATIC WATER PRESSURE e0 pot
TO SYSTEM
DRAIN VALVE
-- DRAIN PIPED TO EXTERIOR
/1 AMES 2000B BACKFLOW PREVENTER
To damaana piping
15
1
80
10
SPRINKLER RISER
NIS
1 WATER METER
V
AIN FLOO
LAN
ALL PIPE TO BE 1 "CPUC
U\LESS OTHERWISE NOTED
6" 120v Bell to be located on
the exterior approach to
home
1/4" = 1'-0"
ACCEPTED
❑ Without Comments
,.s Noted 11 Red
❑ Per The Attacned Letter
These plans have been reviewed by fhe Tukw 13
Preverpor.eureau for conform?i'-e ' id cunei C
sr ,arcs -AcCektance Is suble to err and
^�A� iCh do not authorize "Ioi:r 01�dcpted
,, R ds and ordlr•ances The resoV, �slh , `or the
Eideouucrof design ests total v >n'th I : :_e signer
Additions, de'pbars or revisions rc drawings after
tnls date will void t`' s acceptance a '_^ recu're a
resubmittal of revised c-aivings ro aCo-^'
Final acceptance is scr!Aec* to field test ano Insccro-
The Tukwila Fire Prevercb^ bu•eau
Date 5,4)-3 c/ By d'l /
to>' ' w, -1, 4,-14pad Ir . wa✓k r dt-ht
yab 1-ev„ c l
Y- Now (S„c.14 f) 4 erg- rrvv -
6 5 3 A warning sign with minimum '/ inch letters shall be affixed
adjacent to the main shutoff valve and shall state the following
WARNING The water system for this home supplies fire
sprinklers that require certain flows and pressures to fight a
fire Devices that restrict the flow or decrease the pressure or
automatically shut off the water to the fire sprinkler system
such as water softeners filtration systems and automatic shut
off valves shall not be added to this system without a review
of the fire sprinkler system by a fire protection specialist Do
not remove this sign
•
Stamp
WASHINGTON STATE
CERTIFICATE OF COMPETENCY
p FIRE PROTECTION SPRINKLER SYSTEMS
1 Michael D Hutchinson
1166 -0599 -BG Level 2
Evergreen Fire Protection Inc
EVERGFP967LZ
c
Sig I r•
General Notes
1 OWNER TO PROVIDE ADEQUATE HEAT (40 F MIN) TO PREVENT
SPRINKLER PIPES FROM FREEZING
2 OWNER TO PROVIDE HARD WIRED HOME SMOKE DETECTION SYSTEM
3 CPVC PIPE SHALL HAVE HANGERS 6 —0" c\c AND NOT MORE THAN
6" FROM ANY SPRINKLER HEAD
4 ALL ATTIC PIPING TO BE TENTED WITH BATT INSULATION TO PREVENT
FREEZING
5 ALL PIPING TO BE 1" CPVC UNO
6 A 6" BELL TO BE LOCATED ON THE EXTERIOR APPROACH TO HOME IF
REQUIRES BY THE LOCAL A H J
7 IF A OUTLET FOR A FUEL FIRED APPLIANCE IS PIPED ON AN EXTERIOR
COVERED DECK A INTERMEDIATE TEMP DRY SPRINKLER WILL BE
INSTALLED
SYM
v
Sprinkler Symbol Legend
SPRINKLER ORIFICE SIZE TYPE & FINISH
RELIABLE RFC 43 16 x16 2 head flow requirement 26 GPM ® 9 6 psi
RELIABLE F1 RES 49 16 x16 FLOW REQUIREMENT 26 GPM ® 9 6 psi
RELIABLE F1 RES 44 SIDEWALL 16 X 20
VICTAULIC DRY UPRIGHT
Reliable F 3 QR DRY Sidewall
TOTAL
QUAN TEMP K FACTOR
21
3
24
155
155
155
200
155
49
43
43
56
56
DATE 9/9/2014
EVE�C EEN FRE PCTECTIO
PO BOX 998
Puyallup, WA 98371
EVERGFP967LZ
Phone (253) 252-7942
' REV
I DRAWN MH
INC
' SHEET 1 OF1
Sheet Title
\F3A 133 FIDE LI\
2603A Lcncfair lot 2
Job Title
/I,
1313 s 160th st
Tu<wilc, .WA 98188
Q ?/ c -At'h
COV'D PATIO
FILE COPY
L
TO UPPER FLOOR
BEN00
FANILY BOOM
16-2 X 15—D
CLOSET
KITCHE\
13-6 X 15
TO SPRINKLERS
atilli-'1-- PRESSURE SWITCH (WIRE TO PUMP)
PRESSURE GUAGE
OPEN TO
3ELOW
UTILITY
300 GALLON WATER TANK
CONP.
LOFT
FLOW SWITCH (WIRE TO EITHER
OUTSIDE BELL OR HOUSE SECURITY
SYSTEM)
DRAIN ASSEMBLY
(PIPE TO TOP OF TANK)
SINGLE CHECK VALVE ASSEMBLY
BONUS ROO
=19-0X13
VAULTEI CL
OPT, CLST
240 volt 1.5 HP pu :+p
3 CAR GARAGE
COV'D
POMC
» FLOOR DLA
INSULATION
MMMMMM MM MM
M Mx.rr M�
STATE 1t
MM MrrMpSNINOTON - q
� CERTIFICATE
OF COMPETENCY
j PURE PROTECTION SPRINKLER SYSTEMS
•
Michael D. Hutchinson
•
•
166 -0599 -BG Level 2
Evergreen Fire Protection, Inc. °m
R
w
='.s7
E l - Ex13Uros a
f 2/3'119 S
General Notes
Sprinkler Symbol Legend
1. OWNER TO PROVIDE ADEQUATE HEAT (40'F. MIN) TO PREVENT
SPRINKLER PIPES FROM FREEZING.
2. OWNER TO PROVIDE HARD WIRED HOME SMOKE DETECTION SYSTEM.
3. CPVC PIPE SHALL HAVE HANGERS 6C-0" c\c AND NOT MORE THAN
6" FROM ANY SPRINKLER HEAD.
4. ALL ATTIC PIPING TO BE TENTED WITH BATT INSULATION TO PREVENT
FREEZING.
5. ALL PIPING TO BE 1" C.P.V.C. U.N.O.
6. A 6` BELL TO BE LOCATED ON THE EXTERIOR APPROACH TO HOME IF
REQUIRES BY THE LOCAL A.H.J.
7. IF A OUTLET FOR A FUEL FIRED APPLIANCE IS PIPED ON AN EXTERIOR
COVERED DECK A INTERMEDIATE TEMP. DRY SPRINKLER WILL BE
INSTALLED.
SPRINKLER ORIFICE SIZE, TYPE & FINISH
RELIABLE RFC 43 16'x16' 2 head flow requirement 26 GPM ® 9.6 psi
RELIABLE F1 RES 49 16'x16' FLOW REQUIREMENT 26 GPM ® 9.6 psi
RELIABLE F1 RES 44 SIDEWALL 16' X 20'
VICTAULIC DRY UPRIGHT
Reliable F 3 QR DRY Sidewoll
TEMP K FACTOR
155' 4.9
155' 4.3
155' 4.3
200' 5.6
155' 5.6
VEGEE\ FRE POTECTIO\ I\C.
PO BOX 998
Puyallup, WA 98371
EVERGFP967LZ
Phone: (253) 252-7942
Sheet Title
NDA 13
76038 Lc
� FIRE LA\
ncfcir Lot 2
Job Title
/13/13 S.
TuKwillc
TOTAL
DATE: 2/13/2015
REV: 1 DRAWN: TH
SHEET: