HomeMy WebLinkAboutPP - 4339 S 160TH ST - LANDFAIR - PERMITS AND PLANS4339 S 160TH ST
ASSOCIATED PERMITS
14-S-209 14-5-207 D14-0142
IFEMEN
SITE LOCATION
CITY OF TUKWILA
FIRE DEPARTMENT
444 Andover Park East
Tukwila, WA 98188
206-575-4407
Date application
accepted:
FIRE PROTECTION SYSTEMS PERMIT APPLICATitON
Applications and plans must be complete in order to be accepted for plan review.
**PLEASE PRINT**
Site Address: 4319 S 160th ST
King Co. Assessor's Tax No.::
Suite Number: Floor:
Tenant Name: New Tenant? ❑ - Yes ❑ - No
Property Owner's Name: Sound Built Homes
Mailing Address: 12815 Canyon Rd E Puyallup,WA 98373
City State Zip
CONTACT PERSON -if there are questions about the submittal.
Name: Mike Hutchinson
Company Name:
Evergreen Fire Protection
Day Telephone:153 - 2 5 2 - 761 f -1 Z
Mailing Address: PO BOX 998 Puyallup 98371
City State Zip
E-mail Address: Evergreenfirepro@msn.com Fax Number: 253-252-7943
Valuation of Project (contractor's bid price): $ 4161.00
Scope of Work (please provide detailed information): new NFPA 13D fire sprinkler system
PERMIT APPLICATION NOTES
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules.
Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit
is commenced within 180 days after its issupnce, or if the work authorized on the site by such permit is suspended or
abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in
writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE
UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY
FOR THIS PERMIT.
BUILDING OWNER OR AUTHORIZED AGENT:
Signature: Date: 9/10/2014
Print Name: Mike Hutchinson Day Telephone: 253-381-4456
Plan Permit App.doc
5/14/10 TFD FP Form 8
SITE LOCATION
CITY OF TUKWILA
FIRE DEPARTMENT
444 Andover Park East
Tukwila, WA 98188
206-575-4407
Date application
accepted:
FIRE PROTECTION SYSTEMS PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
**PLEASE PRINT**
King Co. Assessor's Tax No.:
4339 S 160th st
Site Address: Suite Number: Floor:
Tenant Name: New Tenant? ®- Yes ❑ - No
Property Owner's Name:
Sound Built Homes
Mailing Address: 12815 Canyon rd. E Puyallup WA 98373
City State Zip
CONTACT PERSON -if there are questions about the submittal.
Mike Hutchinson
Name:
253 252 7942
Day Telephone:
Evergreen Fire Protection
Company Name:
PO Box 998 Puyallup WA
Mailing Address:
evergreenfirepro@msn.com City State Zip
E-mail Address: Fax Number:
Total number of new/relocated devices or sprinkler heads: 24
Valuation of Project (contractor's bid price): $ 4161.00
Scope of Work (please provide detailed information): New 13 D fire system
PERMIT APPLICATION NOTES
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules.
Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit
is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or
abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in
writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE
UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY
FOR THIS PERMIT.
BUILDING 0 OR AUTIZED AGENT:
Signature: Date:
Print Name: ` ` {, } a � t ' Day Telephone:
Plan Permit App.doc 1/2/13 TFD FP Form 8
3
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with per
0,0b)
� y - 5- ac%
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Project: Aj S -F e____
Sprinklers:
Fire Alarm:
Typ of I spection
Address: s31
Suite #:
s
/1,0
Conta Person:
Special Instructions:
SP
Phone No.:
IR Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
Sprinklers:
Fire Alarm:
Hood & Duct:
&'
-1''e-71- — o14
P/ 00-4
a 5 Crwt ittP v.,•‘ A)
SP
iv, L —op._
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Inspector: (
Date:
3/7/4,1----
Hrs.:
I
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
I
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy withrmit
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Project: 47Type
4M7/€
Sprinklers:
of Inspection':/
Address: v,;2jContact
Suite #: 37" 5 X60
sa
Person:
Special Instructions:
Occupancy Type: ,
Phone No.:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
PA'frt‘ b N S' _
//LeuP� 7.a.c� �A �,+f� inti 5 F,�-,
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type: ,
Inspector: l7�� l7353
Date:/Z/yO
Hrs.: /6
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
3/14/14
T.F..D. Form F.P. 113
DATE: 9/10/2014 C:\program files\HRS Systems\hhouse34\2603aa.rdf
t+
EVERGREEN FIRE PROTECTION, INC.
10509 64th AVENUE E
PUYALLUP,WA 98373
RESIDENTIAL SPRINKLER SYSTEM
HYDRAULICS CALCULATION REPORT
FOR
Landfair lot 4
Tukwila,WA
4339 S 160th st
Date: 9/10/2014
File No:
Data File Name: 2603aa.rdf
SPRINKLER SPACING
Page 1
256.0 sq. ft./spklr.(max) Max. Dist. Bet. Spklrs: 16.0 ft.
Min. Dist. Bet. Spklrs: 8.0 Max. Dist. Spklr. to Wall: 8.0 ft.
SPRINKLER SPECIFICATIONS
Mfr: 1 Reliable Descr: RA0612 RFC43 F1 Conc. Pend. (16x16) K=4.30
Calculated K Factor for Arm -Overs & Drops:
1.0 ft. x 1.101 in. Drop: K=4.26 (Incl. 1 Tee)
0.0 ft. x 1.101 in. Arm -Over: K=4.25 (Incl. 1 Tee & 1 Ell)
PIPE SPECIFICATIONS
Type: CPVC S-40 HWC: 150
WATER SUPPLY
Source: Public Test Date: By:
Static: 60.0 psi Resid: 0.0 psi Flow: 0.0 gpm
Public Main Size: 0 in
Domestic Demand: 0.0 gpm at node number 0
SPRINKLER DEMAND
No.S0lrs. Min Spklr. Press. Node Total Avail. Req'd
Flowing Flow (psi) No. Flow Press. Press.
1 13.0 9.3 1 13.0 60.0 33.4
2 13.0 9.3 1 26.1 60.0 46.8
REVIEWING AUTHORITY
City of Tukwila
1
IAicheel D. Hubddnson
110 Lave! 2
Ever resin Fee Inc.
712
DATE: 9/10/2014 C:\program files\HRS Systems\hhouse34\2603aa.rdf Page 2
P
R
E
S
S
U
R
E
(
S
1
WATER SUPPLY CURVE
60.0 CA �C
54.0
48.0
42.0
36.0
30.0
24.0
18.0
12.0
6.0
CB
CD
0.0 1 1 1 1 1 1 I 1 1 I
04 8 12 16 20 24 28 32 36 40
FLOW (GPM)
Static = 60.0 psi (fixed pressure)
(1 sprinkler flowing) (2 sprinklers flowing)
A = Available Water Supply
60.0 psi @ 13.0 gpm
B = Required Water Supply
33.4 psi @ 13.0 gpm
C = Available. Water Supply
60.0 psi @ 26.1 gpm
D = Required Water Supply
46.8 psi @ 26.1 gpm
DATE: 9/10/2014 C:\program files\HRS Systems\hhouse34\2603aa.rdf Page 3
w
RESULTS OF ANALYSIS
NFPA NODE & PIPE DATA
1 Sprinkler Flowing
Node Tag Elevation Node Type Pressure Discharge Notes
(FT) (PSI) (GPM)
1 20.0 K= 4.26 9.3
2 20.0 9.7
3 20.0 9.7
4 20.0 11.7
5 10.0 16.5
6 0.0 22.6
7 0.0 22.9
8 0.0 27.9
9 0.0 28.4
10 0.0 SOURCE 33.4
13.0
Pipe Tag K-fac AF AF to L C (Pt)
Frm Node El (ft) PT (q) node/ Nom ID Fit F (Pe) Notes
To Node El (ft) PT TF(Q) disch Act ID T FL/FT (Pf)
Pipe: 1 4.26 7.00 150 0.4
3 20.0 9.7 13.0 Disch 1.000 B: 5 5.00 0.0
1 20.0 9.3 13.0 1.101 12.00 0.031 0.4
Pipe: 2 0.00 3.00 150 0.0
3 20.0 9.7 0.0 1.000 B: 5 5.00 0.0
2 20.0 9.7 0.0 1.101 8.00 0.000 0.0
Pipe: 3 0.00 B: 5 51.00 150 2.1
4 20.0 11.7 13.0 1 1.000 L: 5 16.00 0.0
3 20.0 9.7 13.0 1.101 6R: 6 67.00 0.031 2.1
Pipe: 4 0.00 10.00 150 4.8
5 10.0 16.5 13.0 3 1.000 L: 5 5.00 4.3
4 20.0 11.7 13.0 1.101 15.00 0.031 0.5
Pipe: 5 0.00 3B:15 34.00 150 6.0
6 0.0 22.6 13.0 4 1.000 L: 5 22.00 4.3
5 10.0 16.5 13.0 1.101 2R: 2 56.00 0.031 1.7
Pipe: 6 0.00 5.00 150 0.3
7 0.0 22.9 13.0 5 1.000 4R: 4 4.00 0.0
6 0.0 22.6 13.0 1.101 9.00 0.031 0.3
Pipe: 7 0.00 1.00 150 5.0
8 0.0 27.9 13.0 6 1.000 0.00 0.0
7 0.0 22.9 13.0 1.101 1.00 0.031 5.0
Fixed Pressure Loss Device: 5.00 psi
Pipe: 8 0.00 79.00 150 0.5
9 0.0 28.4 13.0 7 1.500 4L:28 28.00 0.0
8 0.0 27.9 13.0 1.598 107.00 0.005 0.5
Pipe: 9 SOURCE 1.00 150 5.0
10 0.0 33.4 13.0 8 1.000 0.00 0.0
9 0.0 28.4 13.0 1.101 1.00 0.031 5.0
DATE: 9/10/2014 C:\program files\HRS Systems\hhouse34\2603aa.rdf Page 4
Fixed Pressure Loss Device: 5.00 psi
RESULTS OF ANALYSIS
NFPA NODE & PIPE DATA
2 Sprinklers Flowing
Node Tag Elevation Node Type Pressure Discharge Notes
(FT) (PSI) (GPM)
1 20.0 K= 4.26 9.3 13.0
2 20.0 K= 4.26 9.4 13.1
3 20.0 9.7
4 20.0 17.1
5 10.0 23.1
6 0.0 33.7
7 0.0 34.7
8 0.0 39.8
9 0.0 41.7
10 0.0 SOURCE 46.8
Pipe Tag K-fac AF AF to L C (Pt)
Frm Node El (ft) PT (q) node/ Nom ID Fit F
(Pe) Notes
To Node El (ft) PT TF(Q) disch Act ID T FL/FT (Pf)
Pipe: 1 4.26 7.00 150 0.4
3 20.0 9.7 13.0 Disch 1.000 B: 5 5.00 0.0
1 20.0 9.3 13.0 1.101 12.00 0.031 0.4
Pipe: 2 4.26 3.00 150 0.2
3 20.0 9.7 13.1 Disch 1.000 B: 5 5.00 0.0
2 20.0 9.4 13.1 1.101 8.00 0.031 0.2
Pipe: 3 0.00 13.1 2 B: 5 51.00 150 7.4
4 20.0 17.1 13.0 1 1.000 L: 5 16.00 0.0
3 20.0 9.7 26.1 1.101 6R: 6 67.00 0.111 7.4
Pipe: 4 0.00 10.00 150 6.0
5 10.0 23.1 26.1 3 1.000 L: 5 5.00 -4.3
4 20.0 17.1 26.1 1.101 15.00 0.111 10.3
Pipe: 5 0.00 3B:15 34.00 150 10.6
6 0.0 33.7 26.1 4 1.000 L: 5 22.00 -4.3
5 10.0 23.1 26.1 1.101 2R: 2 56.00 0.111 14.9
Pipe: 6 0.00 5.00 150 1.0
7 0.0 34.7 26.1 5 1.000 4R: 4 4.00 0.0
6 0.0 33.7 26.1 1.101 9.00 0.111 1.0
Pipe: 7 0.00 1.00 150 5.1
8 0.0 39.8 26.1 6 1.000 0.00 0.0
7 0.0 34.7 26.1 1.101 1.00 0.111 5.1
Fixed Pressure Loss Device: 5.0 psi
Pipe: 8 0.00 79.00 150 1.9
9 0.0 41.7 26.1 7 1.500 4L:28 28.00 0.0
8 0.0 39.8 26.1 1.598 107.00 0.018 1.9
Pipe: 9 SOURCE 1.00 150 5.1
DATE: 9/10/2014 C:\program files\HRS Systems\hhouse34\2603aa.rdf
10 0.0 46.8 26.1 8 1.000
9 0.0 41.7 26.0 1.101
Fixed Pressure Loss Device:
Legend:
PT - Total Pressure at Node
F1 - Flow rate (gpm)
L - Pipe Length
F - Fitting Length
T - Total Length of Pipe
0.00
1.00 0.111
5.0 psi
C - Hazen -Williams Coefficient
FL/FT - Friction Loss per Foot
Pt - Total Pressure Loss
Pe - Elevation Pressure Loss
Pf - Friction Pressure Loss
Fitting Code Letters:
E=45 Ell, L=90 Ell, B=TeeBch, R=TeeRun, C=Couplg,
The maximum velocity of water flow occurs in pipe
at 4.38 ft/s with 1 sprinkler flowing.
The maximum velocity of water flow occurs in pipe
at 8.79 ft/s with 2 sprinklers flowing.
PIPE FITTINGS TABLE
Pipe Table Name: standard.npt
PAGE: C MATERIAL: CPVC S-40 HWC: 150
Diameter Equivalent Fitting Lengths
(in) E L B R C
45 Ell 90 Ell TeeBch TeeRun Couplg
1.101 1.00 5.00 5.00 1.00 1.00
1.598 2.00 7.00 8.00 1.00 1.00
Page 5
0.0
5.1
S=SwgChk, G=GatV1v,
6
9
in Feet
S G X Y
SwgChk GatVly X Y
8.00 2.00 0.00 0.00
14.00 3.00 0.00 0.00
X= X, Y=
z
z
0.00
0.00
A negative value for flow rate indicates the direction of flow is from the second pipe nc
A Fixed Pressure Loss Device calcualtes as a positive friction loss
A Fire Pump calculates as a negative friction loss
Sprinkler system has been hydraulically calculated with the
HASS HOUSE 3.4 computer program (License No. R609099990)
to provide an average imbalance of 0.010 gpm at each node and
a maximum imbalance of 0.09 gpm with one sprinkler
flowing, and 0.015 gpm at each node and maximum imbalance
of 0.15 gpm with 2 sprinklers flowing in accordance
with NFPA 13 and 13D or 13R.
The minimum source pressure is 20.0 psi with a minimum required pressure
of 46.8 psi and a 7 minute flow of 183 gal. and a 10 minute flow of 260.8 gallons.
The minimum pressure at any node is 9.3 psi at node 1.
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
1
COV'D PATIO
ACCEPTED
Thebe plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current City
st ndards Acceptance is subject to errors and
of which do not authorize violations of adopted
standards and ordinances The responsibility for the
dequacy of design rests totally with the designer
oibons, deletions or revisions to these drawings after
this date will void this acceptance and will require a
resubmittal of revised drawings for subsequent approval
TUKWI A FIRE DEPARTMENT
Please call 206-575-4407 and
give this Fire Permit No.
and exact address for shut-
down
hutdown or rem approval t
Final acceptance Is subject to field test and Inspection by
The Tukwila Fire Prevention Bureau
Date ! s°Zi-1‘i By ,4i», i/ 1
3ED00M 2
10-5 X 10-7
UP FROM MAIN FLOOR
BEDROOM 3
FAMILY ROOvi
MASTER SUITE
f frV4 i 1 e,10- w, -4 -lit U. poo -f S'C 11
Co1,.,Pt y wIk 44446 4/0 4‘) al..fiR 1
1)17aw iej+ ret„Iatci
IoW 0,444 ) 4y.*
CLOSET
KITCHEN
CLOSET
6 53 A warning sign with minimum'/ inch letters shall be affixed
adjacent to the main shutoff valve and shall state the following
WARNING The water system for this home supplies fire
sprinklers that require certain flows and pressures to fight a
fire Devices that restrict the flow or decrease the pressure or
automatically shut off the water to the fire spnnkler system
such as water softeners filtration systems and automatic shut-
off valves shall not be added to this system without a review
of the fire sprinkler system by a fire protection specialist Do
not remove this sign
CLOSET
0
BEDROOM 4
11-0 X 13-5
0
DINING R Ove
11-0 x 11-6
COFFERED CLG
SPRINKLER RISER
UTILITY
BONUS
19-0
VAULTE
FOYER
3 CAR GARAGE
0
LIVING ROOV
COV'D
PORCH
STATIC WA1ER PRESSURE 00 ps
U »E� ELOO 9LA\
TO SYSTEM
WATER FLOW
INDICATOR
INSULATION
PRESSURE
GAUGE
VAI\ EL00�
DRAIN VALVE
-- DRAIN PIPED TO EXTERIOR
AME3 2000B BACKFLOW PREVENTER
To do nenh &frog
15
10 1" WATER METER
ALL PIPE TO BE 1 "CP\/ C
UNLESS OTHERWISE NOTED.
6" 120v EeII to be IocatelF1 on
the exterior approach to
home
SPRINKLER RISER
INSULATION TENTING DETAIL
WASHINGTON STATE
CERTIFICATE OF COMPETENCY
II FIRE PROTECTION SPRINKLER SYSTEMS
!Michael D Hutchinson
1166 -0599 -BG Level 2
Evergreen Fare Pr • cbon Inc
EVERGF'967
12131 14
General Notes
Sprinkler Symbol Legend
1 OWNER TO PROVIDE ADEQUATE HEAT (40F MIN) TO PREVENT
SPRINKLER PIPES FROM FREEZING
2 OWNER TO PROVIDE HARD WIRED HOME SMOKE DETECTION SYSTEM
3 CPVC PIPE SHALL HAVE HANGERS 6 —0" c\c AND NOT MORE THAN
6" FROM ANY SPRINKLER HEAD
4 ALL ATTIC PIPING TO BE TENTED WITH BATT INSULATION TO PREVENT
FREEZING
5 ALL PIPING TO BE 1" CPVC UNO
6 A 6" BELL TO BE LOCATED ON THE EXTERIOR APPROACH TO HOME IF
REQUIRES BY THE LOCAL A H J
7 IF A OUTLET FOR A FUEL FIRED APPLIANCE IS PIPED ON AN EXTERIOR
COVERED DECK A INTERMEDIATE TEMP DRY SPRINKLER WILL BE
INSTALLED
SPRINKLER ORIFICE SIZE TYPE & FINISH
RELIABLE RFC 43 16 x16 2 head flaw requirement 26 GPM ® 9 6 psi
RELIABLE F1 RES 49 16 x16 FLOW REQUIREMENT 26 GPM CSD 9 6 psi
RELIABLE F1 RES 44 SIDEWALL 16 X 20
VICTAULIC DRY UPRIGHT
Reliable F 3 QR DRY Sidewall
TEMP K FACTOR
155 4 9
155 4 3
155 4 3
200 5 6
155 5 6
EVE�C EEN FRE POTECTI0N I\C
PO BOX 998
Puyallup, WA 98371
EVERGFP967LZ
Phone (253) 252-7942
TOTAL 24
DATE 9/9/2014
' REV I DRAWN MH
I SHEET 1 OF1
Sheet Title
Job Title
\T3A 133
7603A Lcnc
FIDE
fcir
X1339 s 160th st
TUKWIIQ, WA 98188