HomeMy WebLinkAboutPP - 4238 S 146TH ST - UNKNOWN - PERMITS AND PLANS4238 S 146TH ST
ASSOCIATED PERMITS
94-5-150
WASHINGTON STATE FIRE MARSHAL'S OFFICE
CONTRACTORS•MATERIAL & TEST REPORT FOR ABOVEGROUND PIPING
FIRE SPRINKLER ADVISORY BOARD
PROCEDURE
Upon completion of work, Inspection and teats shall be made by the contractor's representative and witnessed by an owner's representative. All defects
shall be corrected and system left in service before contractor's personnel finally leave the Job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and contractor. It Is under-
stood the owner's representative's signature In no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply
with approving authority', requirements or local ordinances.
PROPERTY NAME
PROPERTY ADDRESS RO ` Z�y
CCEPTED BY AUTHORITIES
(IfyAME)
— k (�u-. LDEs?,!.* V.63 tD�HCE
• PLANS'
DATE
lo --6 —7(7/
ADDRESS 444_
A.^� ry,
INSTALLATION CONFORMS TO ACCEPTED PLANS
EQUIPMENT USED IS APPROVED
IF NO, EXPLAIN DEVIATIONS
OYES UNO
❑ YES ❑ NO
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION
OF CONTROL VALVE AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT?
IF NO, EXPLAIN
INSTRUCTIONS
LOCATION
OF SYSTEM
HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES:
1. SYSTEM COMPONENTS INSTRUCTIONS
2. CARE AND MAINTENANCE INSTRUCTIONS.
3. NFPA 13A
SPRINKLERS
SUPPLIES BUILDINGS
YES U NO
OYES UNO
❑YES NO
❑YES NO
OYES ONO
MAKE
MODEL
YEAR OF
MANUFACTURE
ORIFICE
SIZE
c �r�• i iztl L
14
I �Z
QUANTITY
1S
TEMPERATURE
RATING
/SS"
PIPE AND
FITTINGS
ALARM
VALVE
013 FLOW
INDICATOR
TYPE OF PIPE lPIOL t kL
TYPE OF FITTINGS
ALARM DEVICE
TYPE 1 MAKE
MODEL
MAXIMUM TIME TO OPERATE
THROUGH TEST CONNECTION
SEC.
MIN
61'71f(
a--
DRY PIPE
OPERATING
TEST
DRY VALVE
Q.OD.
MAKE
MODEL ( SERIAL NO.
MAKE
MODEL
SERIAL NO.
" TIME TO TRIP
THRU TEST
CONNECTION
MIN.
WATER
PRESSURE
SEC.
WITHOUT
O.O.D.
PSI
AIR
PRESSURE,... -A
�sr
TRIP - T/
N
RESSURE
Y TIME WATER
REACHED
TEST OUTLET
PSI
MIN.
SEC.
ALARM
OPERATED
PROPERLY
NO
YES
WITH
Q.O.D.
IF NO, N
' MEASURED FROM TIME INSPECTORS TEST CONNECTION IS OPENED
85A (OVER)
FEB 2 1 1q9
PT'LUGE &
Fi1EACTION
'IALVES
OPERATION
Cl PNEUMATIC ❑ ELECTRIC 0 HYDRAULI
PIPING SUPERVISED DYES U NO GETECI s Pc1rmtSUPERVISED UYES U NO
DOES VALVE OPERATE FROM THE MANUAL TRIP ANEW Mot E3 (0N1 ROL .': TATIONS UYES UNO
IS THERE AN ACCESSIBLE FACILITY IN EA - - `C; IIT FOR TESFINO ' IF NO, EXPLAIN
OYES I NO
DOES EACH CIRCUIT OPFiIA1 E.
SUPERVISION LOSS ALARM
YES • HO
MAKE
TEST
DF!;C:IIIPTION
ODEL
DOES EACH CIRCUIT MAXIMUM TIME TO
c. PERATE VALVE RELEASE OPERATE RELEASE
'1'1731NO MIN SEC
f2'1 tr n for two I• ra or 50 per .4 bars) above 11'IIc r41oure In exact c4 150 pal (10.2
H�J$T6Illy; ttydradatle leets .hall be mad. at rol Ieea than 200 ('el ( )
bars) to two horn. DmRererelal dryplpa wive clappers shall be )eft open c4:11ry teat b prroe rt damage. All aboveground piping Leakage shall be stopped.
ELEUMATIC; Establish 40 pal (27 bare) ,Jr presets* and mtasure dropwhich troll not cx ni i 1-1/2 psi (0.1 bars) In 24 hours. Teat pressure balls al normal wafer
Ievsl and air • reaure and measure e1 preaure drop whkhr,holl n:A exc - ad 1I/ Ds 1'J.1 t•• , alln 24 hours.
ALL PIPING HYDROSTATICALLY TESTED A T P`il FOR. I is ;•S. IF O, ST TE REASON
DRY PIPING PNEUMATICALLY TESTED OYES ❑ NO
EQUIPMENT OPERATES PROPERLY AYES ONO
DO YOU CERTIFY AS THE SPRINKLER SYSTEM CONTRACTOR 11IAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM
SIUCATE OR DERIVATIVES OF SODIUM SIUCATE, BRINE, OR OTIiER CORROSIVE CHEMICALS WERE NOT USED FOR TEST-
ING SYSTEMS OR STOPPING LEAKS? OYES 13 NO
r:;: T?; / if DRAIN
TEST READING OF GAGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST
SUPPLY TEST CONNECTION: PSI CONNECTION OPEN WIDE PSI
UNDERGROUND MAINS AND LEAD IN CONNECTIONS TO SYS TEM (i1SERS FLUSI IED BEFORE CONNECTION MADE TO
SPRINKLER PIPING.
VERIFIED BY COPY OF THE U FORM NO. 85B OYES 0 NO OTHER
FLUSHED BY INSTALLER OF UNDER-
GROUND SPRINKLER PIPING BYES 0 NO
BLANK TESTING NUMBER ,JSED LOCATIONS
GASKETS
WELDED PIPING YES NO
EXPLAIN
NUMBER REMOVED
IF YES.. .
00 YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WEU.(I Li PRUCEDU� EtE S COMPLY
WITII THE REQUIREMENTS OF AT LEAST AWS 010.9, LEVEL AR -3
G0 YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WEL'.:FIRS OUAUFIED IN
COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST AWS D10.9, 1..EVL AR -3
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANf ;E WITH A
DOCUMENTED QUALITY CONTROL PROCEDURE TO INSURE 11 'AT Pit DISCS ARE
RETRIEVED, THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAG AND OTHER
WELDING RESIDUE ARE REMOVED, AND THAT THE INTERNAL DIAMETERS OF ❑YES
PIPING ARE NOT PENETRATED
DO YOU CERTIFY THAT YOU HAVE A CONTROL FEA ;URE TO ENSURE THAT ALL ❑YES
CUTOUTS (DISCS) ARE RETRIEVED?
WERE FUNCTIONAL FLOW TEST DOES AHJ REQUIRE A FUNCTIONAL
SULFLOW OF
TS SATISFACTORY? N21 114v./ Ile pw ®Sb � �''❑YES
NAME PLATE PROVIDED IF NO, EXPLAIN
OYES ONO
CUTOUTS
(DISCS1
FUNCTIONAL
FLOWTEST
HYDTWUQC
DATA NAMEPLATE.
❑YES ONO
OYES ONO
❑ NO
❑ NO
UNO
❑ NO
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN:
REMARKS
SIGNATURES
NAMEF SPRINKLER CONTRACTOR
��C G 1 e_E POTECTE'Cf- S4'5T>` Dfr[S L��l
TESTS WITNESSED BY
Fr PER OVV/ (SIGNED)
F R SPRINK R CONTRACTOR (SIGNED)
FOR APPROVING AUTHORITY
CONTRACTOR LICENSE #
TITLE
DATE
IAL)
TITLE
TITLE
DATE
DATE
THAT THE INFORMATION HEREIN IS TRUE AND THAT Ti II 1;('RINKLER SYSTEM WAS INSTALLED IN ACCORD-
RCW 18-160 AND THE RULES ADOP TED BY THE WASH" ;(.11 ON ADMINISTRATIVE CODE AS ADMINISTERED BY
RE MARSHAL
GISTRATION # 3 e.,74 0 c,43
(IAP.CERTIFICATE O )MPETENCY HOWER (PRINT OR TYPE)
il.lfE OF CERTIFICATE OF COMPETENCY HOLDER 1L
DATE )x -1—' L
Sheet of 7
HYDRAULIC CALCU..ATIONS
P'ir^lemp Pr-a't b icw-s "Sysmteminmes., =r -roc
26217 Maple Valley/Black Diamond Rd. SE
Maple Valley. WA 98038
tP.SA Z
Job _ RK Builders
4238 S. 146th Steet, Tukwila. WA. 98168
Authority having Jurisdiction
QTY
Density
Area of Application
Coverage per Sprinkler
_ _ Tukwila
L.H./Residential
0.07 qpm/sa.ft.
392 square feet
196 sq. ft.
Date 07/16/94
Job: RKRES
Number of Sprinklers Calculates t
System type_ _ Wet
Water Supply 70.00 psi Static. 20.00 psi Residual @ 1000.0 qpm
Demand _ _ _ 32.74 psi @ 16.0 gpm @ B.O.R.
38.84 psi @ 16.0 gpm @ Supply
69.98 psi available @ 16.0 qpm
Demand is below curve by 31.14 psi
Sprinklers _ _ Central GSR Concealed
94
r
ati
CID
i4111
-
Static = 70.00 psi, Residual =
Demand at BOR = 32.74 psi with
System demand = 38.84 psi with
Pressure available = 69.98 psi
Demand is below curve by 31.14
20.00 psi ata flow of 1000.0 gpm.
16.0 gPm flowing.
16.0 gpm�flowing.
when 16.0 spm is flowing.
psi. (44.5%)
4iii iiPAU " 3 M
gia
Sheet 3
Ace Fire Protection Systems, Inc.
Sprinkler Systems hydraulic Flow Calculations
RK Builders
4238 S. 146th Steet, Tukwila, WA. 98168
Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (sdpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Notes
Branchline-No. 1
C = 150
A 5.0 PT 13.80 1 End head
16.0=4.30(13.80)".5 F 12.8 PE 0.00
1 16.0 0.88 1E 1T T 17.8 0.1307,5 PF 2.32 8.35
PT 16.12 5 Cross main Jct
K -factor for branchline no. 1 = 16.0/(16.12)".5 = 3.98
Sheet 4
Ace Fire Protection Systems. Inc.
Sprinkler Systems Hydraulic Flaw Calculations
RK Builders
4238 5. 146th Steet. Tukwila. WA. 98168
Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Notes
Cross mein C = 150
A 11.5 PT 16.12 5 BL1
16.0=3.98(16.12)-.5 F 8.5 PE 0.00
5 16.0 0.88 1T T 20.0 0.13115 PF 2.62 8.36
PT 18.75 7 Bulk Jot
K -factor for Cross main = 16.0/(18.75).5 = 3.70
Sheet 5
Ace Fire Protection Systems, Inc.
Sprinkler Systems Hydraulic Flow Calculations
RK Builders
4238 S. 146th Steet. Tukwila. WA. 98168
Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (qpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Notes
Bulk C = 150
A 11.0 PT 18.75 7 CM
16.0=3.70(18.751%5 F 13.9 PE 4.33 (EL= 10.00 ft)
7 16.0 1.11 1T lE T 24.9 0.04347 PF 1.08 5.31
A 15.0 PT 24.16 8 ** C = 120 **
F 15.0 PE 0.00
8 16.0 1.05 7E 1GV T 30.0 0.08612 PF 8.58 5.94 1DET = 6.00#
1DET PT 32.74 10
Under grouid C = 150
A 220.0 PT 32.74 10 B.O.R.
F 23.6 . PE 4.33 (EL= 10.00 ft)
10 16.0 1.60 2E 1T T 243.6 0.00725 PF 1.77 2.55
PT 38.84 11 Supply Jct
Available flow at 38.84 psi is 774.4 qpm which is 758.4 qpm from curve.
Su?p1Y pressure available with 16.0 gpm flowing is 69.98 psi,
thus system requirement is 31.14 psi below supply carve. (44.5%)
Ace Fire Protection Systems. Inc.
Sprinkler Systems Hydraulic Flow Calculations
RK Builders
4238 S. 146th Steet. Tukwila. WA. 98168
Discharge Pressure Outlet
Node (g m) (psi) K -Value Source
Sheet (p
Elevation
(ft) Comments
1 16.0 13.80 Orif= 4.30
5 - 16.12
7 - 18.75
8 - 24.16
10 - 32.74
11 - 38.84
Supply
20.00
20.00
20.00
10.00
10.00
0.00
Sheet ?
Ace Fire Protection Systems, Inc.
Sprinkler Systems Hydraulic Flow Calculations
RK Builders
4238 S. 146th Steet, Tukwila, WA. 98168
Actual Total Elev Frio Frio Press Press
Pipe Diam Len Len Head Flow Loss Loss Vel Nodes I Beg @ End
No. (inch) (Ft) (Ft) (Ft) (Gpm)(Psi/Ft)(Psi)(Fos) Beg End (Psi) (Psi)
1 0.88 5.0 17.8 0.00 16.0 0.1308 2.32 8.4 1 5 13.80 16.12
Fit= 12.8 lE 1T
5 0.88 11.5 20.0 0.00 16.0 0.131? 2.62 8.4 5 7 16.12 18.75
Fit= 8.5 1T
7 1.11 11.0 24.9 10.00 16.0 0.0435 1.08 5.3 7 8 18.75 24.16
Fit= 13.9 1T lE
8 1.05 15.0 30.0 0.00 16.0 0.0861 2.58 5.9 8 10 24.16 32.74
Fit= 15.0 7E 1GV 1DET
10 1.60 220.0 243.6 10.00 16.0 0.0072 1.77 2.5 10 11 32.74 38.84
Fit= 23.6 2E 1T
Sheet I of 7
HYDRAULIC CALCULATIONS
Ao_.ee f.5)essi=eeinnes, Ir�c
26217 Maple Valley/Black Diamond Rd. SE
Maple Valley. WA 98038
ME A 2
Job_ _ RK Builders
4238 S. 146th Steet. Tukwila. WA. 98168
Authority having Jurisdiction_ _ Tukwila
Occupancy_ _ _ L.H./Residential
Density _ 0.07 gpm/sa.ft.
Area of Application_ _ _ _ _ 392 square feet
Coverage per Sprinkler 196 sa. ft.
Number of Sprinklers Calculated:
Date 07/16/94
Job: RKRES
System type_ _ Wet
Water Supply _ 70.00 psi Static. 20.00 psi Residual @ 1000.0 gpm
Demand _ _ _ _ 36.68 psi @ 26.2 QOM @ B.O.R.
45.41 psi @ 26.2 gpm @ Supply
69.94 psi available @ 26.2 Spm
Demand is below curve by 24.53 psi
Sprinklers _ _ Central GBR Concealed
1-Z0- 94
E
Pv .ssaari. [PSI
Si II
Sheet 2
a c.ft
9r,
•
! r i
I
Static = 70.00 psi, Residual = 20.00 psi ata flow of 1000.0 QPM.
Demand at BOR = 36.68 psi with 26.2 gom flowin.
System demand = 45.41 psi with 26.2 gpm s�flowing.
Pressure available = 69.94 psi when 26.2 gpm is flowing.
Demand is below curve by 24.53 psi. (35.1%)
filittq ll'AU "MI
-g
Sheet 3
Ace Fire Protection Systems, Inc.
Sprinkler Systems Hydraulic Flow Calculations
RK Builders
4238 S. 146th Steet, Tukwila, WA. 98168
Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Notes
Branchline No. 1 C = 150
A 5.0 PT 9.10 1 End head
13.0=4..30(9.10)".5 F 12.8 PE 0.00
1 13.0 0.88 1E 1T T 17.8 0.08894 PF 1.58 6.78
PT 10.68 5 Cross main Jct
K -factor for braichline no. 1 = 13.0/(10.68)".5 = 3.98
Branchline No. 2 C = 150
A 1.0 PT 9.10 3 End head
13.0=4..30(9.10)".5 F 12.8 PE 0.00
3 13.0 0.88 1E 1T T 13.8 0.08896 PF 1.22 6.78
PT 10.32 5 Cross main Jct
K -factor for branchline no. 2 = 13.0/(10.32)".5 = 4.05
Sheet
Ace Fire Protection Systems, Inc.
Sprinkler Systems Hydraulic Flow Calculations
RK Builders
4238 5. 146th Steet, Tukwila, WA. 98168
Pine Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fos) Notes
Cross main
K=8.02=3.97+4.05 A 11.5 PT 10.68 5
26.2=8.02(10.68)".5 F 8.5 PE 0.00
5 26.2 0.88 1T T 20.0 0.3274 PF 6.55 13.71
PT 17.23 7
K -factor for Cross main = 26.2/(17.23)".5 = 6.31
C = 150
ELI + BL2
Bulk Jct
Sheet 6
Ace Fire Protection Systems. Inc.
Sprinkler Systems Hvdraulic Flow Calculations
RK Builders
4238 S. 146th Steet, Tukwila. WA. 98168
Pipe Flow Dia Fitting Length Fr Loss Press Hvd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Notes
Bulk
A 11.0 PT 17.23 7
26.2=6.31(17.23) .5 F 13.9 PE 4.33
7 26.2 1.11 1T 1E T 24.9 0.10825 PF 2.69
A 15.0 PT 24.25 8
F 15.0 PE 0.00
8 26.2 1.05 7E 1GV T 30.0 0.21446 PF 12.43
1DET PT 36.68 10
C = 150
CM
(EL= 10.00 ft)
8.70
** C = 120 **
9.73 1DET = 6.00#
Under ground C = 150
------ A 220.0 PT 36.68 10 B.O.R.
F 23.6 PE 4.33 (EL= 10.00 ft)
10 26.2 1.60 2E 1T T 243.6 0.01805 PF 4.40 4.17
PT 45.41 11 Supply Jct
Available flow at 45.41 psi is 681.4 Qpm which is 655.2 Qpm from curve.
Supply pressure available with 26.2 gpm flowing is 69.94 psi,
thus system rec$rement is 24.53 psi below supply curve. (35.1%)
a
Ace Fire Protection Systems. Inc.
Sprinkler Systems Hydraulic Flow Calculations
RK Builders
4238 S. 146th Sheet, Tukwila. WA. 98168
Discharge Pressure Outlet
Node (gpm) (psi) K -Value Source
Sheet Cy
Elevation
(ft) Comments
1 13.0 9.10 Orif= 4.30
3 13.0 9.10 Orif= 4.30
5 - 10.68
7 - 17.23
8 - 24.25
10 - 36.68
11 - 45.41
Supply
20.00
20.00
20.00
20.00
10.00
10.00
0.00
4
J
Sheet _%
Ace Fire Protection Systems, Inc.
Sprinkler Systems Hydraulic Flow Calculations
RK Builders
4238 S. 146th Steet. Tukwila. WA. 98168
Actual Total Elev Fric Fric Press Press
Pipe Diam Len Len Head Flow Loss Loss Vel Nodes I Beg @ End
No. (inch) (Ft) (Ft) (Ft) (Gpm)(Psi/Ft)(Psi)(Fos) Beg End (Psi) (Psi)
1 0.88 5.0 17.8 0.00 13.0 0.0890 1.58 6.8 1 5 9.10 10.68
Fit= 12.8 1E 1T
3 0.88 1.0 13.8 0.00 13.0 0.0899 1.22 6.8 3 5 9.10 10.68
Fit= 12.8 1E 1T
5 0.88 11.5 20.0 0.00 26.2 0.3271 6.55 13.7 5 7 10.68 17.23
Fit= 8.5 1T
7 1.11 11.0 24.9 10.00 26.2 0.1082 2.69 8.7 7 8 17.23 24.25
Fit= 13.9 1T 1E
8 1.05 15.0 30.0 0.00 26.2 0.2145 6.43 9.7 8 10 24.25 36.68
Fit= 15.0 7E 1GV 1DET
10 1.60 220.0 243.6 10.00 26.2 0.0181 4.40 4.2 10 11 36.68 45.41
Fit= 23.6 2E 1T
Sheet 1 of 7
HYDRAULIC CALCULATIONS
Amacee Firee SYsteemes,
26217 Maple Valley/Black Diamond Rd. SE
Mahle Valley. WA 98038
Date 07/16/94
Job: RKRES2
Job_ _ RK Builders
4238 S. 146th Street, Tukwila, WA. 98168
Authority having Jurisdiction_
Occupancy
Density
Area of Application
Coverage per Sprinkler
Number of Sprinklers Calculated.
Tukwila
L.H./Residential
0.07 gym/sa.ft.
392 sure feet
196 sa. ft.
System type_ _ Wet
Water Supply _ 70.00 psi Static, 20.00 psi Resid.ral @ 1000.0 glom
Demand _ _ _ _ 43.05 psi @ 16.0 glom @ B.O.R.
44.82 psi @ 16.0 vpm @ Supply
69.98 psi available @ 16.0 glom
Demand is below curve by 25.16 psi
Sprinklers _ _ Central GBR Concealed
r
0
tij
3
v
1-6
N
•
Priek 111119'1111
i-
Sheet
[ PIS I
ENE
L
Static = 70.00 psi. Residual =
Demand at BOR = 43.05 psi with
System demand = 44.82 psi with
Pressure available = 69.98 psi
Demand is below curve by 25.16
20.00 psi at a flow of 1000.0 spm.
16.0 gK, n flowing.
16.0 Spm flowing.
when 16.0 gpm is flowing.
Psi. (36.0%)
anAUD 41115,1 tams Ja;Fll
Sheet 3
Ace Fire Protection Systems, Inc.
Sprinkler Systems Hydraulic Flow Calculations
RK Builders
4238 S. 146th Street, Tukwila, WA. 98168
Pitz Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (gt m) (inch) and Dev (ft) (Psi/ft) (psi) Ref (fps) Notes
Branchline No. 3 C = 150
A 10.0 PT 13.80 1 End head
16.0=4.30(13.80)".5 F 25.5 PE -1.73 (EL= --4.00 ft)
1 16.0 0.88 6E T 35.5 0.13075 PF 4.65 8.35
A 26.0 PT 16.71 2
F 42.6 PE 1.73 (EL= 4.00 ft)
2 16.0 0.88 2T 6E T 68.6 0.13075 PF 8.96 8.35
PT 27.41 5 Cross main Jct
K -factor for braich1ine no. 3 = 16.0/(27.41)-.5 = 3.06
Sheet 4
Ace Fire Protection Systems, Inc.
Sprinkler Systems Hydraulic Flow Calculations
RK Builders
4238 S. 146th Street, Tukwila, WA. 98168
Pica Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Notes
Cross main C = 150
A 15.0 PT 27.41 5 BL3
16.0=3.06(27.41)A.5 F 17.8 PE 1.30 (EL= 3.00 ft)
5 16.0 1.11 2E 1T T 32.8 0.04347 PF 1.43 5.31
PT 30.14 7 Bulk Jct
K -factor for Cross main = 16.0/(30.14)^.5 = 2.91
.41
Ace Fire Protection Systems, Inca
Sprinkler Systems Hydraulic Flow Calculations
RK Builders
4238 S. 146th Street. Tukwila. WA. 98168
Sheet 5
Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Notes
Bulk C = 120
A 15.0 PT 30.14 7 CM
16.0=2.91(30.14)^.5 F 15.0 PE 4.33 (EL= 10.00 ft)
7 16.0 1.05 7E 1DET T 30.0 0.08612 PF 8.58 5,.94 1DET = 6.00#
1GV PT 43.05 10
l hcler ground
A 220.0 PT 43.05 10
F 23.6 PE 0.00
10 16.0 1.60 2E 1T T 243.6 0.00725 PF 1.77 2.55
PT 44.81 11
C = 150
B.O.R.
Supply Jot
Available flow at 44.81 psi is 690.3 gpm which is 674.3 gpm from curve.
SuplY pressure available with 16.0 gpm flowing is 69.98 psi,
thus system requirement is 25.16 psi below wooly curve. (35.9%)
Ace Fire Protection Systems, Inc,
SprinklerSystems Wdraulic Flow Calculations
RK Builders
4238 S. 146th Street, Tukwila, WA. 98168
Discharge Pressure Outlet
Node (gpm) (psi) K -Value Source
Sheet (p
Elevation
(ft) Comments
1
2
5
7
10
11
16.0
13.80 Orif= 4.30
16.71
27.41
30.14
43.05
44.81
SUDO1Y
13.00
17.00
13.00
10.00
0.00
0.00
• . . •
Ace Fire Protection Systems, Inc.
Sprinkler Systems Hydraulic Flow Calculations
RK Builders
4238 S. 146th Street, Tukwila, WA. 98168
Sheet 7
Actual Total Elev Fric Fric Press Press
Pipe Diam Len Len Head Flow Loss Loss Vel Nodes @ Beg @ End
No. (inch) (Ft) (Ft) (Ft) (Gpm)(Psi/Ft)(Psi)(Fos) Beg End (Psi) (Psi)
1 0.88 10.0 35.5 -4.00
Fit= 25.5 6E
2 0.88 26.0 68.6 4.00 16.0 0.1308 8.96 8.4 2 5 16.71 27.41
Fit= 42.6 2T 6E
5 1.11 15.0 32.8 3.00 16.0 0.0435 1.43 5.3 5 7 27.41 30.14
Fit= 17.8 2E 1T
7 1.05 15.0 30.0 10.00 16.0 0.0861 2.58 5.9 7 10 30.14 43.05
Fit= 15.0 7E 1DET 1GV
10 1.60 220.0 243.6 0.00 16.0 0.0072 1.77 2.5 10 11 43.05 44.81
Fit= 23.6 2E 1T
16.0 0.1308
4.65 8.4 1 2 13.80 16.71
HYDRAU_IC CALCULATIONS
Pira Pr-ortc+ctiorit S)sgtgns,
26217 Maple Valley/Black Diamond Rd. SE
Maple Valley, WA 98038
Job_ _ RK Builders
4238 S. 146th Street, Tukwila, WA. 98168
Authority having Jurisdiction
Occupancy
Density
Area of Application
Coverage per Sprinkler
_ _ Tukwila
L.H./Residential
0.07 gpm/sq.ft.
392 square feet
1•• ft.
Ni.mber of Sprinklers Calculat
Sheet 1 of %
Date 07/16/94
Job: RKRES2
System type_ _ Wet
Water Supply 70.00 DSi Static, 20.00 psi Resid.ial @ 1000.0 QPM
Demand _ _ _ _ 57.92 psi @ 26.9 gpm @ B.O.R.
62.54 psi @ 26.9 gpm @ SupplY
69.94 psi available @ 26.9 qpm
Demand is below curve by 7.40 psi
Sprinklers _ _ Central GSR Concealed
6
• ••
Pry s aar� C PW I ?
a
•
•
•
Sheet 2
Static = 70.00 psi, Residjal = 20.00 Psi at a flow of 1000.0 gam.
Demand at BOR = 57.92 psi with 26.9 gam flowing.
System demand = 62.54 psi with 26.9 spam flowing.
Pressure available = 69.94 Psi when 26.9 qpm is flowing.
Demand is below carve by 7.40 psi. (10.6x)
41t14ellPAU 'AWN
t'idpI S8' T N) analo
t
Ace Fire Protection Systems, Inc.
Sprinkler Systems Hydraulic Flow Calculations
RK Builders
4238 S. 146th Street, Tukwila, WA. 98168
3
Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Notes
Branchline No. 3 C = 150
A 10.0 PT 9.10 1 End head
13.0=4.30(9.10)-.5 F 25.5 PE -1.73 (EL= -4.00 ft)
1 13.0 0.88 6E T 35.5 0.08894 PF 3.16 6.78
A 26.0 PT 10.53 2
14.0=4.30(10.53)-.5 F 42.6 PE 1.73 (EL= 4.00 ft)
2 26.9 0.88 2T 6E T 68.6 0.34348 PF 23.55 14.07
PT 35.81 5 Cross main Jct
K -factor for tra,chline no. 3 = 26.9/(35.81)-.5 = 4.50
sheet 4
Ace Fire Protection Systems, Inc.
Sprinkler Systems Hydraulic Flow Calculations
RK Builders
4238 S. 146th Street, Tukwila, WA. 98168
Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Notes
Cross main C = 150
A 15.0 PT 35.81 5 BL3
26.9=4.50(35.81)-.5 F 17.8 PE 1.30 (EL= 3.00 ft)
5 26.9 1.11 2E 1T T 32.8 0.11365 PF 3.73 8.93
PT 40.84 7 Bulk Jct
K -factor for Cross main = 26.9/(40.84).5 = 4.21
Sheet 5
Ace Fire Protection Systems, Inc.
Sprinkler Systems Hydraulic Flow Calculations
RK Builders
4238 S. 146th Street, Tukwila, WA. 98168
Pipe Flow Dia Fitting Length Fr Loss Press FNd Vel
No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Notes
Bulk C = 120
A 15.0 PT 40.84 7 CM
26.9=4.21(40.84)^.5 F 15.0 PE 4.33 (EL= 10.00 ft)
7 26.9 1.05 7E 1DET T 30.0 0.22517 PF 12.76 9.99 1DET = 6.00#
1GV PT 57.92 10
lhder grou id
A 220.0 PT 57.92 10
F 23.6 PE 0.00
10 26.9 1.60 2E 1T T 243.6 0.01895 PF 4.62 4.28
PT 62.54 11
C = 150
B.O.R.
Supply Jct
Available flow at 62.54 psi is 357.6 gpm which is 330.7 gam from curve.
5uo1Y pressure available with 26.9 gpm flowing is 69.94 psi,
thus system requirement is 7.40 psi below supply curve. (10.6%)
Ace Fire Protection Systems, Inc.
Sprinkler Systems Hydraulic Flow Calculations
RK Builders
4238 S. 146th Street, Tukwila, WA. 98168
Discharge Pressure Outlet
Node (spm) (psi) K -Value Source
Sheet G
Elevation a
(ft) Comments
1 13.0 9.10 Orif= 4.30
2 14.0 10.53 Orif= 4.30
5 - 35.81
7 - 40.84
10 - 57.92
11 - 62.54
Supply
13.00
17.00
13.00
10.00
0.00
0.00
Ace Fire Protection Systems, Inc.
Sprinkler Systems Hydraulic Flow Calculations
RK Builders
4238 S. 146th Street, Tukwila, WA. 98168
Actual Total
Pipe Diam Len Len
No. (inch) (Ft) (Ft)
Sheet "?
Elev Fric Fric
Head Flow Loss Loss Vel Nodes
(Ft) (Gpm)(Psi/Ft)(Psi)(Fps) Beg End
Press
@ Beg
(Psi)
Press
@ End
(Psi)
1 0.88 10.0 35.5 -4.00
Fit= 25.5 6E
2 0.88 26.0 68.6 4.00 26.9 0.3435 23.55 14.1 2 5 10.53 35.81
Fit= 42.6 2T 6E
5 1.11 15.0 32.8 3.00 26.9 0.1137 3.73 8.9 5 7 35.81 40.84
Fit= 17.8 2E 1T
7 1.05 15.0 30.0 10.00 26.9 0.2252 6.76 10.0 7 10 40.84 57.92
Fit= 15.0 7E 1DET 1GV
10 1.60 220.0 243.6 0.00 26.9 0.0190 4.62 4.3 10 11 57.92 62.54
Fit= 23.6 2E 1T
13.0 0.0890 3.16 6.8
1 2 9.10 10.53
i M �7Y• ~� -
'2m 1 w '
.6.66
y _ w 44*
6 6-
r 'c
t
1
443
.S, .
22
3
• !
4 22
-
X 24
Ty(
9
r
8
4 3—
3-
I F
• z -
F+
-4
-g
k �; psi
a
1.4
sem_
Gt
i'
3
Y ` A
— 4-:— r
•8
-64
•
K F" x a
S
3,466
794"4,4" 644E4
;r..� "rye -E
1
6444.
f
1
1
1
1
11
r
i• SUPPLY TO SPRKS;
s
I"WiLJq N3 550 PACKFLOW
NA> 1p, ke-S.suel.GG44441a
sourrc 146,/h
4 CITY HAIN EX19T
sir RAN
1.401-0
6
4
4—
•1.4
-FIRE SPRK;SUPPL'( R&R --
p
s
E
I. z
'--
t
GENERAI' COTES:
•
•
64,
31 44
4
•
riT
40
•
1 . ALL MATERIALS & INSTALLATION TO BE PER NEPA -13-D.- -‘41"." '44
2, ALL PIPING JI‘ND FITTINGS TO BE CPVC; EXCEPT WHERE: --... wc--;--it'-'4:44
6 .‘. OWNER. TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN 7,1.------41_.,1-4--„ri
._ PIPES FROM FREEZING Iti AREAS PKOTECTED ..WITH A WET"_ -;;#--Y,:-:-'-'
7 . INSTALLATION AND TESTING TO BE- PER THE' AUTHORITY '-'-e:"'- -"4,14"i"-#4.
-HANGER SPACING joR CPVC
4.
In PIPE - MAXIMUM OF V-0"
t
11
t,sYm TYPE HEAD
UPRIGHT ON LINE
4:0 UPRIGHT ON stva
- 4-0 PFNI3FNT ON UNE
SPRINKLERS
LEGEND
FINISH
-,ESCUTCHEON OTY
EAR THQU AK E BRACE
--II-- FLEXIBLE COUPLING
RIGID COUPLING
REDUCING COUPLING
DROP
HANGER LEGEND ,
#1 LI HOOX w/2 NO 15x2" (RIVE SCREwS FOR 1`-2- PIPE
OR LAG SCREW PER NFPA IN FOR 2-1/2" AND LARGER PIPE
5 - EYE SOCKET w/3/tr x 2-1 Jr LAG SCREW, A.T, ROO & PIPE RING
0-, t. PIPE TO BOTTOM OP DECK
1-4rFA 15 -ID
4,1
4-4
- MAXIMUM SPACING FROM WALL; FOR CENTRAL GER CONCEALED. RESI. -4144 ---'-_-_
- SPRINKLER -IS -1 t -Ow . MAXIMUM SPACING BETWEEN SPRINKLERS -ler -I-4-
-141-0". MINIMUM SEPARATION BETWEEN -SPRINKLERS _IS 8* -0`t; 4 if, ._ __
Liss( ortiER-sI
ACCEPTED
ITHOUT COMMENTS.
AS NOTED IN RED
PER THE ATTACHED LETrER
The drawings affixed hereto have been
reviewed and accepted by the City of
Tukwila Fire Dept. Additions, deletions
or revisions to these drawings after this
date will void this acceptance and will
require a resubmittal of revised drawings.
Final acceptance is subject to field -
inspection by a representative of this
DATE 571 -
CITY OF TUKWILA
575 4407
SYSTEM DESI9N CRITERIA
SCREwED CAP
DRY PENDENT
SiDEwALL
•• KED PIECE NUMBER
HANGER LOCATION
0 HYDRAULIC REFERENCE POINT 1
TOTAL, PRINgLERS THIS SHEET
t. PIPE TO nmsmeo ctooR
TUKWILA FIRE DEPARTMENT
PleaSe call' 575-4407
and give this job
No
and exact address for shuta
down or restoration approval.
4-64
41,6
FILE 7 "
ACE
FIRE PFt0lEC110N SYSTEMS. INC. - -.-
26211 MAPLE VALLEY/BLACK DIAMOND RD, - MAPLE VALLEY WA 9ecol _ 4
206-432-4401 CONTI/ 1.10. ACtriPS1471,i
OR:e1G- TITLE la.EFLEC.TED._ CUT,*
DATE JULY 2OF 1994 REv1SED - CONTR. #
APPROVALS BY4-1-1.-41e.1.1
zlev
kfti