FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: Courtyard Marriott
400 Andover Park West
Permit No.: 09-S-192
Date: November 23, 2009
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ' of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2' inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch Tines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-05, section 13.5.6.2.2.
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• Comply with obstructed/non-obstructed construction rules for sprinkler head
placement.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
• Modifications involving 30 or more heads require hydrostatic test and system
isolation if necessary.
• For dry pipe and double interlock preaction systems, in addition to the standard
hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24
hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the
24 hours shall be corrected.
• These conditions apply to all sprinkler piping exposed as necessary to
accomplish the permitted scope of work.
All code references are NFPA 13, 2007 Edition.
r
Dec 11 08 05:00p NW Fire Systems 2067727504 p.2
•
r//rdi EST FRE SYSTEM
$PIIttilI z fin AUDI
$avlu tires, ftatestlog Property • 4111'
Date: December 10.2008
Fax Letter
To: Al Metzler, Tukwila Fire Department
Headquarters - Station 51
444 Andover Park East
Tukwila, WA 98188
Job Name: Courtyard Marriott
400 Andover Park West
Tukwila, WA. 98188
i up W1LA FIRE DEPARTAMkJM1,
Please call: 575.4407,
and give this job
Iva. 0 $— S- S3 y
and exact address for shute
Clarifications: Northwest Fire Systems Will Provide Labor, Material, And installation For The Following:
1. Remove and replace 903 existing recessed standard response chrome sprinklers and horizontal sidewali
sprinklers with new quick response sprinklers throughout property.
2. Replace 17 water or air gauges.
1 Final sign off and acceptance by Tukwila Fire Department.
'Note: Cut sheets for the new sprinklers will be attached with this letter.
All work to be done during normal business hours Monday — Friday 8:00 AM — 4:30 PM
Access to rooms and shutdowns and draining will need to be facilitated with the help of the engineering
staff:
Signed
Clark Potter
7111y24 ir"
77-u-ag
406 Stevens Avenge NW, Rentor, wA 98057 • Office: 206772.7502 • Fax: 206.772.7504 • www ewfiresyetems.core
GENERAL SYSTEM NOTES
PANEL:
1. THE FIRE ALARM CONTROL PANEL (FACP) IS TO BE MOUNTED TO THE SURFACE. THE TOP OF THE PANEL
SHALL NOT EXCEED 6 FEET ABOVE FINISHED FLOOR SURFACE. A MINIMUM CLEARANCE OF 36" WORKING
SPACE SHALL BE MAINTAINED.
2. THE SUPPLEMENTAL NOTIFICATION APPLIANCE CONTROL PANEL (SNAG) IS TO BE MOUNTED SURFACE,
BESIDE THE FACP. THE TOP OF THE PANEL SHALL NOT EXCEED 6 FEET ABOVE FINISHED FLOOR SURFACE.
A MINIMUM CLEARANCE OF 36" WORKING SPACE SHALL BE MAINTAINED.
3. THE SNAC IS TO BE POWERED BY THE SAME DEDICATED 120 VAC CIRCUIT AS THE FACP. TWO
CONDUCTORS TO 120 VAC, ONE CONDUCTOR TO ISOLATED GROUND, 20 AMP DEDICATED CIRCUIT. A
HOUSE GROUND WILL NOT BE ACCEPTABLE.
4. NEITHER THE BOTTOM OF THE FACP NOR THE SNAC SHALL BE PENETRATED.
DEVICES:
1. ALL MANUAL PULL STATIONS SHALL HAVE THE TOP OF THE STATION AT 48 INCHES ABOVE THE FINISHED
FLOOR.
2. ALL SIGNALING DEVICES SHALL HAVE THE BOTTOM OF THE DEVICE PLACED AT 80 INCHES ABOVE
FINISHED FLOOR WITHIN THE SPACE, OR THE TOP OF THE DEVICE 6 INCHES BELOW THE CEILING,
WHICHEVER IS LOWER.
3. THE AUDIBLE DEVICES SIGNAL SHALL BE SET TO THE TEMPORAL SETTING.
4. ALL DEVICES ARE TO BE LOCATED PER THE DRAWINGS.
5. WHEN APPLICABLE, VERIFY WITH MECHANICAL CONTRACTOR THE EXISTENCE AND LOCATION OF ALL
MOTORIZED SMOKE DAMPERS. THESE ARE TO BE 120 VAC DEVICES ON AS FEW CIRCUITS AS POSSIBLE.
THESE DEVICE CIRCUITS ARE TO BE CONTROLLED BY THE FACP THROUGH AN INTERFACING RELAY.
6. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR ALL LOCATIONS OF THE SPRINKLER
WATERFLOW, DRY FLOW, HI/LO AIR, TAMPER SWITCHES AND PIV OR 0, S, & Y VALVES.
7. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR THE EXISTENCE OF SPRINKLER HEAT TAPE.
THIS HEAT TAPE SHALL BE MONITORED BY THE FACP AND SHALL REQUIRE AN APPROPRIATE RELAY THAT
WILL PROVIDE SUPERVISION FOR HEAT TAPE GROUND FAULTS AND LOSS OF PRIMARY POWER.
8. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR THAT ALL APPLICABLE INTERSTITIAL
CEILING, ATTIC, OR FLOOR SPACES ARE PROTECTED WITH SPRINKLER HEADS.
9. ALL SPRINKLER WATERFLOW ZONES SHALL BE NON-SILENCEABLE PER U.L. 864. THE CONDITION MUST
BE RETURNED TO A NORMAL CONDITION BEFORE THE FACP CAN BE SILENCED.
WIRING:
1. TWO DEDICATED PHONE LINES TO BE INSTALLED BY OWNER TO TRANSMITTER.
2. ALL AUDIBLE / VISUAL CIRCUITS ARE TO BE 14 AWG FPL WIRE. (RISER OR PLENUM RATED WIRE WHERE
REQUIRED PER NEC).
3. AUDIBLE / VISUAL CIRCUITS ARE TO HAVE AN END OF LINE RESISTOR (ELR) AS APPROPRIATE WITH THE
FACP/SNAC.
4. THE DETECTION COMMUNICATION LOOP IS TO BE 16 AWG TWISTED, NON -SHIELDED, MID -CAP FPL WIRE.
(RISER OR PLENUM RATED WIRE WHERE REQUIRED PER NEC).
5. THE DETECTION COMMUNICATION LOOP DOES NOT REQUIRE AN ELR AT THE END OF THE CIRCUIT.
6. WIRE TO WEATHERPROOF DEVICES SHALL BE STUBBED OUT ONLY. SURFACE WEATHERPROOF BACK
BOXES SHALL BE PROVIDED WITH DEVICES.
7. ALL FIRE ALARM WIRES ARE REQUIRED TO BE IDENTIFIED AND APPROPRIATELY MARKED.
8. PER NEC, NO AC VOLTAGE WIRING OF ANY KIND SHALL BE RUN IN THE SAME CONDUIT OR RISER AS THE
LOW VOLTAGE FIRE ALARM SYSTEM WIRING.
9. ALL JACKETED CABLE MUST INCLUDE A JACKET REMOVAL PULL STRING AS PART OF THE CABLE.
10. SHIELDED CABLE IS NOT AN ACCEPTABLE SUBSTITUTION FOR CABLE WITHOUT "SHIELDED" AS PART OF
THE DESCRIPTION.
GENERAL:
1. ALL FIRE ALARM JUNCTION BOXES ARE TO BE PAINTED RED.
2. ALL END OF LINE DEVICES SHALL HAVE AN IDENTIFYING E.O.L. STICKER AT THE E.O.L. LOCATION.
3. ONLY CONDUCTORS INTENDED FOR TERMINATION TO THE SPECIFIC DEVICE ON ANY GIVEN JUNCTION
BOX SHALL BE LEFT OPEN FOR TERMINATION IN THAT JUNCTION BOX. ALL OTHER CONDUCTORS SHALL
PASS THROUGH, OR BE SPLICED THROUGH, THAT JUNCTION BOX.
WARRANTY
ALL EQUIPMENT AND LABOR PROVIDED BY ABSCO ALARMS, INC. HAS A WARRANTY OF ONE YEAR
FROM DATE OF INVOICE. THIS WARRANTY EXCLUDES ALL COVERAGE FOR CONSEQUENTIAL DAMAGES,
AND IS GIVEN IN LIEU OF ALL OTHER EXPRESS WARRANTIES OR IMPLIED WARRANTIES OF FITNESS,
HABITABILITY, OR MERCHANTABILITY OTHERWISE PROVIDED UNDER THE LAWS OF WASHINGTON. ANY
WARRANTY WORK PERFORMED BY ABSCO ALARMS, INC. DOES NOT EXTEND THE WARRANTY OF ONE
YEAR FROM THE DATE OF THE INVOICE.
THIS WARRANTY SHALL BE VOID IF A PERSON OR FIRM OTHER THAN ABSCO ALARMS, INC. OR THE
CONTRACTOR AUTHORIZED BY ABSCO ALARMS, INC. PERFORMS OR RE -PERFORMS ANY WORK
IDENTIFIED WITHIN THE ORIGINAL SCOPE OF THE WORK OF THE CONTRACT WITH ABSCO ALARMS, INC.
LEGAL NOTICE: THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
ABSCO ALARMS, INC. ANY REPRODUCTION IN PART OR IN WHOLE WITHOUT THE WRITTEN PERMISSION
OF ABSCO ALARMS, INC. IS PROHIBITED. PATENT RIGHTS (WHERE APPLICABLE) COPYRIGHTS AND ALL
OTHER PROPRIETARY RIGHTS ARE EXPRESSLY RESERVED BY ABSCO ALARMS, INC.
SITE MAP
APCWEST
S 1.18th St
S1.5001 St
S 164E11 4,t «... .
S 10)t. h St
Cry: tat S.oring5 P;t
7 1 seat, St
S 16.1th St
S1515thSt
S 167th St
S Hall °3
n Heights
pQuest Inc. S 172nd St_
Map Data Z 2009 TeleAtta,•
FIRE ALARM REPORTS AND LEGENDS
Battery Calculations for Transponder: NAC1
Part No:HPFF8 - HPFF8 NAC Expander/Power Supply
Part No.
Qty.
Description
Standby
Total Standby
Alarm
Total Alarm
NAC
HPFF8
Panel Equipment
P2W
P2W Wall Mount Hom/Strobe Multi-Candella, 15CD
31'-0
134.0000mA
HPFF8
1
HPFF8 NAC Expander/Power Supply
50.0000mA
50.0000mA
100.0000mA
100.0000mA
19.799V
(0.3251V)
N:003
Total Panel Stby
50.0000mA
Total Panel Alarm
100.0000mA
19.6053V
(0.1937V)
Peripheral Devices
P2W
P2W Wall Mount Hom/Strobe Multi-Candella, 15CD
38'-0
134.0000mA
PC2W
2
PC2W Ceiling Mount Hom/Strobe Multi-Candella (Notification)
0.0000mA
0.0000mA
218.0000mA
436.0000mA
P2W
2
P2W Wall Mount Horn/Strobe Multi-Candella (Notification)
0.0000mA
0.0000mA
134.0000mA
268.0000mA
PC2W
1
PC2W Ceiling Mount Horn/Strobe Multi-Candella (Notification)
0.0000mA
0.0000mA
79.0000mA
79.0000mA
PC2W
1
PC2W Ceiling Mount Horn/Strobe Multi-Candella (Notification)
0.0000mA
0.0000mA
107.0000mA
107.0000mA
Standby time: 24 Hrs 5.88Ah
Alarm time: 5 Min 0.042Ah
Battery requirement: 5.922Ah
Compensation Factors - Standby: 1.2 Alarm: 1.2 Requirement with compensation: 7.107Ah
Total Peripheral Stby
0.0000mA
Total Periph Alarm
890.0000mA
Total Standby Amps
50.0000mA
Total Alarm Amps
990.0000mA
Standby time: 24 Hrs 1.2Ah
Alarm time: 5 Min 0.082Ah
Battery requirement: 1.283Ah
Compensation Factors - Standby: 1.2 Alarm: 1.2 Requirement with compensation: 1.539Ah
Battery Calculations for Panel: FACP
Part No: - 7200 Analog Addressable Fire Alarm Panel
Part No.
Qty.
Description
Standby
Total Standby
Alarm
Total Alarm
NAC
HPFF8
Panel Equipment
P2W
P2W Wall Mount Hom/Strobe Multi-Candella, 15CD
31'-0
134.0000mA
7200
1
7200 Analog Addressable Fire Alarm Panel
245.0000mA
245.0000mA
490.0000mA
490.0000mA
19.799V
(0.3251V)
N:003
Total Panel Stby
245.0000mA
Total Panel Alarm
490.0000mA
19.6053V
(0.1937V)
Peripheral Devices
P2W
P2W Wall Mount Hom/Strobe Multi-Candella, 15CD
38'-0
134.0000mA
ASD-PL2F
3
ASD-PL2F Analog Photo Smoke Sensor (Signaling line)
0.0003mA
0.0009mA
6.5000mA
19.5000mA
19.3529V
(0.078V)
N:006
Total Peripheral Stby
0.0009mA
Total Periph Alarm
19.5000mA
19.2352V
(0.1177V)
Honeywell
P2W '
P2W
226'-0
890.0000mA
Honeywell ^
ABD=PL2F !>
Total Current: 890.0000mA
(Total VDrop Percent:5.71%) Total Voltage Drop : 1.1648V
Total Standby Amps
245.0009mA
Total Alarm Amps
509.5000mA
Standby time: 24 Hrs 5.88Ah
Alarm time: 5 Min 0.042Ah
Battery requirement: 5.922Ah
Compensation Factors - Standby: 1.2 Alarm: 1.2 Requirement with compensation: 7.107Ah
Circuit Calculations Aux Panel: NAC1 Card: 02 Circuit:N1
CircuitName: N1
Circuit Type: Notification Terminal Voltage: 20.4V:DC Amperage: 2.0000A
Cable: 14/2 Parallel FPL Fire Wire #14
Calculations based on Running Total Length.
Design Criteria: Ambient temperature: 167°F Max. operating voltage drop: 20%
Device
Part No
Appliance Desc
Aux Panel
Distance
Current
Voltage
20,4V
Voltage Drop
NAC
HPFF8
N:001
P2W
P2W Wall Mount Hom/Strobe Multi-Candella, 15CD
31'-0
134.0000mA
20.1241V
(0.2759V)
N:002
PC2W
PC2W Ceiling Mount Horn/Strobe Multi-Candella, 115CD
43'-0
218.0000mA
19.799V
(0.3251V)
N:003
PC2W
PC2W Ceiling Mount Hom/Strobe Multi-Candella, 15CD
36'-0
79.0000mA
19.6053V
(0.1937V)
N:004
P2W
P2W Wall Mount Hom/Strobe Multi-Candella, 15CD
38'-0
134.0000mA
19.4309V
(0.1744V)
N:005
PC2W
PC2W Ceiling Mount Horn/Strobe Multi-Candella, 30CD
24'-0
107.0000mA
19.3529V
(0.078V)
N:006
PC2W
PC2W Ceiling Mount Horn/Strobe Multi-Candella, 115CD
54'-0
218.0000mA
19.2352V
(0.1177V)
Honeywell
P2W '
P2W
226'-0
890.0000mA
Honeywell ^
ABD=PL2F !>
Total Current: 890.0000mA
(Total VDrop Percent:5.71%) Total Voltage Drop : 1.1648V
Bill of Material
Qty.
Description
Manufacturer
Model
Part No.
1
Aux Panel: NAC1
Notification
NAC
HPFF8 NAC Expander/Power Supply
1
HPFF8 NAC Expander/Power Supply
Honeywell
HPFF8
HPFF8
ItXli
•
PC2W Ceiling Mount Hom/Strobe Multi-Candella
PC2W
Dx
P2W Wall Mount Horn/Strobe Multi-Candella
1
Panel: FACP
I
1
7200 Analog Addressable Fire Alarm Panel
Honeywell
7200
7200
226
14/2 Parallel FPL Fire Wire
Windy City Wire
P767962-S/NP729100-S
P767962-S/NP729100-S
89
16/2 Twisted FPL Fire Wire
Windy City Wire :
P761362 / NP728100-B
P761362 / NP728100-B
4
PC2W Ceiling Mount Hom/Strobe Multi-Candella
Honeywell
'PC2W b:
PC2W
2
P2W Wall Mount Hom/Strobe Multi-Candella
Honeywell
P2W '
P2W
12
ASD-PL2F Analog Photo Smoke Sensor
Honeywell ^
ABD=PL2F !>
ASD-PL2F
12
ADB-FLF Base, Flanged, for Analog Sensor
Honeywell
ADB-F''L`f'`r.
ADB-FLF
Fire Alarm Symbol Legend -.
SYMBOL
DESCRIPTION
MODEL NUMBER
U
7200 Analog Addressable Fire Alarm Panel
7200
FACP
Notification
NAC
HPFF8 NAC Expander/Power Supply
HPFF8
®
ASD-PL2F Analog Photo Smoke Sensor
ASD-PL2F
ItXli
•
PC2W Ceiling Mount Hom/Strobe Multi-Candella
PC2W
Dx
P2W Wall Mount Horn/Strobe Multi-Candella
P2W
E = EXISTING
N = NEW
R = REPLACE
Circuit Legend
Abbreviation
Type
Name
U
Signaling line
Addressable
V
Notification
Notification
Wire Path Label Legend
Chr. Position
Character Purpose
DJN
Quantity of the same circuit
#1
Project Name
Circuit name
#2
10950
Wire Gauge
#3
ACC'
TED
O Without Comments
P As Noted in Red
O Per The Attached Letter
These plans' have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current City
standards. Acceptance Is subject to errors and
omissions which do not authorize violations of adopted
standards and ordinances. The responsibility for the
adequacy of design. rests totally with the designer.
Additions, deletions or revisions to these drawings after
this date will void this acceptance and will requires
resubmittal of revised drawings for subsequent approval.
Pinal acceptance is subject to field test and Inspection by
The Tukwila Fire Prevention Bureau. �1
Date: By:
1✓AL'A"►r/1 ('S al<d,i<w cIYG44- brtukcrs
ccce etvzo < wro- bvrtviteY w(Atc 1✓tgi.rs .
IUKWItA FIRE DEPART!'I
Please call: 575.440
and give this job
No. )%- F-01-)
and exact address for shots
down or restoration apnrovz
NOTICE
A completed, signed, Tukwila
Fire, Department Pre-test
Certificate must be presented
to the Inspector prior to
commencement of Acceptance
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
termination of the testing,
PAID
JAN 2 3 2010
Tukwila Fire
Firm Name and Address
P.O. BOX 2246
LYNNWOOD, WA 98036
PH: 425.771.1166
FAX: 425.771.4422
www.abscoalarms,com
i
Project Name and Address
0
w
< 1.11
ct
>"- W
U �
o
¢¢
0
ct 54)
U
00
CO
00
0)
i
FIRE DEPARTMENT USE ONLY %
DESIGNER OF RECORD
DANIEL J. NORTON
ABSCO ALARMS, INC.
19023 36TH AVE W STE E
LYNNWOOD, WA 98036
PHONE: (425) 771-1166
FAX: (425) 771-4422
EMAIL: DNORTON®ABSCOALARMS.COM
NICET: # 096137
REDMOND DOR: # 00-B-025
1 -01/22/10
Submittal Set
DH
Rev.# -Date
Revision
By
Drawn By
D.H.
Checked By
DJN
Date
01/22/10
Project Name
Courtyard by Marriott
Project Number
10950
System Type
FIRE ALARM
SYSTEM
i
i
Sheet Name O
REPORTS,
LEGENDS,
COVER
SHEET
Sheet Title
FZOOE1
SHEET 1 OF 2
1
7
8
l -
i
/
/
/
L-
10'
15'
N1•N:004
1-5CD ,.
R !!.
N1•N:005
--1
L. 30CD
I*—
\ -7 N1•N:003
v 15CD
FLAG NOTE:
> PROVIDE DEVICE ADDRESSES
25'
7 111 •N:002
(DE
ELR848.OmA
N1•N:006
115CD
15CD
R
i
NOTE:
3 SMOKE DETECTORS ARE BEING ADDED TO SLC
CIRCUIT. ADDITIONAL CURRENT DRAW IS 19.50mA,
DOES NOT REPRESENT IMPACT ON EXISTING
BATTERY LOAD
MEASUREMENT KEY
50'
FACP
1
NAC
1 N1 #14
(e 'E
/
i/////////////11111111
111
111
1! 1 1 1!1
100'
/4
LOBBY FLOOR PLAN .‘p
SCALE: 1/8” = 1'-0"
/
/
1/
/
/f
`D 4 -§K
•
Firm Name and Address
P.O. BOX 2246
LYNNWOOD, WA 98036
PH: 425.771.1166
FAX: 425.771.4422
www.abscoalarms.com
Project Name and Address
i -
O
<Woo
E-- ;1;
oe CD
>0- LIJ
mU(2cm) 1:1:1.L;10 :D�
Q=z�
c4)
O
.
LEGAL NOTICE:
THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
ABSCO ALARMS, INC. ANY REPRODUCTION
IN PART OR IN WHOLE WITHOUT THE
WRITTEN PERMISSION OF ABSCO ALARMS,
INC. IS PROHIBITED. PATENT RIGHTS
(WHERE APPLICABLE) COPYRIGHTS AND ALL
OTHER PROPRIETARY RIGHTS ARE
EXPRESSLY RESERVED BY ABSCO ALARMS,
INC.
•
DESIGNER OF RECORD
DANIEL J. NORTON
ABSCO ALARMS, INC.
19023 36TH AVE W STE E
LYNNWOOD, WA 98036
PHONE: (425) 771-1166
FAX: (425) 771-4422
EMAIL: DNORTON@ABSCOALARMS.COM
NICET: # 096137
REDMOND DOR: # 00—B-025
✓
.
1- 01/22/10
Submittal Set
DH
Rev.# -Date
Revision
By
'Drawn By
D.H.
Checked By
DJN
Date
01/22/10
Project Name
Courtyard by Marriott
Project Number
10950
•
System Type
FIRE ALARM
SYSTEM
.
Sheet Name
LOBBY
FLOOR PLAN
✓
•
Sheet Title/
FZ1
•
SHEET 2 OF 2
✓
LEGEND
SYM SIN#
EXISTING SPRINKLER PIPING
NEW SPRINKLER PIPING
EXISTING SPRINKLERS TO REMAIN
P NEW PENDENT SPRINKLER
1 TOTAL
RELOCATED PENDENT SPRINKLER
4 TOTAL
LENGTHEN 1" DROP FOR LOWERED CEILING
5 TOTAL
SPRINKLERS
•
TY3231
TYCO TY -FRB QUICK RESPONSE CHROME RECESSED PENDENT - 1/2" 155'
STD COVERAGE CHROME CANOPY K=5.6
GENERAL LEGEND
--D
--4
0
BOD
BOB
BOJ
FOS
FOW
EARTHQUAKE BRACING
PIPE HANGER
GROOVED CAP
RIGID COUPUNG ( UNLESS NOTED )
CAP
PLUG
CENTERUNE
HYDRAULIC REFERENCE POINT
CENTERLINE PIPE TO BOTTOM OF DECK
CENTERLINE PIPE TO BOTTOM OF BEAM
CENTERLINE PIPE TO BOTTOM OF JOIST
FACE OF STUD
FACE OF WALL
FOC
AFF
CH
R.C.
4
F
E/C
C/C
C/E
GG
TG
TxF
ATR
FACE OF CONCRETE
ABOVE FINISHED FLOOR
CEILING HEIGHT
REDUCING COUPLING
OUTLET COUPUNG
WELDED OUTLET
"FIT" FITTING
END TO CENTER
CENTER TO CENTER
CENTER TO END
GROOVE/GROOVE
THREAD/GROOVE (ALSO "GT")
THREAD/"FIT" (ALSO "FxT")
ALL—THREAD ROD
O
1111
j _ iu� TASL)r,
.nnomenum
111.iie''>tli,�(
domosimmiiiiidioso oft.
OF TA
c_ OF WIND
McNpyirw-1. o,41 1 k4 Zai - . .
Co vf-vi. 5st. a frwit s`7a c. " +1111-)-)11
SPRINKLER PLAN
1 /8" = 1'-0"
GENERAL NOTES
SPRINKLER SYSTEM DESIGN PER N.F.P.A. #13
ALL MATERIALS SHALL BE NEW AND U.L. LISTED OR F.M. APPROVED ���
-: - MI II.. = Orot',hq„/ 4t -q -
NEW WORK WILL HAVE NO ADVERSE AFFECTS ON HYDRAULICS OF SYSTEM
1” THREADED PIPING TO BE 'DYNA—THREAD'
IAA a x .
0 12' 4' 8'
a�
FILE COPY
11111111461WEIMUM
3315 South 116th St Ste 115, Tukwila, WA 98168
206.772.7502 • fx 206.772.7504
www.nwfiresystems.com • LIC # NORTHFS928CR
LOBBY REINVENTION OF THE
COURTYARD BY MARRIOTT
SEATTLE SOUTHCENTER, WA
400 ANDOVER PARK WEST
TUKWILA, WASHINGTON
DATE: 11/09
DRAWN: G.B. SCALE: AS NOTED
1 OF 1
400 ANDOVER PK W
09-S-192
Firm Name and Address
P.O. BOX 2246
LYNNWOOD, WA 98036
PH: 425.771.1166
FAX: 425.771.4422
www.abscoalarms.com
Project Name and Address
LOUNGE DETAIL
NOT IN SCOPE
14-2" AFF
HOME THEATER
LOUNGE
N1•N:007
, N 1T-10" AFF
■
////////// <t /111///////////i ■ iV/, ////://// '+
10'-3" AFF
BUSINESS CENTER
N 1 •N:006
\/110CD
R
2 N1 #14
■'%%/%%//,
!\ 115CD
f
1G-3" AFFN
// //////////7/////////////i
16'-8" AFF
1 S1 #16 -
RECEPTION 0 I FACP
T-11"AFF
NOT IN SCOPE
LEGAL NOTICE:
THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
ABSCO ALARMS, INC. ANY REPRODUCTION
IN PART OR IN WHOLE WITHOUT THE
WRITTEN PERMISSION OF ABSCO ALARMS,
INC. IS PROHIBITED. PATENT RIGHTS
(WHERE APPLICABLE) COPYRIGHTS AND ALL
OTHER PROPRIETARY RIGHTS ARE
EXPRESSLY RESERVED BY ABSCO ALARMS,
INC.
DESIGNER OF RECORD
ERICK SLABAUGH
ABSCO ALARMS, INC.
19023 36TH AVE W STE E
LYNNWOOD, WA 98036
PHONE: (425) 771-1166
FAX: (425) 771-4422
EMAIL: ESLABAUGHOABSCOALARMS.COM
NICET: # 91413
8'-i 0" AFF
M DIA PODS
12-3" AFF
Ni • N:003
15CD
R
FLAG NOTE:
1> PROVIDE DEVICE ADDRESSES
> RELOCATE DEVICE
e
Drawn By
D.H.
r`
Checked By
DJN
3 - 02/05/10
Re -Submittal with ceiling elevations
DH
2 - 01129/10
Added 2 hom strobes & 1
smoke detector perAHJ
DH
1- 01/22/10
Submittal Set
DH
Rev.# -Date
Revision
By
e
Drawn By
D.H.
r`
Checked By
DJN
Date
01/22/10
Project Name
Courtyard by Marriott
Project Number
10950
MEASUREMENT KEY
MEDIA PODS DETAIL
Sheet Name
LOBBY
FLOOR PLAN
Sheet Title
LOBBY FLOOR PLAN
SCALE: 1/8" = 1'-0"
SHEET 2 OF 2
GENERAL SYSTEM NOTES
PANEL:
1. THE FIRE ALARM CONTROL PANEL (FACP) IS TO BE MOUNTED TO THE SURFACE. THE TOP OF THE PANEL
SHALL NOT EXCEED 6 FEET ABOVE FINISHED FLOOR SURFACE. A MINIMUM CLEARANCE OF 36" WORKING
SPACE SHALL BE MAINTAINED.
2. THE SUPPLEMENTAL NOTIFICATION APPLIANCE CONTROL PANEL (SNAC) IS TO BE MOUNTED SURFACE,
BESIDE THE FACP. THE TOP OF THE PANEL SHALL NOT EXCEED 6 FEET ABOVE FINISHED FLOOR SURFACE.
A MINIMUM CLEARANCE OF 36" WORKING SPACE SHALL BE MAINTAINED.
3. THE SNAC IS TO BE POWERED BY THE SAME DEDICATED 120 VAC CIRCUIT AS THE FACP. TWO
CONDUCTORS TO 120 VAC, ONE CONDUCTOR TO ISOLATED GROUND, 20 AMP DEDICATED CIRCUIT. A
HOUSE GROUND WILL NOT BE ACCEPTABLE.
4. NEITHER THE BOTTOM OF THE FACP NOR THE SNAC SHALL BE PENETRATED.
DEVICES:
1. ALL MANUAL PULL STATIONS SHALL HAVE THE TOP OF THE STATION AT 48 INCHES ABOVE THE FINISHED
FLOOR.
2. ALL SIGNALING DEVICES SHALL HAVE THE BOTTOM OF THE DEVICE PLACED AT 80 INCHES ABOVE
FINISHED FLOOR WITHIN THE SPACE, OR THE TOP OF THE DEVICE 6 INCHES BELOW THE CEILING,
WHICHEVER IS LOWER.
3. THE AUDIBLE DEVICES SIGNAL SHALL BE SET TO THE TEMPORAL SETTING.
4. ALL DEVICES ARE TO BE LOCATED PER THE DRAWINGS.
5. WHEN APPLICABLE, VERIFY WITH MECHANICAL CONTRACTOR THE EXISTENCE AND LOCATION OF ALL
MOTORIZED SMOKE DAMPERS. THESE ARE TO BE 120 VAC DEVICES ON AS FEW CIRCUITS AS POSSIBLE.
THESE DEVICE CIRCUITS ARE TO BE CONTROLLED BY THE FACP THROUGH AN INTERFACING RELAY.
6. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR ALL LOCATIONS OF THE SPRINKLER
WATERFLOW, DRY FLOW, HI/LO AIR, TAMPER SWITCHES AND PIV OR 0, S, & Y VALVES.
7. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR THE EXISTENCE OF SPRINKLER HEAT TAPE.
THIS HEAT TAPE SHALL BE MONITORED BY THE FACP AND SHALL REQUIRE AN APPROPRIATE RELAY THAT
WILL PROVIDE SUPERVISION FOR HEAT TAPE GROUND FAULTS AND LOSS OF PRIMARY POWER.
8. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR THAT ALL APPLICABLE INTERSTITIAL
CEILING, ATTIC, OR FLOOR SPACES ARE PROTECTED WITH SPRINKLER HEADS.
9. ALL SPRINKLER WATERFLOW ZONES SHALL BE NON-SILENCEABLE PER U.L. 864. THE CONDITION MUST
BE RETURNED TO A NORMAL CONDITION BEFORE THE FACP CAN BE SILENCED.
WIRING:
1. TWO DEDICATED PHONE LINES TO BE INSTALLED BY OWNER TO TRANSMITTER.
2. ALL AUDIBLE / VISUAL CIRCUITS ARE TO BE 14 AWG FPL WIRE. (RISER OR PLENUM RATED WIRE WHERE
REQUIRED PER NEC).
3. AUDIBLE / VISUAL CIRCUITS ARE TO HAVE AN END OF LINE RESISTOR (ELR) AS APPROPRIATE WITH THE
FACP / SNAC.
4. THE DETECTION COMMUNICATION LOOP IS TO BE 16 AWG TWISTED, NON -SHIELDED, MID -CAP FPL WIRE.
(RISER OR PLENUM RATED WIRE WHERE REQUIRED PER NEC).
5. THE DETECTION COMMUNICATION LOOP DOES NOT REQUIRE AN ELR AT THE END OF THE CIRCUIT.
6. WIRE TO WEATHERPROOF DEVICES SHALL BE STUBBED OUT ONLY. SURFACE WEATHERPROOF BACK
BOXES SHALL BE PROVIDED WITH DEVICES.
7. ALL FIRE ALARM WIRES ARE REQUIRED TO BE IDENTIFIED AND APPROPRIATELY MARKED.
8. PER NEC, NO AC VOLTAGE WIRING OF ANY KIND SHALL BE RUN IN THE SAME CONDUIT OR RISER AS THE
LOW VOLTAGE FIRE ALARM SYSTEM WIRING.
9. ALL JACKETED CABLE MUST INCLUDE A JACKET REMOVAL PULL STRING AS PART OF THE CABLE.
10. SHIELDED CABLE IS NOT AN ACCEPTABLE SUBSTITUTION FOR CABLE WITHOUT "SHIELDED" AS PART OF
THE DESCRIPTION.
GENERAL:
1. ALL FIRE ALARM JUNCTION BOXES ARE TO BE PAINTED RED.
2. ALL END OF UNE DEVICES SHALL HAVE AN IDENTIFYING E.O.L. STICKER AT THE E.O.L. LOCATION.
3. ONLY CONDUCTORS INTENDED FOR TERMINATION TO THE SPECIFIC DEVICE ON ANY GIVEN JUNCTION
BOX SHALL BE LEFT OPEN FOR TERMINATION IN THAT JUNCTION BOX. ALL OTHER CONDUCTORS SHALL
PASS THROUGH, OR BE SPLICED THROUGH, THAT JUNCTION BOX.
WARRANTY
ALL EQUIPMENT AND LABOR PROVIDED BY ABSCO ALARMS, INC. HAS A WARRANTY OF ONE YEAR
FROM DATE OF INVOICE. THIS WARRANTY EXCLUDES ALL COVERAGE FOR CONSEQUENTIAL DAMAGES,
AND IS GIVEN IN LIEU OF ALL OTHER EXPRESS WARRANTIES OR IMPLIED WARRANTIES OF FITNESS,
HABITABILITY, OR MERCHANTABILITY OTHERWISE PROVIDED UNDER THE LAWS OF WASHINGTON. ANY
WARRANTY WORK PERFORMED BY ABSCO ALARMS, INC. DOES NOT EXTEND THE WARRANTY OF ONE
YEAR FROM THE DATE OF THE INVOICE.
THIS WARRANTY SHALL BE VOID IF A PERSON OR FIRM OTHER THAN ABSCO ALARMS, INC. OR THE
CONTRACTOR AUTHORIZED BY ABSCO ALARMS, INC. PERFORMS OR RE -PERFORMS ANY WORK
IDENTIFIED WITHIN THE ORIGINAL SCOPE OF THE WORK OF THE CONTRACT WITH ABSCO ALARMS, INC.
LEGAL NOTICE: THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
ABSCO ALARMS, INC. ANY REPRODUCTION IN PART OR IN WHOLE WITHOUT THE WRITTEN PERMISSION
OF ABSCO ALARMS, INC. IS PROHIBITED. PATENT RIGHTS (WHERE APPLICABLE) COPYRIGHTS AND ALL
OTHER PROPRIETARY RIGHTS ARE EXPRESSLY RESERVED BY ABSCO ALARMS, INC.
SITE MAP
uthce-nter
S 166th St
to - S 167th St
S168thSt ..11 d
en Heights �S 170th St
Baker Blvd
Strander Blvd
Track Cr
pQuest Inc. S 172nd St__
Wig Blvd
>;
Map tiara, 2flti9NAVTEQ or TeleAtEas
FIRE ALARM REPORTS AND LEGENDS
Battery Calculations for Transponder: NAC1
Part No:FF8 - FF8 NAC Expander/Power Supply
Part No.
Qty.
Description
Standby
Total Standby
Alarm
Total Alarm
NAC
FF8
Panel Equipment
HPFF8 NAC Expander/Power Supply
Honeywell
20.4V
HPFF8
MD-NAC4
1
NAC Module
50.0000mA
50.0000mA
100.0000mA
100.0000mA
910683
1
Panel Power Supply
0.0000mA
0.0000mA
0.0000mA
0.0000mA
N:004
PC2R
Peripheral Devices
Total Panel Stby
50.0000mA
Total Panel Alarm
100.0000mA
ASD-PL2F
4
Peripheral Devices
0.0003mA
0.0012mA
6.5000mA
26.0000mA
PC2R
2
PC2R Ceiling Mount Hom/Strobe Multi-Candella (Notification)
0.0000mA
0.0000mA
218.0000mA
436.0000mA
P2R
3
P2R WaII Mount Hom/Strobe Multi-Candella Red (Notification)
0.0000mA
0.0000mA
134.0000mA
402.0000mA
P2R
1
P2R Wall Mount Hom/Strobe Multi-Candella Red (Notification)
0.0000mA
0.0000mA
280.0000mA
280.0000mA
PC2R
1
PC2R Ceiling Mount Hom/Strobe Multi-Candella (Notification)
0.0000mA
0.0000mA
79.0000mA
79.0000mA
PC2R
1
PC2R Ceiling Mount Hom/Strobe Multi-Candella (Notification)
0.0000mA
0.0000mA
107.0000mA
107.0000mA
(0.0442V)
Total Peripheral Stby
0.0000mA
Total Periph Alarm
1304.0000mA
Total Current: 1304.0000mA
(Total VDrop Percent:6.95%) Total Voltage Drop : 1.4171V
Total Standby Amps
50.0000mA
Total Alarm Amps
1404.0000mA
Standby time: 24 Hrs 1.2Ah
Alarm time: 5 Min 0.117Ah
Battery requirement: 1.317Ah
Compensation Factors - Standby: 1.2 Alarm: 1.2 Requirement with compensation: 1.58Ah
Battery Calculations for Panel: FACP
Part No: - 7200 Analog Addressable Fire Alarm Panel
Part No.
Qty.
Descrption
Standby
Total Standby
Alarm
Total Alarm
NAC
FF8
Panel Equipment
HPFF8 NAC Expander/Power Supply
Honeywell
20.4V
HPFF8
7200
1
7200 Main Panel Card
245.0000mA
245.0000mA
490.0000mA
490.0000mA
N:003
P2R
P2R WaII Mount Hom/Strobe Multi-Candella Red, 15CD
Total Panel Stby
245.0000mA
Total Panel Alarm
490.0000mA
N:004
PC2R
Peripheral Devices
43'-0
218.0000mA
19.6548V
(0.3879V)
ASD-PL2F
4
ASD-PL2F Analog Photo Smoke Sensor (Signaling line)
0.0003mA
0.0012mA
6.5000mA
26.0000mA
N:006
P2R
P2R WaII Mount Hom/Strobe Multi-Candella Red, 110CD
Total Peripheral Stby
0.0012mA
Total Periph Alarm
26.0000mA
N:007
PC2R
PC2R Ceiling Mount Hom/Strobe Multi-Candella, 30CD
24'-0
107.0000mA
19.1007V
(0.078V)
N:008
PC2R
PC2R Ceiling Mount Hom/Strobe Multi-Candella, 115CD
Total Standby Amps
2450012mA
Total Alarm Amps
516.0000mA
Standby time: 24 Hrs 5.88Ah
Alarm time: 5 Min 0.043Ah
Battery requirement: 5.923Ah
Compensation Factors - Standby: 1.2 Alarm: 1.2 Requirement with compensation: 7.108Ah
Circuit Calculations Aux Panel: NAC1 Card: 07 Circuit:N1
CircuitName: N1
Circuit Type: Notification Terminal Voltage: 20.4V:DC Amperage: 2.0000A
Cable: 14/2 Parallel FPL Fire Wire #14
Calculations based on Running Total Length.
Design Criteria: Ambient temperature: 167°F Max. operating voltage drop: 20%
Device
Part No
Appliance Desc
Distance
Current
Voltage
Voltage Drop
NAC
FF8
Aux Panel
HPFF8 NAC Expander/Power Supply
Honeywell
20.4V
HPFF8
N:002
P2R
P2R WaII Mount Hom/Strobe Multi-Candella Red, 15CD
27'-0
134.0000mA
20.0841V
(0.3159V)
N:003
P2R
P2R WaII Mount Hom/Strobe Multi-Candella Red, 15CD
4'-0
134.0000mA
20.0427V
(0.0414V)
N:004
PC2R
PC2R Ceiling Mount Hom/Strobe Multi-Candella, 115CD
43'-0
218.0000mA
19.6548V
(0.3879V)
N:005
PC2R
PC2R Ceiling Mount Hom/Strobe Multi-Candella, 15CD
36'-0
790000mA
19.4086V
(0.2462V)
N:006
P2R
P2R WaII Mount Hom/Strobe Multi-Candella Red, 110CD
38'-0
280.0000mA
19.1787V
(0.2299V)
N:007
PC2R
PC2R Ceiling Mount Hom/Strobe Multi-Candella, 30CD
24'-0
107.0000mA
19.1007V
(0.078V)
N:008
PC2R
PC2R Ceiling Mount Hom/Strobe Multi-Candella, 115CD
54'-0
218.0000mA
18.9829V
(0.1177V)
ADB-FLF
N:001
P2R
P2R Wail Mount Hom/Strobe Multi-Candella Red, 15CD
33'-0
134.0000mA
20.3558V
(0.0442V)
259'-0
' 1304.0000mA
Total Current: 1304.0000mA
(Total VDrop Percent:6.95%) Total Voltage Drop : 1.4171V
Bill of Material
Qty.
Description
Manufacturer
Model
Part No.
1
Aux Panel: NAC1
Notification
NAC
HPFF8 NAC Expander/Power Supply
1
HPFF8 NAC Expander/Power Supply
Honeywell
HPFF8
HPFF8
►X 4
PC2W Ceiling Mount Hom/Strobe Multi-Candella
PC2W
D5<1
P2W Wall Mount Hom/Strobe Multi-Candella
1
Panel: FACP
1
7200 Analog Addressable Fire Alarm Panel
Honeywell
7200
7200
226
14/2 Parallel FPL Fire Wire
Windy City Wire
P767962-S/NP729100-S
P767962-S/NP729100-S
89
16/2 Twisted FPL Fire Wire
Windy City Wire
P761362 / NP728100-B
P761362 / NP728100-B
4
PC2W Ceiling Mount Hom/Strobe Multi-Candella
Honeywell
PC2W
PC2W
4
P2W Wall Mount Hom/Strobe Multi-Candella
Honeywell
P2W ,
P2W
18
ASD-PL2F Analog Photo Smoke Sensor
Honeywell
ASD-PL2F
ASD-PL2F
18
ADB-FLF Base, Flanged, for Analog Sensor
Honeywell
ADB-FLF r
ADB-FLF
Fire Alarm Symbol Legend
SYMBOL
DESCRIPTION
MODEL NUMBER
U
7200 Analog Addressable Fire Alarm Panel
7200
FACP
Notification
NAC
HPFF8 NAC Expander/Power Supply
HPFF8
1
Wire Gauge
ASD-PL2F Analog Photo Smoke Sensor
ASD-PL2F
►X 4
PC2W Ceiling Mount Hom/Strobe Multi-Candella
PC2W
D5<1
P2W Wall Mount Hom/Strobe Multi-Candella
P2W
E = EXISTING
N = NEW
R = REPLACE
Circuit Legend
Abbreviation
Type
Name
U
Signaling line
Addressable
V
Notification
Notification
Wire Path Label Legend
Chr. Position
Character Purpose
Checked By
DJN
Quantity of the same circuit
#1
Re -Submittal with ceiling elevations
1
Circuit name
#2
DH
1
Wire Gauge
#3
r•
r
Firm Name and Address
P.O. BOX 2246
LYNNWOOD, WA 98036
PH: 425.771.1166
FAX: 425.771.4422
www.abscoalarms.com
r
Project Name and Address
I --
H
O
Of (If 23
WE--Ne ('");
� o0
C) rn
>-w<
m V ofc;
�I-O>-- o <�
Q=z�
O
U
i
i
FIRE DEPARTMENT USE ONLY
DESIGNER OF RECORD
ERICK SLABAUGH
ABSCO ALARMS, INC.
19023 36T1-1 AVE W STE E
LYNNWOOD, WA 98036
PHONE: (425) 771-1166
FAX: (425) 771-4422
EMAIL: ESLABAUGHOABSCOALARMS.COM
NICET: 91413
co
i
•
D.H.
t`
v
Checked By
DJN
3 - 02/05/10
Re -Submittal with ceiling elevations
DH
2 - 01/29/10
Added 2 hom strobes & 1
smoke detector per AHJ
DH
1-01/22/10
Submittal Set
DH
Rev.# -Date
Revision
By
i
Drawn By
D.H.
t`
v
Checked By
DJN
Date
01/22110
Project Name
Courtyard by Marriott
Project Number
10950
i
System Type
FIRE ALARM
SYSTEM
•
Sheet Name Q
REPORTS,
LEGENDS,
COVER
SHEET
4. Sheet Title i
SHEET 1 OF 2
•
r
i
4
6
7
G
8
{
4
A—
B—
c-
E—
F—
G—
r
^
i
}
_1-7z
_
Ik
r
zs
ki 17V E
± 6-3a 5)--
4=4.4
t
L.
PRINTS ISSUED
ACREI
TORY NORTHERN VERSION WITH INDOOR
POOL AND SPA
GUESTROOMS 149
PPOVIOID
STALL, SiZI
AISLE WIDTH
-
LOCATION MAP
NOTE
•
SEE MARRIOTT GUIDELINE DRAWITGS FC41
17711
THIS SITE PLAN HAS BEEN PREPARED
WITMUT THE BENEFIT OF TOPOCAAPHICAL
tFoRmArcri
J. .
it4cevF..
1 11 1? Pc'01-- 4FA-
41,
I 414,
—/4-0
IsL
kiN
4-1
F/r-L/(1-A/e
1
Esm-
1
•
•
pou7 G[LL
anion
corporation
INTERNATIONAL HEADQUARTERS
MARRIOTT DRIVE
WASHINGTON, D C 20058
SHEET TITLE
6-21 T
DRAWN
ISSUED 10 47 660
JOB NO DWG NO
C S70
4,4
•
,fh rpm 41 ffrigaaaaaa
1
l-.
ff. 61n lava aft..
2
3
A
B—
C
D
—
I"=
o'
SITE DATA
AREA 4 4± ACRES
BUILDING AREA 82,070 S F ( 149 UNITS)
ZONING "C-2" DISTRICT, REGIONAL RETAIL BUSINESS
SETBACKS BJILDING
r RONT 20'
SIDE 10'
REAR 10'
LANDSCAPE
FRONT 10'
SIDE 5'
REAR 0'
MAXIMUM BUILDING HEIGHT 3 STORIES OR 35 FEET
1
•
dll
N 01°47'28" E 20
30'
w
ac
Q
w
a_
0
0
z
( J
DIRECTIONAL
SIGN
PARKING
REDU I RED
wMI JST
STALL SIZE
STALLS
A°PLY FOR COOPERATI
°R(\1 I nED
STALLS
-- 9' x19' STANDARD
12 5'x19' BARRIER FREE
8 5',(161 COMPACT STALLS' 3f°/ ALLOkED'
- 168 STANDARD
4 BARRIER FREE
172 TOTAL'
VE PARKING AGREEMENT)
-119 STANDARD
49 COMPACT (28%)
4 BARRIER FREE
172 TOTAL
r
I4
I �
llI
Andover Park West
N 01°0505" E
609 15'
VERT1CA CURB
11
1
w —77 "
CONCRETE WALK
30'
C
LANDSCAPE
C
19' 215' C 16'
16' C
AREA;
•
TYP
I0
T
P T
C
C
C
C
c
1--
a_
co>- C
F-
C
c
C
c
J
C
C
C
16'
1 TYP
C
0
LANDSCAPE
16' C 25' ,}, 19'
TYP r TYP I TYP
C
LO
C co
a.
1-
Lc)'cL
co
C
c
C
C
C
C
C
C
C
C
C
G
C
C
C
c
C
C
C,
C
\}
11
r
9'
TYP
LANDSCAPE
Z1.2
GUEST ENTRANCE
IRE
E 1 1
EXIT ' I
SERVICE
39 ,
Indoor Pool & Spa
FIRE EXIT
•
HC
N
/V
—74
V/
-5' WALK
TYP
2" PAINTED DASHED LINE(WHITE)
9'
TYP
LANDSCAPE
Guestroom Wing
I�+ °' 3 Story
14
F.F. 27.0
cl
5' WALK
TYP
ro
r
I
Guestroom Wing
Ir
3 Story
F.F. 27.0
LANDSCAPE
SATELITE DISH W/
LANDSCAPE SCREENI
1
HC
2
r
Lounge F. F. 26.75
r
.*_ 3 5' TYP
44
o
HC
TYPICAL
TRANSFORMER RAD
LOCATION
„a,
__HI
.f
li/
Public,„Space
1 Story
F.F. 27.0
SCREENI
1
1
1
•
5'
HC ,
1 2” PAINTED DASHED LINE(WHITE)
9'
TYP
LANDSCAPE
AREA
lu
Ii,
( LAN1)SCAPE1
\ BERW
e-* _.
� R
! Y
5' TY
SIDEW SLK
a.
0
0
z
—J
S.�.J
SCREENING
///////////// ///// / ////////////// ,//I/
r
■...
,," = 136 73
0'
/// //% / // // / / / /
r /
10'
30'
100'
LANDSCAPE
BERM
1
w
o_
0
z
d
25' 12'*
A
25'
a
( MEASURED)
S 88°16'17"E
,ra
COURTYARD SIGN
CYI00 at 33'
(SEE SIGN DET )
mj\R 3 " '237
R= 41028
A= 12° 10'
L = 8715'
C = S 07°5
86 99'
150'
• iQ fe'1 '''
• • �o: aR
• • e
se
Os Tit cio.estr
R y�
B.C.E. JOB #2310
PRINTS ISSUED
rr�
2
PER FEB REVIEW 1?0/B WP
1 PER MARRIOTT' RI VI 1 „
NO DESCRIPTION DATE
REVISIONS
BY
ALL MEASUPEMENTS MUST BE CHECKED
ON THE JOB BY THE CONTRACTOR
ALL PRINTS AND SPECIFICATIONS ARE THE
PROPERTY OF THE OWNER AND MUST BF
RETURNED UPON COMPLETION OF THE WORK
a)
cc
0
w c‘.#1
z
w
I es
0 0
CC
CC
corporation
INTERNATIONAL HEADQUARTERS
MARRIOTT DRIVE
WASHINGTON, D C 20058
SHEET TITLE
Conceptual Site, Pla-n
DRAWN G D F
MSUED
Barghausen
Consulting Engineers Inc.
Land Planning, Survey & Engineering Specialists
6625 5o 190th St Sotto 102 Kant Wash, 98032 (206) 872..5522
CHECKED
SCALE u
APPR
JOB NO
C870
DWG NO
H