HomeMy WebLinkAboutPP - 14624 TUKWILA INTERNATIONAL BLVD - UNKNOWN - PERMITS AND PLANS14624 TUKWILA INTERNATIONAL BLVD
ASSOCIATED PERMITS
07-F-053
MEI wow
2X1 6" DUCT
O
G J 0
-J M 7a
t0l1 ► U...
Z al
zw0
d
U
C
2
E
03
JZ4 Ci)
V1 p
Q 0
to ,_
1 •
0
2
z
0.
EI,C TrzAc 'r - PeVIGc5/00-Tver5
UNDE2. *bop r e'E-0 -ro 541) MT
c*3. f lV icy -1-101J
Kik--uP WM-DS 'N
Ott SII Aoll tfill o N
. . , r
ACCEPTED
Without Comments
As Noted in Red
Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current city
standards. Acceptance is subject to errors and
omissions which do not authorize violations of adopted
I stanoaras and orainances. The responsibility fo'\the
3dequacy of design rests totally with the designer.
Additions, deletions or revisions to these drawings atter
this date will void this, acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to ;held test and inspection by
The Tukwila Fire, Prevention Bureau.
Date: 42 f /0 ?'By: 5g
TUKWILA FIRE DEPARTMt,1be
Please call: 575.4407
and give this job
No. 01- F- 05.E s.
and exac+ *ddress for strut•
down or restoration approval.
4-6 24— ► ,,(a. (-'i g kth
14624 TUKWILA INTERNATIONAL BLVD
ASSOCIATED PERMITS
02-F-233
NET Satis£AXtion To: randy
.f
From: Max Benjamin 11-19-02 10:44am p. 8 of 12
! (4 2 Ll ILA/;10. vdh (v4
; u� wr1
vi.w.10. 9e Icig
Backup Battery Calculations
In the event of an AC power loss, the VISTA-32FB must be supported by a 12VDC, 7AH
min/34.4 max sealed lead acid battery.
As shipped, the VISTA-32FB enclosure can house up to 14AH batteries (i.e., two 7AH batteries
wired in parallel). The optional VISTA-ULKT enclosure kit may be used to house up to 34.4 AH
batteries.
The battery's capacity must be sized to provide 4 hours (commercial burglary installations),
24 hours (local or central station commercial fire installations), or 60 hours (remote station
commercial fire installation of standby time followed by 5 minutes (commercial fire
installations or 15 minutes (commercial burglary installations) of alarm time. This can be
determined as follows:
1. If using the polling loop, fill out the Polling Loop Current Draw Worksheet (shown below)
to determine the total current.
2. Fill out the Total Control Panel Load Worksheet (shown below) to determine the total
standby and alarm load drawn from the control panel's internal '12V power supply.
3. Fill out the Battery Capacity Calculation Worksheet, following the other worksheets, to
determine the required capacity for the back-up battery. Select one of the batteries given
in the Battery Selection Table (later in this section) which has a capacity greater than or
equal to the calculated battery.
NET SatisFAXtion To: randy
From: Max Benjamin 11-19-02 10:44am p. 9 of 12
Section 20 - Final Power -Up Procedure
Polling Loop Current Draw Worksheet
Refer to the Polling Loop Expansion section for device restrictions for fire and burglary
usage.
RPM DEVICE
CURRENT
# OF UMTS
TOTAL
4192SD Photo Smoke
0.4mA
1
Q
70 �' / ,
4192SDT Smoke w/Heat
0.4mA
4192CP Ion Smoke
0.4mA
4275 Dual PIR
1 .OmA
4278 Quad PIR
1.0mA
4208U 8 -Zone RPM
4208SNF 8 -Zone RPM
27.3mA
33.6mA
l
4190WH
High mode 2.0mA
Low mode 1.0mA
4190SN
2.0mA
4193SN
1.5mA
Aux. Power 1 Output Subtotal
(terminals 11 and 12)
4293SN
1.0mA
4939SN-WH
1.0mA
4944SN-WH
1.0mA
4959SN
1.0mA
4191WH
4191SN-WH
1.0mA
5192SD
0.4mA
5192SDT
0.4mA
TOTAL Cannot exceed 128MA*
* The total current cannot exceed 128mA. If total load exceeds 128mA, then a 4297 Loop
Extender Module can be used. This module is powered from the panel's auxiliary power,
and provides a separate polling loop output, which can support an additional 128mA load.
Note that the total number of polling loop points connected to the panel cannot exceed 32.
Total Control Panel Load Worksheets
To calculate the total current for the Aux. Power 1, Aux Power 2, Bell 1 and Bell 2 outputs
and polling loop current, multiply the each device's standby and/or alarm current by the
number of units used.
1. Enter devices used
on Aux. Power 1
output, calculate
standby and alarm
currents, then add
to get Aux. Power 1
current subtotal.
AUX. POWER 1
Device Model #
OUTPUT I
Device Current X # of Units
Total Current
= Standby
Alarm
SysTC qg 1
tit
% O 4" ,
1
Q
70 �' / ,
sit 74,1,: ./
41 6 0 /Pr, 4
l
4 am li
Aux. Power 1 Output Subtotal
(terminals 11 and 12)
1.0A max
1.7A max
20-3
NET SatisFAXtion To: randy
From: Max Benjamin
VISTA-32FB Installation and Set -Up Guide
11-19-02 10:14am p. 10 of 12
2. Enter devices used
on Aux. Power 2
output, calculate
standby and alarm
currents, then add
to get Aux. Power 2
current subtotal.
3. Enter devices
connected to Bell 1
output, calculate
alarm currents,
then add to get Bell
1 output current
subtotal.
4. Enter devices
connected to Bell 2
output, calculate
alarm currents,
then add to get Bell
2 output current
subtotal.
5. Enter the total
polling loop current
using values
calculated in the
polling loop
worksheet.
AUX. POWER 2
Device Model #
OUTPUT
Device Current X # of Units
I Total Current
= Standby
Alarm
ohi
Sr .ti i7s' se,.<�z.
�iiJ
psil mil
1
xxxxxx
Jai mq
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
Aux. Power 2 Output Subtotal
(connector J4 -pin 5)
400mA max
400mA max
BELL 1 OUTPUT
Device Model #
Device Current X # of Units
I Total Current
= Standby
Alarm
ohi
Sr .ti i7s' se,.<�z.
�iiJ
psil mil
1
xxxxxx
Jai mq
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
Bell 1 Output Subtotal (terminals 3 & 4) 1.7 amp max
XXXXXX
BELL 2 OUTPUT
Device Model #
Device Current X # of Units
I Total Current
= Standby
Alarm
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
Bell 2 Output Subtotal (terminals 5 & 6) 1.7 amp max
XXXXXX
Polling Loop
Total Current
Standby
Alarm
(Enter worksheet total. both standby & alarm columns)
Polling Loop Subtotal
20-4
NET SatisFAXtion To: randy
From: Max Benjamin
11-19-02 10:44am p. 11 of 12
Section 20 — Final Power -Up Procedure
6. Enter total
calculated subtotals
of all listed outputs,
then add to get the
combined current.
7. These values are
fixed.
8. Enter the calculated
combined current,
then add to total
PCB current.
9. Using the total
calculated power
supply load (step 8),
calculate the
battery capacity
required for the
installation.
COMBINED AUX. POWER, BELL, AND RELAY OUTPUT
Total Current
Standby
Alarm
Aux. Power 1 Output Subtotal
300mA
50m, q
Aux. Power 2 Output Subtotal
5mA
(inactive)
15mA
(active)
Bell 1 Output Subtotal
XXXXXX
lig fin 4
Bell 2 Output Subtotal
XXXXXX
Polling Loop Subtotal
Add all subtotals
(Cannot exceed 1.0A max. standby/2.3A max alarm)
70 " R
a.31 R., A
VISTA-32FB PCB CURRENT
Total Current
Standby
Alarm
Includes 2 -wire smoke detector loading on zones 1 & 2 and
trigger output currents
300mA
470mA
5140DLM Backup Dialer Module
5mA
(inactive)
15mA
(active)
*5140DLM actually draws 55mA when active. However, since VISTA-32FB PCB
current includes built-in main dialer current, and since main dialer is inactive
when 5140DLM is active, 5140DLM imposes only 15mA added current on power
supply.
TOTAL CONTROL PANEL LOAD
Total Current
Standby
Alarm
Combined aux. power, bell, and polling loop total
(Use total standby load from previous worksheet)
For 4 -hour standby time. use the following formula:
Total standby load x 4 hours x 1.4 loading/contingency
factor
For 24-hour or 60 -hour standby time. use the following
formula: Total standby load x 24 or 60 hours x 1.1
contingency factor
`;f SY `f
• • •
S a y /
r
Total PCB current
3 DS pp A
- 1 S ..>
Total control panel load
3 0 ,rh, h
-71 b .4414
Battery Capacity Calculation Worksheet
Capacity
Formula
Calc Value
Standby Capacity
(Use total standby load from previous worksheet)
For 4 -hour standby time. use the following formula:
Total standby load x 4 hours x 1.4 loading/contingency
factor
For 24-hour or 60 -hour standby time. use the following
formula: Total standby load x 24 or 60 hours x 1.1
contingency factor
`;f SY `f
• • •
S a y /
r
Alarm Capacity
(Use total alarm load from previous worksheet)
Total alarm load x 0.083 hours (for 5 -min. alarm)
x 0.250 hours (for 15 -min. alarm)
- 1 S ..>
Total Capacity
Add standby and alarm capacities
;7p5 7174
20-5
NET SatisFAXtion To: randy
From: Max Benjamin 11-19-02 10:44am p. 12 of 12
VISTA-32FB Installation and Set -Up Guide
10. Using the battery
capacity value from
step 9, select the
appropriate
battery.
Battery Selection Table
Capacity
Recommended Battery
Comments
7 AH
Yuasa NP7-12
12 AH
Yuasa NP12-12
Fits in VISTA-ULKT enclosure only.
14 AH
Yuasa NP7-12 (connect 2 in
parallel)
17.2 AH
Yuasa NPI 8-12
Fits in VIS'T'A-ULKT enclosure only.
24 AH
Yuasa NP12-12 (connect 2 in
parallel)
Fits in VISTA-ULKT enclosure only.
28 AH
Yuasa NP7-12 (connect 4 in
parallel)
Fits in VISTA-ULKT enclosure only.
Connecting 4 NP7-12 batteries in
parallel requires a second optional SA
5140-1 dual battery harness.
34.44 AH
Yuasa NPI8-12 (connect 2 in
parallel)
Fits in VISTA-ULKT enclosure only.
y
9.1vk'E 70 (tLT 1GG
)
//WA. S/2oL? 141 L ( A]
/or ea
AL °p,
60(; )14)
171 (m A)
L
0
ROOF.
+� 24' 0.6. W/tat I AL
SHATHNG OVER
3/4' PLY.
tvt
1/4 %O�PE6
I3OGKNG
T
/
T
J
ROOF FRAMING PLAN
5/14' _ . MV.
2x10 • T.24'O.G.
EA. .. PER.
1-i�RRIG GLS' H
ax ALT; •15T
( FM' ), PArs v a... ti FN. -
OViR 4 WALLS
WALL. ;' AT1ON K -i3
bd 0
P.T. 4x
r
Pkdera -L
$4' .fit:/tRh'I
A1I4t'Aw, o e.
rei 5.O.
e•ee••e••
1..e.
e• •
•s..•
e.•
•
1 • •
•••
'•ee. • e e•
i.•e••••00•
•••e••
• • •••••••
•e 6.0.0•
.��0•••••
.••••
•••••e•0•
000••00•
14.00•••0•
• ••0•••••
•••••••••
1.00060000
00•••0.0
Ing
1
WATER TANKS
J
TYPICAL SECTION
RG
1
FOOTING• PLAN
12'-0'
J
7-1-: 2x 6 RM J015T (""\ -
ti 2x6 H.R. J019T
d a 16' O.G. V//
3/4' PLY. OVER
( 3 ) P.T. 4'x8'S017J
5PAG8, A 60' OA
r-4'
r-4'
r-4'
r-4'
I'-4'
r-4'
r-4'
I'-4'
r-4'
FLOOR FRAMING PLAN
LINDER COLNTER
EQUIPMENT PLAN
T
L
1
j
121-0'
12
PLATE LIE --
30 YR. COME
ROO■6
if
_
r
.-)%P L C ?." ;} '? ; ILO A ,,
'+�. G.
P li,z:Or $�}`1 (. P+'"«U Cif A ti' FL's; t
AND Y INCLUDEds�:3?.;�7Y ..a '". raj.
� t r�'-v6EW rte,
HARDPANS..
1.-x.._:
DAM
x EDGE BAND
.00
SOUTH ELEVATION
Ti
PLATE LINE
v
L
0'-6'
PE iMIT NO
HIS SET OF APPROVED PLANS
KU i.7 SE ON THF JOB AT ALL
IM rOURING CONSTRUCTION.
THIS BUILDING IS NOT TO BE
OCCUPIED UNTIL AFTER FINAL
INSPECTION APPROVAL BY THE
TUKWILA Ef. NDIRIG DIVISION
DEPARTMENTOF CO V MUN1TY DEVELOPMENT
.ars�asrra.n,u-m+r .:
SE -'ARAT . PERMIT
REQUIRED ED FOR:
LY'cJECH NI
.u. :�., E. ,�;CAL
ELECT TICAL
L LUf 'ING
g -G AS PIPING
CITY OF TUKWILA
r: f': stir ��4air1�}
,,,://:1/0//jJ
11 11 11
1 x ED6E DAN,
5'-O'
HARDPAN
x EDGE BAND
FLOOR PLAN
u
WEST ELEVATION
2
3
T-1
T-1
Ix EDGE BAND
HARDPANS
-
TUKWILA FIRE DEPARTMElit
Please call: 575.44074
and give this -- job
No.oZ-/ --
and enact address €or shut.
:J o ation approvat
T -I
RAMP AS READ
EAST ELEVATION
NOTICE
A
Depa
coin
any
pleted, signed,hkwila Vitt
} ent Pre-test Certificate must*,
nted to the Inspector prior to
cement of Acceptance Testing of
e Alarm and De,ection Systems.
f test will result in $40 Re -
Fee and termination •of.•
testing.
if
J
0
1
1th+'at
A • Ni tec n
P r 1 is r tf.
HARM'
vention Bureau for ccir n,
dards. Acceptance is st
ssions which do not a ill
standards on' arr.?innr1c. s -
adequacy of U::ijr)
Additions, deietict,s o
this date will void this acce
resubmittal of revise die, ::ir
Final acceptance is sube t
• n
PTE
ments
shed Letter
0
L
wed by The Tukwi'a Fire
Tenix, with current city
a t tis errors and
pied
the
r.
after
.n.ce .Ira a
`e1 �:. ; It approval.
field t_st t inspection
ureau.
4
NORTH ELEVATION
a e: a r,'r
VED
CITY OF�TUKWILA
AUG 19 2002
PERMIT CENTER
DOI"' i ls
3:E JED
NOV 2 0 2002 OA'
2'!37
/0 a
LL
ghtt
9
N
0
0
N
tib
co
0
z
0
i�
w
z
J
(253) 709.•0598
w
LL co
w
as
2 51
cc
E0 N .�
wv U m
zwL
wo Lri
cD
N
N
O
N
1W=
iciiiL!i:i4;-
iici-mn-ii_ziu):>_:.0:00---1110_6_
pzcW�
���
lLO UOF-O
cW~��:Ocf)O1LLY
�n!!::::::
ozvz���=moo
` -Jh- dZ oLj(7Wp> OOUOJ
Z =n- ��N'S��F_UOtn1- 6�— WI ,W-mZI--Zcw1�!HzWOKQ��}c1 d AZO Z-WUZ�Ot7Z�N UO
tn— �
°w°u-VwimwF-OHO F-a�F_ 'a
WZWZw�U\Otn���Zii
Uu_ =�cnF-Z-(15EA O
Z�ow�UZU--z zpo
<1-n-wo .00Jb�_jp
ww,..mw¢MMOi--
1-1-- 0o.va 1 .0)0W0h- -
DESIGNED BY:
CHECKED BY:
APPROVED BY:
SCALE:
HORIZ.: 1/2' - 1'- 0'
VERT; A', NOTED
DATE:
AUGUST Ib 2002
DRAWN BY:
SHEET NUMBER
OF
REVISION