HomeMy WebLinkAboutPP - 15210 TUKWILA INTERNATIONAL BLVD - UNKNOWN - PERMITS AND PLANS15210 TUKWILA INT 95-F-270 ERNATIONAL BLVD ASSOCIATED PERMITS - -10 5 — 1 A B C E MATERIAL LIST F G H LI J ITEM SYM QTY PART NUMBER DESCRIPTION MANUFACTURER ) MOUNTING - WEST 1 PANEL CONNECTIONS, DETAILS & RISER DIAGRAM 1 1100-0316 FIRE ALARM CONTROL PANEL (CLP -4) FCI TOP 72" AFF IFACP NAC - POWER SONIC IN FACP i TYP 2 2 PS -1270 STAND-BY BATTERIES (12V, 7.0 AH) 3 1 MT-24-LSM-VFR HORN/STROBE _ WHEELOCK TOP 90" A -F ;o; 4 C 2 1100-0615 MANUAL PULL STATION (MS -2) FCI TOP 48" AFF 5 O 3 - KITCHEN HOOD CONTROL (EXISTING) - 6 0 1 70-600000-155 DUCT DETECTOR, WITH PHOTOELECTRIC HEAD (DH -60 PSD) FENWAL — - 7 2 4 112-6808J IONIZATION SMOKE DETECTOR (CPD -7051) FCI ON 2 -WB 1 8 - 4 110-51120 i DETECTOR BASE (2 -WB) FCI CEILING j 9 - 1 06-129500-003 SAMPLING TUBE' 48" FENWAL - 10 1 138-A0701 REMOTE ZONE ANNUNCIATOR (RZA-MC6/RTI) FCI 60" AFF -' ANN 11 - 1 1120-0547 ANNUNCIATOR MODULE (CLA) FCI IN CLP -4 12 ,o; 1 LSM-24-VFR STROBE WHEELOCK 80" AFF 13 -'c,- 1 111-0502B REMOTE ALARM INDICATOR (RA -911) FEN WAL 60" AFF 14 - 1 138-311-A SURFACE BACKBOX FCI - 15 - 1 138-3490A WEATHER PROOF KIT FCI - ELECTICAL NOTES 1. INSTALLATION SHALL COMPLY WITH NFPA 70, PARTICULARLY ARTICLE 760 SECTION C, AND SHALL ALSO COMPLY_ WITH NFPA 72 AND ALL LOCAL ELECTRICAL CODES AND LOCAL —tURISDLCTION. 2. CONDUIT SHALL BE 1/2"—EM SPECIFICALLY NOTED ON PRINTS. 3. CONDUIT WHICH MAY BE INDICATED ON PRINTS, IS DIAGRAMMATIC AND CAN BE REROUTED PER FIELD REQUIREMENTS. 4. AC POWER, SHALL NOT OCCUPY THE SAME CONDUIT- AS FIRE ALARM CIRCUITS (MOST FIRE ALARM CIRCUITS ARE NEC CLASS 3). 5. CLASS A FIRE PROTECTION CIRCUITS SHALL UTILIZE A SEPARATE CONDUIT FOR WRING RETURN PATH TO THE PANEL. 6. FIRE PROTECTION WIRING NOT REQUIRED TO BE IN CONDUIT PER SPECIFICATIONS, CODE OR USER REQUIREMENTS, SHALL BE TYPES FPL, FPLR OR TYPE FPLP. TYPE FPLP SHALL BE USED IN PLENUMS. WIRING SHALL BE SECURED TO BUILDING STRUCTURE. 7. FIRE PROTECTION CIRCUITS SHALL NOT BE PARALLEL BRANCHED (TEE TAPPED) TO ENSURE SUPERVISION OF WIRING. 8. POLARITY OF ALL FIRE DETECTION WIRING SHALL BE MAINTAINED THROUGHOUT ENTIRE SYSTEM; WIRE �4 SHALL BE MARKED AND IDENTIFIED WHERE SPLICED. 9. THE FIRE ALARM PANEL GROUND SHALL BE A SEPARATE CONTINUOUS GROUND WIRE BACK TO THE SOURCE GROUND; CONDUIT GROUND IS NOT ACCEPTABLE PER MANUFACTURER'S SPECIFICATIONS. - 10. ALL FIELD WIRING SHALL BE CHECKED FOR SHORTS AND GROUNDS. WIRING SHALL THEN BE MEGGARED BEFORE CONNECTION OF DEVICES TO THE SYSTEM WIRING. WIRING SHALL BE MADE UP FOR THIS TEST SO THAT ALL WI9ING COMPRISING THE SYSTEM IS TESTED. MEGGAR TEST RESULTS SHALL BE RECORDED AND SUBMITTED WITH SYSTEM TEST RESULTS. 11. FIRE ALARM PANEL SHALL BE SUPPLIED BY A DEDICATED CIRCUIT BREAKER; OTHER EQUIPMENT SHALL NOT SHARE THE FIRE ALARM CIRCUIT. THIS BREAKER SHALL BE CLEARLY MARKED "FIRE ALARM". 12. POWER SHALL NOT BE APPLIED TO THE FIRE ALARM PANEL UNLESS A REPRESENTATIVE FROM THE MANUFACTURER IS PRESENT. 13. RECORD ALL CHANGES TO WIRING CONNECTIONS, DEVICE PLACEMENT, WIRE ROUTING OR CONDUIT RUNS ON AS -BUILT DRAWINGS. RETURN THE AS -BUILT DRAWINGS TO - ENGINEERED FIRE SYSTEMS, INC. SEQUENCE OF EVENTS ALARM: ACTIVATION OF A MANUAL PULL STATION, *T DETECTOR OR HOOD SYSTEM SHALL: 1. ACTIVATE ALL INDICATING APPLIANCE CIRCUITS THROUGHOUT THE BUILDING. 2. ACTIVATE THE GENERAL ALARM CONTACTS IN THE FIRE ALARM CONTROL PANEL. 3. DISPLAY ALARM LOCATION BY ZONE LED AT THE FIRE ALARM CONTROL PANEL AND REMOTE ANNUNCIATOR PANEL. ALARM RESET: USER RESET OF THE SYSTEM SHALL CLEAR THE ALARM FUNCTIONS OF THE PANEL; UNLESS DEVICE(S) ARE STILL IN ALARM OR A SUBSEQUENT ALARM OCCURS. 1. THIS SHALL OCCUR BY ACTUATION OF THE RESET/ LAMP TEST KEY. ALARM SILENCE: USER SILENCE OF AN ALARM WILL SILENCE THE AUDIBLE ALARM SIGNAL; VISUAL SIGNAL WILL REMAIN UNTIL TROUBLE IS CLEARED. 1. THIS SHALL OCCUR BY ACTUATION OF THE ALARM/ TROUBLE SILENCE KEY. TROUBLE: SYSTEM TROUBLE, INCLUDING GROUNDING OR OPEN CIRCUIT OF SUPERVISED CIRCUITS, POWER OR SYSTEM FAILURE SH ALL: 1. ACTIVATE THE GENERAL TROUBLE CONTACTS IN THE FIRE ALARM CONTROL PANEL. TROUBLE SILENCE: USER SILENCE OF A TROUBLE WILL SILENCE THE AUDIBLE TROUBLE SIGNAL; VISUAL SIGNAL WILL REMAIN UNTIL SYSTEM TROUBLE IS CLEARED. 1. THIS SHALL OCCUR BY ACTUATION OF THE TROUBLE/ ALARM TROUBLE SILENCE SWITCH. LAMP TEST: MANUAL LAMP TEST ACTIVATES PANEL LEDS AND LAMPS. 1. THIS SHALL OCCUR BY ACTUATION OF THE RESET/LAMP TEST SWITCH. K L M N 0 DRAWING SCHEDULE FP -1 MATERIAL LIST, NOTES, LEGEND, SEQUENCE OF EVENTS & SCHEDULES FP -2 FLOOR PLAN - EAST FP -3 FLOOR PLAN - WEST FP -4 PANEL CONNECTIONS, DETAILS & RISER DIAGRAM A33REV1 TION LEGEND AFF ABOVE ,FINISH FLOOR AFG ABOVE iFINISH GRADE DWG DRAWING EOL END OF LINE RESISTOR EMT ELECTRICAL METALLIC TUBING GND GROUN[3 IDC INITIATING DEVICE CIRCUIT MIN MINIMUM NAC NOTIFACTION APPLIANCE CIRCUIT RM ROOM i TYP TYPICA'1. - 48" 0 tti-e - L _ ANN 1 60" 72" 80" // wgzisismil 1 EQUIPMENT MOUNTING DETAIL SCALE: ACCEPTED ❑ WITHOUT COMMENTS. X.AS NOTED IN RED FER THE ATTACHED LETTER The drawings affixed hereto have been reviewed and accepted by the City of Tukwila Fire Dept Additions, deletions )r revisions to these drawings after this Jate will void this acceptance and will require a resubmittal of revised drawings. Final acceptance is subject to field- inspection-by ield- inspectionby a representative of this department DAT.E. l0 2> 1� �BY:..A ,s--/ CITY OF TUKWILA 575-4407 NTS TUKWILA FIRE DEPARTMENT Please call: 575.4407 and give this job No. 9 -/_- a?O and exact address for shut' down or restoration approval. c» c/) a 0 0 z ,_ ( re) LLI N) ¢� w� LLi cn >0 lr >- 0 c 0 00 r- 0 rn rn Q Q Z Vf } z }- LJJ 0 z 0 0 U N SYSTEM W LL DRAWN: JLB DESIGNED: EMJ CHECKED: KJA DATE:9-14-94 REVISIONS: 0 ISSUED FOR REVIEW A\ REVISED PER COMMENTS 10/95 JOB NO.:2293 PERMIT NO. 94-010 DWG. TITLE: MATERIAL LIST,NOTES, LEGEND,SCHEDULES, SEQUENCE OF EVENTS DA. NO. FP -1 OF 4 A -- 10 9 - 8 - 7 — 6 — 4 3 n 8 C MATCH LINE D E F C H L DRIVE-THRU i I' J K LL DINING AREA W 8 #1 6 KITCHEN U / ►M EN CORRIDOR FLOOR PLAN - EAST SCALE 1 /4"= WOMEN CREW ROOM WALK—IN FREEZER w W M M M O 0 z = Q _N) ~Ln QN wLr) EicN O 'N c D 0 z P'Si co in F— Q > ` (f) >-: V W 0 ryQ n -J a - Q 1-c-1 - Z W n U TUKWILA, WASHINGTON DRAWN JLB DESIGNED EMJ CHECKED KJA DATE 9-14-94 REVISIONS 0 ISSUED FOR REVIEW A\ REVISED PER COMEENTS 10/95 JOB NO. 2293 PERMIT NO 94-010 DWG TITLE FLOOR PLAN - EAST DWG NO FP -2 OF 4 A B C -10 - 4 D E F C H 4 EOL SEATING AREA 2#16 MATCH LINE I 2 DINING AREA 6 --AI '1 EOL 10#16 8#16 ?LAY AREA - 8#16 FLOOR PLAN - WEST SCALE 1/4"=1 e i i z 0 F -- z O U (Y 0 LL CN LL K L M N 0 (/) eZ n• 00 00 00 rn z O Z U) LIJ CO H— Lr)Q W >0 0 1158 INDUSTRY Q COMMERCIAL co =ESTAUA\T ALA\iI SYSTEM 15210 PACIFIC HWY. S. DRAWL JLB DESIGNED EMJ CHECKED KJA DATE 9-14-94 REVISIONS 0 ISSUED FOR REVIEW \RE\1SED PER COMMENTS 10/95 JOB NO 2293 PERMIT NO 94-010 DWG TITLE FLOOD+ PLAN — WEST W DWG NO FP -3 0F4 -- 10 9 8 — 7 6 — 4 - 3 2 — 1 J6 J5 MC6 5 4 3 2 1 V� V T 0 0 0 0 0 0 0 N M J4 u) N aD • 0 4 5 6 7 8 J5 2 3 4 5 J6 8 CLA L 3 9K S I i a� 1/2W` 00000000000000000000 0000000000.00 LZONE1�ZONE+2�ZONE+3ZONE �4�NALM I RLYN�TR RLYLNOTIF APPL 1�NOTIF APPL 21 EXT _t POWER ff6D'ir CLC CABLE MUST LAY FLAT NO TWISTS IDC#3 EXT PWR k®@®® .-. 1 + 4- I -t- ,-... I— F- • Y W v'1 �_ W I -- —I I— _J TB2 3 9K 1/2W J CC F— DH -60 DH -60 1OA ALARM CONTACTS c.) ooo o z z 15 i6 17 18 1X0 TB 1 t_1 L �W1 sur4 6 "3 ALM --4 AN3 TI RESET/ LAMP TEST AC POUR 0 TROUBLE 0 SYSTEM ALARM 0 TROUBLE 0 ZONE 1 ALARM 0 TROUBLE 0 ZONE 2 0 BOARD SUPV ALARM 0 TROUBLE 0 ZONE 3 0 GROUND SUPV ALARM 0 TROUBLE 0 ZONE 4 0 POWER SUPPLY TROUBLE SILENCE 0 TROUBLE 0 SIGNAL ALARM,/ TROUBLE SILENCE CLP -4 GND GRN/YEL d RED BLK 12V ' 12V 7OAH 7OAH STAND-BY BATTERIES TRANSFORMER - T GRN LK BLK EARTH GROUND 120 VAC SWITCH & JUMPER LEGEND IN IN FOR ZONE 1 WATERFLOW OPERATION W2 IN FOR ZONE 2 WATERFLOW OPERATION W3 IN FOR ZONE 3 WATERFLOW OPERATION bi4 IN FOR ZONE 4 WATERFLOW OPERATION W6 IN FACTORY USE ONLJ W7 IN FACTOR) USE ONLY FJ1 CUT FOR NO ALARM CONTACT PJ3 CUT FOR NC ALARM CONTACT PJ6 CUT FOP NO TROUBLE CONTACT RJ7 CUT FOR NC TROUBLE CONTACT SW3 UP FOR ZONE 4 SUPERVISORY FIRE ALARM CONTROL PANEL DETAIL --, SCALE NTS I JUMPER PLUG (DP1) SETTINGS I Y 12 VDC I I L. I ) 04 J1 AHU 'MOTOR STARTER I i I i SUPPLIED BY ELECTRICAL DUCT DETECTOR WIRING DETAIL SCALE NTS CONTRCATOR 24 VDC THE SETTINGS FOR THE 24VDC MODEL ARE 24VDC 101 dBA CODE 3 HORN DP1 SET ON 124 SW1 POS 1 SET Ci\1 1 SvV1 POS 2,3,4 SET ON 1'1,O PC BOARD LAYOUT SHOWING LOCATION -OF JUMPER PLUG (DP1) AND SWITCH (SW1 PRESS) HERE FOR ( 0) PRES:i • HERE FOR (1) + IN OUT HORN/STROBE PROGRAMMING & WIRING DETAIL SCALE NTS USE A POINTED OBJECT SUCH AS A BALL POINT PEN TO CHANGE SWITCH POSITION (DO NOT USE SCREWDRIVER BLADE) PRESS FIRMLY UNTIL IT CLICKS INTO POSITION EOLR 3 9K 1/2W NAC OUTPUT NOTIFICATION APPLIANCE WIRING DETAIL EOLR 3 9K 1,/2Vv r- MANU• PULL STATION SMOKE DETEC OR OR HOOD CONTROL SCALE NTS (+) IDC INPUT INITIATING DEVICE WIRING DETAIL 2#16 IDC #4 IDC #3 4#16 2#16 2#16 IDC #2 EOL STORAGE ROOM NAC #1 EOL - moo` V ANN 2#16 7#16 120VAC EARTH GND FACPI 3#12 SCALE NTS EOL PLAY AREA EOL DUCT DETECTOR 571 AHU MOTOR CONTROL SUPPLIED BY CONTRACTOR 2#16 IDC #1 RISER DIAGRAM SCALE NTS KITCHEN EOL HOOD CONTROLS (EXISTING) /7ngineered .Fre Systems 1158 INDUSTRY DRIVE, SEATTLE, WASHINGTON 98188 (206) 575-3637,`M 3138 COMMERCIAL DRIVE, ANCHORAGE, ALASKA 99501 (907) 274-7973 SYSIEMS DRAWN JLB DESIGNED EMJ CHECKED KJA DATE 9-14-94 REVISIONS 0 ISSUED FOR REVIEW A REVISED PER COMMENTS 10/95 w w JOB NO 2293 PERMIT NO 94-010 DWG TITLE PANEL CONNECTIONS DETAILS & RISER DIAGRAM DWG F NO -4 OF4 l 15210 TUKWILA INTERNATIONAL BLVD ASSOCIATED PERMITS 17-5-203 08-H-452 08-5-497 40�,W CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Submittal Address: 6300 Southcenter Blvd, Suite 209, Tu wila WA 98188 SITE LOCATION Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: 0043000090 Site Address: 15210 International Blvd Suite Number: Floor: Tenant Name: Mc Donalds New Tenant? ❑ - Yes ❑ - No Property Owner's Name: Comiskey, Robert Mailing Address: 15210 International Blvd Tukwila WA 98188 City State Zip CONTACT PERSON -if there are questions about the submittal. Name: Angie Voelpel Day Telephone: 253-857-2056 Company Name: Emerald Fire LLC Mailing Address: 11021 Cramer Rd KPN E-mail Address: angiev@emeraldfirellc . corn Giq Harbor WA 98329 City State Zip Fax Number: 253-857-2312 Total number of new/relocated devices or sprinkler heads: 15 Valuation of Project (contractor's bid price): $ 7,027.00 Scope of Work (please provide detailed information): Fire Sprinkler TI per NFPA 13 2016 PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING i ER OR AUTHORIZED AGENT: Sig Print Name: Angie Voelpel Day Telephone: 253-857-2056 Plan Pennit App.doc 1/2/13 TFD FP Form 8 Date: 10-10-2017 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: McDonalds 15210 Tukwila Intl. Bl. Permit No.: 08-S-497 Date: October 24, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ` of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Maintain a 4 ft. clear space around the sprinkler riser for emergency access. • All valves controlling the water supply for automatic sprinkler systems and waterflow switches on all sprinkler systems shall be electrically supervised. • The FDC shall have a downward angle bend between 22.5 and 45 degrees, with a 5 -inch Storz fitting and Knox FDC locking Storz cap. • The height of FDC's shall be 36 to 48 inches above grade. • FDC's shall be oriented in the direction of fire apparatus access, have a 4 ft clear space in front and to the sides of the connection, be appropriately signed and protected from potential vehicular damage. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2007 Edition. • v FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: McDonalds 15210 Tukwila Intl. BI. Permit No.: 08-H-452 Date: September 15, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Nozzle heights above appliances to be per manufacturers installation guidelines. • Install splash guards between fryers and ranges/charbroilers. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. • The suppression system manual pull station shall be located no closer that 10 ft. and no farther than 20 ft. from the cooking equipment. WASHINGTON SURVEYING & RATING BUREAU 2101 4th Avenue Suite 300 Seattle, WA 98121 P 206.217.9772 F 206.217.9329 www.wsrb.com Underwriting Information, Filings & Property Loss Costs Jose A. Buitrago Senior Field Representative/ Plan Review jose.buitrago@wsrb.com 206.273.7157 10. Hangers should be installed according to UL listing and as specified by NFPA 13. 11. Extend sprinkler protection to all areas including exterior eaves, soffits, canopies, combustible blind and roof spaces, and to roof skylights. Serving the Property and Casualty Insurance Industry Since 1911 WASHINGTON SURVEYING & RATING BUREAU 2101 4th Avenue Suite 300 Seattle, WA 98121 P 206.217.9772 F 206.217.9329 www.wsrb.com Underwriting Information, Filings & Property Loss Costs Jose A. Buitrago Senior Field Representative/ Plan Review jose.buitrago@wsrb.com 206.273.7157 September 25, 2008 PLAN SHEETS 1 of 1 SUBJECT McDonalds 15210 — International Blvd. Tukwila, Washington The attached plans have been reviewed as follows: The following revisions or additions to the design as shown would qualify the protection for improved rates based upon information shown on these plans. Completed copies of the Contractor's Material and Test Certificates for both the overhead and underground piping should be submitted to this Bureau, including tests of the local alarm and main water supply test pipe (2 -inch). All piping, valves, and fittings should be listed and labeled by UL for fire service and installed, tested, and flushed in accordance with NFPA standards. A minimum temperature of 40°F must be maintained with a thermostatically controlled heating system in all areas containing wet pipe sprinkler equipment. 1. Flow tests generated by computer model are not acceptable for fire insurance rating purposes. Provide flow test conducted within the last 5 years. Provide detailed information regarding location and date of flow test, number and diameters of outlets flowed, pitot pressures, whether or not stream straighteners were used. 2. A density of .15/1,500 is acceptable for Group I occupancy (restaurant). 3. Hydraulic Calculations does not include 100 gpm at the base of the riser (BOR) for inside hose allowance as required per WSRB plus the 250 gpm (ordinary hazard occupancy) for outside hose allowance as required by NFPA 13. 4. The system should be designed to provide combined sprinider/hose residual flow after adjusting the flow test for a cushion of 10% below the static pressure (minimum of 5 psi and maximum of 10 psi cushion). 5. Provide a variable pressure alarm valve and outside water motor alarm gong. 6. Provide an outside property indicating control valve (P1V). 7. Insulation batts should be secured in place with wire mesh to prevent sagging and possible obstruction to sprinkler discharge. 8. Provide sleeve with minimum 2 -inch cleardnee around supply mains through concrete floors and around piping through masonry walls or partitions. 9. Provide complete calculations indicating that the sway bracing is ca.. r = : withstanding the forces as stipulated in NFPA 13. Serving the Property and Cal,* ric• e 1 0 0tf`'Gt of dd Si t �` e.8 ^ „c\C�Si��11 “1 t 10; to, }o 0 MCDONALDS, TUKWILA T.I. 15210 Pacific Hwy, Tukwila, WA 98188 FIRE SPRINKLER PRODUCT SUBMITTAL DATA Emerald Fire 11021 Cramer Road KPN Gig Harbor, WA 98329 Phone: 253-857-2056 — Fax: 253-857-2312 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: McDonalds 15210 Tukwila Intl. BI. Permit No.: 17-S-203 Date: October 31, 2017 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3 6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. ✓ .. • Comply with NFPA 13 obstruction tables. • All valves controlling the water supply for automatic sprinkler systems and waterflow switches on all sprinkler systems shall be electrically supervised. • All interior control valves shall be readily accessible, labeled and located not more than 6 ft. above the floor. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2013 Edition. 6 SILENT KNIGHT 5700 Calculations Parisi SLI: Location: 5100 1 Crew Area Global Project Values. Project Name: Project ID: Prepared By: Date: McDonalds 1Roy L. Cats 19/3/2008 Standby Hours: Alarm Mins: Derating Factor: 24 5 1 1.2 1 Voltage Drop Warning Threshold % .1 10 Wiredet. 5100 Add. fire Alarm Ceram', Pane; Volts: 24 VDC 4dlax 44AC Cusses*: 2.5 Amps Max Panel Current 2.5 Amps Ckt.# Circuit Name 5700 5700 CTRL Panel Current Draw Qty Standby Alarm 1 0.206 0.356 SLC -DEV Addrsbl SLC Devices 8 5860 LCD Remote Annunc 0.000 0.004 5824 Serial/Parallel Module 5496 Power Expawder 58654 LED Annunciator (4G) 5865-3 LED Annunciator (30) 5880 LED Driver Module vtsies Other SO -Duct Duct Hsg w/Relay 5883 Relay Module PG141-110#1 PGM -I/O #2 tat #1 Nac #2 Total Standby Cur ent(Amps) Standby Time In Hours 0.000 0.000 0.000 0.000 4.000 4.000 0.000 0.000 0.000 0.000 0.000 0.000 9.400 (1.40(1 0.000 l 0.000 0.000 0.000 0.000 0.000 Wire AWG & Type Ohms Per Length(ft) Actual Volts 1000 Ft. One -Way Ohms EOL %Drop 0.000 0.533 #16 Solid 4.02 0.2136 2.041 Total Alarm Current (Amps) Total Standlohy l444 Rengtmed 24 0.083 Alarm Time In Minutes / 60 4555-0.'174 Total Combined AH Required 5.12 Multiply By The Derating Factor 1.20 Minimum Battery AmpHours Required 6.15 Total Mann i141 Required 150 1.09 19.15 6.11% 1.21 19.76 3.15% (5 Mins) Command Shortcuts Configure Circuits Print Page • Project Information Project Name: McDonalds Prepared By: Roy L. Cats Project ID: 0 Date: 9/3/2008 Ckt. Number: PGM -1/O #1 Ckt. Name: Nac #1 Panel ID: 5700 I/O Use Notification Appl Circuit Qty Device 4 JGentex HS24-110 Hom/Strobe 4 JGentex ST24-30 Strobe Current Draw Each Current Draw Total Standby Alarm Standby Alarm 0.000 0.195 0.000 0.000 Unused 0.000 0.092 0.000 Unused 0.000 0.000 0.000_ 0.000 0.000 0.780 0.368 0.000 Totals 0.000 0.000 0.000 0.000 1.148 Ckt. Number. PGM -I/0 #2 Ckt. Name: Nac #2 Qty Device 1 Gentex HS24-110 Hom/Strobe Panel ID: 5700 h o Use:) Notification Appi Circuit Current Draw Each Current Draw Total Standby Alarm Standby Alarm 0.000 0.195 1 Gentex ST24-30 Strobe 0.000 0.158 1 Gentex WGEC24-75 Outdoor Horn/Strobe Unused D.000 0.000 0.180 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.000 0.195 0.158 0.180 0.000 0.000 0.533 HRS SYSTEMS, INC 4792 LAVISTA ROAD TUCKER, GA 30084 HYDRAULIC CALCULATIONS FOR NORCO FIRE PROTECTION, INC. 24024 SE 261ST PLACE MAPLE VALLEY,WA 98038 DRAWING NUMBER: E0816A DATE: 9/5/08 -DESIGN DATA - OCCUPANCY CLASSIFICATION:ORDINARY HAZARD DENSITY: .15 gpm/sq. ft. AREA OF APPLICATION: 1500 sq. ft. COVERAGE PER SPRINKLER: 121 sq. ft. TYPE OF SPRINKLERS CALCULATED: SSP NUMBER OF SPRINKLERS CALCULATED: 19 HOSE -STREAM DEMAND: 250 gpm TOTAL WATER REQUIRED (INCLUDING HOSE):634.9 gpm FLOW AND PRESSURE (AT BASE OF RISER):384.9 gpm @ 28.4 psi TYPE OF SYSTEM: WET WATER SUPPLY Static:50 psi Residual:20 psi Flow:3200 GPM Source Elevation Relative to Finished Flow Level: 0 ft. INSTALLING CONTRACTOR Name: EMERALD FIRE Address:11021 CRAMER RD. KPN GIG HARBOR,WA. 98329 Phone:253-857-2056 Certification number:EMERAFL980MR NAME OF DESIGNER: STEVE ADAMSON AUTHORITY HAVING JURISDICTION: TUKWILA F.D. NOTES: Calculations performed by HASS 7.9 under license # 50110271 granted by HRS SYSTEMS, INC. TUCKER, GA 30084 USA. (Notes continue after pipe calculations results.) DATE: 9/5/2008 JOB TITLE: MC DONALD WATER SUPPLY ANALYSIS SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 C:\HASS7S\E0816A.SDF 0 0 0 0 0 0 0 0 0 0 0 0 W In V M N 0 0 N DATE: 9/5/2008 C:\HASS78\E0816A.SDF SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 JOB TITLE: MC DONALD NFPA WATER SUPPLY DATA SOURCE NODE TAG STATIC PRESS. (PSI) RESID. FLOW PRESS. @ (PSI) (GPM) 49 50.0 20.0 3200.0 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE TOTAL HOSE STREAM ALLOWANCE AT SOURCE OTHER HOSE STREAM ALLOWANCES TOTAL DISCHARGE FROM ACTIVE SPRINKLERS NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE (FT) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 29A 30 31 32 17.1 17.1 17.1 17.1 17.1 17.1 17.1 17.1 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 10.8 10.8 10.8 10.8 K= K= K= K= K= K= K= K= K= K= K= K= K= K= K= K= K= K= K= 5.43 5.43 5.43 5.43 5.43 5.43 5.43 5.43 5.43 5.43 5.43 5.43 5.43 5.43 5.43 5.43 5.43 5.43 5.43 AVAIL. PRESS. (PSI) 48.5 TOTAL @ DEMAND (GPM) 634.9 GPM 250.0 GPM 0.0 GPM 384.9 GPM REQ'D PRESS. (PSI) 634.9 39.8 PRESSURE DISCHARGE NOTES (PSI) (GPM) 11.2 12.1 13.1 14.3 11.7 12.6 13.6 14.8 13.2 14.8 16.7 15.0 15.2 16.4 11.5 12.0 13.0 15.6 18.8 11.8 12.6 13.7 15.1 15.1 12.2 13.2 14.3 15.6 15.7 21.3 13.9 15.6 17.6 18.2 18.9 19.6 20.5 18.6 19.2 20.0 20.9 19.7 20.9 22.2 21.0 21.2 22.0 18.4 18.8 19.6 21.4 23.6 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 9/5/2008 C:\HASS78\E0816A.SDF JOB TITLE: MC DONALD NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES (FT) (PSI) (GPM) 33 10.8 16.2 34 10.8 17.3 35 10.8 21.1 36 10.8 21.1 37 10.8 12.1 38 10.8 13.0 39 10.8 14.0 40 10.8 16.4 41 10.8 21.1 42 10.8 21.2 43 10.8 21.3 44 10.8 21.7 45 10.8 23.8 46 1.0 28.4 47 0.0 35.3 48 0.0 - - - - 38.3 49 0.0 SOURCE 39.8 384.9 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 9/5/2008 C:\HASS78\E0816A.SDF JOB TITLE: MC DONALD NFPA PIPE DATA Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) End El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Nodes El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 1 5.43 18.2 Disch 1.33 120 0.5 20 17.5 11.8 0.0 1.000 T: 5 5.00 0.2 1 17.1 11.2 18.2 1.049 6.33 0.109 0.7 Pipe: 2 5.43 18.9 Disch 21 17.5 12.6 0.0 1.000 2 17.1 12.1 18.9 1.049 T: 5 1.33 120 5.00 6.33 0.117 0.6 0.2 0.7 Pipe: 3 5.43 19.6 Disch 1.33 120 0.6 22 17.5 13.7 0.0 1.000 T: 5 5.00 0.2 3 17.1 13.1 19.6 1.049 6.33 0.126 0.8 Pipe: 4 5.43 20.5 Disch 23 17.5 15.1 0.0 1.000 4 17.1 14.3 20.5 1.049 Pipe: 5 5.43 18.6 Disch 25 17.5 12.2 0.0 1.000 5 17.1 11.7 18.6 1.049 Pipe: 6 5.43 19.2 Disch 26 17.5 13.2 0.0 1.000 6 17.1 12.6 19.2 1.049 Pipe: 7 5.43 20.0 Disch 27 17.5 14.3 0.0 1.000 7 17.1 13.6 20.0 1.049 Pipe: 8 5.43 20.9 Disch 28 17.5 15.6 0.0 1.000 8 17.1 14.8 20.9 1.049 T: 5 T: 5 T: 5 T: 5 T: 5 2.00 120 5.00 7.00 0.137 1.33 120 5.00 6.33 0.113 1.33 120 5.00 6.33 0.121 1.33 120 5.00 6.33 0.131 2.00 120 5.00 7.00 0.141 Pipe: 9 5.43 19.7 Disch 1.00 120 30 10.8 13.9 0.0 1.000 2E: 4 4.00 9 10.8 13.2 19.7 1.049 5.00 0.127 Pipe: 10 31 10 5.43 20.9 Disch 10.8 15.6 0.0 10.8 14.8 20.9 1.000 T: 5 1.049 Pipe: 11 5.43 22.2 Disch 32 10.8 17.6 0.0 1.000 T: 5 11 10.8 16.7 22.2 1.049 Pipe: 12 5.43 21.0 Disch 33 10.8 16.2 0.0 1.000 12 10.8 15.0 21.0 1.049 E: 2 0.67 120 5.00 5.67 0.141 0.67 120 5.00 5.67 0.158 6.58 120 2.00 8.58 0.143 0.8 0.2 1.0 0.5 0.2 0.7 0.6 0.2 0.8 0.7 0.2 0.8 0.8 0.2 1.0 0.6 0.0 0.6 0.8 0.0 0.8 0.9 0.0 0.9 1.2 0.0 1.2 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 9/5/2008 C:\HASS78\E0816A.SDF JOB TITLE: MC DONALD Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) End El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Nodes El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 13 5.43 21.2 Disch 2.17 120 1.0 33 10.8 16.2 0.0 1.000 T: 5 5.00 0.0 13 10.8 15.2 21.2 1.049 7.17 0.144 1.0 Pipe: 14 34 14 10.8 10.8 5.43 17.3 16.4 22.0 Disch 0.0 22.0 1.000 T: 5 1.049 0.83 120 5.00 5.83 0.155 Pipe: 15 5.43 18.4 Disch 1.33 120 37 10.8 12.1 0.0 1.000 2E: 4 4.00 15 10.8 11.5 18.4 1.049 5.33 0.112 Pipe: 16 38 16 Pipe: 17 39 17 Pipe: 18 40 18 Pipe: 19 42 19 Pipe: 20 21 20 Pipe: 21 22 21 Pipe: 22 24 22 Pipe: 23 24 23 Pipe: 24 28 24 Pipe: 25 26 25 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 5.43 13.0 12.0 5.43 14.0 13.0 5.43 16.4 15.6 5.43 21.2 18.8 0.0 12.6 11.8 0.0 13.7 12.6 0.0 15.1 13.7 0.0 15.1 15.1 0.0 15.6 15.1 0.0 13.2 12.2 18.8 Disch 0.0 18.8 19.6 Disch 0.0 19.6 21.4 Disch 0.0 21.4 23.6 Disch 0.0 23.6 0.0 18.2 18.2 18.2 20 18.9 2 37.1 37.1 21 19.6 3 56.7 0.0 20.5 20.5 20.5 23 56.7 22 77.2 0.0 18.6 18.6 1.000 1.049 1.000 1.049 E: 2 T: 5 E: 2 T: 5 1.000 T: 5 1.049 1.000 1.049 1.000 1.049 1.250 1.380 1.250 1.380 2.000 2.067 2.000 2.067 1.000 1.049 E: 2 T: 5 1.33 120 7.00 8.33 0.116 0.83 120 7.00 7.83 0.125 0.50 120 5.00 5.50 0.148 6.50 120 7.00 13.50 0.176 8.00 120 0.00 8.00 0.109 10.00 120 0.00 10.00 0.107 6.00 120 0.00 6.00 0.235 1.33 120 0.00 1.33 0.005 8.67 120 0.00 8.67 0.058 8.00 120 0.00 8.00 0.113 0.9 0.0 0.9 0.6 0.0 0.6 1.0 0.0 1.0 1.0 0.0 1.0 0.8 0.0 0.8 2.4 0.0 2.4 0.9 0.0 0.9 1.1 0.0 1.1 1.4 0.0 1.4 0.0 0.0 0.0 0.5 0.0 0.5 0.9 0.0 0.9 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 9/5/2008 C:\HASS78\E0816A.SDF JOB TITLE: MC DONALD Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) End El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Nodes El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 26 0.0 18.6 25 10.00 120 1.1 27 17.5 14.3 19.2 6 1.250 0.00 0.0 26 17.5 13.2 37.8 1.380 10.00 0.111 1.1 Pipe: 27 0.0 37.8 26 6.00 120 1.5 29 17.5 15.7 20.0 7 1.250 0.00 0.0 27 17.5 14.3 57.9 1.380 6.00 0.244 1.5 Pipe: 28 29 28 Pipe: 29 29A 29 0.0 77.2 24 17.5 15.7 20.9 8 2.000 17.5 15.6 98.1 2.067 0.0 98.1 28 10.8 21.3 57.9 27 2.500 3E:25 17.5 15.7 156.0 2.635 Pipe: 29A 44 10.8 29A 10.8 0.0 0.0 21.7 156.0 29 4.000 21.3 156.0 4.260 Pipe: 30 0.0 0.0 31 10.8 15.6 19.7 1.000 30 10.8 13.9 19.7 1.049 T:26 2E: 4 1.33 120 0.00 1.33 0.091 15.33 120 24.71 40.04 0.066 42.50 120 26.33 68.83 0.006 9.42 120 4.00 13.42 0.127 0.1 0.0 0.1 5.5 -2.9 2.6 0.4 0.0 0.4 1.7 0.0 1.7 Pipe: 31 0.0 19.7 30 16.00 120 2.0 32 10.8 17.6 20.9 10 1.250 0.00 0.0 31 10.8 15.6 40.6 1.380 16.00 0.127 2.0 Pipe: 32 0.0 40.6 31 36 10.8 21.1 22.2 11 1.500 32 10.8 17.6 62.8 1.610 T: 8 18.17 120 8.00 26.17 0.134 3.5 0.0 3.5 Pipe: 33 0.0 0.0 8.17 120 1.1 34 10.8 17.3 42.2 1.250 0.00 0.0 33 10.8 16.2 42.2 1.380 8.17 0.136 1.1 Pipe: 34 0.0 42.2 33 11.00 120 3.8 35 10.8 21.1 22.0 14 1.500 2E: 8 16.00 0.0 34 10.8 17.3 64.2 1.610 T: 8 27.00 0.140 3.8 Pipe: 35 0.0 0.0 4.00 120 36 10.8 21.1 64.2 34 4.000 0.00 35 10.8 21.1 64.2 4.260 4.00 0.001 Pipe: 36 41 36 0.0 64.2 35 10.8 21.1 62.8 32 4.000 10.8 21.1 127.0 4.260 Pipe: 37 0.0 0.0 38 10.8 13.0 18.4 1.000 37 10.8 12.1 18.4 1.049 7.00 120 0.00 7.00 0.004 8.00 120 0.00 8.00 0.112 0.0 0.0 0.0 0.0 0.0 0.0 0.9 0.0 0.9 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 9/5/2008 C:\HASS78\E0816A.SDF JOB TITLE: MC DONALD Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) End El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Nodes El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 38 0.0 18.4 37 9.50 120 1.0 39 10.8 14.0 18.8 16 1.250 0.00 0.0 38 10.8 13.0 37.3 1.380 9.50 0.108 1.0 Pipe: 39 40 39 Pipe: 40 41 40 Pipe: 41 42 41 Pipe: 42 43 42 Pipe: 43 44 43 Pipe: 44 45 44 Pipe: 45 46 45 Pipe: 46 47 46 Pipe: 47 48 47 Pipe: 48 49 48 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 1.0 10.8 0.0 1.0 0.0 0.0 0.0 0.0 0.0 16.4 14.0 0.0 21.1 16.4 0.0 21.2 21.1 0.0 21.3 21.2 0.0 21.7 21.3 0.0 23.8 21.7 0.0 28.4 23.8 0.0 35.3 28.4 38.3 35.3 Source 39.8 38.3 37.3 38 19.6 17 56.9 56.9 39 21.4 18 78.3 78.3 40 127.0 36 205.3 205.3 41 23.6 19 228.9 0.0 228.9 42 228.9 228.9 43 156.0 29A 384.9 0.0 384.9 44 384.9 0.0 384.9 45 384.9 0.0 384.9 46 384.9 0.0 384.9 47 384.9 1.250 1.380 1.500 T: 8 1.610 4.000 4.260 4.000 4.260 4.000 T:26 4.260 10.00 120 0.00 10.00 0.237 15.50 120 8.00 23.50 0.202 6.00 120 0.00 6.00 0.011 5.00 120 0.00 5.00 0.013 7.33 120 26.33 33.66 0.013 47.17 120 4.000 2L:16 15.80 4.260 62.97 0.034 4.000 4.260 9.80 120 0.00 9.80 0.034 184.00 140 4.000 3L:26 29.07 4.100 G: 3 213.07 0.030 Fixed Pressure Loss Device 3.0 psi, 384.9 gpm 4.000 4.100 T:29 L: 9 10.00 140 37.79 47.79 0.030 2.4 0.0 2.4 4.7 0.0 4.7 0.1 0.0 0.1 0.1 0.0 0.1 0.4 0.0 0.4 2.1 0.0 2.1 4.6 -4.2 0.3 6.9 -0.4 6.5 1.5 0.0 1.5 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9 DATE: 9/5/2008 C:\HASS78\E0816A.SDF JOB TITLE: MC DONALD NOTES (HASS): (1) Calculations were performed by the HASS 7.9 computer program under license no. 50110271 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.001 gpm and a maximum imbalance at any node of 0.053 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 12.4 ft/sec at pipe 27. SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10 DATE: 9/5/2008 C:\HASS78\E0816A.SDF JOB TITLE: MC DONALD Utility Report: Equivalent K -Factor Calculator Node Sprinkler Pres. Dia. Pipe Ftgs. Total H -W Equivalent Name K -Factor (psi) (in) Len.(ft) Len.(ft) coef. K -factor 1 5.60 7.00 1.049 1.00 T 6.00 120.00 5.43 15210 TUKWILA INTERNATIONAL BLVD ASSOCIATED PERMITS 08-F-447 08-S-497 99-F-421 08-H-152 17-5-203 McDonalds 15210 Pacific Highway South Tukwila, Wa. 98188 0 LEFT SIDE VIED - HA PULL STATION LOCATION TO BE ACCESSIBLE TO PERSONNEL AND AWAY FROM FIRE HAZARD AREA TO ALLOW MANUAL OPERATION OF FIRE SUPPRESSION SYSTEM TO COOKING STATION II I I 111 1 MU v1 _ELEVATION VI D - HASE NOTES 1. FOR LEFT HANDED CHASE USE A MIRRORED IMAGE OF THIS DRAWING 2. REFER TO BILL OF MATERIALS ON UNIVERSAL HOOD DRAWINGS RIGHT SIDE VI FW - CHASE (Sp 0 6ac,k 206-340-4300 45 1/2' 11/4'1 TO GRILL HOOD 2 1/2' 10 3/4' NOTE 3/B' UNION AT TANK WITH UNION RING ON TANK ADAPTER SIDE. 6 1/4' 29 1/2' AGENT PIPING DFTAII N.N. T• S. Sanderson Safety Dave Carisen 2600 Airport Way S. Seattle 98134 TOP VIED - TANK TOP VIEW - AUTOMAN PULL STATION 4 3/4' A 1/2' TD GRILL HOW - 3 1/A' 7 1/2' 7 5/8' 5 1/2' 5' TRU-ARC TRU-ARC 40 1/4' 27 1/2' TD BOTTOM OF CHASE TO GAS VALVE ETECTION, GAS VALVE. AND REMOTE PULL STATION DETAIL N. T. S. (g EEITsgi'EM DEC ' 19°9 PJ d rjn LED) l R-102�fIRE IS{JPPRESS' 18' UTILITY CHASE UNIVERSAL HOOD GAS OR ELECTRIC 14cDOt1ALD'S CORP. OAK BROOK. IL. eV 011,24 Arme ANSUL. e , 11=0440.= r4lEcpr weary Rau zz nnem I.S.K.. R02-477-11010 SHEET 1 of I 0 Wthout Comments As Noted :ri Red ❑ Et Per The Attached Letter V (a ±-12 a) a) 0 ii. ' ci0 0 ca co 0. (a "0 a) a ) 1.12 N C 2 tmC .0 'a -5C u U C O.0 ~ a) .c 17! Q 0 N ` C d) co I— .3 a) O ..-• .� -0 7 _o 0 > 0 ..-! "' a3 -0 c 5 Cl) ''- a) ,o a) a) ? N a) >. N 0 a.) ..O "1E (a O O) '5 J N +�+ O 'N 0- .0 ED_ ti N m cn > a) �- Iii 03 N .3 O 0 (`a 0� co 00CC 1--- 70 O C C cu '- 0 (1)1:3 T C 0 0 a) N C (Ti U) trz 0 W C U 0 -Q a) > N a) ((i 0 'O 2:1 C j N U V a 0 O> V as CO N m Q 3 n3 p iOD —7 > O (a C t- —_ N N N 0 N 0 a) -§ a) 12,13 .42c 'C Ca cu QNj e 75,c .E 6 N 2(19 t0 a) { rC \0 ;.N ACT CEILING AT 9'-6" A.F.F. ACT CEILING AT 9' 611A.F.F. Sprinkler Legend Symbol Manufacturer SIN Model Quantity K -Factor Type Size Response Finish Temperature O TYCO TY323 TY -FRB 15 5.6 Pendent 'r4 Quick Chrome 200°F IIIIIIHNI Swivel Ring �+ o i /— Pipe Total = 15 and "A' Dimension SYMBOLS LEGEND EXISTING 200 DEGREE PENDENT TO REMAIN EXISTING PENDENT TO BE RELOCATED OR REMOVED AND PLUGGED \ PIPE HANGER SOFFIT AT 0" A.F.F. ACT CEILING AT 9'-6" A F.F. 0 rTh O \ 0 • Li NO WORK THIS AREA. N.I C• - L 1 0 S MEMMli t't 44' i .. - '-t tt-U t;3t�'-J-tt b7 tit it tl�;Tiftk1UJ bird Bt. .F �:t&G it-zt�. ;F9tH 1 I IyI odOQ Si;oLCEiLImlopErr' 1 I TO CLcEILINGARCIV ____1 i �_ I i .1 tat 1ttttJL' I ; SECTION CUT 114"=1'-0" I I I 0'1'2' 4' LL— FIRE FI ROTECTION PLAN 1/4"=V-0" I I I 1 0' 1' 2' 4' Hanger No. 13S Top Beam C -Clamp with Retaining Strap (Joist) Retaining Strap—, NI • Hanger No. 04T Beam C -Clamps Model 300 Michigan Model 300 Michigan Top Beam C -Clamp r l � e Top Beam Clamp or Equal Equal with Lack Nut / 1.5'x1.5" i onLTgoJoeyn -- Unistrut Header lb Rounded to Q Nearest Inch= Steel Bar I -Beam or Joist 'e' - = e Al , — Thread Q'Rod = o 1 AggivslinThs IIIIIIHNI Swivel Ring �+ o i /— Pipe Note on Plan: Hanger Number and "A' Dimension 4' HANGER DETAILS NTS CONSTRUCTION NOTES: I. ALL WORK PER N FPA 13 2016. 2. RELOCATE PENDENT SPRINKLERS DUE TO NEW CEILING LAYOUT. 3. NO CHANGES TO VOID ABOVE CEILING. 4. NO CHANGES TO EXISTING PLAY AREA. El As Nob Per The A.tta .ie +_eater These plans have heen reviewed b The Tukwila Fire Levention Bure.a current City : ndards. Accepr nce i subject : _r o s and •:;;Missions which ,:,ri o'atio ,s of adopted ._:;naargs and orc :,:-o(::.. The resper,cmi!:�,v for the ::adequacy of de.sigi...2sts totally with the ;. signer. ditic?ns, deletion ;-evisions to crest:-. drawings after tills' date will void t i`.. _: _Ceptance and will ; euuire a resubmit -tali"` , �,Is. •:..•,Nines fc� .i,s e, .rl,. approval. Final acceptance is suoJect to field test ano inspection by The Tukwila Fire Prevention Bureau. Date:/O-31—( ) By. unvILA FIRE DEP/T.1471T i'ieas z `1 20,5-575-4<07 and fire �`��� ►=Tit r`e'r € ft No. and scL for shut- down own or approval. VJ IX V a' M ® ME ma' ci in 0 g LL 111 [1/5 tr?' g wwo��w i L t-- ' d 'tui REVISIONS: XX/XX/XX XXXXXXXXXXXMC1 PAID CCT 2017. UKWILA FIRE 4--21'1 ;,K3/0 s WASHINGTON STATE CERTIFICATE OF COMPETENCY FIRE PROTECTION SPRINKLER SYSTEMS Michael Todd Hallengren 7223-0107-C Level 3 Emerald Fire, L.L.C. EMERAFL980 R /41 4 4.4 44,,, Signature o -►o-i) Expires 1/17 JOB NAME: " J 0 gc— Ugr. SHEET NAME Cl) J W 08 W I- 0 z Zirs AJ Y_ W J z 0 W DRAWN BY: AD/MH DATE: 9/9117 JOB #: 217108 SHEET NO: FP1 `t Unistrut/Top Hanger No. 04T Beam C -Clamps Model 300 Michigan Inverted r l Top Beam Clamp or Equal 11 i / 1.5'x1.5" onLTgoJoeyn -- Unistrut Header lb AggivslinThs All Thread Rod Pipe Swivel Ring-\ with Spring Nut Note on Plan: Hanger Number, Unistrut Size "A' Dimension, and Length HANGER DETAILS NTS CONSTRUCTION NOTES: I. ALL WORK PER N FPA 13 2016. 2. RELOCATE PENDENT SPRINKLERS DUE TO NEW CEILING LAYOUT. 3. NO CHANGES TO VOID ABOVE CEILING. 4. NO CHANGES TO EXISTING PLAY AREA. El As Nob Per The A.tta .ie +_eater These plans have heen reviewed b The Tukwila Fire Levention Bure.a current City : ndards. Accepr nce i subject : _r o s and •:;;Missions which ,:,ri o'atio ,s of adopted ._:;naargs and orc :,:-o(::.. The resper,cmi!:�,v for the ::adequacy of de.sigi...2sts totally with the ;. signer. ditic?ns, deletion ;-evisions to crest:-. drawings after tills' date will void t i`.. _: _Ceptance and will ; euuire a resubmit -tali"` , �,Is. •:..•,Nines fc� .i,s e, .rl,. approval. Final acceptance is suoJect to field test ano inspection by The Tukwila Fire Prevention Bureau. Date:/O-31—( ) By. unvILA FIRE DEP/T.1471T i'ieas z `1 20,5-575-4<07 and fire �`��� ►=Tit r`e'r € ft No. and scL for shut- down own or approval. VJ IX V a' M ® ME ma' ci in 0 g LL 111 [1/5 tr?' g wwo��w i L t-- ' d 'tui REVISIONS: XX/XX/XX XXXXXXXXXXXMC1 PAID CCT 2017. UKWILA FIRE 4--21'1 ;,K3/0 s WASHINGTON STATE CERTIFICATE OF COMPETENCY FIRE PROTECTION SPRINKLER SYSTEMS Michael Todd Hallengren 7223-0107-C Level 3 Emerald Fire, L.L.C. EMERAFL980 R /41 4 4.4 44,,, Signature o -►o-i) Expires 1/17 JOB NAME: " J 0 gc— Ugr. SHEET NAME Cl) J W 08 W I- 0 z Zirs AJ Y_ W J z 0 W DRAWN BY: AD/MH DATE: 9/9117 JOB #: 217108 SHEET NO: FP1 `t I I cbtiva+u) s mer Wr 9B B.2 - Fp DISTRIBUTION PIPING II I I I REmo 0 MECHANICAL GAS VALVE (P/N 55601) FRONT ELEVATION SolvDes 56 -very 2600 Prig-porw1Ay 5 20(Q .3.0 -4300 Doole RIGHT SIDE ELEVATION SECTION VIEW 'B -B" SCALE NTS AGENT STORAGE TANK (P/N 429862) 45 1/2' (1/4') TO GRILL HOOD ACTUATION HOSE(S) (P/N 79007) 2 1/8' DETECTION LINE 9 3/8' NOTE 3/8' UNION AT TANK WITH UNION RING ON TANK ADAPTER SIDE. 36 1/4' v \y� 5 1/4' OEM RELEASE (P/N 79493) CARTRIDGE (P/N 17492/423441) 36' L J \_/ \_/ \_/ 1 SECTION VIEW 'A -A' SCALE: NTS PULLEY TEE (P/N 427929) TO DETECTION LINE HOOD - TRU-ARC 3' "U PULL STATION (P/N 54011) 4. 4 _� `a 4 5/16' E PULLEY ELBOW <P/N 423250) �Itl DPDT AP ACTION SWITCH 114 r (P/N 423879) TO GAS VALVE. ------"- 37 5/8' DETECTION, GAS VALVE, AND REMOTE PULL STATION DETAIL 1 & 2 GRILL HOOD N. T. S. AGENT PIPING DETAIL 3/61su S.r�.;,C,LS'J N. T. S. / Df 1 1 SEP 10 2008 Tukv,fila Fire McDONALD'S PROJECT UH 2002/R102 W/CHASE p030\uo 30\u-oC,rtoSE Pc,R. S/S ^- R-102 FIRE SUPPRESSION SYSTEM SINGLE TANK 18' UTILITY CHASE- FRANKE GRILL STATIONS GAS OR ELECTRIC McDONALD'S CORP. OAK BROOK, IL. DA RENSION DA ANSUL, NARINEIlEE AR 5sE a3 3513 114, DRAWING AND INC DMA. TARRO-MFAEU-ARE--n1EOROPERLV-DE90{WE• - PROTECTION A SMALL NOT BE USED. RE911000CED 61 RS ANERRED, ME PRIM EKPRESS CONSENT OF INC =WAN, NOR SNALL ANT DATA OR INFORMATCN CONTANCD HERON BC USD IN DMWZADO1 D["COOMPANY. MANNER SS TENT W. INC FINOR EXPRESS TTEN AO DA 6/12/03 SC 1. 5' =1' -0' OWN. GI•1ND. AA8 JP DRAVANG MUNBER R02-536-110 1 of 1 REV. 2fr • 2' 8 13, 4 2' 81' 8' 1' 93' TOP ELEVATION ABOVE GRIDDLE / SURFACE AIMED TIT SURFACE __--./ _- Cu L / AIMING DETAIL 1 1 j __ r. _. _..-7 c 1._.._.._._�.._._�_.___.._..I --., 1.___.._._� I T�1 4 (D 1'-1 3/8" 1•-1 3/8". 3 1/2" TO OUTSIDE • OF HCO 1 TO REGULATED RELEASE IN CHASE (79493) 5 3/16" 1'-2 7/8". DETECTION ISOMETRIC N.T.S. 3" TO OUTSIDE OF HOOD 1 6 3/8"� 32 1/2' TO 3 GAL. TANK IN CHASE (429862) 2 5/8" 5 1/8" 4 1/16" IF GRILL DIVIDER IS USED, REFER TO NOTE #11 AND AIMING DETAIL ON THIS SHEET. FRONT ELEVATION 32 1/2" 7 5/8" 8 7/8"J ,/-9 7/16., 2 /2" 5 1/8" 3 5/8"-11 4 1/16" 7 5/8 9 7/16" 8 7/8" 3 5/8p 5 10'-20' ABOVE GRIDDLE SURFACE AIMED TO CENTER RIGHT END PIPING ISOMETRIC N.T.S. HOOD PENETRATION -DETAIL McDONALD'S PROJECT UH 2002/R-102 ELEC. GAS BILL OF MATERIALS ITEM 0TY OTY PART No. DESCRIPTION 79493 OEM REG. RELEASE/BRACKET ASSEMBLY 2 429862 3.0 GAL. TANK 3 79372 3.0 GAL. ANSULEX Low pH 4 419337 2W NOZZLE 5 2 2 419343 2120 NOZZLE 6 419335 18 NOZZLE 7 17492/423441 101-20 CARTRIDGE a 417369 TERMINAL DETECTOR PACKAGE 9 3 3 417369 SERIES DETECTOR PACKAGE 10 3 3 415742 FUSIBLE LINK, TYPE K 360' F (GRILL AND DUCT) 11 4 4 423250 PULLEY ELBOW ASSEMBLY (FOR 1/2' EMT) 12 54011 REMOTE PULL STATION ASSEMBLY 13 423879 SNAP ACTION SWITCH - DPDT 14 55601 1' ANSUL MECHANICAL GAS VALVE 15 427929 PULLEY TEE 16 2 2 79007 HOSE ACTUATION NOTE' THE FIRST NUMBER IN ANY NOZZLE DESIGNATION INDICATES THE FLOW NUMBER OF THE NOZZLE. OPTIONAL REMOTE PULL STATION NOTES: THE FOLLOWING SPECIFICATIONS ARE FOR ADDITIONAL REMOTE PULL STATIONS WHERE CODES APPLY: 1. WHEN PROVIDING INSTALLATION MATERIAL FOR EXTRA REMOTE PULL STATIONS, USE ONLY 1/2" EMT CONDUIT, COMPRESSION FITTINGS AND P/N 423250 PULLEY ELBOWS. 2. ALL EXISTING PULL STATIONS WILL REMAIN INSTALLED AND CONNECTED ON CHASE. 3. RIGIDLY FASTEN ALL CONDUIT. WHEN BRACKETING IN THE ATTIC SPACE, REGARD FUTURE SERVICE (BY OTHER TRADES) REQUIREMENTS. TAKE PRECAUTIONS THAT PREVENT IHE CONDUIT FROM BEING SUBJECT TO DAMAGE. 4. ROUTE CONDUIT AS DIRECTLY AS POSSIBLE FROM THE OPTIONAL REMOTE PULL STATION TO THE LOCATION (IN CHASEWAY) NOTED ON DRAWING R02-536-110 FOR EACH STATION. 5. CONDUIT IS TO BE ROUTED THROUGH THE EOUIPMENT TO THE AUTOMAN PER THE DETAILS ON THIS SHEET AND DRAWING R02-536-110. GENERAL NOTES: 1. THIS INSTALLATION IS TO BE MADE IN ACCORDANCE WITH THE R-102, UL300 INSTALLATION MANUAL AND IN ACCORDANCE WITH ALL STATE AND LOCAL CODES. 2. ALL PIPE LENGTHS TO BE FIELD VERIFIED. 3. THESE DRAWINGS MAY BE USED TO SECURE APPROVAL FROM THE AUTHORITY HAVING JURISDICTION. 4. IT IS NECESSARY THAT ALL PIPE FITTINGS AND NOZZLES BE WRENCH TIGHTENED AND SECURELY SUPPORTED AND THAT ALL NOZZLES ARE PROPERLY AIMED AS INDICATED IN THE R-102 INSTALLATION MANUAL. 5. THE WIRE ROPE FOR THE DETECTOR AND REMOTE PULL STATION AND MECHANICAL GAS VALVE IS TO BE INSTALLED BY AN AUTHORIZED AND FACTORY TRAINED DISTRIBUTOR OR SERVICE REPRESENTATIVE. 6. THIS INSTALLATION IS TO BE INSPECTED, PUT INTO OPERATION AND CERTIFIED BY AN AUTHORIZED AND FACTORY TRAINED DISTRIBUTOR OR SERVICE REPRESENTATIVE. 7. ELECTRICAL CONTACTS AND WIRING FOR APPLIANCE SHUT OFF TO BE PROVIDED BY THE ELECTRICAL CONTRACTOR. PIPING AND CONDUIT H000 PENETRATIONS TO BE WELDED 8. 9. THIS DRAWING IS FOR USE WITH A RIGHT HANDED CHASE. FOR LEFT HANDED CHASE USE A MIRRORED IMAGE OF THIS DRAWING. 10. DIMENSIONS MAY VARY FROM SHOWN ±1 INCH 11 IF A GRILL DIVIDER IS UTILIZED, PROTECTION WITH AN ADDITIONAL 2120 NOZZLE WILL BE NEEDED. THE ADDTIONAL 2120 NOZZLE I5 TO BE INSTALLED ABOVE THE OTHER SIDE OF THE GRILL. PIPING NOTES: 1. PIPE SHALL BE 3/8" SCHEDULE 40 BLACK IRON, CHROME PLATED OR STAINLESS STEEL 2. PIPE ENDS SHALL BE REAMED AND BLOWN CLEAR OF CHIPS AND SCALE BEFORE ASSEMBLY. INSIDE OF PIPE AND FITTINGS MUST BE FREE OF OIL AND DIRT. 3. PIPING DIMENSIONS GIVEN ARE FROM CENTER TO CENTER OF FITTINGS. 4. FINAL NOZZLE LOCATION MAY NOT VARY FROM LOCATION SHOWN. 5. ADD UNIONS AS NEEDED. 2`. 6. ANSUL AUTOMAN /TANK LOCATED IN CHASE. 7. ALL PIPE CONNECTIONS MUST USE TEFLON TAPE ON THE MALE THREADS ONLY. MAKE CERTAIN TAPE DOES NOT COVER LAST THREAD ON PIPE END. 8. MAKE CERTAIN THAT THERE IS A MINIMUM OF 6' (SIX FEET) OF PIPE BETWEEN THE AGENT TANK AND ANY NOZZLE PROTECTING A FRYER. CONDUIT NOTES: 1. CONDUIT RUNS ARE DIMENSIONED CENTER TO CENTER OF CONDUIT, EXCEPT: A TO FACE(S) OF DETECTOR BRACKET(S). B TO TOP SURFACE OF AUTOMAN. C TO BACK OF MANUAL PULL PAN D TO SURFACE OF GAS VALVE BOX 2. O SHOWS LOCATION FOR PULLEY COVER SCREWS 2 SHOWS BACKSIDE OF PULLEY ELBOW 3. QUANTITY FOR DETECTION LINE IN H000 ONLY. THIS DESIGN IS IN COMP! IANCE WITH UL 300. NFPA 96 2, NFPA 17A S`IS 1L' Citic-: • NO -1A3 CiPbOI;. R-102 FIRE SUPPRESSION SYSTEM 2 GRILLS 75' UH 2002 HOOD GAS OR ELECTRIC - FRANKE McDONALD'S CORPORATION OAK BROOK IL. JMP 10/05 JMP DIRECTED 191 NUMBER OF FUSIBLE IRIRL USED 10/05 JMP RE V. NO. NY DATE CHKD APPD. DATE AIM SUL a MAWNEIW. W 91E13.2542 DRS DRAY.. AND THE DATA CONTAw(0 HERON ARE DIE PROMPT* Or ANNA nRE RODUCED OR PRIOIDTECTION AND SHALL NOT BE MA R CONES& CONSOTT 0 ME CWP NT. NOR SMALL /NT DATA E*0 a (00551 CONTAINED ABE USED MI A NANNER INCW4siENT OTH THE PRIOR DORM .1iEx DON aT THE COMPANY. DATE 6/12/03 SCALE AAB JP o. DRAVANG NUMBER R02-533-111 1 OF 1 REV. 1 38' 9 ' 33" TO OUTSIDE OF HOO i� TO CHASE REGULATED D493)LEASE 5 3/16' 31' 3' 5 5/8' .5..3/_4'___ DETECTION ISOMETRIC 2'-9' 5 5/8' N.T.S. ELEC. GAS BILL OF MATERIALS ITEM QTY OTY PART No. DESCRIPTION 1 ..73493 OEM REG. RELEASE/BRACKET ASSEMBLY 2 429862 3.0 GAL. TANK 3 79372 3.0 GAL. ANSULEX Low pH 4 1 419337 2W NOZZLE 5 3 3 419340 245 NOZZLE 6 419335 1N NOZZLE * *** * ** 7 174927423441 101-20 CARTRIDGE 417368 TERMINAL DETECTOR PACKAGE 9 2 2 .. 41763.9 SERIES DETECTOR PACKAGE 10 3 415739 FUSIBLE LINK, TYPE K 165'F 3 415741 FUSIBLE LINK, TYPE K 2801 (HIGH EFFICIENCY ( 100K BTU) 3 417743 FUSIBLE LINK, TYPE K 4501- CLOW EFFICIENCY > IDOK BTU) 11 2 2 423250 PULLEY ELBOW ASSEMBLY 032 1/2' EMT) 12 1 54011 REMOTE PULL STATION ASSEMBLY 13 423879 SNAP ACTION SWITCH - DPDT 14 55601 I' ANSUL MECHANICL GAS VALVE 3"•TO OUTSIDE OF HOOD TO 3 GAL. TANK IN CHASE (429862). PLAN VIEW • POSITION NOZZLE TIP ANYWHERE ALONG OR WITHIN THE PERIMETER OF THE FRYPOT AIMING AT CENTER. 245 NOZZLE POSITIONING • DETAIL (FRYER) Q Q FRONT ELEVATION PIPING ISOMETRIC N.T.S. * 15 427929 PULLEY TEE 16 2 2 79007 H0SE ACTUATION - -2' 20'-27' ABOVE TOP OF FRYER AIMED TO INTER NOTE: THE FIRST NUMBER IN ANY NOZZLE DESIGNATION INDICATES THE FLOW NUMBER OF THE NOZZLE. OPTIONAL REMOTE PULL STATION NOTES: THE FOLLOWING SPECIFICATIONS ARE FOR ADDITIONAL REMOTE PULL STATIONS WHERE CODES APPLY: 1. WHEN PROVIDING INSTALLATION MATERIAL FOR EXTRA REMOTE PULL STATIONS, USE ONLY 1/2' EMT CONDUIT, COMPRESSION FITTINGS AND P/N 423250 PULLEY ELBOWS. 2. ALL EXISTING PULL STATIONS WILL REMAIN INSTALLED AND CONNECTED ON CHASE. 3. RIGIDLY FASTEN ALL CONDUIT. WHEN BRACKETING. IN THE ATTIC SPACE. REGARD FUTURE SERVICE (BY OTHER TRADES) REQUIREMENTS. TAKE PRECAUTIONS THAT PREVENT THE CONDUIT FROM BEING SUBJECT TO DAMAGE. 4. ROUTE CONDUIT AS DIRECTLY AS POSSIBLE FROM THE OPTIONAL REMOTE PULL STATION TO THE LOCATION (IN CHASEWAY) NOTED ON DRAWING R02-536-110 FOR EACH STATION. 5. CONDUIT IS TO 8E ROUTED THROUGH THE EQUIPMENT TO THE AUTOMAN PER THE DETAILS ON THIS SHEET AND DRAWINGS R02-536-110. GFNERAL NOTES: 1. THIS INSTALLATION IS TO BE MADE IN ACCORDANCE WITH THE R-102, UL300 INSTALLATION MANUAL AND IN ACCORDANCE WITH ALL STATE AND LOCAL CODES. 2. ALL PIPE LENGTHS TO BE FIELD VERIFIED. 3. THESE DRAWINGS MAY BE USED TO SECURE APPROVAL FROM THE AUTHORITY HAVING JURISDICTION. 4. IT IS NECESSARY THAT ALL PIPE FITTINGS AND NOZZLES 8E WRENCH TIGHTENED AND SECURELY SUPPORTED AND THAT ALL NOZZLES ARE PROPERLY AIMED AS INDICATED IN THE R-102 INSTALLATION MANUAL 5. THE WIRE ROPE FOR THE DETECTOR AND REMOTE PULL STATION AND MECHANICAL GAS VALVE IS TO BE INSTALLED BY AN AUTHORIZED AND FACTORY TRAINED DISTRIBUTOR OR SERVICE REPRESENTATIVE. 6. THIS INSTALLATION IS TO BE INSPECTED, PUT INTO OPERATION AND CERTIFIED 8Y AN AUTHORIZED AND FACTORY TRAINED DISTRIBUTOR OR SERVICE REPRESENTATIVE. 7. ELECTRICAL CONTACTS AND WIRING FOR APPLIANCE SHUT OFF TO BE PROVIDED BY THE ELECTRICAL CONTRACTOR. 8. PIPING AND CONDUIT HOOD PENETRATIONS TO 8E WELDED * 9. 165 DEG. F. FUSIBLE LINK TO BE USED WITH ELECTRIC FRYERS ONLY. * 10. 280. DEG. F. FUSIBLE LINKS TO BE USED ON ALL HIGH EFFICIENCY GAS FRYERS OF 100,000 BTU OR LESS. PER FULL VAT. * 11. 450 DEG. F. FUSIBLE LINKS TO 8E USED ON ALL LOW EFFICIENCY GAS FRYERS OF OVER 100,000 BTU PER FULL VAT. 12. THIS DRAWING IS FOR USE WITH A RIGHT HANDED CHASE FOR LEFT HANDED CHASE USE A MIRRORED IMAGE OF THIS DRAWING. 13. DIMENSIONS MAY VARY FROM SHOWN ±1 INCH PIPING NOTES: 1. PIPE SHALL BE 3/8' SCHEDULE 40 BLACK IRON, CHROME PLATED OR .STAINLESS STEEL 2. PIPE- -ENDS.. SHALL- BE -REAMED AND BLOWNCLEAROF CHIPS AND SCALE BEFORE ASSEMBLY. INSIDE OF PIPE AND FITTINGS MUST BE FREE OF OIL AND DIRT. 3. PIPING DIMENSIONS GIVEN ARE FROM CENTER TO CENTER OF FITTINGS. 4. . FINAL NOZZLE LOCATION MAY NOT VARY FROM LOCATION SHOWN. 5. ADD UNIONS AS NEEDED. * * 6. ANSUL AUTOMAN / TANK LOCATED IN CHASE. ALL PIPE CONNECTIONS MUST USE TEFLON TAPE ON THE MALE THREADS ONLY. .MAKE CERTAIN TAPE DOES NOT COVER LAST THREAD ON PIPE END. HOOD PENETRATION DETAIL RIGHT END McDONALD'S PROJECT UH 2002/R-102 8. MAKE CERTAIN THAT THERE IS A MINIMUM OF 6' (SIX FEET) OF PIPE BETWEEN THE AGENT TANK AND ANY NOZZLE PROTECTING A FRYER. CONDUIT NOTES. 1:- .CONDUIT RUNS ARE DIMENSIONEDCENTERTO CENTER OF CONDUIT, EXCEPT: A): TO FACE(S) OF DETECTOR BRACKET(S). - - 9)) T0 -TOP -SURFACE OF AUTOMAN. - C 7O BACK OF. MANUAL PULL PAN 0) TO SURFACE OF GAS VALVE BOX 2. O. SHOWS LOCATION FOR PULLEY COVER SCREWS O SHOWS BACKSIDE OF PULLEY ELBOW 3. ..QUANTITY FOR DETECTION LINE IN HOOD ONLY. -THdS DTGN-`COMPLIANCE WITH 'UL 300. NEPA 96 8 NEPA 17A R-102 FIRE SUPPRESSION SYSTEM 3 VAT FRY STATION R.H. 50' UH 2002 HOOD GAS OR ELECTRIC - FRANKE McDONALD'S CORPORATION OAK -BROOK -IL. O. BY DATE CHKO. REVISION PPP" OATS ANSUL M*9INE11EE WI 54743.2542 INS QUMHG ANO ME OATH. COMPINED ROOM ARE THE1 r)OPmTT Of.ANSI 1IC N PP OIECIION AID MALL INT BE USED.*EPRO.= OR NANSPERRCO. IRTNOR INE PRIOR OO#ESS C1.45LMT.6 THE CO PAHY. NON SHALL AMY OATH *4 TWO. H OEINEDJ TOTEM E,4 O M A INNERNIWt951EHT PAN THE PRIOR CORES *UTHONSATIM CP THE CO PAHY. - DA 6/12/03 SCALE 1'=12' AAB MOTO. JP 1APP*. HAWING NUMBER R02-519-110 1 OF 1 0 IF GRILL DIVIDER IS USED REFER TO NOTE ##11 AND AIMING DETAIL ON THIS SHEET N PLAN VIEW 10'-20' ABOVE GRIDDLE SURFACE AIMED TO C NTER AIMING DETAIL [ 6' 3Y2" TO OUTSIDE OF HOG TO REGULATED RELEASE IN CHASE (79493) Qr 1' 116' 32' - --10" 10'-20' ABOVE GRIDDLE SURFACE AIMED TO C LATER I CP J n (1 14, FRONT ELEVATION RIGHT END 1'- 256" DETECTION ISOMETRIC N.T.S. 3" TO OUTSIDE OF HOOD • TO 3 GAL. CHASE (429862) IK N PIPING ISOMETRIC N.T.S. HOOD PENETRATION DETAIL V cDONALD'S PROJECT UH 2002/R-102 ** * ** ** ** ITEM ELEC. GAS QTY OTY PART No. BILL OF MATERIALS DESCRIPTION 79493 OEM REG. RELEASE/BRACKET ASSEMBLY 2 429862 3.0 GAL. TANK 3 79372 3.0 GAL. ANSULEX Low pH 4 419337 2W NOZZLE 5 419343 2120 NOZZLE 419335 IN NOZZLE 7 17492/423441 101-20 CARTRIDGE 417368 TERMINAL DETECTOR PACKAGE 9 415742 FUSIBLE LINK, TYPE K 360' F 10 2 2 423250 PULLEY ELBOW ASSEMBLY (FOR 1/2' EMT) 11 54011 REMOTE PULL STATION ASSEMBLY 02 423879 SNAP ACTION SWITCH - DPDT 13 55601 1' ANSUL MECHANICAL GAS VALVE 14 427929 PULLEY TEE 15 2 79007 HOSE ACTUATION NOT : THE FIRST NUMBER N ANY NOZZLE DESIGNATION INDICATES THE FLOW NUMBER OF THE NOZZLE. OPTIONAL REMOTE PUI I STATION NOTES: THE FOLLOWING SPECIFICATIONS ARE FOR ADDITIONAL REMOTE PULL STATIONS WHERE CODES APPLY: 1. WHEN PROVIDING INSTALLATION MATERIAL FOR EXTRA REMOTE PULL STATIONS, USE ONLY 1/2" EMT CONDUIT, COMPRESSION FITTINGS AND P/N 423250 PULLEY ELBOWS. 2. ALL EXISTING PULL STATIONS WILL REMAIN INSTALLED AND CONNECTED ON CHASE. 3. RIGIDLY FASTEN ALL CONDUIT. WHEN BRACKETING IN THE ATTIC SPACE, REGARD FUTURE SERVICE (BY OTHER TRADES) REQUIREMENTS. TAKE PRECAUTIONS THAT PREVENT THE CONDUIT FROM BEING SUBJECT TO DAMAGE. 4. ROUTE CONDUIT AS DIRECTLY AS POSSIBLE FROM THE OPTIONAL REMOTE PULL STATION TO THE LOCATION (IN CHASEWAY) NOTED ON DRAWING R02-536-110 FOR EACH STATION. 5. CONDUIT IS TO BE ROUTED THROUGH THE EQUIPMENT TO THE AUTOMAN PER THE DETAILS ON THIS SHEET AND DRAWINGS R02-536-110. GENFRAL NOTES: 1. THIS INSTALLATION IS TO BE MADE IN ACCORDANCE WITH THE R-102, UL300 INSTALLATION MANUAL AND IN ACCORDANCE WITH ALL STATE AND LOCAL CODES. 2. ALL PIPE LENGTHS TO BE FIELD VERIFIED. 3. THESE DRAWINGS MAY BE USED TO SECURE APPROVAL FROM THE AUTHORITY HAVING JURISDICTION. 4. IT IS NECESSARY THAT ALL PIPE FITTINGS AND NOZZLES BE WRENCH TIGHTENED AND SECURELY SUPPORTED AND THAT ALL NOZZLES ARE PROPERLY AIMED AS INDICATED IN THE R-102 INSTALLATION MANUAL. 5. THE WIRE ROPE FOR THE DETECTOR AND REMOTE PULL STATION AND MECHANICAL GAS VALVE IS TO BE INSTALLED BY AN AUTHORIZED AND FACTORY TRAINED DISTRIBUTOR OR SERVICE REPRESENTATIVE. 6. THIS INSTALLATION IS TO BE INSPECTED, PUT INTO OPERATION AND CERTIFIED BY AN AUTHORIZED AND FACTORY TRAINED DISTRIBUTOR OR SERVICE REPRESENTATIVE. 7. ELECTRICAL CONTACTS AND WIRING FOR APPLIANCE SHUT OFF TO BE PROVIDED BY THE ELECTRICAL CONTRACTOR. PIPING AND CONDUIT HOOD PENETRATIONS TO BE WELDED 8. 9. THIS DRAWING IS FOR USE WITH A RIGHT HANDED CHASE. FOR LEFT HANDED CHASE USE A MIRRORED IMAGE OF THIS DRAWING. 10. DIMENSIONS MAY VARY FROM SHOWN ±1 INCH 11. IF A GRILL DIVIDER IS UTILIZED, PROTECTION WITH AN ADDITIONAL 2120 NOZZLE WILL BE NEEDED. THE ADDTIONAL 2120 NOZZLE IS TO BE INSTALLED ABOVE THE OTHER SIDE OF THE GRILL. PIPING NOTES: 1. PIPE SHALL BE 3/8" SCHEDULE 40 BLACK IRON, CHROME PLATED OR STAINLESS STEEL 2. PIPE ENDS SHALL BE REAMED AND BLOWN CLEAR OF CHIPS AND SCALE BEFORE ASSEMBLY. INSIDE OF PIPE AND FITTINGS MUST BE FREE OF OIL AND DIRT. 3. PIPING DIMENSIONS GIVEN ARE FROM CENTER TO CENTER OF FITTINGS. 4. FINAL NOZZLE LOCATION MAY NOT VARY FROM LOCATION SHOWN. 5. ADD UNIONS AS NEEDED. * * 6. ANSUL AUTOMAN / TANK LOCATED IN CHASE. 7. ALL PIPE CONNECTIONS MUST USE TEFLON TAPE ON THE MALE THREADS ONLY. MAKE CERTAIN TAPE DOES NOT COVER LAST THREAD ON PIPE END. 8. MAKE CERTAIN THAT THERE IS A MINIMUM OF 6' (SIX FEET) OF PIPE BETWEEN THE AGENT TANK AND ANY NOZZLE PROTECTING A FRYER. CONDUIT NOTES' 1. CONDUIT RUNS ARE DIMENSIONED CENTER TO CENTER OF CONDUIT, EXCEPT: A) TO FACE(S) OF DETECTOR BRACKET(S). B TO TOP SURFACE OF AUTOMAN. C TO BACK OF MANUAL PULL PAN D TO SURFACE OF GAS VALVE BOX 2. O SHOWS LOCATION FOR PULLEY COVER SCREWS O SHOWS BACKSIDE OF PULLEY ELBOW * * * 3. QUANTITY FOR DETECTION LINE IN HOOD ONLY. THIS DESIGN IS IN COMPLIANCE WITH UL 300, NFPA 96 & NFPA I7A SNiSZ'w` Oa - R -102 FIRE SUPPRESSION SYSTEM 1 -GRILL STATION R.H. 43.5' UH 2002 HOOD GAS OR ELECTRIC - FRANKE McDONALD'S CORPORATION OAK BROOK IL. REV. BY DATE CHKO REVISION APP° DATE ANSUL. XIARINETTEE N 54113-2512 THIS DRAWN° AND THE DATA CONTAJNED HEREIN ARE THE PROPERTY OF ANSI., ORE PROTECTION AND SHALL NOT BC USED, REPRODUCED OR TRANSFERRED. THE PRIOR EXPRESS CONSENT OF THE C.TAINAUTHORIZATION HEREIN BE USED OE IN COURANT. INCONSISTENT WM THE PRIOR EXPRESS R DATE 6/12/03 SCALE AAB CHILD. JP ORAVANG NUMEIER R02-517-110 1 OF I ACCEPTED Without Comments As Noted In Red Per The Attached Letter nec .x73{, have h,?eci ' L i 'd by The Tukwila Fire r,.,{ u r,..,: . > With current city r- , errors and L,ations of adopted • .,r,tornf:sbility for the ad , :Y:,, ; •„ . the designer. `, d,r^i tit:::. : drawings atter 1 this d;.i!'P 41.i! Y? ... ,_ require a resubmittal of r Ji.6e0 Orawir,s for suosequent approval. Final acceptance is subject to field test and inspection IA The Tukwila Fire Prevention Bureau. A'Date: I - �� -C3 By: ruKW1LA FIRE DEPARTMY4lfsl, Please call: 575-4402 and give this job No. n V ->- and exact address for shut. 1.s' it or rstst.)ration aporoval: IMPORTANT NOTICE Because of increased demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4407 to schedule your inspections a minimum of 48 hours in advance of the date you want an inspection. FILE COPY 4 PCV PROJECT COVER SHEET CIVIL DRAWINGS C1 OF 6 COVER SHEET C2 OF 6 T.E.S.C. PLAN NOTES AND DETAILS C3 OF 6 T.E.S.C. NOTES C4 OF 6 GRADING AND STORM DRAINAGE PLAN C5 OF 6 STORM AND PAVEMENT NOTES AND DETAILS C6 OF 6 LAYOUT AND DIMENSIONING PLAN SD1 OF 7 SITE DETAILS SD2 OF 7 SITE DETAILS SD3 OF 7 SITE DETAIL S SD4 OF 7 MENU BOARD AND DRIVE THRU CANOPY DETAILS 5D5 OF 7 DRIVE 11 -IRU CANOPY DETAILS SD6 OF 7 GATEWAY DETAILS SD7 OF 7 TRASH YARD DETAILS SW1 OF 1 SEWER AND WATER PLANS SL1 OF 1 SITE LIGHTING PLAN LANDSCAPE PLANS L1.1 OF 2 LANDSCAPE CONSTRUCTION PLANS COVER SHEET L2.1 OF 2 LAYOUT/PLANTING PLAN AND DETAILS SITE PLAN SP1 OF 1 ARCHITECTURAL SITE PLAN ARCHITECURAL/BUILDING CV COVER SHEET DRIVE THRU DT1.0 DRIVE -11 -IRU PLANS & DETAILS ARCHITECTURAL A1.0 PARTIAL FLOOR PLAN A1.1 PARTIAL FLOOR PLAN A1.2 REFLECTED CEILING PLAN A1.3 ROOF PLAN A2.0 ELEVATIONS A2.1 ELEVATIONS A3.0 PLAYPLACE SECTIONS & DETAILS A3.1 PLAYPLACE SECTIONS & DETAILS A4.0 ENLARGED RESTROOM PLAN & DETAILS A4.1 ENLARGED PLAN DETAILS A5.0 WALL SECTIONS & DETAILS A5.1 WALL SECTIONS & DETAILS A5.3 WALL SECTIONS & DETAILS A5.3 WALL SECTIONS & DETAILS A6.0 DOOR, HARDWARE & FINISH SCHEDULES STRUCTURAL S1.0 PARTIAL FOUNDATION PLAN S1.1 PARTIAL FOUNDATION PLAN S2.0 PARTIAL ROOF FRAMING PLAN S2.1 PARTIAL ROOF FRAMING PLAN S3.0 SECTIONS AND DETAILS S3.1 SECTIONS AND DETAILS S3.2 SECTIONS AND DETAILS S3.3 SECTIONS AND DETAILS S3.4 SECTIONS AND DETAILS S4.0 SHEAR WALL SCHEDULE & GENERAL NOTES MECHANICAL M0.0 GENERAL NOTES M..O MECH/ELEC. ROOF PLAN M2.0 MECHANICAL PLAN M3.1 DETAILS & SCHEDULES M4.0 3 -VAT (UH -50) HOOD ASSEMBLY M4.1 GRILL (UH -83) HOOD ASSEMBLY M4.2 GRILL (UH -43) HOOD ASSEMBLY PLUMBING PO.O P1.1 P1.2 P1.4 P2.0 P3.0 P3.1 P3.2 GENERAL NOTES WATER PIPING PLAN WASTE & STORM PLAN GAS PIPING PLAN ROUGH -IN PLUMBING PLAN & SCHEDULES DOMESTIC SUPPLY ISOMETRIC DIAGRAMS WASTE & VENT ISOMETRIC DIAGRAMS FIXTURE SCHEDULE & DETAILS ELECTRICAL E1.0 POS ELECTRICAL RISER DIAGRAM E1.1 PARTIAL ROUGH IN FLOOR PLAN E2.1 PARTIAL LIGHTING PLAN & SCHEDULE E3.0 ELECTRICAL SCHEDULE E3.1 ELECTRICAL & LIGHTING NOTES E4.0 WIRING DETAILS E4.1 LIGHTING CONTROLS E4.2 ELECTRICAL UTILITIES CALC'S & DIAGRAMS KITCHEN EQUIPMENT K1.0 KITCHEN COVER SHEET K2.0 KITCHEN EQUIPMENT PLAN K2.1 KITCHEN EQUIPMENT SCHEDULE SW tii SECTION 22, TOWNSHIP 23 N9 RANGE 4 E W.M. IP I® SUR' .Y 0 PARCEL A: THAT PORTION OF LOT 4 IN BLOCK 2 OF THIRD ADDITION TO ADAMS HOME TRACTS, ACCORDING TO PLAT RECORDED IN VOLUME 15 OF PLATS AT PAGE 17, IN KING COUNTY, WASHINGTON, LYING EAST OF STATE ROAD NO. 1. PARCEL B: LOT A OF KING COUNTY SHORT PLAT NO. 377015, RECORDED JULY 18, 1977 UNDER RECORDING NO. 7707180912, IN KING COUNTY, WASHINGTON. r'� n r, i-. r ! r, n rl=ARCEL D I EASEMENTS FOR PARKING AND ACCESS AS ESTABLISHED BY DEEDS RECORDED MARCH 6, 1962 AND JULY 18, 1977 UNDER RECORDING NUMBERS 5395322 AND 7707180912. PARCEL C: THAT PORTION OF LOT 3 IN BLOCK 2 OF 3RD ADDITION TO ADAMS HOME TRACTS, AS PER PLAT RECORDED IN VOLUME 15 OF PLATS, PAGE 17 IN KING COUNTY, WASHINGTON, LYING EAST OF STATE. ROAD NO. 1, AS CONVEYED BY DEED RECORDED UNDER RECORDING NO. 2004575. LEGAL DESCRIPTION AND TITLE INFORMATION IS DERIVED FROM FIRST AMERICAN TITLE INSURANCE CO. REPORT NO. NCS-264466-WA1, DATED NOVEMBER 1, 2006. 1. SLOPE EASEMENT RECORDED UNDER REC. NO. 2593707 HAS BEEN PLOTTED. 2. ELECTRIC TRANSMISSION AND DISTRIBUTION LINE EASEMENT RECORDED UNDER REC. NO. 3610199 DOES NOT CONTAIN A LEGAL DESCRIPTION SUFFICIENT TO DETERMINE ITS EXACT LOCATION AND THEREFORE CANNOT BE PLOTTED. 3. EASEMENT AGREEMENT RECORDED UNDER REC. NO. 5395321 HAS BEEN PLOTTED. 5. ELECTRIC TRANSMISSION AND/OR DISTRIBUTION EASEMENT RECORDED UNDER REC. NO. 5497120 HAS BEEN PLOTTED. 6. EASEMENT RECORDED UNDER REC. NO. 5533740 HAS BEEN PLOTTED. 8. EASEMENT RECORDED UNDER REC. NO. 7707180912 HAS BEEN PLOTTED. 9. REFERENCE SURVEY RECORDED UNDER REC. NO. 8304079007. SEE THE FULL DOCUMENT FOR ALL OF THE DETAILS. 10. REFERENCE ORDINANCE NO. 3506 RECORDED UNDER REC. NO. 20040603002498. SEE THE FULL DOCUMENT FOR ALL OF THE DETAILS. CONTACT/OWNER/APPLICANT McDONALD'S CORPORATION (PRIMARY CONTACT) 12131 113TH AVE NE, SUITE 103 KIRKLAND, WA 98034 CONTACT: DOUG BATES PHONE: (425) 242-2411 FAX: (425) 242-2498 EMAIL: DOIIG.BATESGUS.MCD.COM ENGINEER D. R. STRONG CONSULTING ENGINEERS 10604 NE 33TH PLACE #101 KIRKLAND, WA '38033 CONTACT: MCI ARD D. OLSON, P.E. PHONE: (425) 827-3063 FAX: (425) 827-2423 EMAIL: RICK.OLSON@DRSTRONG.COM LANDSCAPE ARCHITECT D. R. STRONG CONSULTING ENGINEERS 10604 NE 38TH PLACE #101 KIRKLAND, WA 98033 CONTACT: TRAVIS W. PRICE, ASLA PHONE: (425) 827-3063 FAX: (425) 827-2423 EMAIL: TRAVIS.PRICE@DRSTRONG.COM ARCHITECT McDONALD'S COROPORATION 10604 NE 381H PLACE #101 KIRKLAND, WA 38033 CONTACT: CHRISTOPHER 1<. DOERSCHLAG STRUCTURAL McDONALD'S COROPORATION 10604 NE 38TH PLACE #101 KIRKLAND, WA 98033 CONTACT: WILLIAM EPPS/PAUL PENSY PHONE: (630) 623-3441 FAX: (630) 623-7786 EMAIL: PAUL.PENSY@US.MCD.COM MECHANICAL/PLUMBING McDONALD'S COROPORATION 2111 McDONALD'S DRIVE OAKBROOK, IL 60523 CONTACT: JASON GREENBERG PHONE: (630) 623-5767 FAX: (425) 623-7786 EMAIL: JASON.GREENBERG@US.MCD.COM ELECTRICAL McDONALD'S COROPORATION 2111 McDONALD'S DRIVE OAKBROOK, IL 60523 CONTACT: MICHAEL SLIKAS GEOTECHNICAL RILEY GROUP, INC. 17522 BOTHELL WAY NE BOTHELL, WA 98011 CONTACT: CHIEN-LIN (JOHNNY) CHEN, P.E. PHONE: (425) 415-0551 FAX: (425) 415-0311 R • PER TUKWILA MUNICIPAL CODE, A MINIMUM OF 1 PARKING SPACE IS REQUIRED PER 50 SQUARE FEET OF USABLE BUILDING AREA PLUS 50 PERCENT OF OUTDOOR SEATING AREA. USABLE BUILDING AREA: 2,987 SF REQUIRED: 2,987 SF / 50 SF = 60 STALLS PROVIDED: 63 STALLS BUILDING ISI-ORIIATION• OCCUPANCY USE GROUP A2 CONSTRUCTION TYPE GROSS BUILDING AREA: BASE BUILDING PLAYPLACE TOTAL BUILDING CODE EDITION: MECHANICAL CODE EDITION: ELECTRICAL CODE EDITION: PLUMBING CODE EDITION: ADDITIONAL CODE EDITION: VB 4,024 SF 1,459 SF 5,483 SF INTERNATIONAL BUILDING CODE 2006 INTERNATIONAL MECHANICAL CODE 2006 NATIONAL ELECTRICAL CODE 2005 UNIFORM PLUMBING CODE 2006 INTERNATIONAL FIRE CODE 2006 WASHINGTON STATE BUILDING CODE WASHINGTON STATE ENERGY CODE WASHINGTON STATE INDOOR AIR QUALITY CODE KING COUNTY HEALTH CODE ICC/ANSI A117.1 2006 WAC 51-53 (VIAL) & WAC 51-11 P ADDRESS J T I F 15210 PACIFIC HWY SOUTH TUKWILA, WA PARCEL NUMBERS 0043000096, 0043000090 & 004300080 WORK AREA: 77,145 SF (SITE) 4,270 SF (OFFSITE) EXISTING ZONING RC (REGIONAL COMMERCIAL) PROPOSED USE RC (REGIONAL COMMERCIAL) ADJACENT SITE USE LDR/RC (LOW DENSITY RESIDENTIAL REGIONAL COMMEP.C!AL) SEWER DISTRICT VALLEY VIEW SEWER DISTRICT WATER DISTRICT #125 FIRE DISTRICT TUKWILA FIRE DISTRICT SCHOOL DISTRICT TUKWILA SCHOOL DISTRICT #406 TELEPHONE SERVICE VERIZON POWER SOURCE PUGET SOUND ENERGY EXISTING IMPERVIOUS AREA 50,422 SF PROPOSED IMPERVIOUS AREA 50,662 SF THE PROJECT PROPOSES TO REDEVELOP AN EXISTING MCDONALD'S RESTAURANT LOCATED ON TAX PARCEL NUMBERS 0043000096, 0043000090, AND 0043000080 INTO A NEW MCDONALD'S RESTAURANT (SITE). THE PARCEL IS LOCATED AT 15210 PACIFIC HIGHWAY SOUTH, IN THE CITY OF TUKWILA, KING COUNTY, WASHINGTON. REDEVELOPMENT ACTIVITIES WILL INCLUDE UPGRADING THE EXISTING FRONTAGE ON SOUTH 152ND STREET TO MEET CURRENT CITY OF TUKWILA STANDARDS, AND COORDINATION OF IMPROVEMENTS TO INTERNATIONAL BOULEVARD WITH THE CITY OF SEA -TAC. SCALE: 1"=1000' ANU EaTHChei, Because of increased demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4407 to schedule your inspections a minium of 48 hours in advance of the d,;te you want an In K "ttO 6a n Without Comments As Noted In t:_ d Per Tile Attached Letter I I ne:F.hrNe .., by The Tukwila Fire tor ;" current city t _..rcrsand of adopted for the ;flet. drawings atter fequire a _.. Sequent approval. I Final acceptance i subject to field test and inspection b) The Tukwila Fire Prevention Bureau. Date: 7-( o b By: /(]7( -374-i.)4111 p.11 ) 4 -i-rz ►, o f col e)(14-5. 1-1s4rt l Y►t ech g h; c a( I o Gicofr deice o ►. - I( -� I ( q -C1 . _ 6(10 /6,1 c7 .4o K , cLddtisscs sh%I( colno1crc.4e cr,-4 C�►, e..( 5--I-fV'- . tt o(oci:cGt- 1 F,4 brraiea, TUKWILA FIRE DEPARTME Q Pease call: 575.4407, - and givee/ this job No. 0 and :xact address for shuts oowsvn or rest;'ration approval: DRAWINGS NOT APPROVED FOR CONSTRUCTION UNLESS STAMPED OR SIGNED APPROVED BY THE REVIEWING AGENCY CALL 48 HOURS BEFORE YOU DIG 1-800-424-5555 NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and -Detection Systems. Failure of test will result in a Re -inspection Fee and _ rminatjon of the testinc, SEP 1 0 2000 Tukwila Fire M:\07\052\plots\3\01-3PCV7052.dwg 4/29/2008 3: 46: 43 PM PDT COPYRIGHT © 2008, D.R. STRONG CONSULTING ENGINEERS INC. 1 01 1 I-- D ILI CO 0 < ° tY(,) 8 0 u CN 1" LESS US LLC 0 E- 5 (f) z w z CO C`Q co 0 D.R. STRONG CONSULTING ENGINEERS ENGINEERS PLANNERS SURVEYORS 10604 NE 38t11PLACE, SUITE 101 KIRKLAND, WA 98033 425.827.3063 OFFICE 800.962.1402 TOLL FREE 425.327 2423 FAX tivww.drstrong.ccm DRAFTED BY: MP DESIGNED BY: 'TYJP PROJECT ENGINEER: 9 OO DATE: O4. j0re PROJECT NO.: 07052 SHEET Pm/ OF 5'x7' LEVEL LANDING @ EXT. DOOR IN/ MAX. 2% SLOPE AWAY FROM BUILDING (TYP.) PROVIDE MIN. 5'x5' LEVEL LANDING @ ALL EXT. DOORS W/ MAX. 2% SLOPE AWAY FROM BUILDING. THE MAIN ENIKY DOOR LOCK MUST BE "READILY DISTINGUISHED AS LOCKED". 129'-8 1/2" FOUNDATION TO FOUNDATION HATGH LIRA PROVIDE MIN. 5'x5' LEVEL LANDING — @ ALL EXT. DOORS N/ MAX. 2% SLOPE AWAY FROM BUILDING (TYP.) 51-0" M.0 EXTERIOR NALL AS5 3.5" STUDS THIS 3'-4" 4'_ 4 1/2" G 0' ONL 3 \ A5) INCOMING WAIEF SERVICE METER AREA. IT L_ SUPPORT ICN W/ FACE Ii ONT GTR q" 7'-2 1/2" 15'-q" HOLD. 17'-11 1/2" HOLD DINING PLAYPLAG DINING 117 to 1 12'-3" HOLD ' CUSTOMER 5 I GE 0 a -Nrt .� N T, 0 c0 m m cco 1„ co t` GREN ROOM MGR'S AREA 4 1/2" f 8'-O 1/.i 41-q" 1 ' 41-0" 4 1 /2 rn 9 1/2 ' 7 1 I 11-1 1/2 8'" x 4 L OPNG AT 6" AFF K I TGHEN J J GOMP. CLOSET EXTENT OF CUSTOMER SEW I GE AREA PLAYPLAG� VEST IBUL N L k\DVA MAL :a--"7-10" 4111 51-q" ORDER fi N m 0 N ti 0 •74 - CONTROL JOINT CONTROL JOINT 18" x 18" DRYWALL OPN6. AT 6" A.F.F. FILLED STEEL PIPE BOLLARD - SEE SITE DETAILS 10' -8 1/2" ?' -•0' 4' -0"M.O. _ ' -0' LINE OF TRELLIS ABOVE 5'-0 4'-0"M.0. 2'-4" 33'-4" (SEE ELEVATION FOR. COLOR THIS AREA) PROVIDE MOP HOLDER 4 1/2"D x12"W SHELF FOR GLEANING 1'DETERGENT STORAGE. 1 1/4" 11-4 " M . • . 8'-6 1/2 N GUARDRA I L - SEE 11/A1.2 - SEE SITE PLAN FOR EXAGT LOCATION AND LENGTH 13'-1 1/2" 31-4" 0 V 0 0 co 0 ONL_yV :6: ,T) 0NO UN C'%_F..OLCO0O N L O C • +.a N N 0 4 V -t�o L QOM-) oo 0. O N� I.- 0 v o :3N-•omau O O _1.1.3 .6 L 0• . Vj +. 0 C p) L L V • Pt:co q N O V - 0 G pi ,- 4-C coo . v • c O cv o c c ,_ O - W 0 0 0 Co C c 0 O) o C (1( a.. V p) 4. O C C •+. c (A d -o O 3 W' E U C o C 0 E.,. X .FO.. 0 y 0 N 00 c N L O O J• '- C 0 0 0 O 0 4. V Q C 2 v V L o� Q(41.p 91.1.14(5i! • 7 N .'�) O O p�j 0 O O V m N N p g C 0) 0 'L 0 p) 0L) -c O FART I AL. FLOOR PLAN Al . 1 1 /4° =1 _0" COLOR ST ST -2 DOLOR ST -2 641-4 1/4" 16'-5 1/2" These s a 3 c 129'-8 1/2" FOUNDATION TO FOUNDATION 11 J (SEE PARTIAL PLAN 1/A1.1 FOR CONTINUATION OF FLOOR PLAN) co 0 0 O 0 Z I .4AMUFACTURE iTIODML # DESertiPTION SYMBOL „...-5 ... •.�!c _9_.FSn^. :.. P 7 .rn. f.. s:_a :'+' "Z ram "COPE OF WORK" INSTALL AN AUTOMATIC FIRE ALARM SYSTEM IN A r 3ef:x (4709`! F acct ALL WIRE TO BE FPLR-FMN -18AWG, -ICA C, FOR Nl-\C-CIRC UITS. ALL STROBES TO BE AT 80" ON BOTT-OK HORNS TO BE 75 DB MINIMUM THROUGHOUT.- ALL PULL STATIONS AT 48" ON TOP. MONITORING VIA UL LISTED CENTER STATION. A FULL SERVICE AGREEMENT IS IN PLACE TO ASSURE PROPER TESTING AND MAINTENANCE PER NFPA 72 STANDARDS. ALL I\ORK TO BE PERFORMED IN WORi{MAN LIKE FASHION. INSTALLATION SHALL MEET NFPA 72, UBC, UFC, WAG, IFC AND ANY LOCAL AHJ CODES. A FULL PRE-TEST SHALL BE COMPLETED PRIOR TO CALLING AHJ FOR FINAL ACCEPTANCE TEST. O9733`, z_ LI. CFPS® x`1473 s Fire Proteatl9n, Ino, 1730 00$0 ROAD, Even T1 WA 93204 DRAWN BY C..- (44,t- CONT#FIIIEPL*Q21 ML LI#CATS*RL0220Q SEATTLE FIRE DEPT#SCP x.0065 NICET#4--#0 7337 CFPS#1473 PROPERTY OFAND ALL RI3FITS REeERV- D FIRE PRO i MOTION. INC. DATE • / 046-0005.00.0 FA— 1 PAR. FLOOR PLAN EXTERIOR NALL ASSEMBLY 2 - SEE ASSEMBLY NOTES ON SHT. A5.0 EXTER I OR WINDOW ASSEMBLY - SEE ASSEMBLY NOTES ON SHT. A5.O 2x4 WOOD STUDS cc) FOUNDATION PROVIDE MIN. 5'xS' LEVEL LANDING ® ALL EXT. DOORS 1N/ MAX. 2% SLOPE ANAY FROM BUILDING (TYP . ) SHIM 4 CONT. SEALANT PERMEABLE BLDG. WRAP OVER 1/2" THK: EXT: GRADE PLYWD. 125'-4" FEN. TO FDN. 1T'-11 1/4" 11'-10 1/2" '-10 3/4 EXTERIOR WINDOW ASSEMBLY SEE NOTES ON SHEET A5:0 SHIM 4 CONT. SEALANT CORIAN SILL BELOW 8'-5" WALL ASSEMBLY 3 VARIATION -663.5" STUDS THIS SECTION S' -O" M.O. 2'-8" S' -0" M.O. ,2'-8" 9 44 " a iiwi cittas VENT PIPING FOR PLAY AREA FLOOR DRAINS 13LPG OVER THK. 5 1/2" GYP. 13D., FINISH W/ MTL. EDGE BEAD A CORNCI' AND J -BEAD a WINDOW FRAME SIM. OPP. a t t HAND TUBE STPFI COLUMN 4 MOMENT FRAME - SF= STRUCTURAL DRAWINGS 2x6 HOOP STUDS a 16" O.G. SEE ASSEMBLY NOTES ON SHEET A5.0 FOR ADDITIONAL NOTES ON EXTER I OR WALL ASSEMBLY 1 TUBE STEEL COLUMN SEE STRUCTURAL EXTERIOR WALL ASSEMBLY 1 SEE ASSEMBLY NOTES ON SHEET A5.0 'SEE PEI. 1/A4.1 FOR ADDITIONAL NOTES ON ARCADE PIER NT DETAIL @ ARCADE 1 I/2"=1'-0" SEE FLOOR PLAN FOR PARTITION TYPE 3. JAMB DETAIL @ COLUMN ty 1 1/2"=1.1 _0" 5" /MIN. ROOF DRA I N OVERFLOW PIPE EXTERIOR ASSEMBLY ASSEMBLY SHEET A5. WALL 1 SEE NOTES ON 0' TUBE STFFI COLUMN SEE STRUCTURAL SHEETS GORIAN SILL 2x4 HOOP BLOCKING GORIAN SILL ,&b "rCP nR'c:4Q< PLAYPLAGE DINING ( SEE NOTE ON H6T FURR-OUT ON 2/A EDGE OF GYP. BOARD F I i =1 I C,1 I BELOW O PLAYPLAGE PINING 1/2" GYP. BD. - SEE PET. 3/A1.1 FOR ADD. INFO. ANOP. ALUM. WINDOW FRAME FILLER P I ECE TO MATCH FRAMING EXTERIOR WINDOW ASSEMBLY SEE ASSEMBLY NOTES ON SHEET A5.0 PLAYPLAGE TOY AREA PERMEABLE B D6. WRAP OVER . GRADE PLYWD. 1/2" THK. 51-1 I M AND SEALANT EXTERIOR WINDOW ASSEMBLY SEE ASSEMBLY NOTES ON 51-1b.i A5.0 4 HINDON JAMB DET ► I L Al 1 1 1/2"=1'-0" PERMEABLE BLDG. WRAP OVER 1/2" THK. EXT. GRADE PLYWD.. EX I LI! I OR WALL ASSEMBLY 1 SEL 4/A5.O 2x HOOD BLOCKING HINDON JAMB DETAIL 1 1/2"=1'-0" /2 1 1/2" 7'-T 1/2" AT VESTIB TE ON HGT OF FURR OUT ON 2/A3.1 PLAYPLAGEQUIPMENT TO BE SELEG 4 COORDINATED BY • MoPON D'S PROJECT MANAGER a sewn ligmow CC dCcS^_j e4' 47: cn d c� a Oso' Fa) 14"D W \ O_ 1 6 It,•, CD to sum r 1'-O /2" 1 5 4" EXTERIOR WALL ASSEMBLY 2 SEE 4/A5.0 GORIAN SILL ANOD. ALUM. WINDOW FRAME W/1/4" TEMP. GLAZING CENTERED ON STUD NAL! PLAYPLAGE 12 VESTIBULE • A4.1 1161 TUBE STEEL COLUMN SEE STRUCTURAL GORIAN SILL SHIM AND SEALANT VESTS L SFP FLOOR PLAN FOR PARTITION TYPE HOOD BLOCKING EXTER I OR HI NPOW SYSTEM SEE 4/A5.0 1 1/4" 1 1 /4 " r `- GUARDRAIL - SEE 11/A1.2 - SEE SITE PLAN FOR EXACT LOCAT I ON AND LENGTH 13'-1 1/2" PROVIDE MIN. 5 LEVEL LANDING EXT. DOORS W/M 2% SLOPE AWAY BUILDING. X5' ALL OM 4 1/2" EQUAL -1'-O 1/2" I-4" _411 -4 '-10 3/4" 15'-1 1/2" CL OF WINDOW AND WALL ASSEMBLY -1 1/2" 18'-11 1/2" 11'-10 1/2" JAMB DETAIL @ COL./CORNER JAMB DETAIL 19 INTERIOR HALL 1 1/2"=1'-0" 85'-O" FDN. TO FDN MATCH LI KEY NOTES SYME3OL LESEND AWNING ABOVE - BY OM 6.G. TO PROVIDE 4"x4"x5'-O" HIGH STAINLESS STFFI CORNER GUARDS AT ALL EXPOSED LOCATIONS IN K I TCHEN/SUPPORT AREA. CORNER GUARDS TO START AT FINISH FLOOR. ATTACH WITH HOOD SCREWS INTO HOOD BLOCKING BULLNOSE COVE BASE HI-1ERE TILE MEETS STAINLESS STEEL CORNER CONCRETE EQMT PAD - STT STRUCTURAL PARTITION TYPE TAG SEE 2/A1.0 DRAFT STOPPING - SEE 2/A1.0 POOR TAG - STS'" DOOR SCHEDULE ON A6.0 CERAMIC WALL TILE a CUSTOMER SERVICE AND KITCHEN SERVING AREAS - TO BE COORDINATED W/FI-NAL DINING DECOR SCHEME 4 McDONALD'S PROJECT MANAGER SUSPENDED DECORATIVE CEILING TREATMENT - SEE DECOR DRAWINGS FOR ADDITIONAL INFORMATION. DROPPED 50IT' IT ABOVE - SEE 1LEGTED CE I L I NG PLAN CO2 FILL BOX (EQUIPMENT SCHEDULE ITEM 41.00) STANDING METAL SEAM BARREL VAULT ROOF SIT ELEVATIONS AND SECTIONS Fg OPTIONAL BULK OIL FILL BOX (EQPM SCHEDULE ITEM Bo 100. 16) CONFIRM USE WITH MGPONALD' S PRO. IFGT MANAGER HIGH IMPACT FLOORING - G.G. TO COORDINATE ACTUAL LOCATION AND EXTENT WITH TOY PLACEMENT ROOF ACCFSS LADDER W/HATCH ABOVE SEE STRUCTURAL FRAMING PLAN FOR LOCATING DIMENSIONS TRELLIS SYSTEM ABOVE SEE 4/A5.0 FOR NOTES SEE ROOF PLAN FOR DIMENSIONS 0 PARTIAL FLOOR PLAN A 1.1 1/4." = 1'-0" (SEE PARTIAL PLAN 1/A1.0 FOR -CONTINUATION OF FLOOR PLAN) SEVERAL NOTES 1 EXTE-R I OR DIMENSIONS ARE TO COLUMN REFERENCE LINES AND EXTERIOR PAGE OF FINISH UNLESS O T HERW I SE NOTED. INiEIOR DIMENSIONS ARE TO FACE OF FINISH. 2. SEE 4/A5.0 FOR EXTERIOR WALL ASSEMBLY TYPES. SEE 2/A1.0 FOR INIi:IOR PARTITION TYPES. INTERIOR PARTITIONS ARE TYPE 'A' UNLESS NOTED OTHERWISE. 3. SEE EXTERIOR ELEVATIONS FOR WINDOW TYPES 4. SEE SHI±1 A6.0 FOR DOOR AND ROOM FINISH SCHEDULES 5. SFE SITE PLAN FOR SIDEWALKS, RAMPS, ETC. 6. GC TO INSTALL H.C. SIGNAGE PER 2006 IBC CHP. 11 4 ICC/ANSI A111.1 2006 (PACKAGE FURNISHED BY OTHERS) AT LOCATIONS AND POSITIONS INDICATED IN PACKAGE OR AS REQUIRED BY LOCAL GODES. 1. SIGNAGE PACKAGE SUPPLIED BY: FORREST PERMA-SIGN 1212 1ST ST., BOX 585 NEN ROCHFIIE, NY 10602 1-600-214-6165 wwlw.forrestpermasIgns.com MAXIMUM OCCUPANCY SIGN TO BE POSTED i' LOCAL CODE. SIGN FURNISHED AND INSTALLED BY GENERAL CONTRACTOR. 8. ALL HANDSINK LOCATIONS SHALL HAVE GEMENT BOARD BACKING 48" IN HEIGHT A.F.F. ° e) I.- 11) 5 :1:1 _c I5 o L Qm� Cr o 0 n• v y,, L -v O O U O- O L U C o�,NL° o V C U L N U D• oEvoo ▪ V v C 01 a ✓ • C ° C =..- c L o -v+ U ✓� ttvoo �'CCovc rt,- ° o ▪ o o (n ) U C c O .0 1 i_ O • _H ~ -o ✓ Q c.+v o s:a :t In O 5 O II) • v N y.L o 1000 3 C 0 j a? ° v rng)w /4 -ft -!,!1...) o O ° 0 w a • U ' N s t='oo reuse on 0 046-0005.00.0 F1\-2 PAR. FLOOR PLAN '0 .\ • ♦• • /9- 7" jeoaNGf/Tio, , a..---.-, — -......,,,,...-.��--- souowoaosew aaeu`aarecrw, c �� scnaxve i hsrczAmP r �� ��A,0 / 30'1 V >i. ss EARTH QUAKE BRACE �� i 0,00 1 o -lo: 4' F/2EEzgR 1 1 4 ii, ,BoVE r AeLoi a/ c474/4./' off, 114Z. PE2 T1/, //L,9 F b. -0—/ 4� 0 7- 8 3-0 �►- 1 l lr4 '' ' N. '410 1/4 -i / • 7-S 1 1 .N 3-0 .- a..---.-, — -......,,,,...-.��--- souowoaosew aaeu`aarecrw, c �� scnaxve i hsrczAmP r �� ��A,0 / 30'1 V >i. ss EARTH QUAKE BRACE �� i 0,00 1 1. All material and equipment to be new and underwriters approved. 2. Piping dimensions are end to end. (0'- 0") 3. Earthquake bracing shall be providedinaccordance with NFPA pamphlet number 13. to be in accordance with 4. Pipe hangers and method of hangingor NFPA pamphlet number 13. 5. Piping shall be accordance with pamphlet number 13. 6. Joining of pipe and fittings, threaded and welded shall be inIQ accordance with NFPA pamphlet 13. 7. Owner to provide adequate heat to prevent water in pipes from freezing in areas protected by a wet pipe sprinkler system. 8. Structural adequancy of the building to support the sprinkler piping is the responsiblity of the owner and/or structural representatives. 9r s7797 -/c - s -ops/ Res,- zo Ps/ w/ 31 oo 0Pt4 /0, t/EAb s c TALE' ii, ,BoVE r AeLoi a/ c474/4./' off, 114Z. PE2 T1/, //L,9 F b. • l ''.1-, -L ' zQ / "z 2- S_g 1- 4A 3 o- 4 /^ i- 1 0 v� _____,„---- e ,/ 0 .,. NI- ° tQ ,o o 1-4 I -a • Z�1�o I-4 9 i 0 zS ,,0'0 0,�1�T%1 A e.� r -"^T a1-4 /`a `'+ !-.i - �U/�� N f I7=1°c.H. 1 PL'4YPZ.AcE E,c , SE/s/v/G e, 9Gc _ - ! be/%1 x 2, as- ()7 of wi97'GX/=/ 42 ,P/,) = 4'/, 8 x /px6$'x 2,93 /yZx Se; x 3,4/ ( " z X 40' x s, 3 (-, 4x/s' rt. „ „ I, ) = Zbl,./G n , S = /o/, 08 = z ..Z X. S.= '/oz, !aD "/ 76., 7 7-07%9L E/a/zz, 40,46 r- -V, S =. SSB, O./32X_ /..i/ORZ 40/1A ..FlLL /''x _7;4%." 40 /97"4____s_"17-47.-557_79° //z" 7-&ez©v4-///3©4T_/At zoso /9_7' _gs".`_7-47. S7..65.4,1,3._S;_iia -Z05'O _:../_ /4 = / ' 9'. _ 7� e.B4d'' 9, _3.5 /d._3_.i1/fl, /3 , 2 7') r,,,y/chi /s 4RE. T4 =- - - aS_g, 8 Co/v,s 7R4-44-1-5 GENERAL NOTES souowoaosew aaeu`aarecrw, c �� scnaxve i hsrczAmP r �� ��A,0 / 30'1 V >i. ss EARTH QUAKE BRACE �� i 0,00 1. All material and equipment to be new and underwriters approved. 2. Piping dimensions are end to end. (0'- 0") 3. Earthquake bracing shall be providedinaccordance with NFPA pamphlet number 13. to be in accordance with 4. Pipe hangers and method of hangingor NFPA pamphlet number 13. 5. Piping shall be accordance with pamphlet number 13. 6. Joining of pipe and fittings, threaded and welded shall be inIQ accordance with NFPA pamphlet 13. 7. Owner to provide adequate heat to prevent water in pipes from freezing in areas protected by a wet pipe sprinkler system. 8. Structural adequancy of the building to support the sprinkler piping is the responsiblity of the owner and/or structural representatives. 9r s7797 -/c - s -ops/ Res,- zo Ps/ w/ 31 oo 0Pt4 /0, t/EAb s c TALE' ii, ,BoVE r AeLoi a/ c474/4./' off, 114Z. PE2 T1/, //L,9 F b. • oV e vty vv r Z'l x Z'/z x 3//G L EQ. /,R.4ci/✓6 /Lo z'/40 /'/r'E 3/8",S T, 7' z" Ayr- TEST/o/2. VA, /d'C `tyz'' _ Gt./ /Z/sE/t ,DETA/L AJ? Sc -,9`E `/ FGoalR /.A Ni 3//64_ /- o" ` J 13 -wily VA, 7AxZ°zx PAl/z/iPET /Z" /L"TJ7's/-/ 3Z"QC-, I it i-� O j cHV . frA 's Joao -SS Per /N V4111 -T POE/Z /two, /Zs 4' P./. /3/' s/7-4- P/i9/✓ / % = id -0" I 1 •I I z8'/37�%ZS" TJL.'s 3Z" 4(.. l/./V. • t,o cm. /nfiiN i -o 0-10' 4/./, s -c?/oN >9' 3/4.1_ art w 1'i Without Con rCrits I D Aa Noted In F�,d ; prt Per The Attached Utter I 1 t nese Mans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is eubi ct to errors and omissions which do not authorize violations of adopted standards and orainances. The regrons'ibtl t for the adequacy of design rests toU.11y with the designer. ' Additions, dal .lofts, or i k vi .,ic'fi1` Io thew drawings atter this date will vpm this eccepi ice ane will require a resubmittal of 1 evised drawings for subsequent approval. Final acceptance is subject to field test and inspection b‘ The Tukwila Fire Prevention Bureau. _ IDate . /0 -).`1- 08 By: 5/ I IMPORTANT NOTICE Because of increased demand our inspectors' schedules are booked r3e7 days ahead. Therefore, you ll need to call 205-575-4407 to schedule your inspections a minimum of 48 hours in advancs of the date you want an inspection. FILE I TUKWILA FIRE DEPARTM1 Please call: 575-4407 and give thisob C/ ' _ `( 1 7 •, ‘a';i. address for shut. or restoration aporoval- NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. V/c,/.N/7Y //?,FP ZN N HANGER LEGEND L WALL BRACKET APPROVING AGENCIES A SAMMY SCREWS • 457 zo S.r� lB COACH SCREW ROD M MACHINE THREAD ROD SPRINKLER INFORMATION CANOPY INFORMATION N TOGGLE BOLT SYMBOL IT QUAN Y TEMP MFR. C BEAM CLAMP & RET. TRAP D EYE ROD O P POWDER DRIVEN STUD CEILING FLANGE O MODEL TYPE FINISH ORIF. MFR. MODEL FINISH 48 7-00 4LO$E QIZ g= S, 4, L„ UP,e4 //7 •Bross L REVISIONS E KWIK BOLT R LONG STRAP • 6 a n H N 4 I, a 1. ,. �LU�E KEG, F FLUSH SHELL S SHORT CLIP n 'I H $SP EXTE'NG til G/%lo/1;%4-- /. G SIDE BEAM BRACKET (#58) TRAPEZE (SEE DETAIL) H STD. SIDE BEAM BRACKET V PIPE STAND J UNISTRUT & CLAMP W WRAP-AROUND U -HOOK K U -BOLT x RISER CLAMP WASH. STATE CONTRACTOR LIC ##EMERAFL980MR ice% Aa,iJ4 .IA s /5-a /co P,ygc//a/G //GOY, S, TZ//// r.,t-/ /9, , TOTAL : //8 DRAWN BY DATE S/ /o8 JOB NO. SHEET /-