HomeMy WebLinkAboutPP - 15666 TUKWILA INTERNATIONAL BLVD - UNKNOWN - PERMITS AND PLANS15666 TUKWILA INTERNATIONAL BLVD
ASSOCIATED PERMITS
NONE
c
UN
CUN
c
F!I Ii
t
A
AN
OLYMPIA FLEET 8c SUPPLY AND SOUTH KI\G COUNTY
PROJECT NO. 92-054
DESIGN; CONSULTANT
401 2ND AVE. S. * SUITE 201 * SEATTLE, WA 98104
TEL. (206) 583-0200 * FAX (206) 583-8826
mr-
LEGEND
A AIR
CW COLD WATER
EC ELECTRICAL CONDUIT
S SANITARY SEWER
SD STORM DRAIN
LIGHT W/STANDARD
DRAWING SCHEDULE
{
M1 OLYMPIA FLEET AND SUPPLY DEMOLITION PLAN
M2 OLYMPIA FLEET AND SUPPLY NEW WORK PLAN
M3 SOUTH KING COUNTY DETACHMENT DEMOLITION PLAN
M4 SOUTH KING COUNTY DETACHMENT NEW WORK PLAN
M5 UNDERGROUND STORAGE TANK DETAILS
M6 UNDERGROUND STORAGE TANK DETAILS
APPROVALS
_L'Y 'iULLIL4 )
WASHINCl.T ON STATE PATROL
ENGINEERING & ARCHITECTURAL SERVICES
APPROVED
AS NOTED
The drawings affixed hereto have been
reviewed and accepted as meeting or
exceeding minimum requirements of the
City of Tukwila Fire Dept , Bureau of Fire
Prevention Additions or revisions to these
drawings after this date shall not be
construed as being approved r reviewed
CITY OF TUKWILA
BUREAU OF FIRE PREVENTION
ILE
1
EXISTING ESI CARD READER. REMOVE
CARD READER AND RETAIN FOR RE -USE.
RETAIN ELECTRICAL CIRCUIT TO CARD
READER FOR RE -USE.
DISCONNECT ELECTRICAL CIRCUITS, WATER AND AIR LINES
TO WATER/AIR HOSE REEL AND RETAIN FOR RE -USE.
CONTRACTOR IS TO REMOVE AND PROPERLY DISPOSE
OF PUMP ISLAND AND PUMP ISLAND EQUIPMENT.
CONTRACTOR MUST RETAIN OVERHANGING CONCRETE
ROOF, COLUMNS AND FOOTINGS. ADDITIONAL SUPPORT
FOR THE CONCRETE ROOF MAY BE REQUIRED
DURING PUMP ISLAND DEMOLITION.
r;
,
1
PNL B
PNIL
IC
I!
1
1-1/2" TANK VENT,
CUT AT GRADE AND
ABANDON REMAINDER
IN PLACE
EMERG SHUT-OFF
AIR COMPRESSOR
SHUT-OFF
VALVE
DRY
WELL
x x r
/- 6" CAST
/ IRON
SD
.. -x
GRAVEL
A.
EXISTING FENCE-,
- - -x —Lx--
EXISTING EXPOSED
CONDUIT ROUTED
CN UNDERSIDE CF
CONCRETE ROOF
- V—
4" S C 0.
.,- 4" CAST
or
IRON
—EC =-{A
0
—EC
a
EXISTING ESI
CARD READER
�
I
1I /
J 11 , /
EXISTING ESi-'
PRINTER
U
w
1
REMOVE BELLS
SYSTEMS
PUSHBUTTON
SWITCH
LIMITS OF
CONCRETE
--x
x -x
SD
ALTERNATE NO. 1
LOCATION OF 1,500 GALLON ABANDONED
FUEL TANK. REMOVE AND PROPERLY
DISPOSE OF TANK, INCLUDING VENT
AND SUPPLY PIPING
2" TANK VENT
x
X4- ---x x--
1
%
CONTRACTOR IS TO REMOVE
INDICATED PORTION OF CHAIN
LINK FENCE AND RE -INSTALL
AFTER COMPLETION OF WORK I
Ir — OFFSET
iALL LINES
,
pimig
1
1
IL
L_J
i1 ---J
n
M
APPROXIMATE LIMITS
OF CONCRETE CUT
4" CAST
IRON
E4" S C.O.
x x --a4 --
TEMPORARY
TEMPORARY FENCE
LOCATION (BY OWNER)
LOCATION OF FUEL TANKS. REMOVE
AND PROPERLY DISPOSE OF TWO 10,000
GALLON UNLEADED FUEL TANKS INCLUDING
VENTS AND SUPPLY PIPING
` SD —®
DRY
APPROXIMATE LIMITS WELL
OF ASPHALT CUT \ £1
"- GRAVEL THIS SIDE
OF FENCE
(ce(
X--
-- ASPHALT THIS SIDE
OF FENCE -\
SD
CB
[-EXISTING EXISTING FENCE
-x x -4- - x
1
\\ f
\ I
OLYMPIA FLEET AND SUPPLY
arP DEMOLITION PLAN
X -
\
T
\,/I � SD
SCALE: 1" = 20'-0"
CB
4
x
I
GENERAL NOTES:
1. CONTRACTOR SHALL PROVIDE LOCATOR SERVICE.
2. ALL WORK SHALL BE PERFORMED BY CONTRACTOR AND
SUPERVISOR LICENSED FOR TANK DECOMMISSIONING.
3. OWNER SHALL PROVIDE SOIL SAMPLING AND TESTING
PER DOE SITE ASSESSMENT REQUIREMENTS.
4. TANKS HAVE CONTAINED LEADED FUEL DISPOSE OF
SLUDGE AS HAZARDOUS WASTE.
5. ANY DAMAGE TO EXISTING FACILITES DURING COURSE
OF WORK SHALL BE RESTORED OR REPLACED AT
CONTRACTOR'S EXPENSE.
lc
I ---
Z
W
W
0Q
J
Lu
cc
Z
O F.--
Lu
Q 0
d. Q
CC
OI
I --V)
V? p
Z Z
0 O
F_ O
0 Ce
Z O
CC
2 LU
I~'
0
LU
—a
0
CC
a_
PROJECT NO. 92-054
DATE:
8/27/92
SHEET TITLE:
OLYMPIA FLEET
AND SUPPLY
DEMOLITION
SHEET NO.
M-1
Z
O
EE
0
N
W
Q
V)
z
O_
N
S
w
Er
(DATE
O
Z
lc
I ---
Z
W
W
0Q
J
Lu
cc
Z
O F.--
Lu
Q 0
d. Q
CC
OI
I --V)
V? p
Z Z
0 O
F_ O
0 Ce
Z O
CC
2 LU
I~'
0
LU
—a
0
CC
a_
PROJECT NO. 92-054
DATE:
8/27/92
SHEET TITLE:
OLYMPIA FLEET
AND SUPPLY
DEMOLITION
SHEET NO.
M-1
ROUTE EXPOSED CONDUIT
APPROXIMATELY 10'-0" UP
PNL B
l
PNL C
DRY
WELL
x -
EMERGENCY PUMP SHUT-OFF
PROVIDE ISOLATION RELAYS IN
MECH/ELECT ROOM FOR ALL
POWER CIRCUITS AT ISLAND
‘AIS.„ COMPRESSOR -1
SHUT-OFF
VALVE
EXISTING EXPOSED
CONDUIT ROUTED
ON UNDERSIDE OF
CONCRETE ROOF
EXISTING CARD READER
(RELOCATED)
x x u
6" CAST
IRON
1
D
SD
EXISTING FENCE
x
-x
\- GRAVEL
2" SUMP/
INTERSTITIAL
VENT
— v-
4" S C 0
f 4" CAST
IRON
AIR/WATER
HOSE REEL
EXISTING
COLUMN
(2) TYP
INDICATES CONDUIT ROUTING,
NOT QUANTITY OR SIZE. SEE
DIAGRAM SHEET M- 5 .
ROUTE CONDUIT
ABOVE T -BAR
CEILING
EXISTING ESI
CARD READER
AND PRINTER
T–BAR
CEILING
=EC —
–EC
■
0
wci CANOPY-'
I .
;n
�II
RLM 9000
PPM 4100
P/M RELAY
J -BOX
(
SO
ALTERNATE NO. 1
BACKFILL EXCAVATION. BACKFILL
SHALL BE COMPACTED TO 95% OR
GREATER. PATCH TO GRADE WITH
4" OF ASPHALT OVER 6" OF 5/8"
MINUS CRUSHED ROCK
LIMITS OF NEW CONCRETE
SLAB 6" MIN W/6x6x10
GAUGE W W M F MATCH
EXISTING GRADE
FILL
GAUGE
SD ®
ROUTE CONDUIT UP EXISTING
COLUMN AND SECURE TO
UNDERSIDE OF CANOPY
LIMITS OF
CONCRETE
ROUTE EXPOSED CONDUIT
APPROXIMATELY 9'-0"
' ABOVE GRADE ON BUILDING
WALL
[CBI
oN_
-x
L i
BACKFILL EXCAVATION
MATCH EXISTING GRAVEL
GRADE
PIPING SUMP
BRINE RESERVOIR
SENSOR
MONITORING WELL
(2) TYPICAL
DRY
WELL
CONTRACTOR TO PROVIDE ADDITIONAL
EXCAVATION TO LOCATE TANK/TANK
SLAB 2'-0" WEST OF FENCE DO NOT
POUR FENCE POSTS WITHIN TANK SLAB
x- — x x- - x x
\- ASPHALT THIS SIDE
OF FENCE
PATCH TO MATCH EXISTING
GRADE WITH CONCRETE
CONDUIT ENTRANCE INTO
BUILDING. DRILL HOLE IN
BRICK WALL APPROXIMATELY
9'-0" FROM GRADE FOR
CONDUIT ENTRANCE
SD
DRY
\h'ELL
4 C P
•
t
GRAVEL THIS SIDE
OF FENCE
x
(cel
OLYMPIA FLEET AND SUPPLY
\EW WORK PLAN
x -
x
EXISTING FENCE
x x x -x --X-
p7 [cBi
X-
SCALE. 1" = 20'-0"
x
SD
x
081
L
19/-0"
HOLD-DOWN BOX BRAVO SYSTEMS,
200 SERIES MODEL 2510-3. PROVIDED
BY CONTRACTOR PER MFR'S INSTRUCTIONS
+op
L --J 4
INSTALL AIR AND WATER
REEL PER MFR'S INSTRUCTIONS
J
TANK VENT
STEEL PUMP ISLAND
FORM (SEE NOTE)
EXISTING CANOPY
COLUMN (2) TYP
s
SUMP/INTERSTITIAL VENT
RELOCATE EXIS1ING CARD READER TO LOCATION
SHOWN. (4) 3/4" CONDUITS TO CARD READER MUST
BE PULLED UP THROUGH 5" SQUARE OPENING AT
BASE OF CARD READER STAND. (SEE UNDERGROUND
CONDUIT DIAGRAM SHEET M- 5 )
NOTE:
PUMP ISLAND FORM: 12 GAUGE STEEL, 13" HIGH, 4'-O" WIDE
WITH SEMI -CIRCULAR ENDS. TOTAL LENGTH 19'-0". FACTORY
FORMED TO REQUIRED SHAPE AS MANUFACTURED BY COXWELL'S
(LOS ANGELES), AMFAB (MEMPHIS), OR APPROVED EQUAL.
CONTRACTOR SHALL PROVIDE FORMS. AFTER PLACEMENT, PRIME
AND PAINT THE PERIMETER BLACK (BK -10 -SLG).
PUMP ISLAND PLAN
' N D�TANKt VENT
1
N.T.S
2��0" Q,- SUMP/
MIN INTERSTITIAL
VENT
COMMERCIAL ZONE PRODUCTS -
TOWEL DISPENSER MODEL
#DBWC. PROVIDED BY
CONTRACTOR. MOUNT TO
CANOPY COLUMN @ 48"
ABOVE ISLAND
CABINET PROVIDED- 1-l'
AND INSTALLED I * I
�
BY OWNER
v
18"
EXISTING
ESI CARD
READER
AIR/WATER
HOSE REEL
GENERAL NOTES:
1. FOR TANK INSTALLATION DETAILS, SEE SHEETS
M- 5 AND M-6 .
REPLACE EXISTING DOWN
SPOUT AND RECONNECT
TO EXISTING 4" CAST IRON
DRAIN UNE
NOTE:
CONTRACTOR TO RETAIN CONCRETE OVERHANG, CANOPY COLUMNS
AND FOOTINGS'
PUMP ISLAND DETAIL
M M-2
N.T.S.
4" CAST IRON S.D.
U
W
0
!Y
a_
DATE:
8/27/92
SHEET TITLE:
OLYMPIA FLEET
AND SUPPLY
NEW WORK
SHEET NO.
VI 2
Z
O
P
E
(.3
v)
W
0
z
O_
W
x
W
1--
< Q
0
O
z
U
W
0
!Y
a_
DATE:
8/27/92
SHEET TITLE:
OLYMPIA FLEET
AND SUPPLY
NEW WORK
SHEET NO.
VI 2
PARTIAL BASEMENT FLOOR PLAN
5
8" LOT DRAIN
@ 18" BELOW ASPHALT
SD
�- MAIN DISTRIBOTION PANEL
U
PANEL B
EXISTING ESI
PRINTER
I,
EXISTING ESI
CARD 'READER
L
r
r7 r
RETAIN EXISTING FUEL PUMP EMERGENCY
SHUT-OFF. PROVIDE ISOLATION RELAYS
IN THE MECH/ELECT ROOM FOR ALL
POWER CIRCUITS AT ISLAND
RETAIN CARD READER
CIRCUITS AND CONDUIT
WITHIN BUILDING FOR
RE -USE
—ASPHALT
• REMOVE CONCRETE
DRIVE SLAB AND GP DE
PATCH TO MATCH
EXISTING WITH ASPHALT
3
st^
MANHOLE
6"
SD
RETAIN AIR, WATER LINES AND PUMP
ISLAND CIRCUIT, UP TO LOCATION
SHOWN FOR RE -USE. CUT AND ABANDON
REMAINER OF' LINES AND CONDUIT
IN PLACE
SD
SLOPE
• • •
V —0
L
DEMO
GUARD POST
2
CANOPY \
EC
`14• ABOVE
GRADE
REMOVE CARD READER AND
PEDESTAL AND RETAIN FOR \
RE -INSTALLATION
1-1/2" TANK
VENT
SOUTH KING COUNTY DETACHMENT
DEMOLITION PLAN
X
0
L
1I/
APPROXIMATE LIMITS
OF ASPHALT CUT
CONCRETE
FILL PAD
SD
WATER
METER
1-1/2"
SCALE: 1/8" = 1.-0-
10" SEWER LINE
15' BELOW ASPHALT
EXISTING
/ FENCE
/
r
(OBJ
LOCATION OF FUEL TANK. REMOVE AND
DISPOSE OF EXISTING 10,000 GALLON
TANK INCLUDING VENTS, SUPPLY PIPING,
DISPENSER, PUMP ISLAND, CANOPY, ETC.
GENERAL NOTES:
1. CONTRACTOR SHALL PROVIDE LOCATOR SERVICE.
2. ALL WORK SHALL BE PERFORMED BY CONTRACTOR AND
SUPERVISOR LICENSED FOR TANK DECOMMISSIONING.
3. OWNER SHALL PROVIDE SOIL SAMPLING AND TESTING
PER DOE SITE ASSESSMENT REQUIREMENTS.
4. TANKS HAVE CONTAINED LEADED FUEL DISPOSE OF
SLUDGE AS HAZARDOUS WASTE.
5. ANY DAMAGE TO EXISTING FACILITES DURING COURSE
OF WORK SHALL BE RESTORED OR REPLACED AT
CONTRACTOR'S EXPENSE.
o
3
"6
i
•'`;
.�-.o
_
41-.
p
h
4•1
o
N
Lu
cc
x
W
ri
N
DESCRIPTION 1
(n
z
O
En
5
w
rr
DATE
f'ON I
PARTIAL BASEMENT FLOOR PLAN
5
8" LOT DRAIN
@ 18" BELOW ASPHALT
SD
�- MAIN DISTRIBOTION PANEL
U
PANEL B
EXISTING ESI
PRINTER
I,
EXISTING ESI
CARD 'READER
L
r
r7 r
RETAIN EXISTING FUEL PUMP EMERGENCY
SHUT-OFF. PROVIDE ISOLATION RELAYS
IN THE MECH/ELECT ROOM FOR ALL
POWER CIRCUITS AT ISLAND
RETAIN CARD READER
CIRCUITS AND CONDUIT
WITHIN BUILDING FOR
RE -USE
—ASPHALT
• REMOVE CONCRETE
DRIVE SLAB AND GP DE
PATCH TO MATCH
EXISTING WITH ASPHALT
3
st^
MANHOLE
6"
SD
RETAIN AIR, WATER LINES AND PUMP
ISLAND CIRCUIT, UP TO LOCATION
SHOWN FOR RE -USE. CUT AND ABANDON
REMAINER OF' LINES AND CONDUIT
IN PLACE
SD
SLOPE
• • •
V —0
L
DEMO
GUARD POST
2
CANOPY \
EC
`14• ABOVE
GRADE
REMOVE CARD READER AND
PEDESTAL AND RETAIN FOR \
RE -INSTALLATION
1-1/2" TANK
VENT
SOUTH KING COUNTY DETACHMENT
DEMOLITION PLAN
X
0
L
1I/
APPROXIMATE LIMITS
OF ASPHALT CUT
CONCRETE
FILL PAD
SD
WATER
METER
1-1/2"
SCALE: 1/8" = 1.-0-
10" SEWER LINE
15' BELOW ASPHALT
EXISTING
/ FENCE
/
r
(OBJ
LOCATION OF FUEL TANK. REMOVE AND
DISPOSE OF EXISTING 10,000 GALLON
TANK INCLUDING VENTS, SUPPLY PIPING,
DISPENSER, PUMP ISLAND, CANOPY, ETC.
GENERAL NOTES:
1. CONTRACTOR SHALL PROVIDE LOCATOR SERVICE.
2. ALL WORK SHALL BE PERFORMED BY CONTRACTOR AND
SUPERVISOR LICENSED FOR TANK DECOMMISSIONING.
3. OWNER SHALL PROVIDE SOIL SAMPLING AND TESTING
PER DOE SITE ASSESSMENT REQUIREMENTS.
4. TANKS HAVE CONTAINED LEADED FUEL DISPOSE OF
SLUDGE AS HAZARDOUS WASTE.
5. ANY DAMAGE TO EXISTING FACILITES DURING COURSE
OF WORK SHALL BE RESTORED OR REPLACED AT
CONTRACTOR'S EXPENSE.
o
3
"6
i
•'`;
.�-.o
SO" Aks v►'
t.
ry
41-.
p
h
4•1
o
N
Lu
cc
x
W
ri
N
Z
W
W
_..J
W
J
O I---
W
0- Q
Fa— v)
V) p
Z Z
O
O
0 Ce
O
2 W
(n
1-
U
O
DATE:
8/27/92
SHEET TITLE:
SOUTH KING COUNTY
DETACHMENT
DEMOLITION
SHEET NO.
M-3
1
PUMP/MOTOR
RELAY
PPM 4100
riRIM 9000
PARTIAL BASEMENT FLOOR PLAN
C
)
5
8" LOT DRAIN
® 18" BELOW ASPHALT
GENERAL NOTES:
1. FOR TANK INSTALLATION DETAILS, SEE SHEETS
M- 5 AND M- 6 .
SD
Li
J -BOX
MAIN DISTRIBUTION PANEL
PANEL B
EXISTING ESI
PRINTER
- J L
ASPHALT
EXISTING ESI
CARD READER
HOLD TIGHT ALONG
WALL, ABOVE T -BAR
CEIUNG
ROUTE CONDUIT
EXPOSED ALONG
WALL
CONDUIT ENTRANCE
INTO BUILDING
�1(
EXTEND EXISTING ELECTRICAL
CONDUIT, AIR AND WATER
ONES TO NEW PUMP ISLAND
LOCATION
INDICATES CONDUIT ROUTING,
NOT QUANTITY OR SIZE. SEE
CONDUIT DIAGRAM SHEET M-5
EC
A
w
8
MONITORING
WELL (2)
TYPICAL
c
EC
EC
PIPING SUMP
50
15"
7
z
CONCRETE BOLLARD
(6) TYPICAL (SEE
DETAIL THIS SHEET)
FIELD VERIFY EXACT LOCATION OF
PUMP ISLAND WITH OWNER
LIMITS OF CANOPY (SEE
\ DETAILS THIS SHEET)
2" SUMP/
INTERSTITIAL
/
VENT
FX' Ti�iG
\f FENCE
0
I
1
1
I
LIMITS OF
CONCRETE
TRENCH
SD
1
— v
0
Y TANK VENT
EC EC
A
_U
EC
7"
WATER
METER
1-1/2"
BRINE
RESERVOIR
SENSOR
X
SD
TANK GAUGE
FILL
RE -INSTALL CARD READER ON
NEW PUMP ISLAND WHERE SHOWN
DISPENSER TO BE LOCATED A
MINIMUM DISTANCE OF 10'-0"
FROM PROPERTY LINE
LIMITS OF NEW CONCRETE SLAB 6" MIN
WITH 6X6X10 GAUGE W.W M F. SLOPE 1/8"
PER FOOT TOWARD CATCH BASIN
INSTALL A 12,000 GALLON FIBERGLASS TANK,
INCLUDING PIPING SUMP, VENTS, SUPPLY PIPING,
ETC.
LIMITS OF NEW CONCRETE SLAB. 6" MIN.
WITH 6X6X10 GAUGE W.W.M F. SLOPE 1/8"
PER FOOT AWAY FROM BUILDING
1\
I \
1 10" SEWER LINE
0-1 15' BELOW ASPHALT
SOUTH KING COUNTY DETACHMENT
NEW WORK
SCALE: 1/8" = 1'-0"
FILE EDGES
611 -EXTRA STRONG
GALV. PIPE CONC.
FILLED
SHED TO DRAIN
CONC. BASE
1 FORM 18"0 AT
=TOP
ASPHALT PAVING
CROWN CONC.
G
C
PIPE BOLLARD DETAIL
SCALE: NONE
SUMP/INTERST1TIAL
VENT
TANK VENT
16'-0"
RELOCATE EXISTING CARD READER TO LOCATION SHOWN.
(4) 3/4" CONDUITS TO CARD READER MUST BE PULLED
LIP THROUGH 5" SQUARE OPENING AT BASE OF CARD
READER STAND. STUB -UP AND CAP. (SEE UNDERGROUND
CONDUIT DIAGRAM SHEET M-5)
M-3 M-3
STUB UP (2) SPARE
3/4 CONDUITS
ATT THIS LOCATION
STEEL PUMP ISLAND
FORM (SEE NOTE)
CANOPY
COLUMN
(2) TYPICAL
INSTALL AIR & WATER
REEL & SUMP PER MFR.
HOLD-DOWN BOX BRAVO SYSTEMS, INSTRUCTIONS
200 SERIES MODEL 2510-3 PROVIDED
BY CONTRACTOR PER MFR'S INSTRUCTIONS.
PUMP ISLAND PLAN
NTS
NOTE:
PUMP ISLAND FORM 12 GAUGE STEEL 13" H191-1,_"4'-0" WIDE
WITH SEMI -CIRCULAR ENDS TOTAL LENGTH 16 -. FACTORY
FORMED TO REQUIRED SHAPE. AS MANUFACTURED BY COXWELL'S
(LOS ANGELES), AMFAB(MEMPHIS), OR APPROVED EQUAL GENERAL
CONTRACTOR SHALL FURNISH AND INSTALL FORMS. AFTER PLACE-
MENT, PRIME AND PAINT THE PERIMETER BLACK (BK -10 -SLG).
DESIGN CONDITIONS:
SNOW LOAD 25LBS/SQUARE FOOT
WIND LOAD 80 MPH
EXPOSURE B
PROVIDE (2) HIGH PRESSURE
SODIUM SURFACE MOUNT
OUTDOOR FIXTURES, 150W EACH.
CONNECT TO EXISTING LIGHT
CIRCUIT. PROVIDE PHOTOCELL
ON CANOPY TO CONTROL
LIGHTS.
4'-0"
18'-0"
2'-O"MIN VENTS
SIDE VIEW
PUMP
ISLAND
12'-0"
COMMERCIAL ZONE PRODUCTS--,,
�o
TOWEL DISPENSER MODEL #DBWC
PROVIDED BY CONTRACTOR.
MOUNT TO CANOPY COLUMN
® 48" ABOVE ISLAND
18" MIN
yExm1c
READER
{ i
11
AIR/WATER T 7'
�I I
I I I
CABINET PROVIDED
AND INSTALLED
BY OWNER
NOTE:
PROVIDE CANOPY AS SHOWN, COMPLETE W/CONCEALED GUTTERS, DOWNSPOUT,
FASCIA, COLUMNS AND LIGHTS. MATERIAL TO BE FACTORY FINISHED. COLOR
SELECTION BY OWNER. CANOPY DRAWINGS SHALL BE SUBMITTED AND APPROVED
BY ENGINEER PRIOR TO MANUFACTURE.
FRONT VIEW
CONTRACTOR TO PROVIDE
FOOTING DETAILS TO
MEET DESIGN CONDITIONS.
r -A CANOPY/PUMP ISLAND DETAIL
wtb17.
NTS
DRAWN:
R.L, C.H-S.
DESIGNED:
GMR
s.
v
0
Lu
0 -
w_
APPROVED:
NLL
DESCRIPTION
z
0
r)
5
w
cr
DATE
O
z
DRAWN:
R.L, C.H-S.
DESIGNED:
GMR
s.
v
0
Lu
0 -
w_
APPROVED:
NLL
LU
W
-J
0 -
CC
J Z
0--
< 0
OO
H V)
o
Z Z
O =
i -'O
0 Ce
Z_ O
= W
1-
U
w
0
0
DATE:
8/27/92
SHEET TITLE:
SOUTH KING COUNTY
DETACHMENT
NEW WORK
SHEET NO.
M-4
BTINTLLTKPER O INSTALL ANR
M-5 MFR'S INSTRUCTIONS
(REFER TO SUMP NOTES BELOW)
3/4" CONDUIT FROM PIPING
SMP TO LEAK DETECTION
CONSOLE IN BLDG ELECT.
ROOM CARRYING SEPARATE
CONDUCTORS FOR BRINE
SENSOR AND SUMP SENSOR.
CONDUIT FOR REMOTE PUMP.
SUMP
SENSOR
3/4" CONDUIT FOR BRINE SENSOR
FROM RESERVOIR TO PIPING SUMP.
CAUTION: DO NOT PLACE STRAPS
BETWEEN THE RIBS OF THE TANK,
ONLY ON RIBS DESIGNATED BY
STENCILLED ARROWS
BRINE SENSOR
BRINE
RESERVOIR
3/4" CONDUIT FOR ELECTRONIC
TANK GAUGE W/SEAL-OFF.
RUN TO TANK MONITOR IN BLDG.
16"DIA. MANHOLE W/SKIRT TO
WITHIN 6" OF TANK SHELL
SPARE
FILL
SAMPLE WELL
SAMPLE-��
WELL
TERMINATE
2'-0" BELOW
TANK
15,000 GALLON (OLYMPIA
FLEET AND SUPPLY),
12,000 GALLON SOUTH KING
COUNTY) UNDERGROUND
FIBERGLASS STORAGE TANK.
DOUBLE WALL W/ BRINE
FILLED ANNULAR SPACE.
THE WSP SHALL PURCHASE
TANK, THE CONTRACTOR
SHALL COORDINATE DELIVERY
AND INSTALLATION WITH
XERXES TANKS
-51M-
12" MIN.
TANK MFR. APPROVED BACKFILL
SECTION A
M-5M-5
SUMP NOTES:
PIPING SUMP MUST BE WATERTIGHT. AFTER ALL PIPING AND
CONDUITS ARE INSTALLED AND BEFORE BACKFILLING AROUND
SUMP, THE SUMP SHALL BE TESTED AS FOLLOWS:
1. FILL PIPING SUMP FULL OF WATER.
2. VISUALLY CHECK FOR ANY LEAKS.
3. REPAIR ANY LEAKS.
4. AFTER ANY WATER LEAKS ARE REPAIRED, LEAVE
THE WATER IN PIPING SUMP OVERNIGHT AND VISUALLY CHECK
WATER LEVEL AND THE PIPING SUMP EXTERIOR FOR LEAKS.
5. IF LEAKS ARE DISCOVERED, REPAIR AND RETEST.
6. AFTER COMPLETION OF TESTING REMOVE ALL WATER FROM SUMP.
SHEET NOTES:
1. SET TANK AT THE DEPTH REQUIRED FOR
THE PRODUCT OR VENT LINE (3'-0" MIN.)
2. PRODUCT LINE TO HAVE A 1/4" PER 1'-0"
SLOPE UPWARD FROM TANK TO DISPENSER.
3. CONTACT LOCATOR SERVICE BEFORE DIGGING.
GASOLINE SUBMERSIBLE PUMPS
RED JACKET "EXTRACTA" MOTORS ARE OF EXPLOSION—PROOF CONSTRUCTION.
ELECTRICAL SERVICE INFORMATION
NTS
Model No.
HP
Volts
Max Load
Amps
Locked Rotor
Amps
Winding Resistance (Ohms),
Min.
Max.
BIk—Orange
Red—Orange
Blk—Red
AGP75S1
3/4
200
250
6.5
22
3.6-4.1
9.6-10.6
13.2-14.6
"ALL INSTALLATION WORK MUST COMPLY WITH LOCAL CODE REQUIREMENTS. IF NO OTHER CODES APPLY,
THE LATEST ISSUE OF THE NATIONAL ELECTRICAL CODE SHOULD BE FOLLOWED."
1. RED JACKET GASOLINE PUMPS ARE DESIGNED TO PUMP GASOLINE OR DIESEL FUELS ONLY HAVING A
MAXIMUM SPECIFIC GRAVITY OF .95 AND MAXIMUM VISCOSITY OF 70 S.S.U. AT 60DEG.. GASOLINE PUMPS
ARE NOT TO BE USED FOR GASOHOL BLENDS (A NEW CHEMICAL PUMP WOULD BE REQUIRED).
2. PUMPING WATER WILL OVERLOAD THE MOTOR AND DAMAGE THE BEARINGS.
3. RED JACKET GASOLINE PUMPS DESIGNED FOR CLASS 1 GROUP D ATMOSPHERE.
T
L
TEMPORARY OR
PERMANENT SHORING
TO BE INSTALLED WHEN
REQ'D. (TYP. ALL SIDES)
SLOPE EXCAVATION
TO ANGLE OF REPOSE
IF SHORING IS NOT'
REQ'D. (TYP. ALL SIDES)
BRINE RESERVOIR
TANK SENSOR
GAUGE (SEP. CIRCUIT)
M -51M-6
SAMPLE WELL
(TYP. OF 2)
M, .4,-5 5
SUMP
SENSOR
18"
t
STAGE II VAPOR RECOVERY/VENT
4" SPARE (PLUGGED)
SUBMERSIBLE PUMP
22" MANWAY W/ 3
4" NPT FITTINGS
TYP.
SUBMERSIBLE LINE SAMPLE SAMPLE 1
PUMP MONITOR WELL WELL
PIPING SUMP
BRINE RESERVOIR
CONC. SLAB 6" MIN. THICKNESS
TANK GAUGE
SPARE (PLUGGED) M-1 M -i
FILL
z
NEW TANK PLAN
NTS
COORDINATE PANEL LOCATIONS
ON WALL WITH OWNER
CONDUITS ONLY.
NO PROBES.
J—BOX
AT PUMP ISLAND
EXISTING CARD READER
L_
DISPENSER W/LIGHT
(4) 3/4" CONDUIT MUST BE PULLED
UP THROUGH 5" SQUARE,OPENING
AT BASE OF CARDREADER-STAND
PULSER
PULSER
SPARE
). )
115V AC DUPLEX OUTLET
(SUPPUED BY CONTRACTOR)
INSTALL PER RLM 9000
INSTRUCTIONS
RED JACKET 9000
TANK MONITOR/
ALARM SYSTEM
INTERFACE SIGNAL CABLE
PPM 4100
PUMP/ -1
MOTOR
RELAY I EXISTING
(PANEL
RE -USE (2) 3/4" CONDUIT
TO CARD READER
UNDERGROUND CONDUIT DIAGRAM
NOTES:
1. EXACT CONDUIT LOCATIONS AT PUMP ISLAND SHALL BE AS DIRECTED
BY OWNER. TERMINATE 6" ABOVE PUMP ISLAND, CAP AND PROVIDE PULL WIRE.
2. ALL CONDUIT TO AND FROM CARD READER SHALL BE RIGID STEEL.
3. ALL CONDUIT 3/4" UNLESS OTHERWISE NOTED.
NTS
t,,174'1
IPAN
READELER
L
1" SPARE
LJ
J
STUB IN SPARE CONDUIT
WITH PULL WIRE NEAR
PANEL AND CAP
PANEL LOCATION
IN BUILDING
SEE SITE PLANS FOR LOCATION
13,_0►�
MIN
O
i
QTANK
0
CV
cc
W
1--
Z
W
U
J
w
CL
0 1--
Q- Q
CL
(` V)
Z
0 0
10
2 W
0 CL
Ci
0
w
0
0
DATE:
8/27/92
SHEET TITLE:
UNDERGROUND
STORAGE TANK
DETAILS
SHEET NO.
M-5
[DESCRIPTION I
cn
z
0
FA
w
w
1—
0
d
z
0
CV
cc
W
1--
Z
W
U
J
w
CL
0 1--
Q- Q
CL
(` V)
Z
0 0
10
2 W
0 CL
Ci
0
w
0
0
DATE:
8/27/92
SHEET TITLE:
UNDERGROUND
STORAGE TANK
DETAILS
SHEET NO.
M-5
CNI #236R 40.25" ROUND MANHOLE
CONC. SLAB
2" SINGLE WALL FRP LINE.
STUB UP INSIDE DISP. HOLD
DOWN BOX AT ISLAND.
STAGE II VAPOR RECOVERY LINE
PIPING SUMP
4" VENT VALVE ASSEMBLY
1/4"/FT7
3/4" CONDUIT—PUMP CONTROLLER
LEAK DETECTION SENSOR.
W/ ENSOR (N BRINE RESERVOIR ERIES
2" SINGLE WALL FRP VENT LINE TO
VENT STACK. USE 2" TELEFLEX
CONNECTOR
4" MANWAY OPENING
1/16"DIA. VENT BLEED HOLE
2" OPW-53V FLOAT VENT
STEEL PROTECTOR PLATES
REMOTE PUMP W/4"
SCH. 40 RISER
1\-11 1\1
2" MIN.
PU P
rTANK TOP
PUMP CLEARANCE PER MFR'S
REQUIREMENTS
2" TELEFLEX CONNECTOR
SINGLE
NNPETIALVEN(COMBIEWITHINTRSTI
RESERVOIR VENT)
2" DOUBLE WALL FRP TO
PUMP ISLAND. (2" PRIMARY PIPE SIZE)
2"X2"X3/4" TEE
2" BALL VALVE
TRANSDUCER SUPPLIED BY OWNER
CONDUIT FOR LINE MONITOR TO
RED JACKET CONSOLE
FLEXIBLE CONDUIT
CONNECT MANWAY Sc PIPING SUMP
PER MFR'S INSTRUCTION
TANK BOTTOM
NOTES: _
1. CONTRACTOR TO VERIFY LENGTH OF SUBMERGED
PUMP UNIT Sc I.D. OF TANK.
2. CONTRACTOR SHALL PROVIDE WATERTIGHT
BULKHEAD FITTINGS ON ALL SUMP PENETRATIONS.
TOTAL CONTAINMENTI`OR APPROVED EQUAL.
22"I.D. MANWAY PRIME W/
POLYKEN 927
1/2"NPT FITTING IN MANWAY FOR AIR
REMOVAL DURING PETROTITE TESTING
CAP OFF 4" SPARE OPENING W/PIPE PLUG
REMOTE PUMP AND VENT
n INSTALLATIONS AT PIPING SUMP END
PREMIUM UNLEADED
PRODUCT DISPENSER
1 1/2" PIPE RISER W/
DISPENSER
1 1/2" UNION (FURNISHED
W/DISPENSER)
ATTACH "CAUTION FIBERGLASS
PIPE" TAG ON RISER BENEATH
DISPENSER
IMPACT SHUT—OFF VALVE
POSITION SHEAR SECTION PER
MANUFACTURER'S INSTRUCTION
3" CONTAINMENT COLLAR
SUPPLIED W/BRAVO
HOLD—DOWN BOX
NTS
TOP OF PUMP ISLAND
HOLD—DOWN BOX BRAVO SYSTEMS 200 SERIES
MODEL 2510-3 PROVIDED BY CONTRACTOR PER
MFR'S INSTRUCTIONS. PROVIDE BULKHEAD FITTINGS
FOR ALL PENETRATIONS.
3/4" CONDUIT
(3) PLACES TYP.
2" TELEFLEX CONNECTOR FOR
STAGE II VAPOR RECOVERY. CAP
OFF INSIDE HOLD—DOWN BOX.
2" NOMINAL I.D. "TELEFLEX"
FLEXIBLE CONNECTOR WITH
3"DIA x 36"LONG "FLEX
PROTECTOR" MANUFACTURED
BY AUSTIN ENGINEER GROUP
OR APPROVED EQUAL.
11 J 3" DOUBLE WALL FRP
2" PRODUCT PIPING
T
18" MIN.
ALL SECONDARY CONTAINMENT
FITTINGS SHALL BE (2) PIECE
CLAMSHELL TYPE.
--- 2"MIN. L4" MIN.
2" SINGLE WALL FRP VENT LINE
TO VERTICAL STACK.
3" FIBERGLASS PIPE CLAMP FITTING
DISPENSER INSTALLATION DETAILS
NTS
12" X 12" CONC. DEADMAN.
OLYMPIA FLEET AND SUPPLY
FILL
PREMIUM UNLEADED
o 0
15,000 GAL
FIBERGLASS TANK
SOUTH KING COUNTY
FILL
PREMIUM UNLEADED
12,000 GAL
FIBERGLASS TANK
1/8" THICK BRASS
'PLATE EMBEDDED INTO
CONC. NEAR FILL.
HOLE FOR BRASS NAIL.
DRIVE 1" INTO CONC.
NOTE:
CONTRACTOR T9 FABRICATE TAGS AND
STAMP. W%1/4 LETTERS AND NUMBERS.
PRODUCT TAG
LENGTH TO BE 24" LONGER
THAN TANK (2 REQ.).
CONSTRUCTION & INSTALLATION
PER MFR'S INSTRUCTIONS
NTS
1 1 1-1 I I
► 11� 11=11 I=111-111-111-111=1 11=111=111=!111=11 I-111-
1=1 El 11=I 1=1 i=l 11=I I H I 1=i i 1=1 11=I I I;
11-
n
M -5 M-6
TIE DOWN DETAIL
EQUIPMENT LIST
OWNER FURNISHED/CONTRACTOR INSTALLED
GAS PUMP RED JACKET MODEL AGP75S1
3/4 HP 220V/1/60 OR APPROVED EQUAL
UNDERGROUND STORAGE XERXES CORP., MODEL HYDROGUARD
TANK DWT -TYPE= II. 8'0, 12,000 GAL (SOUTH KING COUNTY)
DWT-TYPEIII. 10'0, 15,000 GAL (OLYMPIA FLEET AND SUPPLY)
XERXES, WATERTIGHT
SUMP
OVERSPILL CONTAINMENT
DISPENSER
AIR/WATER REEL
TANK MONITOR
PUMP MOTOR RELAY
OPW-1 OR EBW 5 GALLON CONTAINMENT SYSTEM.
TOKHEIM MODEL 785 -1 -RC -APC DOUBLE HOSE
SINGLE PRODUCT. INCLUDES TOKHEIM HOSE
BREAKAWAY MODEL 697EBW, (2) 3/4" HOSES W/WHIP,
(2) 100 SERIES VAPOR RECOVERY HOSE RETRACTORS,
MODEL #100-6, (2) HEAVY DUTY, HIGH HOSE, 1-1/2" SQ.
TUBING MTG POSTS AND HARDWARE FOR 3/4"x14' HOSES
AND (2) OPW MODEL 11AP-B UNLEADED NOZZLES
COXWELL CRUT-125-125 W/ELECTRIC HEATER & AUTOMATIC
THERMOSTAT. 1/4" X 25' AIR AND WATER HOSES ON LOCKING
RETRACTABLE REELS COMPLETE W/STAINLESS STEEL
LOCKABLE TOP
RED JACKET RLM 9000 SERIES MODEL 400-062-5RJ TANK MONITOR
SYSTEM WITH RED JACKET RJ 400-098-5 INVENTORY SENSOR
AND RED JACKET RJ LINE PRESSURE SENSOR KIT. INCLUDES RED
JACKET SYSTEM START-UP
RED JACKET MODEL 880-029
N.T.S.
4"
0
J
PIPE
SECTION
TANK
HOLD-DOWN STRAPS
TANK
BOTTOM
ELEV.
SCHED. 40 PVC CAP
12"DIA. OPW 104—MV MANHOLE
W/9" SKIRT AND BOLT DOWN LID.
OPW 633—TCP-4 ADAPTOR
OPW 634—TT CAP
GRAVEL
FILL
\-3/4" CONDUIT TO ALARM LOCATION
SEAL OFF END.
•
1/8" x 6" SLOTS
CUT IN PIPE
NOTE:
PROVIDE 4" SCHED. 40 FACTORY
LOTTED PVC WELLSCREENS
MAX. 0.05 SLOTS ALTERNATE:
" SCHED. 40 PV PIPE W/
CONTINUOUS SLOT EFFECT AS
SHOWN IN DETAIL
SAMPLE WELL
M-5 M-6
SPARE
r
(2 TYPICAL)
SPARE
FILL
NTS
INSTALL 4"
OIPEPLN
NSPARE
TANK OPEN—
ING
c
/—\
(3) STEEL PROTECTOR
PLATES
/n\
•
11
OPW 633—TCP-4
ADAPTOR
OPW 634—TT CAP
2," MIN.
[4 MAX.
t
SPILL CONTAINER
PRODUCT TAG
AND NAME PLATE
HOLDER (TYP.)
4" SCH 40 PIPE RISERS.
TO BE PRIMED Sc WRAPPED.
OPW-61 SOC
DIMENSION PER MFR'S
INSTRUCTIONS
\U/
\ 1/
\U/
TANK CONNECTIONS
AT FILL END
NTS -
HIGH LEVEL SHUT—OFF
0
N
crN
wl
W
00
1---
z
w
w
Q
J
w
aQ �-
o
Q V) (NJ
1- a)V)o
z
o o z
ct
zcw
w -�
(/)c o
Q z o%
a.
1-=
0
w
0
0
DATE:
8/27/92
SHEET TITLE:
UNDERGROUND
STORAGE TANK
DETAILS -
DESCRIPTION I
ul
z
0
(75
w
DATE
d
z
0
N
crN
wl
W
00
1---
z
w
w
Q
J
w
aQ �-
o
Q V) (NJ
1- a)V)o
z
o o z
ct
zcw
w -�
(/)c o
Q z o%
a.
1-=
0
w
0
0
DATE:
8/27/92
SHEET TITLE:
UNDERGROUND
STORAGE TANK
DETAILS -