14201 INTERURBAN AVE S ASSOCIATED PERMITS 19-5-232 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Galliano's Mixed Use 14201 Interurban Ave S. Permit No.: 19-S-232 Date: December 3, 2019 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe. Section 18.5.5. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions. Section 18.4. • Longitudinal sway tracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line. Section 18.5.6. • Provide lateral and longitudinal bracing for changes in pipe direction per section 18.5.7. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement. Section 18.6. • Restraints for branch lines shall be at intervals per table 18.6.4 (a(b) and section 18.6, and restrain sprig ups greater than 4. Section 18.6.6. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • All valves controlling the water supply for automatic sprinkler systems and waterflow switches on all sprinkler systems shall be electrically supervised. • All interior control valves shall be readily accessible, labeled and located not more than 6 ft. above the floor. • Provide sprinkler protection beneath all stairs per NFPA 13, 9.3.4. • Elevator hoistways shall comply with NFPA 13 Section 9.3.6. • Each floor of a multi -story building shall have sectional control valves and waterflow switches. • Install Knox locking caps on all dry standpipe hose connections and FDC's. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more sprinkler heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a Toss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. • Weld stamps shall be inspected on the ground, before pipe is hung. • The main drain to be plumbed to sanitary sewer. • Maintain a 4 foot clear space around the sprinkler riser(s) for emergency access. • Provide a spare sprinkler head and wrench box at the riser. • When the sprinkler rise is located inside a room, the door to the room shall have a sign with one -inch letter which reads "SPRINKLER RISER". • A fire department connection (FDC) is required. The FDC shall have a 30 degree down bend with a 5 -inch Storz fitting and Knox locking Storz cap. • The height of the FDC shall be 36 to 48 inches above grade. • FDC's shall be oriented in the direction of fire apparatus access, have a 4 foot clear space in front and to the sides of the connection , be appropriately signed, have the building address served by the FDC stenciled vertically in 3 -inch high white numbers on a "safety red" background directly beneath the hose connection facing the direction of vehicular access, and protected from vehicular damage. • The FDC shall be within 50 ft. of a fire hydrant. • An electrically supervised post indicating or wall indicating valve (PIV,WIV) is required. • Post Indicator Valves (PIV's) shall have the building address served by the PIV stenciled vertically in 3 -inch high white numbers on a "safety red" background, facing the direction of apparatus access. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2019 Edition. SITE PLAN 1" vtV (oc 4o 104.5 SDo (X0401 Gad qnA INTERURBAN AVE SOUTH EXISTING FIRE HYDRANT N 0 Withoin.. Comments As1lot'�.135( red. Per The acted Letter These plans have been reviewed :,y The Tukwila Fire =- vention Bureau for conformance with current City endards. Acceptance is subje -1`) errors and :nisslons which do not authorize violations of adopted :dards and ordinances. The resp ns bility for the guacy of design rests totally Mtn u e designer. ;dditions, 'deletions or revisions to there drawings after tis date will void this 7,icceptance and val require a resubmit) of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: ()--5 -19 By: Fire Permit Number nt - s - To schc,,cluie tnspccfions coil 206-575-4407 GALLIANO'S RESTAURANT GENERAL NOTES 01. SEE THE FIRE PROTECTION EQUIPMENT DATA FOR ALL APPLICABLE MATERIALS AND EQUIPMENT INSTALLED UNDER THIS CONTRACT. 02. THESE FIRE PROTECTION PLANS AND CALCULATIONS HAVE BEEN DESIGNED WITH THE INTENT OF COMPLYING WITH ALL NFPA 13, 2016, STATE CODES, AND THE REQUIREMENTS OF THE LOCALAUTHORITY HAVING JURISDICTION. 03. ALL MATERIALS, DEVICES, AND HANGERS INSTALLED UNDER THIS CONTRACT SHALL BE UL LISTED AND/OR FACTORY MUTUAL APPROVED. 04. ALL MATERIALS, DEVICES, AND HANGERS SHALL BE INSTALLED IN ACCORDANCE WITH THEIR LISTINGS AND NFPA 13, 2016 05. ANY AND ALL ELECTRICAL AND/OR ALARM WIRING, CONNECTIONS AND TERMINATIONS, SHALL BE PROVIDED BY OTHERS. 06. IT SHALL BE THE SOLE RESPONSIBILITY OF THE OWNER TO PROVIDE, INSTALL AND MAINTAIN AN APPROVED MONITORING SYSTEM OF ALL FIRE PROTECTION SYSTEM, ELECTRICAL COMPONENTS AND/OR ANY OTHER COMPONENTS AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION. 07. IT SHALL BE THE SOLE RESPONSIBILITY OF THE OWNER TO PROVIDE ADEQUATE HEAT THROUGHOUT THE FACILITY WHERE' WET' PIPE SPRINKLER SYSTEMS ARE PRESENT, TO PREVENT FREEZING OF SPRINKLER SYSTEM COMPONENTS (MIN +0° F). 08. THE OWNER SHALL MAINTAIN A CLEAR SPACE OF 18" BETWEEN THE TOP OF STORAGE AND STANDARD SPRINKLERS. 09. ALL SPRINKLER PIPING PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE SEALED WITH AN APPROVED MATERIAL EQUAL TO THE RATING OF SUCH ASSEMBLY. SEE DETAIL FOR REFERENCE. 10. ALL NEW SPRINKLER PIPING INSTALLED UNDER THIS CONTRACT SHALL BE HYDRO-STATICALLYTESTED IN ACCORDANCE WITH ALL APPLICABLE NFPA ENGINEERING STANDARDS AND STATE AND LOCAL CODES. 11. UPON SUCCESSFUL INSTALLATION AND COMPLETION, THE FIRE PROTECTION CONTRACTOR SHALL PROVIDE AND INSTALL A SPARE SPRINKLER HEAD BOX WITH ADEQUATE SPRINKLERS AND WRENCHES PER NFPA REQUIREMENTS. PROVIDE AND INSTALL HYDRAULIC CARDS, AND 24 HOUR PHONE NUMBER SHALL BE POSTED. PROVIDE COMPLETE OPEP.ATIONS AND MAINTENANCE MANUALS, AND COMPLETE CONTRACTORS MATERIALS AND TEST CERTIFICATES. INSURE ALL SYSTEM CONTROL VALVES SHALL BE LEFT FULLY OPEN AND IN SERVICE INSURE ALL SYSTEM DEVICES SHALL BE IDENTIFIED PER NFPA REQUIREMENTS. 12. ADEQUATE DRAINAGE OF FIRE PROTECTION PIPING SHALL BE PROVIDED PER NFPA REQUIREMENTS. 13. CHLORINATION OF FIRE PROTECTION PIPING IS NOT PART OF THE INSTALLING FIRE PROTECTION CONTRACTORS WORK 14. PAINTING OR PRIMING OF FIRE PROTECTION PIPING IS NOT PART OF THE INSTALLING FIRE PROTECTION CONTRACTORS WORK 15. FIRE EXTINGUISHERS AND CABINETS ARE NOT PART OF THE INSTALLING FIRE PROTECTION CONTRACTORS WORK 16. PROTECTION OF ELECTRICAL DEVICES, SUCH AS CIRCUIT BREAKER PANELS FROM WATER DISCHARGE IS NOT PART OF THE INSTALLING FIRE PROTECTION CONTRACTORS WORK. 17. ALL REQUIRED INTERIOR/EXTERIOR DOOR SIGNAGE SHALL BE PROVIDED AND INSTALLED BY OTHERS. 18. ALL EARTHQUAKE BRACING TO BE IN ACCORDANCE WITH NFPA-13. 19. LISTED FLEXIBLE COUPLINGS SHALL BE PROVIDED ON ALL 21/2"AND LARGER PIPE, 20. FLEXIBLE COUPLING SHALL BE LOCATED IN ACCORDANCE WITH NFPA-13 AS FOLLOWS: A. WITHIN 24" OF THE TOPAND BOTTOM OF ALL RISERS. B. WITHIN 12" ABOVE AND BELOW FLOORS IN MULTISTORY BUILDINGS. C. WITHIN 3 FEET OF ALL CONCRETE AND MASONRY WALL PENETRATIONS. D. AT OR NEAR BUILDING EXPANSION JOINTS. E. WITHIN 24" OF THE TOP OF DROPS EXCEEDING 15 FEET IN LENGTH TO PORT. )NS OF SYSTEMS SUPPLYING MORE THEN ONE SPRINKLER, REGARDLESS OF PIPE SIZE. F. ABOVE AND BELOW ANY INTERMEDIATE POINTS OF SUPPORT FOR A RISER OR OTHER VERTICAL PIPE. 21. CLEARANCE SHALL BE PROVIDED AROUND ALL PIPING EXTENDED THROUGH WALLS, FLOORS, PLATFORMS, AND FOUNDATIONS, INCLUDING DRAINS, FIRE DEPARTMENT CONNECTIONS, AND OTHER AUXILIARY PIPING. 22. LONGITUDINAL SWAY BRACING SPACED ATA MAXIMUM OF 80 FEET SHALL BE PROVIDED FOR FEED AND CROSS MAINS. (NOT REQUIRED WHEN RODS ARE LESS THEN 6 IN. LONG) 23. TOPS OF RISER SHALL BE SECURED AGAINST DRIFTING IN ANY DIRECTION, UTILIZING A FOUR-WAY BRACE. 24. LATERAL SWAY BRACING SPACED ATA MAXIMUM OF 40 FEET SHALL BE PROVIDED FOR FEED AND CROSS MAINS. (NOT REQUIRED WHEN LESS THAN 6" FROM TOP OF PIPE TO ATTACHMENTTO STRUCTURE) 25. BRACING SHALL BE ATTACHED DIRECTLY TO FEED AND CROSS MAINS. 26. THE LAST LENGTH OF PIPE ATTHE END OF FEED OR CROSS MAIN SHALL BE PROVIDED WITH A LATERAL BRACE. LATERAL BRACES SHALL BE ALLOWED TO ACTAS LONGITUDINAL BRACES IFTHEYARE WITHIN 24 INCHES OF THE CENTERLINE OF THE PIPING BRACED. 27. BRANCHLINE RESTRAINT IS REQUIRED WHEN PIPE IS MORE THAN 6" FROM DECK 28. THE END SPRINKLER ON EACH BRANCHLINE SHALL BE RESTRAINED AGAIA NST EXCESSIVE MOVEMENT BYAPPROVED MEANS. 29. C -TYPE CLAMPS (INCLUDING BEAM AND LARGE FLANGE CLAMPS), WITH OR WITHOUT RETAINING STRAPS, SHALL NOT BE USEDTOATTACH BRACES TO THE BUILDING STRUCTURE. SCOPE OF WORK Z >. re0 GLACIER FIRE PROTECTION WILL P AUTOM SPR TO THE REQUIREMENT E AND ONE DRY NFPA 13. 2 1= 0 LL LL LL h LL 0 U m L a 0 EXCLUSIONS PAINTING OR LABELING OF PIPE AND/OR EQUIPMENT ELECTRICAL WIRING OF ANY KIND INCLUDING BUT NOT LIMITED il`S i'(I TER SWITCH, ELECTRIC BELL, AND TAMPER SWITCHES CENTRAL STATION MONITORING EQUIPMENT, WIRING AND SERVICES CEILING AND WALL REMOVAUREPLACE TO FACILITATE THE INSTALLATION OF THE SPRINKLER SYSTEM. UNDERGROUND WORK OF ANY KIND a DESIGN CRITERIA TYPE VA SPRINKLED 1ST FLOOR -1599 SQ FT TYPE B & 5532 SQ FTTYPE U PRIVATE GARAGE 2ND FLOOR - 6016 SQ FT TYPE R-2 & 192 SQ FT COVERED DECK & 860 SQ FT UNCOVERED 3RD FLOOR - 4984 SQ FTTYPE R-2 & 192 SQ FT COVERED DECK & 1032 SQ FT UNCOVERED PER NFPA 13 (2016) RM -01 (PARKING GARAGE) THE DENSITY SHALL BE .15 GPM/SF OVER THE MOST REMOTE 1500 SQ FT. AREA SHALL BE INCREASED 30% FOR A DRY SYSTEM TO A .15 GPM/SF OVER THE MOST REMOTE 1950 SQ FT. 130 SQ FT MAX SPACING RM -02 (RESIDENCE) THE DENSITY SHALL BE 13 GPM/SF OVER THE MOST REMOTE 5 SPRINKLERS WITHIN A CORRIDOR. 16'-0 x 164-0 MAX SPACING WATER FLOW INFORMATION 0) 32 C c% (1) CO LL 01 00 uri to to. D rn co ti r N O 2 Z co to 8 0 Lal ce LL (0 M g 1n v 0 it m co 1 m .01 3) 0 .71N IX NORTH WATER FLOW INFORMATION PROVIDEDTUKWILAWATER PUBLIC WORKS STATIC: 155 PSI RESIDUAL: 20 PSI FLOW: 5492 GPM DRAWING INDEX FP 0.00 FP 0.10 FP 2.10 FP2.20 FP 2.30 SITE PLAN AND NOTES DETAILS MAIN LEVEL SPRINKLER PLAN SECOND LEVEL SPRINKLER PLAN THIRD LEVEL SPRINKLER PLAN GLACIER FIRE PROTECTION LLC PO BOX 7980 BONNEY LAKE, WA 98391 P: (253)501-7558 www.glacierfireprotection.com GLACIFP834MJ f-i.w.w.-wwwww_w.._wwwww_wweww. I WASHINGTON STATE • • CRIRIfICATI OF COMPITENCY N I• FI PROTECTION SPRINKLER i I • Erin Clayton 1 I 7544.08174 Level3 I I©4Protection, L.L.C. I LACIFPS3MJ 11 a 10/3012019 Interurban Ave South 88168 SCALE: 1/8" =1'-0" DRAWN BY: Erin Clayton REVISIONS DESCRIPTION FLOOR/AREA SITE PLAN AND NOTES CEILING CEILING TOPEN WEB STEEL 1 OR WOOD TRUSS OBSTRUCTION ELEVATION VIEW A GREATER THAN 3C or 3D (U E DA�R) SION C OR D WHICHEVER FIGURE 8.6.5.2.1.3 MINIMUM DISTANCE FROM OBSTRUCTION (SSU/SSP) ELEVATION VIEW FIGURE 5-6.5.1.2 (a) POSITIONING OF SPRINKLERS TO AVOID OBSTRUCTION TO DISCHARGE (SSU/SSP) TABLES & FIGURES LISTED ABOVE ARE FROM NFPA 13, 2013 ed. NFPA copyright 2007 INDIVIDUAL UL/FM LISTING REQUIREMENTS MAY VARY FROM THOSE FOUND ABOVE. SEE MANUFACTURERES LITERATURE FOR COMPLETE SPRINKLER HEAD PERFROMANCE INFORMATION OBSTRUCTION INFORMATION SCALE: N.T.S. MIN. DISTANCES FOR TEMPERATURE RESIDENTIAL SPRINKLERS HEAT SOURCE 165 DEGREE 1" 200 DEGREE 1 1/2" 2" 2 1/2" 3" SIDE OF OPEN OR RECESSED FIRE PLACE 36 in 8" 12 in FRONT OF RECESSED FIREPLACE 60 in LD.' 36 in COAL -OR WOOD BURNING STOVE 42 in I.D. 12 in KITCHEN RANGE 18 in THREADED LIGHTWALL 9 in WALL OVEN 18 in 12-0 9 in HOT AIR FLUES 18 in N/A 9 in UNINSULATED HEAT DUCTS 18 In N/A 9 in UNINSULATED HOT WATER PIPES 12 in 2.104 6 in SIDE OF CEILING OR WALL MOUNTED HOT AIR DIFFUSERS 24 in 15-0 12 in FRONT OF WALL MOUNTED HOT AIR DIFFUSERS 36 in NIA 18 In HOT WATER HEATER OR FURNACE 6 in 2.365 3 in LIGHT FIXTURE N/A N/A EDDYTHREAD 0W -250W 6 in 1.425 3 in PER NFPA 13D TABLE 7.5.5.3 PIPE SPECFICATIONS NOMINAL PIPE SIZE (IN.) 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4" 6" 8" INDIDE DIAMETER LD. I.D. LD.' 1.D. I.D. I.D. I.D. LD. I.D. I.D. THREADED LIGHTWALL N/A 12-0 12-0 12-0 12-0 12-0 N/A N/A N/A N/A DYNA-THREAD N/A 1.080 1.408 1.639 2.104 12-0 12-0 15-0 15-0 15-0 DYNA-FLOW N/A NIA 1.836 1.728 2.203 2.365 3.314 4.310 N/A N/A EDDYTHREAD .0856 1.090 1.425 1.655 2.124 1 Flom and Strobe by others EDDYFLOW N/A NIA 1.5`15 1.734 2.209 2.729 3.342 4.316 E -Z FLOW N/A NIA NIA N/A N/A NIA N/A 4.300 6.369 SCHEDULE 40 N/A 1.049 1.380 1.6"10 2.067 2.469 SCHEDULE 10 .874 1.4971.442 1.682 2.157 2.635 3.260 4.260 5.295 6.357 COPPER 1.101 1.3941.598 2.003 CPUC PER NFPA 1 2013 ED. CEILING CEILING TOPEN WEB STEEL OR WOOD TRUSS Round to Nearest Inch m ELEVATION VIEW A GREATER THAN 4C or 4D (USE DIMENSION C OR D, WHICHEVER IS GREATER) FIGURE 8.8.5.2.1.3 MINIMUM DISTANCE FROM OBSTRUCTION (EXTENDED COVERAGE UPRIGHTS & PENDENTS) ELEVATION VIEW FIGURE 8.8.5.1.2(a) POSITIONING OF SPRINKLERS TO AVOID OBSTRUCTION TO DISCHARGE (EXTENDED COVERAGE UPRIGHTS & PENDENTS) 54O‘ t.516-60 1a 4- All Thread Rod `6 FIRE DEPARTMENT CONNECTION SCALE : N.T.S. HANGER SPACING LEGEND NOMINAL PIPE SIZE (IN.) 3/4" 1" 1 1/4" 1 1/2"" 1 21/2" 3" 4" 6" 8" >TL PIPE SCH 40, SCH 10, DF,EF N/A 12-0 12-0 1-0 15-0 15-0 15-0 15-0 15-0 15-0 THREADED LIGHTWALL N/A 12-0 12-0 12-0 12-0 12-0 N/A N/A N/A N/A COPPER 8-0 8-0 10-0 '1 t' -0 12-0 12-0 12-0 15-0 15-0 15-0 CPVC 5-6 6-0 6-6 7-0 8-0 9-0 10-0 N/A N/A N/A PER NFPA 13 5.2.2.1 (A) SYSTEM SENSOR 24V EXTERIOR FLASHING LIGHT AND HORN. SUBJECT DEVICE IS PROVIDED BY OTHERS AS WELL AS ALL REQUIRED MOUNTING, MONITORING, WIRING AND SUPERVISION. THE INSTALLING CONTRACTOR SHALL VERIFY THE FINAL LOCATION WITH THE LOCAL AUTHORITY PRIOR TO MOUNTING. ROUGH BRASS, 4 x 21/2 x 2112 NST YARD FDC CONNECTION PROVIDED AND INSTALLED B Y OTHERS. CONNECTION SHALL BE LOCATED FROM 18" MINIMUM TO 48" MAXIMUM ABOVE FINISH GRADE, w/ PLATE LABELED "AUTO-SPKR", RED BREAK CAPS. REFER TO CIVIL FOR LOCATION. WOOD BEAM SPRIG DETAIL TYPICAL HANGER DETAIL #5 EARTHQUAKE BRACE LEGEND TOtCO FIG. SI909, #910, OR EQUIV. TABLES & FIGURES LISTEDABOVEARE FROM NFPA 13, 2007 ed. NFPA copyright 2007 INDIVIDUAL UL/FM LISTING REQUIREMENTS MAY VARY FROM THOSE FOUND ABOVE. SEE MANUFACTURERES LITERATURE FOR COMPLETE SPRINKLER HEAD PERFROMANCE INFORMATION OBSTRUCTION INFORMATION SCALE: N.T.S. SCALE : N.T.S. SCALE : N.T.S. = FOUR-WAY BRACE LOCATED AT TOP OF ALL RISERS "� \ `,------.._,_„..... TOLCO FIG. #4A OR EQUIVALENT 1 Sammy Screew POSITIONING OF SPRINKLERS TO AVOID OBSTRUCTION TO DISCHARGE (SSU/SSP) DISTANCE FROM SPRINKLERS TO SIDE OF OBSTRUCTION (A) LESS THAN 1' 1' TO LESS THAN 1'-6" 14-6" TO LESS THAN 2'4' 7-0" TO LESS THAN 2'-6" 7-6" TO LESS THAN 3'-0" 3'-0" TO LESS THAN 3'-6" 3'-6" TO LESS THAN 4'-0" 4'-0" TO LESS THAN 4'-6" 4'-6" TO LESS THAN 5'4' 5'-0" AND GREATER I -BEAM - TOP BEAM CLAMP = LATERAL BRACE LOCATED AT MAXIMUM OF 40 FEET ON CENTER FOR ALL FEED AND CROSS MAINS 1" SCHEDULE 40 PIPE / 3/8" All Thread Rod Pre -Drill Hole FEED OR CROSS MAIN = LONGITUDINAL BRACE LOCATED AT MAXIMUM OF 80 FEET ON CENTER FOR ALL FEED AND CROSS MAINS FOUR-WAY BRACE SCALE : N.T.S. GLACIER FIRE PROTECTION LLC PO BOX 7980 BONNEY LAKE, WA 98391 P: (253)501-7558 WVVUb.g acierftreprotedion.com GLACIFP834MJ MAXIMUM ALLOWABLE DISTANCE OF DEFLECTOR ABOVE BOTTOM OF OBSTRUCTION (IN.) (B) 0 2-1/2" 3-1/2" 5-1/2" 7-1/2" 9-1/2" 12" 14" 16-1/7' 18" PER NFPA 13 8.6.5.1.2 ALL THREAD ROD - DROP DETAIL SCALE : N.T.S. SWIVEL RING HANGER SPRINKELR PIPE TYPICAL HANGER DETAIL #1 SCALE : N.T.S. (Fig. 1000) Fast Clamp Sway Brace Attachment Structural Fastener TYPICAL HANGER DETAIL #6 SCALE : N.T.S. (A\ SPRINKLER RISER DETAIL SCALE: NTS (Fig. 909) Sway Brace Attachment or equal 1" Pipe, Schedule 40 BRANCH LINE 1" GLOBE VALVE Side Sammy Screw eral Brace POSITIONING OF SPRINKLERS TO AVOID OBSTRUCTION TO DISCHARGE (EXTENDED COVERAGE UPRIGHTS & PENDENTS) DISTANCE FROM SPRINKLERS TO SIDE OF OBSTRUCTION (A) LESS THAN 1' 1' TO LESS THAN 1'.6" 1'-6" TO LESS THAN 7-0" 2'-0" TO LESS THAN 7-6" 2'-6" TO LESS THAN 3'-0" 3'-0" TO LESS THAN 3'-6" 3'-6" TO LESS THAN 4'-0" 4'4' TO LESS THAN 4'-6" 4'-6" TO LESS THAN 5'-0" 5'-0" TO LESS THAN 5'-6" 5'-6" TO LESS THAN 6'-0" 6'-0" TO LESS THAN 6'-6" 6'-6" TO LESS THAN 7-0" 7-0" AND GREATER 1 BEAM MAXIMUM ALLOWABLE DISTANCE OF DEFLECTOR ABOVE BOTTOM OF OBSTRUCTION (IN.) (B) 0 0 (Fig. 4L) UL Listed Pipe Clamp for Sway Bracing (FIg. 980) Universal Swivel Sway Brace Attachment Structural Fastener Pipe 26 ,o d (Fig. 909) Sway Brace Attachment or equal 1" GLOBE VALVE 1" 1" Pipe, Schedule 40 1" 1" 3" 3" 5" 7" 7 7" 9" 11" 14" SPRINKLER PIPE IVEL RING HANGER DRUM DRIP DRAIN TYPICAL L SPRINKLER RISER MATERIAL LIST Item Number Quantity Size icrlplon Manufacturer 1 1 4" Gr Flange 2 1 4" Gr SS Put Piece 3 1 3" C200 BFG Double Check ow Ames 4 1 21/2" Buerfly Velve 5 1 2 1/2" Ex Lour Pressure Dry Valve Reliable 6 1 Riser Mount Air Compressor 7 1 2 1/2" Butterfly Valve Reliable 8 1 2 1/2" Riser Manifold Flow Switch, Gauge, Drain 9 1 3" Check Valve 10 1 3" x 4" Feed to F.D.C. 11 1 Flom and Strobe by others PARCEL # 3365901480 1" PIPE SCALE : w.T.s. Longitudinal Brace ARMOVER DETAIL SCALE : N.T.S. TYPICAL HANGER DETAIL #2 SCALE : N.T.S. ZIT°11tidsopeaNDPAril 1"45 GALVANIZED ELBOW WITH ANT PER NFPA 13 8.8.5.1.2 DRY SYSTEM NOTES DRY SYSTEM INSPECTORS TEST/ DRUM DRIP SCALE : N.T.S. 1. DRY SYSTEM PIPING TO BE SCHEDULE 10AND SCHEDULE 40 BLACK STEEL PIPE w/ BLACK FITTINGS. 2. SYSTEM DESIGN: PARKING GARAGE - ORDINARY HAZARD GROUP 1 : 12'-6 x 10'-O UNO 250 GPM HOSE ALLOWANCE 1 ?SUPPLY 2 1" GLOBE VALVE 2x 1 RED. COUPUNG 2x1'.0" 1" SHO NIPPLE & CAP AT4'-a"AFF 3. ALL DRY SYSTEM MAINS & CROSSMAINS TO BE INSTALLED WITH A MINIMUM PITCH OF 1/4" EVERY 10 FEET. BRANCHLINES TO BE INSTALLED WITH A MINIMUM PITCH OF 1/2" EVERY 10 FEET. 4. LOW DRAINS (DRUM DRIPS) SHOULD BE INSTALLED WHERE THERE ARE TRAPPED AREAS IN THE SYSTEM. 5. DRY SYSTEM VOLUMES = 77.16 GALLONS DRY SYSTEM SCALE: 1/4" =1'-0' REVISIONS DESCRIPTI DRUM DRIP DETAIL r•••_-_•-•IIII_wn_•••r_•-n_s__as-1 V W T STATE II II T'EOF CONWETERCY II FIRE PR Tllt EP SYSTEMS a ■ Erin Clayton a 7544-0817-0 Level3 a Glacier Fire Protection, L.L.C. II 8 GLACIFP834MJ a 1 08/05/2019 Signature FP 2.10 ✓ eassonsonsfunanymmosnammunrese DATE: 10131/19 CONTRACT 5:60002 FLOOR /AREA DETAILS AND NOTES SHEET NUMBER 2 of 5 CORE AND SHELL 5.-71/2 REST ROOMS REST ROOMS FIELD VERIFY ELEVATIONS AND +SEI OBSTRUCTIONS ELEVATOR STAIRS; _.L 0 GLACIER FIRE PROTECTION LLC PO 80X 7980 BONNEY LAKE, WA °. 1 P: (253) 501-7558 www.glaciereprotection.com GLACIFP834MJ REMOTE AREA #1 Hydraulic Information Remote Area 1 OCCUP Y CLASSIFICATION Ord nary Group I DENSITY (8pm/ft2) 0.18 for 15 fft2 r unl 1 1 ) TOTAL HOSE STREAMS250.t>o DRIr CAPACITY , 77.1 TOTAL HEADS FLOWING 19 K -FACTOR 5.6 TOTAL WATER REQUIRED 726.08 TOTAL SSURE REQUIRED 130.927 BASE of RISER (gpm) 726.08 BASE of RISER (psi) 130.527 SAFETY MARGIN (psi) +20.576 (13.8°,) PARCEL # 3365901480 =III= =ME COM 1111111011 110112:111 11111112111 ICI= =I =I 1110=21 12111001 11011101111 =11 CI2110 10'-1'/2 .OM HEAT TRACE OR HEATED SOFFIT TO BE PROVIDED TO WET PIPE PROVIDED BY OTHERS PARKING GARAGE SCALE: 1/4"=1'-0" 0'-6 12'-6 REVISIONS DESCRIPTION Nov 1, 2019] WASHINGTON STATE CERTIFICATE OF NCY FIRE PROTECTION E R SYSTEMS Erin Clayton 7544-0817-C Level 3 Glacier Fire Protection, L.L.C. GLACIFP834M.1 DATE: 10/31/19 CONTRACT #:80002 FLOOR /AREA FIRST FLOOR SHEET NUMBER FIRST FLOOR SCALE :114" =1'-0 08/06/2018 COVERED BALCONY COVERED BALCONY BEDROOM LIVING T -10Y2 8'-0 8%0 -3 41111k 411111 ler MASTER BEDROOM STAIRS MASTER BEDROOM CLOSET ENTRY KITCHEN FIELD VERIFY ELEVATIONS AND CEILING1 OBSTRUCTIONS 7'-9Y2 11/2 1Y2 1'/2 11/2 1Y2 ENTRY ENTRY 1 V-11,2 KITCHEN 1 *-111/2 0 KITCHEN BEDROOM DINING BEDROOM 8'-0 LIVING OPEN BALCONY SECOND FLOOR OPEN BALCONY OPEN BALCONY Nov 1, 2019] ✓ mommISIIIVINIMINIIIMINU11101UNIIMINMEIONIMIllal 1 1 1 1 1 1 1 11 WASHINGTON STATE • CERTIFICATE OF COMPSTINICY FIRE PROTECTION SPRINKLER SYSTEMS • Erin Clayton 7544-0817-C Level 3 • Glacier Fire Protection, L.L.C. 1 GLACIFP834MJ 1 08/05/2019 Signature Oiseneseamemanwinumeimempoomemomosei Sprinkler Legend .ce a ce3 a) u. to '10 LL 1!--) 0 0) .2 es z• 4.1 a. 01 .2 0 co. LL 6 3 .2 a .2 .2 t1 to D (c1 10 co 1-• a CZ '11". 3 co 00 NORTH GLACIER FIRE PROTECTION LLC PO BOX 7980 BONNEY LAKE, WA 98391 P: (253) 501-7558 www.glacierfireprotection.com GLACIFP834MJ PARCEL # 3365 1480 'Cr z 001 ce —J z CO 0 1 2 3 4 5 6 SCALE: 1/4" = V-0" DRAWN BY: ERIN CLAYTON REVISIONS NO. DESCRIPTION DATE: 10/31/19 CONTRACT 9:13= FLOOR /AREA SECOND FLOOR SHEET NUMBER FP 2.30 4 015 BEDROOM COVERED BALCONY LIVING MASTER BEIM MASTER BEDROOM STAIRS STAIRS CLOSET KITCHEN KITCHEN CLOSET ENTRY CORRIDOR FIELD VERIFY ELEVATIONS AND CEILING OBSTRUCTIONS 11/2 —10'-101/2 11/2 O'-6 0'-6 GLACIER FIRE PROTECTION LLC PO BOX 7980 BONNEY LAKE, WA 98391 P: (253) 501-7558 www.glacierfireprotection.oam GLACIFP834MJ CLOSET CLOSET BEDROOM ENTRY KITCHEN PARCEL # 3365901480 KITCHEN LIVING H drau ic Information Remote Area 2 OCCUPANCY CLASSIFICATIONResidential DENSITY gpmfft2) 0.10 for (Actual 431ft2) TOTAL HEADS FLO , K -FACTOR 4,9 TOTAL WATER REQUIRED 156.53 TOTAL PRESSURE REQUIRED 48.268 BASE of SER (gpm) 156.53 BASE of RISER (psi) 48.258 SAFETY MARGIN (psi) + 106.555 (:,: .8%) BEDROOM MASTER BEDROOM REMOTE AREA #2 BEDROOM OPEN BALCONY BALCONY BELOW BALCONY BELOW BALCONY BELOW pmespensesimmeamegansimenumenimieweseponseming WASHINGTON STATE 1 CERTIFICATE OF COMPETENCY FIRE ravrecnoti spasm= *wrests Erin Clayton 7544-0817-C Level 3 Glacier Fire Protection, LLC. GLACIFF8341VM REVISIONS NO. DESCRIPTION DATE: 10/31/19 CONTRACT #:60002 FLOOR /AREA THIRD FLOOR SHEET NUMBER Tutor% ci "no