HomeMy WebLinkAboutPP - 13504 TUKWILA INTERNATIONAL BLVD - PACIFIC VILLAGE APARTMENTS - PERMITS AND PLANS13504 TUKWILA INTERNATIONAL BLVD
ASSOCIATED PERMITS
98-F-059
BACK - UP BATTERY
CALCULA TIONS
PROJECT NAME : PACIFIC VILLAGE APARTMENTS
PROJECT ADDRESS : 13504 PACIFIC HW Y. S.
TUKWILA, WA. 98168
TYPE OF PANEL : RAD/ONICS
MODEL NUMBER : 7024
TO : TUKWILA FIRE DEPT.
ATTN
FROM : JAMIE FOSSETT
Ace Fire & Security Systems
P.O. Box 3363 Lacey, Wa. 98509-3363
1-800-354-1555
WORKSHEET 1-1
CALCULATING TOTAL BACK-UP BATTERY
LOAD FOR FIRE ALARM SYSTEMS
A B Is IA
# OF ' CURRENT PER CURRENT PER SUB TOTAL 'SUB TOTAL
TYPE OF DEVICE DEVICE DEVICE DEVICE CURRENT DEVICE CURRENT'
DEVICE IDLE STATUS ALARM STATUS IDLE STATUS ALARM STATUS •
1 RADIOMCS 7212
0 250
0 250
y......,,.... L1�..L. -
v.00%1J.J1./V
2
3 SYSTEM SENSOR
1 ---
0.152
--- 0.152
4,
5
6
7i
8
9
10
11
12
13
14
15
16
17
18
19
20
TOTALS FROM COLUMNS Is & IA SHEET 1-2(IF USED)
►.H. = AMP. HOURS
COLUMN Is TOTAL DEVICE 0.210
CURRENT IDLE STATUS
is= SYSTEM STANDBY CURRENT
Ts= TIME DURATION (48 HRS)
T.- CVT=\I Al ASMI /"I I�esrArr
COLUMN to TOTAL DEVICE 0.652
CURRENT ALARM STATUS
TA= TIME DURATION IN ALARM (5 MIN.=0.0833) IF MORE SPACE IS NEEDED USE SHEET 1-2
K = 1.15 BATTERY CAPACITY COEFFICENT
L
IS n IS / T ` to /% IA / , /t • /1.1 1.
( 0.210 x24) + ( 0.652 x0.08331 x1.15= 5.8584
TOTAL AMP.HRS. = 6.0
AMP HRS PRCIVIIlFil = Z0
SYMBOL LEGEND
ILAsej
O
FRE ALARM CONTROL PANEL
MANUAL PULL STATION. WALL MOUNT ® 48 NCI -ES AFF.
RATE OF RISE HEAT DETECTOR
FRE ALARM HORN/STROBE
WALL MOUNT 0 80" AFF.
ACCEPTED
PROJECT NAME . Pacific Village Apartments (Laundry Rm. only)
PROOECT ADDRESS : 13504 Pa 'fie /My. SN"
thout comments
Tukwila, a. 9 :, . 8 As Noted In Red
u Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
TYPE OF PANEL : RADIONICS Prevention Bureau for conformance with current city
standards. Acceptance Is subject to errors and
MODEL NUMBER : 7024 omissions which do nor authorize violations of adopted
standards and ordinances. l he responsibility for the
i; adequacy of design rests totally with the designer.
ti Additions, deletions or revisions to these drawings after
, cnis date will void this acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to field test and inspection by
" The Tukwila Fire Prevention Bureau.
Date: 3 1 f1 By: 51/
TO : Tukwila Fire Dept.
A T TN
FROM : JAMIE FOSSETT
Ace Fire & Security Systems
P.O. Box 3363 Lacey, Wa. 98509-3363
1-800-354-1555
,f.
TUKWILA FIRE DEPARTMENT.
Please call: 575.4407
and give this job
No.
and exact address for shut.
&wn or restoration approval►
4 13 D^
91 MAR 1.31998
000000000000000000 \i‘
L? -_,
172 4L)