Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
PP - 13225 TUKWILA INTERNATIONAL BLVD - SIERRA SUE APARTMENTS - PERMITS AND PLANS
13225 TUKWILA INTERNATIONAL BLVD ASSOCIATED PERMITS 06-F-211 FIRS ALARM SYSTEM TUWILA, WASHINGTON SEPTEMBER 12, 2006 These se plans have been reviewed by The Tukwila Fire P vrenton- Bureau for conformance with current city s' t::irds. Acceptance is subject to errors and of t Ions which do not authorize violations of adopted st ^r, and ordinances. The responsibility for the a.,. .!sy of design rests totally with the designer. ..;03, deletions orf ✓visions to these drawings after ti will void this acceptance and wi# require a real io: nittai of revised drawings for subsequent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: /0//7/ °C- By: TUKWILA FIRE DEPARTMENI Please call: 575.4402 and give this job - F a/ and exact address for Shata. down or restoration-appr• NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. SHEET # DESCRIPTION FA -01 SHEET INDEX,SYMBOL LIST,GENERAL NOTES,WIRE DESIGNATIONS FA- 02 TYPICAL DETAILS AND CALCULATIONS FA -03 FIRST FLOOR FIRE ALARM PLAN FA- 04 SECOND FLOOR FIRE ALARM PLAN FA -05 ATTIC FIRE ALARM PLAN AND RISER DIAGRAM IMG INDEX WIRE SCHEDULE AND CONDUIT FILL CHART SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END WIRE DESIGNATION 1. 2. ALL WALL -MOUNTED AUDIBLE & VISUAL SIGNALING APPLIANCES SHALL HAVE THEIR HEIGHTS ABOVE THE FINISHED FLOOR AT 80' TO BOTTOM. NFPA 72, 1999 EDITION, ALLOWS 80'-96' FOR VISUAL DEVICES (CH. 4-4.4) AND REQUIRES A MINIMUM OF 90' TO TOP FOR AUDIBLE DEVICES OR 6' FROM CEILING, WHICHEVER IS LOWER (CH. 4-3.5). FOR SLEEPING AREAS GREATER THAN 16' (LINEAR) VISIBLE NOTIFICATION SHALL BE WITHIN 16' OF PILLOW AND GREATER THAN OR EQUAL TO 24' FROM CEILING TO TOP OF LENS FOR 110cd (CH. 4-4.4.3,2) ALL EQUIPMENT SHALL BE U.L. LISTED. 3 ELECTRICAL CONTRACTOR SHALL FURNISH ACCESS PANELS TO AREAS THAT REQUIRE SERVICING, TROUBLE SHO❑TING, ETC. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. CONDUITR RUNS ARE DIAGRAMMATIC. FOLLOW INTENT OF WIRE RUN WITH BEST CONDUIT RUN. KEEP AS BUITS DRAWING ON SITE FOR GUARDIAN TECHNICIANS.(GUARDIAN SECURITY SYSTEMS, INC., TEL (206)622-6545), FACTORS SUCH AS EXCESSIVE VOLTAGE DROP, ADDITI❑NAL PARTS, ENGINEERING, ETC., THAT ARE A RESULT OF CONDUIT RUN DEVIATIONS SHALL BE THE SOLE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR, DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIR -FLOW, NOR CLOSER THAN 3 FEET (900rnrn) FROM AN AIR SUPPLY DIFFUSER. EXCEPTION WHEN DETECTOR IS USED AS DUCT DETECTOR. IT CAN BE LOCATED IN DUCT OR IN FRONT OF DUCT WITHIN 5 FEET. ALL FAN SHUTDOWN FUNCTIONS, DAMPER CLOSURES, AND ASSOCIATED MECHANICAL SYSTEM FIRE ALARM INTERFACE SHALL BE BY MECHANICAL CONTRACTOR. DUCT SMOKE DETECTORS COORDINATE WITH DIVISION 15 FOR EXACT LOCATION. ALL I20VAC POWER REQUIREMENTS FOR THE FIRE ALARM SYSTEM SHALL BE FURNISHED BY THE ELECTRICAL CONTRACTOR AND SHALL MEET ALL REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. ALL FIRE ALARM DEVICE BACKBOXES, FIRE ALARM TERMINAL CABINETS, GUTTERS, JUNCTION BOXES, AND ASSOCIATED CONDUITS SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. REFER TO FIRE ALARM SYMBOL LIST AND/OR MOUNTING DETAILS FOR ADDITIONAL INFORMATION. SYSTEM SUPPLIER PROVIDED BACKBOXES SHALL BE INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. SMOKE DETECTOR TESTING SHALL BE ACCOMPLISHED WITH APPROVED SMOKE AS PER THE MANUFACTURERS INSTRUCTIONS. PER NFPA 1999 EDITION PAGE 72-35. 2-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEANUP OF ALL TRADES IS COMPLETE AND FINAL. ALL WIRING, INITIATING DEVICES AND ANNUNCIATOR PANEL SHALL BE SUPERVISED TO THE PRINCIPAL POINT OF ANNUNCIATION. THE FIRE ALARM CONTROL PANEL TO SUPERVISE THE ANNUNCIATOR PANEL, ALL INITIATING AND INDICATING DEVICE CIRCUITS. ALL WIRING SHALL BE CUT FOR IN AND OUT. WIRING SHALL NOT BE LOOPED THROUGH DEVICES. ALL SPLICED WIRE POSSESSING SHIELDS SHALL HAVE SHIELDS SPLICED AND TAPED TO PREVENT GROUND FAULTS. POINT AND COMMON ANNUNCIATION AND T -TAPPING (EXCEPT SLC LOOP) ARE PROHIBITED, PROVIDE 3/4' CONDUIT FROM FIRE ALARM CONTROL PANEL TO TELEPHONE BACKBOARD FOR OWNER PROVIDED CENTRAL STATION MONITORING EXCEPTION WHEN USING GUARDIAN WIRELESS APPROVED MONITORING. THE ALARM SYSTEM SHALL HAVE AN AUDIBILITY OF NOT LESS THAN 15dB ABOVE AMBIENT N❑ISE LEVELS. 17. ALL FLOW SWITCHES COORDINATE WITH SPRINKLER CONTRACTOR, ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED PER MANUFACTURER'S SPECIFICATIONS. SYSTEM SHALL BE FURNISHED AND INSTALLED BY A SIEMENS AFFILIATE AND AUTHORIZED'PYR❑TRONICS 19. DISTRIBUTOR. 20. FIRE ALARM SYSTEM INSTALLATION COMPANY SHALL BE UL LISTED (UUJS). 21. INSTALLATION SHALL BE IN STRICT COMPLIANCE WITH NFPA, LOCAL AND STATE, NEC AND CONTRACT DRAWINGS 22, ALL CONDUIT SIZING AND ROUTING BY ELECTRICAL CONTRACTOR PER NEC AND AHJ 18. 23. 24. 25. THE FACP SHALL NOT BE ENERGIZED WITHOUT THE PRESENCE OF G.S.S. TECHNICIANS A SET OF INSTALLATION AS -BUILT DRAWINGS SHOWING ACTUAL CONDUIT AND CONDUCTOR ROUTES SHALL BE KEPT BY PROJECT FOREMAN FOR USE BY G.S.S. FIELD TECHNICIANS. A SET OF AS BUILT DRAWINGS TO BE TURNED INT❑ G.S.S. INC. WITH APPROPRIATE COLOR CODED MARKUP DRAWINGS (SEE SYMBOL LEGEND FOR COLOR C❑DING), ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (e.g., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.e., MULTI -CONDUCTOR CABLE), ENCLOSURE OR RACEWAY. EXCEPTION! THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL BE PERMITTED TO BE RUN IN THE SAME CABLE ASSEMBLY, ENCLOSURE OR RACEWAY UNDER ANY OF THE F❑LL❑WING CONDITIONS! (1) (2) (3) 26. FOR A DISTANCE NOT TO EXCEED 3r1 (10ft.) WHERE THE OUTGOING AND RETURN CONDUCTORS ENTER OR EXIT THE INITIATING DEVICE, NOTIFICATION APPLIANCE, OR CONTROL UNIT ENCLOSURES, SINGLE CONDUIT/RACEWAY DROPS TO INDIVIDUAL DEVICES OR APPLIANCES, SINGLE CONDUIT/RACEWAY DROPS TO MULTIPLE DEVICES OR APPLIANCES INSTALLED WITHIN A SINGLE ROOM NOT EXCEEDING 92.9M SQUARED (1000ft.) IN AREA, A GOAL OF NFPA 6.4.2,2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305mm aft.) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22ri (4ft.) WHERE THE CABLE IS INSTALLED HORIZONTALLY. QUANTITY 1 1 1 1 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM CONTROL PANEL MXL-IQ SIEMENS PROVIDED 66" A.F.F. TO TOP PS REMOTE POWER SUPPLY PS-24-8MC WHEELOCK PROVIDED 66" A.F.F. TO TOP T -R INTERFACE MODULE W/ RELAY TRI -R SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR (PHOTOELECTRIC) FP -11 W/ DB -11 BASE SIEMENS 4S DEEP BOX 1 -GANG RING CEILING 20 HEAT DETECTOR 22 22 88 1 1 FPT-1 1 W/ DB -11 BASE SIEMENS 4S DEEP BOX 1 -GANG RING CEILING F MANUAL FIRE ALARM STATION (CONVENTIONAL) MS -51 SIEMENS 4S DEEP BOX 1 -GANG RING 48" A.F.F. TO CENTER SINGLE INPUT INTERFACE MODULE TRI-B6M SIEMENS 4S DEEP BOX 48" A.F.F. TO CENTER FIRE ALARM HORN WEATHERPROOF WP ALARM BELL NH -12/24R MB -G10 -24R WHEELOCK WHEELOCK 4S BOX WBB-R 80" A.F.F. TO CENTER VERIFY IN FIELD WEATHERPROOF Wp STROBE RSSWP WHEELOCK WPSBB VERIFY IN FIELD nI �' I BOX F.B.O. F.B.O. N/A VERIFY IN FIELD EX EXISTING DEVICE N/A N/A N/A N/A A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EOL END LIF LINE RESIST❑R` N/A N/A N/A N/A F.B.❑, FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A --- GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A GENERAL NOTES SYMBOLS LEGEND Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved ca 614 ict -4 co NO FAX (206) 628-4990 TEL. (206) 622-6545 i 7 5 5 > 71 J oJ i WIRE DESIGNATION 0 SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D D' H P S S' DATA LINE -ADDRESSABLE LOOP - FEED TWISTED PAIR WITH SHIELD #16 FPL/FPLR DATA LINE -ADDRESSABLE LOOP - RETURN TWISTED PAIR WITH SHIELD #16 FPL/FPLR DOOR HOLDER POWER - 24VDC PAIR #14 FPL/FPLR DEVICE POWER - 24VDC PAIR #14 FPL/FPLR SIGNALING CIRCUIT (STROBE) - FEED TWISTED PAIR WITH SHILED #14 FPL/FPLR SIGNALING CIRCUIT (STROBE) - RETURN TWISTED PAIR WITH SHILED #14 FPL/FPLR RED (JACKET) RED (JACKET) RED (JACKET) RED (JACKET) RED (JACKET) RED (JACKET) SUBMITTED FOR APPROVAL CONDUIT FILL CHART (DCI) (NA/ NB) (PCU NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 O.D. .0467 .210 0.D. .0346 .156 0.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. Lua I-- Q CI SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END WIRE DESIGNATION 1. 2. ALL WALL -MOUNTED AUDIBLE & VISUAL SIGNALING APPLIANCES SHALL HAVE THEIR HEIGHTS ABOVE THE FINISHED FLOOR AT 80' TO BOTTOM. NFPA 72, 1999 EDITION, ALLOWS 80'-96' FOR VISUAL DEVICES (CH. 4-4.4) AND REQUIRES A MINIMUM OF 90' TO TOP FOR AUDIBLE DEVICES OR 6' FROM CEILING, WHICHEVER IS LOWER (CH. 4-3.5). FOR SLEEPING AREAS GREATER THAN 16' (LINEAR) VISIBLE NOTIFICATION SHALL BE WITHIN 16' OF PILLOW AND GREATER THAN OR EQUAL TO 24' FROM CEILING TO TOP OF LENS FOR 110cd (CH. 4-4.4.3,2) ALL EQUIPMENT SHALL BE U.L. LISTED. 3 ELECTRICAL CONTRACTOR SHALL FURNISH ACCESS PANELS TO AREAS THAT REQUIRE SERVICING, TROUBLE SHO❑TING, ETC. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. CONDUITR RUNS ARE DIAGRAMMATIC. FOLLOW INTENT OF WIRE RUN WITH BEST CONDUIT RUN. KEEP AS BUITS DRAWING ON SITE FOR GUARDIAN TECHNICIANS.(GUARDIAN SECURITY SYSTEMS, INC., TEL (206)622-6545), FACTORS SUCH AS EXCESSIVE VOLTAGE DROP, ADDITI❑NAL PARTS, ENGINEERING, ETC., THAT ARE A RESULT OF CONDUIT RUN DEVIATIONS SHALL BE THE SOLE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR, DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIR -FLOW, NOR CLOSER THAN 3 FEET (900rnrn) FROM AN AIR SUPPLY DIFFUSER. EXCEPTION WHEN DETECTOR IS USED AS DUCT DETECTOR. IT CAN BE LOCATED IN DUCT OR IN FRONT OF DUCT WITHIN 5 FEET. ALL FAN SHUTDOWN FUNCTIONS, DAMPER CLOSURES, AND ASSOCIATED MECHANICAL SYSTEM FIRE ALARM INTERFACE SHALL BE BY MECHANICAL CONTRACTOR. DUCT SMOKE DETECTORS COORDINATE WITH DIVISION 15 FOR EXACT LOCATION. ALL I20VAC POWER REQUIREMENTS FOR THE FIRE ALARM SYSTEM SHALL BE FURNISHED BY THE ELECTRICAL CONTRACTOR AND SHALL MEET ALL REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. ALL FIRE ALARM DEVICE BACKBOXES, FIRE ALARM TERMINAL CABINETS, GUTTERS, JUNCTION BOXES, AND ASSOCIATED CONDUITS SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. REFER TO FIRE ALARM SYMBOL LIST AND/OR MOUNTING DETAILS FOR ADDITIONAL INFORMATION. SYSTEM SUPPLIER PROVIDED BACKBOXES SHALL BE INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. SMOKE DETECTOR TESTING SHALL BE ACCOMPLISHED WITH APPROVED SMOKE AS PER THE MANUFACTURERS INSTRUCTIONS. PER NFPA 1999 EDITION PAGE 72-35. 2-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEANUP OF ALL TRADES IS COMPLETE AND FINAL. ALL WIRING, INITIATING DEVICES AND ANNUNCIATOR PANEL SHALL BE SUPERVISED TO THE PRINCIPAL POINT OF ANNUNCIATION. THE FIRE ALARM CONTROL PANEL TO SUPERVISE THE ANNUNCIATOR PANEL, ALL INITIATING AND INDICATING DEVICE CIRCUITS. ALL WIRING SHALL BE CUT FOR IN AND OUT. WIRING SHALL NOT BE LOOPED THROUGH DEVICES. ALL SPLICED WIRE POSSESSING SHIELDS SHALL HAVE SHIELDS SPLICED AND TAPED TO PREVENT GROUND FAULTS. POINT AND COMMON ANNUNCIATION AND T -TAPPING (EXCEPT SLC LOOP) ARE PROHIBITED, PROVIDE 3/4' CONDUIT FROM FIRE ALARM CONTROL PANEL TO TELEPHONE BACKBOARD FOR OWNER PROVIDED CENTRAL STATION MONITORING EXCEPTION WHEN USING GUARDIAN WIRELESS APPROVED MONITORING. THE ALARM SYSTEM SHALL HAVE AN AUDIBILITY OF NOT LESS THAN 15dB ABOVE AMBIENT N❑ISE LEVELS. 17. ALL FLOW SWITCHES COORDINATE WITH SPRINKLER CONTRACTOR, ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED PER MANUFACTURER'S SPECIFICATIONS. SYSTEM SHALL BE FURNISHED AND INSTALLED BY A SIEMENS AFFILIATE AND AUTHORIZED'PYR❑TRONICS 19. DISTRIBUTOR. 20. FIRE ALARM SYSTEM INSTALLATION COMPANY SHALL BE UL LISTED (UUJS). 21. INSTALLATION SHALL BE IN STRICT COMPLIANCE WITH NFPA, LOCAL AND STATE, NEC AND CONTRACT DRAWINGS 22, ALL CONDUIT SIZING AND ROUTING BY ELECTRICAL CONTRACTOR PER NEC AND AHJ 18. 23. 24. 25. THE FACP SHALL NOT BE ENERGIZED WITHOUT THE PRESENCE OF G.S.S. TECHNICIANS A SET OF INSTALLATION AS -BUILT DRAWINGS SHOWING ACTUAL CONDUIT AND CONDUCTOR ROUTES SHALL BE KEPT BY PROJECT FOREMAN FOR USE BY G.S.S. FIELD TECHNICIANS. A SET OF AS BUILT DRAWINGS TO BE TURNED INT❑ G.S.S. INC. WITH APPROPRIATE COLOR CODED MARKUP DRAWINGS (SEE SYMBOL LEGEND FOR COLOR C❑DING), ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (e.g., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.e., MULTI -CONDUCTOR CABLE), ENCLOSURE OR RACEWAY. EXCEPTION! THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL BE PERMITTED TO BE RUN IN THE SAME CABLE ASSEMBLY, ENCLOSURE OR RACEWAY UNDER ANY OF THE F❑LL❑WING CONDITIONS! (1) (2) (3) 26. FOR A DISTANCE NOT TO EXCEED 3r1 (10ft.) WHERE THE OUTGOING AND RETURN CONDUCTORS ENTER OR EXIT THE INITIATING DEVICE, NOTIFICATION APPLIANCE, OR CONTROL UNIT ENCLOSURES, SINGLE CONDUIT/RACEWAY DROPS TO INDIVIDUAL DEVICES OR APPLIANCES, SINGLE CONDUIT/RACEWAY DROPS TO MULTIPLE DEVICES OR APPLIANCES INSTALLED WITHIN A SINGLE ROOM NOT EXCEEDING 92.9M SQUARED (1000ft.) IN AREA, A GOAL OF NFPA 6.4.2,2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305mm aft.) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22ri (4ft.) WHERE THE CABLE IS INSTALLED HORIZONTALLY. QUANTITY 1 1 1 1 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM CONTROL PANEL MXL-IQ SIEMENS PROVIDED 66" A.F.F. TO TOP PS REMOTE POWER SUPPLY PS-24-8MC WHEELOCK PROVIDED 66" A.F.F. TO TOP T -R INTERFACE MODULE W/ RELAY TRI -R SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR (PHOTOELECTRIC) FP -11 W/ DB -11 BASE SIEMENS 4S DEEP BOX 1 -GANG RING CEILING 20 HEAT DETECTOR 22 22 88 1 1 FPT-1 1 W/ DB -11 BASE SIEMENS 4S DEEP BOX 1 -GANG RING CEILING F MANUAL FIRE ALARM STATION (CONVENTIONAL) MS -51 SIEMENS 4S DEEP BOX 1 -GANG RING 48" A.F.F. TO CENTER SINGLE INPUT INTERFACE MODULE TRI-B6M SIEMENS 4S DEEP BOX 48" A.F.F. TO CENTER FIRE ALARM HORN WEATHERPROOF WP ALARM BELL NH -12/24R MB -G10 -24R WHEELOCK WHEELOCK 4S BOX WBB-R 80" A.F.F. TO CENTER VERIFY IN FIELD WEATHERPROOF Wp STROBE RSSWP WHEELOCK WPSBB VERIFY IN FIELD nI �' I BOX F.B.O. F.B.O. N/A VERIFY IN FIELD EX EXISTING DEVICE N/A N/A N/A N/A A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EOL END LIF LINE RESIST❑R` N/A N/A N/A N/A F.B.❑, FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A --- GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A GENERAL NOTES SYMBOLS LEGEND Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved ca 614 ict -4 co NO FAX (206) 628-4990 TEL. (206) 622-6545 i 7 5 5 > 71 J oJ i REV. BY: 0 DATE: 09/12/06 BACKROUND PLAN PROVIDED BY: ..ICP MIIlARFP• 'Ana 1 . DESCRIPTION SUBMITTED FOR APPROVAL Lua I-- Q CI (D cv �- 0 2aaaaa � Z ZFino 0 W �'B L. Q x(r...?.. QNZ � a�Wg o D< 2 Q m.)LIPW `Lcy?). (i) 111>- 2"" 'SCALE: NUI 10 SCALE DRAWN BY: D.GA'RCA DESIGNED BY: B. A L MMi1 E D A DATE: 09/12/06 BACKROUND PLAN PROVIDED BY: ..ICP MIIlARFP• 'Ana 1 . SHEET 1 FA -01 PA is SEP 25 2006 Tukwila 2- Fir9, % 13'7 M:\t7ravngs\5lerra 51e Apartments\FA PW65.dwq, 9/ 18/ 2006 1:58:05 AM, 19M6 FOV 655 INC. WBEMEMEMEWBEWWWWWXEWWXEWMEWMEWWXEXEWWMEMEWBEWMEWWWWWWMEMEWWWWW EWWMEXEW*WWWWWWWWWW NE 31E ) Job Names Panel Locations Date Performed' BATTERY SIZING CALCULATION SIERRA SUE APARTMENTS FACP BATTERY CALCULATION 09-16-2006 QTY. DEVICE NAME STD-BY(Amps) ALARM( Amps) 1 MXLi MKB-2 1 MXL: MMB -2 1 PS! MPS -6 20 HEATS FPT-11 1 MOD_M: TRI -R 1 SMOKE FP -11 22 TRI-B6M 1 BELL: MB -G10 -24R 24 HORN: NH -12/24 1 STR: RSSWP 0, 0050 0. 0120 0. 0640 0. 0150 0. 0016 0. 0008 0, 0000 0. 0000 0. 0000 0. 0000 0. 0050 1. 5000 0. 5000 0, 0150 0. 0035 0. 0008 0. 0000 0. 0300 0, 6480 0. 1070 Stand -By Load = Stand -By Time = Tota l s = 0. 0984 0. 0984 Amps 24 Hrs, Stand -By = 2. 36 Amp*Hrs Total = Stand -By + Alarm = 2.36 + 0.23 = 2. 59 Amp*Hrs Alarm Load = Alarm Time = 2. 8093 2. 8093 Amps 5/60 Hrs. Alarm = Multiply by De -Rating Factor of 1.25 ---> 2. 59 0, 23 AmpA(Hrs * 1.25 = 3.24 WWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWW )4( )1( MINIMUM BATTERY SIZE = 3.24 Ampere*Hours WWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWW **** RECOMMENDED MINIMUM BATTERY SIZE = 7.00 Ampere*Hours *****************SEW*******************SEW**WWWWWW***WWWWWWWWWWW BATTERY SIZING CALCULATION WWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWW Job Names SIERRA SUE APARTMENTS Panel Locations POWER SUPPLY BATTERY CALCULATION Date Performed: 09-16-2006 QTY. DEVICE NAME STD-BY(Amps) ALARM(Amps) 1 WHEEL! PS-24-8MC 64 HORN: NH -12/24 0. 0800 0. 0000 0. 2490 1, 7280 Stand -By Load = Stand -By Time = Tota l s = 0. 0800 0. 0800 Amps 24 Hrs, Stand -By = 1. 92 Amp*Hrs Total = Stand -By + Alarm = L92 + 0.16 = 2. 08 Amp*Hrs 1. 9770 Alarm Load = 1.9770 Amps Alarm Time = 5/60 Hrs. Alarm = 0.16 Amp*Hrs Multiply by De -Rating Factor of 1.25 ---> 2. 08 * 1. 25 = 2. 61 *********************************************** )4( )1( * MINIMUM BATTERY SIZE = 2. 61 Ampere*Hours �E WWWWWWNEWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWW **** RECOMMENDED MINIMUM BATTERY SIZE = 7. 00 Ampere*Hours WXEMEWNEMEWWMEME*NEXEXEMEBE*ME*XEXEMEXEXE**BEXEXE*NEMEBE*NE*BE**BE*BEME*MEBEMEMEWMEMEMEMEBEMEMEBEMEBEMEMEBE )1E WORST CASE VOLTAGE DROP CALCULATION WWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWW Job Name: Circuit: Date Performed: 1 BELL: 12 HORN: 1 STR: SIERRA SUE APARTMENTS SIGNALING CIRCUIT S5 ( BLDG C NORTH ) 09-16-2006 MB -G10 -24R at NH -12/24 at RSSWP at 0, 0300 Amps 0, 0270 Amps 0, 1070 Amps each = each = each = 0. 0300 Amps 0, 3240 Amps 0. 1070 Amps Circuit Length = 382 Ft to End Circuit Load = 0.4610 Amps Total = 0. 4610 Amps Wire Size = #14 AWG Voltage = 24. 0 Volts (Ckt. Load) * (Ckt. Length) * 21. 6 Voltage Drop = * 100% (Circular Mils) * (Volts) ( 0. 4610 ) ( 382 ) * 21. 6 Voltage Drop = * 100% C 4110 ) * ( 24,0) Voltage Drop = 3.86% **************w************ * VOLTAGE DROP = 3.86% ******************wwwwwwwww WWW31EII WWWWWWWWWNEWW31EWW31 WWWWSIEWWWWWWWWWWSIEWWXEME31 WWXEWWWW31 WWWWWWWWW31 WW ) WORST CASE VOLTAGE DROP CALCULATI❑N WWWWWWWW*************3333********3333************************* Job Name: Circuli' Date Performed' SIERRA SUE APARTMENTS SIGNALING CIRCUIT S1 ( BLDG A SOUTH ) 09-16-2006 16 H❑RN: NH -12/24 at 0,0270 Amps each = 0,4320 Amps Total = 0. 4320 Amps Circuit Length = 381 Ft to End Wire Size = #14 AWG Circuit Load = 0.4320 Amps Voltage = 24.0 Volts (Ckt. Load) * (Ckt, Length) * 21. 6 Voltage Drop = * 100% (Circular Mils) * (Volts) ( 0. 4320 ) E ( 381 ) * 21. 6 Voltage Drop = NE 100% ( 4110 ) ( 24.0) Voltage Drop = 3.60% wwwwwwwwwwwwwwwwwwwwwwwwwww * VOLTAGE DROP = 3.60% NE *************************** WWWWWSMEWWWW31 WSIEWWWWWWWWWWWSIEWSMEWW31 WSIEWW31 WWME*MEWWWWWWWWWWW31 WWW)IEWSME31 WWW 3E WORST CASE VOLTAGE DROP CALCULATI❑N MEWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWW Job Name: Circuit: Date Performed: SIERRA SUE APARTMENTS SIGNALING CIRCUIT S6 ( BLDG C NORTH ) 09-16-2006 12 FORM NH -12/24 at 0.0270 Amps each = 0.3240 Amps Circuit Length = Circuit Load = Tota . = 0. 3240 Amps 394 Ft to End Wire Size 0.3240 Amps Voltage (Ckt. Load) * (Ckt. Length) = #14 AWG = 24.0 Volts 21. 6 Voltage Drop = * 100% (Circular Mils) * (Volts) ( 0. 3240 ) * ( 394 ) * 21. 6 Voltage Drop = * 100% ( 4110 ) * ( 24.0) Voltage Drop = 2.80% *************************** * VOLTAGE DROP = 2.80% wwwwwwwwwwwwwwwwwwwwwwwwwww WORST CASE VOLTAGE DROP CALCULATION �E WWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWW Job Name: SIERRA SUE APARTMENTS Circuits SIGNALING CIRCUIT S2 ( BLDG A SOUTH ) Date Performed: 09-16-2006 16 HORN: NH -12/24 at 0.0270 Amps each = 0.4320 Amps Total = 0. 4320 Amps Circuit Length = 405 Ft to End Wire Size = #14 AWG Circuit Load = 0.4320 Amps Voltage = 24.0 Volts (Ckt. Load) * (Ckt. Length) ) 21. 6 Voltage Drop = * 100% (Circular Mils) * (Volts) ( 0. 4320 ) * ( 405 ) * 21. 6 Voltage Drop = * 100% ( 4110 ) ( 24.0) Voltage Drop = 3.83% wwwwwwwwwwwwwwwwwwwwwwwwwww * VOLTAGE DROP = 3.83% *************************** CALCULATIONS *WW*W**W****WW***W*WWWWW331EWW*****XEXEW**ME***WSIE**SIE**W**SIESIEW31 *XE**MEW NE WORST CASE VOLTAGE DROP CALCULATI❑N �E WWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWW Job Names Circuits Date Performed: SIERRA SUE APARTMENTS SIGNALING CIRCUIT S3 ( BLDG B WEST ) 09-16-2006 16 HORN' NH -12/24 at 0.0270 Amps each = 0.4320 Amps Circuit Length = 283 Ft to End Circuit Load = 0.4320 Amps Total = 0.4320 Amps Wire Size = #14 AWG Voltage = 24.0 Volts (Ckt, Load) * (Ckt. Length) * 21,6 Voltage Drop = * 100% (Circular Mils) * (Volts) ( 0. 4320 ) * ( 283 ) * 21. 6 Voltage Drop = * 100% ( 4110 ) ( 24.0) Voltage Drop = 2.68% wwwwwwwwwwwwwwwwwwwwwwwwwww * VOLTAGE DROP = 2.68% wwwwwwwwwwwwwwwwwwwwwwwwwww wwwwwwwwwwwwwwwWwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwwww )1E Job Names Circuits Date Performed: WORST CASE VOLTAGE DROP CALCULATION SIERRA SUE APARTMENTS SIGNALING CIRCUIT S4 ( BLDG B WEST ) 09-16-2006 16 HORN' NH -12/24 at 0.0270 Amps each = 0.4320 Amps Circuit Length = Circuit Load = Voltage Drop = Total = 0.4320 Amps 317 Ft to End Wire Size = #14 AWG 0. 4320 Amps Voltage = 24. 0 Volts (Ckt, Load) * (Ckt. Length) NE 21. 6 (Circular Mils) * (Volts) NE 100% ( 0. 4320 ) * ( 317 ) * 21. 6 Voltage Drop = * 100% ( 4110 ) ( 24,0) Voltage Drop = 3.00% wwwwwwwwwwwwwwwwwwwwwwwwwww NE VOLTAGE DROP = 3. 00% WWWWWW****************WWWWW 404 O C/) LLI 644 z 0 I -- (z) z_ ca61 W W C!) C!) FAX (206) 628-4990 TEL. (206) 622-6545 z O_ CJS W C0 Q 1 IREV. BY: 0 2 0 ,,.moi BACKROUND PLAN PROVIDED BY: t _I(1R NI IkARFR• .4 lQ 1/ DESCRIPTION SUBMITTED FOR APPROVAL W I (D o- N O <'«2 0 0 DSVDC P LJ r' 2 Ii�•+ D0 NOT USE t.; IJ 1 PRINTER (PROGRAMMER 1; MOM -4 1uu�l[uT13ul LOOP PI ALARM CytaAVS RBL CONTACTS I • • • • • • I 0 DATA 002 NOT USED NJ POWER TO MOM 4 F4 154 FUSE FOR MOM -4 F1 04 FUSE MP -6 SMI3-2 BATTERY h2 20A FUS MPS -6 • POWER SUPPLY : MPS -12. POWER SUPPL • • • F3 CB -2 CB -1 NAC -2 NAL -1 2A FUSE I CZM-1 POWER f NAC -1 NAC -2 CZM-1 POWER /-\ • . • ) • • . • 2 • • TB3 2 2 12A VAC MAR SOURCE NON WNW NW 0 0� u 0 0 e• co E9 1 -s e Pouez Supply • E0 MXL-IQ WIRING DIAGRAM 2 2 SI(1JALIIE CIRCUIT S6 SIGNALING CIRCUIT S5 L1 2 1.2 EARTH 2 AC LOSS TROUBLE RELAY FORM -C 2BVDC 1 AMP COMMON TROUBLE RELAY FORM -C 28VDC 1 AMP casTROL NAC ACTIVATION FROM FACP TO NEXT BOOSTER SHORTED (NO ALARM OPEN (NO ALARM CONTROL a NAC ACTIVATIDI FROM FACP TO NEXT BOOSTER SHORTED (NO ALARM OPEN (NO ALARM AC POWER SELECTION 32O.'24OVAC • W1 SWEI SYS RESET !NJ- PETI- DPYJ. 1N1/ P.Ei'l+ C NC '711R 1. S W1 INR- PET;- JJRY2 1N2l FE:T2+ C NC TD5 T59 AUX RESET Slro'%I1 I AUX r;1; 756 T53 i r I BT OUT1 DUT2 DU T3 OUT4 + - + - + - + - (�1 0 2+ 2 2 2 2 2- 2- 2 2 2 2- Z?• , S4 - t + S3 22 S2 2 TYPICAL PS-24-8MC WIRING DIAGRAM TYPI AL DETAIL NAC OUTPUTS EOLR 2.2J< CLASS A OR B (POWER -LIMITED, SUPERVISED) AUXILIARY POWER OUTPUT 3.5A OP 'EDE) 0.2A 241ft or 0.06A 60HR (CP MODE) (POWER LIMITED, FAIL SAFE) RED BLACK TRI-B6M N � ORANGE FROM FACP OR POWER SUPPLY TO NEXT ADDRESSABLE DEVICE + FROM MXL OR IXL (ICON -1) CONTROL PANEL ADDRESSABLE LOOP DRIVER CIRCUIT OR FROM PREVIOUS ADDRESSABLE DEVICE GROUND 3.6K, 1/4W END OF LINE DEVICE SUPERVISED SWITCH TRI-B6M MODULE WIRING DETAIL HORN + \- HORN TYPICAL WIRING FOR HORN TO INITIATING CIRCUIT OF CERBERUS PYROTRONICS COMPATIBLE CONTROL UNIT DETECTOR BASE: MODEL DB -11 OR MODEL DB -3 WITH DB-ADPT HORN OPTIONAL to o REMOTE ALARM INDICATOR MODELS RLI-1/RLI-2 la TYPICAL WIRING FOR FP -11 & FPT-11 DETECTOR BASE TO NEXT DEVICE OR END OF LINE Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved hr pQ� NWS <4) Ct IL `,2 Ct \u, 'SCALE: NOT TO SCALE 1 DRAWN BY: D.GARCIA G ,,.moi AC POWER SELECTION 32O.'24OVAC • W1 SWEI SYS RESET !NJ- PETI- DPYJ. 1N1/ P.Ei'l+ C NC '711R 1. S W1 INR- PET;- JJRY2 1N2l FE:T2+ C NC TD5 T59 AUX RESET Slro'%I1 I AUX r;1; 756 T53 i r I BT OUT1 DUT2 DU T3 OUT4 + - + - + - + - (�1 0 2+ 2 2 2 2 2- 2- 2 2 2 2- Z?• , S4 - t + S3 22 S2 2 TYPICAL PS-24-8MC WIRING DIAGRAM TYPI AL DETAIL NAC OUTPUTS EOLR 2.2J< CLASS A OR B (POWER -LIMITED, SUPERVISED) AUXILIARY POWER OUTPUT 3.5A OP 'EDE) 0.2A 241ft or 0.06A 60HR (CP MODE) (POWER LIMITED, FAIL SAFE) RED BLACK TRI-B6M N � ORANGE FROM FACP OR POWER SUPPLY TO NEXT ADDRESSABLE DEVICE + FROM MXL OR IXL (ICON -1) CONTROL PANEL ADDRESSABLE LOOP DRIVER CIRCUIT OR FROM PREVIOUS ADDRESSABLE DEVICE GROUND 3.6K, 1/4W END OF LINE DEVICE SUPERVISED SWITCH TRI-B6M MODULE WIRING DETAIL HORN + \- HORN TYPICAL WIRING FOR HORN TO INITIATING CIRCUIT OF CERBERUS PYROTRONICS COMPATIBLE CONTROL UNIT DETECTOR BASE: MODEL DB -11 OR MODEL DB -3 WITH DB-ADPT HORN OPTIONAL to o REMOTE ALARM INDICATOR MODELS RLI-1/RLI-2 la TYPICAL WIRING FOR FP -11 & FPT-11 DETECTOR BASE TO NEXT DEVICE OR END OF LINE Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved hr pQ� NWS <4) Ct IL `,2 Ct \u, 'SCALE: NOT TO SCALE 1 DRAWN BY: D.GARCIA DESIGNED BY: B.AL_MEDA DATE: 09/12/06 BACKROUND PLAN PROVIDED BY: t _I(1R NI IkARFR• .4 lQ 1/ • SHEET FA -02.1 M:\17ravrric \5erra 5.1e Apatments\rA PWG541wq, 9/18/ 2006 7:58:I5 AM, CMG FOR 655 INC. BUILDING B WEST 1 S3 Q S3 UP UP TO 2ND FLOOR JBOX D,S1,S2 .11116. ri 77' ( i 1 1 a n.. TO POWER SUPPLY PS (CKTS Sl&S2), TO FACP (D) BUILDING A SOUTH UP UP FLAGNOTE PROVIDE STI3150 WEATHER STOPPER II TO MANUAL PULL STATION. INSTALL THE TRI-B6M MONITOR MODULE INSIDE THE .APARTMENT UNIT NEAREST TO THE MANUAL PULL STATION. UP ... S3 UP TO 2ND FLOOR JBOX o--D,S3,S4 TO POWER SUPPLY PS (CKTS S3&S4), TO FACP (D) BUILDING C NORTH S5—c, *u S5 S5 S5 it q S5 S5 S5 11 q S5 S5 fl S5 7 S5 D,S5,S6—o TO FACP (CKTS S5&S6),(D) /\ UP 11 - s OOH Ff 4 q S5 UP \\ ; 4 S5 EOL S5 0 00 Z N O SD LD . :(\j LL_ Q W 44 7 Cly 114 CC O cn W Q 3 1- I` J TEL. (206) 622-6545 0 7 5 0 J 0 J J IREV. BY: 0 2 0 DATE: 09/12/06 BACKROUND PLAN PROVIDED BY: FI RNi N[APviI LE .ICP NI IRARI-R• d(lQ 1 i DESCRIPTION SUBMITTED FOR APPROVALI DATE 09/12/06 ©aaaaa `\ 1 W 0 U-0 J 'SCALE: 3/32"" = 1'0- ' "0 - DRAWN DRAWN BY: D.GACIA DESIGNED BY: B.AL_MEDA DATE: 09/12/06 BACKROUND PLAN PROVIDED BY: FI RNi N[APviI LE .ICP NI IRARI-R• d(lQ 1 i FIRE ALARM Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved • SHEET FA -03 M:\I7rawhgs\Serra Sue Apartments\FA t7WG5.dwq, 9/ 18/ 2006 >:IO:OO PM, PMG POP 655 INC, BUILDING B WEST [( DN { DN TO 1ST S2 FLOOR JBOX UP TO ATTIC JBOX LJ n 11 11 , 1 f F (1 DN ( BUILDING A SOUTH FLAGNOTE D PROVIDE STI3150 WEATHER STOPPER II TO MANUAL PULL STATION. INSTALL THE TRI-B6M MONITOR MODULE INSIDE THE APARTMENT UNIT NEAREST TO THE MANUAL PULL STATION. S4 \'' S4 f 6� DN TO 1ST o FLOOR JBOX UP TO ATTIC BOX D, DN TO 1ST FLOOR JBOX UP TO ATTIC JBOX BUILDING C NORTH S6 lit S6 3 S6 i 3 1 1 .3 S6 4 8 S6 ,J S6 SG s 00 \D J00IF `1. Al 41Vr Fl A D 4 EOL S6 ,.. ocZ Nt) aO 0\ z 0 z_ LU J Q LU CU) O C/) LLJ Cf) NO FAX (206) 628-4990 TEL. (206) 622-6545 7 J J 7 J 1 J IREV. BY: 0 DATE: 09/12/06 BACKROUND PLAN PROVIDED BY: FORM M,e\Iv1 E t InP MUMBER• SAflQl DESCRIPTION SUBMITTED FOR APPROVAL W I— 0 o _N a) O 2 <<<<<} Z g 'SCALL: .5/52" = 1 -0-. DRAWN BY: D_GACBA DESIGNED BY: i=, . A L_ M E D A DATE: 09/12/06 BACKROUND PLAN PROVIDED BY: FORM M,e\Iv1 E t InP MUMBER• SAflQl • FIRE ALARM Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved SHEET FA -04 � M:\I7rawtigs\5ierra ie Apartments\FA t7W65.dwq, 9/ 18/ 2006 7:5831 AM, !MG FOP 6551%. BUILDING B WEST D Ii 1 DN TO 2ND 0 FLOOR JBOX DN TO 2ND FLOOR JBOX BUILDING A SOUTH BUILDING B WEST ATTIC 0 0 0 0 0 0 DN TO 2ND FLOOR JBOX BUILDING C NORTH D • • • 4 IC IRE Fl EOL S4 S S SECOND FLOOR S S T ■ S • • T ■ S • • T ■ S • • T ■ S • T ■ S • T ■ S S : : V 0 S 7 ■ S • T ■ S S T : ■ : EOL S3 FIRST FLOOR CD- D,S D,2S BUILDING A SOUTH ATTIC EOL S2 S SECOND FLOOR S S S S S S S S S S S EOL S1 FIRST FLOOR S S S S S S S o- D,S D,2S f3 PS T -R D,2S ® 0® 0 0 0 0 D, D ® li BUILDING C NORTH ATTIC S S T 0 : ■ : CI 0 CI T ■ S S S T ■ S S S S S S S ■ i ■ i ■ i ■ i ■ EOL S6 SECOND FLOOR D,S -o FACP Df4G 4 • • S S S S S S S S S S S S S EOL S5 FIRST FLOOR 00 w FAX (206) 628-4990 TEL. (206) 622-6545 Ci-;)- O_ Fl J W U) Q J J REV. BY: 0 2 0 DATE: 09/12/06 BACKROUND PLAN PROVIDED BY: FIRM N A N,1 .- .1CR NUMBER• 5 1-0911 \l DESCRIPTION SUBMITTED FOR APPROVAL' LU71 I Q CI 09/12/06 2 <<<<< i 'SCALE: 3/32" = 1'0" DRAWN BY: D_GARCOA DESIGNED BY: B.ALM EDA DATE: 09/12/06 BACKROUND PLAN PROVIDED BY: FIRM N A N,1 .- .1CR NUMBER• 5 1-0911 FIRE ALARM Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved SHEET FA -05 M:\I2rawN5\51erra 5iie Apartments\Ievisicn 2-27-07\PA 12wgs.c}wq, 2/ 28/ 2007 7:3h00 AM, t2MG F6 655 INC BUILDING B WEST u" SI UP TO 2ND FLOOR JBOX D,S1,S2 I! LI Ij ii I I —D o -D n :J rl a. TO POWER SUPPLY PS (CKTS S1&S2), TO FACP (D) BUILDING A SOUTH FLAGNOTE it PROVIDE STI3150 WEATHER STOPPER II TO MANUAL PULL STATION. INSTALL THE TRI—B6M MONITOR MODULE INSIDE THE APARTMENT UNIT NEAREST TO THE MANUAL , PULL STATION. .�P j— S3 UP TO 2ND ° FLOOR JBOX D,S3,S4 TO POWER SUPPLY PS (CKTS S3&S4), TO FACP (D) BUILDING C NORTH �c� •� c N .o LM rs n I- 1571' y al 8 r� 12 c o -� s CL. «s S5 D,S5,S6 TO FACP (CKTS S5&S8),(D) UNIT 100 t STORAGE ROOM D n— FACPIPS AUNDRY IT -R1 RADIO DIALER BATHROOM I� 9 I 1`\ BEDROOM BEDROOM I BEDROOM ROOM i 3o ci41 hoY►,/l�sf�,c. -iiRS-r P! .ccs FiIR^ AL,afR S5 S5 i' ( S5 S5 55 55 S5 F I A\ FIRE ALARM LIP it S5 EOL S5 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved ) CO 0' z 0 z_ !L CU ) 0 r) FAX (206) 628-4990 TEL. (206) 622-6545 J )J JJ REV. BY: 0 0 0- SI BACKROUND PLAN PROVIDED BY: FI ISI NAI /1 E t _InP MIIAAPPR• t,.el _nal i \1 C,—S1 SUBMITTED FOR APPROVALI AS PER AHJ CHANGES ON FEB. 23 TEST / 09/12/06 J d--. S1 2 <<<<< c>-- si EOL „,,r S1 I i .j n :J rl a. TO POWER SUPPLY PS (CKTS S1&S2), TO FACP (D) BUILDING A SOUTH FLAGNOTE it PROVIDE STI3150 WEATHER STOPPER II TO MANUAL PULL STATION. INSTALL THE TRI—B6M MONITOR MODULE INSIDE THE APARTMENT UNIT NEAREST TO THE MANUAL , PULL STATION. .�P j— S3 UP TO 2ND ° FLOOR JBOX D,S3,S4 TO POWER SUPPLY PS (CKTS S3&S4), TO FACP (D) BUILDING C NORTH �c� •� c N .o LM rs n I- 1571' y al 8 r� 12 c o -� s CL. «s S5 D,S5,S6 TO FACP (CKTS S5&S8),(D) UNIT 100 t STORAGE ROOM D n— FACPIPS AUNDRY IT -R1 RADIO DIALER BATHROOM I� 9 I 1`\ BEDROOM BEDROOM I BEDROOM ROOM i 3o ci41 hoY►,/l�sf�,c. -iiRS-r P! .ccs FiIR^ AL,afR S5 S5 i' ( S5 S5 55 55 S5 F I A\ FIRE ALARM LIP it S5 EOL S5 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved ) CO 0' z 0 z_ !L CU ) 0 r) FAX (206) 628-4990 TEL. (206) 622-6545 J )J JJ REV. BY: 0 0 0 0 BACKROUND PLAN PROVIDED BY: FI ISI NAI /1 E t _InP MIIAAPPR• t,.el _nal i \1 DESCRIPTION SUBMITTED FOR APPROVALI AS PER AHJ CHANGES ON FEB. 23 TEST W Q 09/12/06 J 0 r, NN 0 2 <<<<< Q W 0 0 J LL ur) / 'SCALE: 3/32" = 1'0" DRAWN BY: D.GAFRCIA DESIGNED BY: ::.AL_M E DA DATE: 09/12/06 BACKROUND PLAN PROVIDED BY: FI ISI NAI /1 E t _InP MIIAAPPR• t,.el _nal i • 1 SHEET FA -03 J