14346 TUKWILA INTERNATIONAL BLVD ASSOCIATED PERMITS 17-F-070 SEQUENCE OF OPERATIONS CAUSE EFFECT Activate Horn Strobe Alarm Circuits Annunciate Alarm At Fire Alarm Control Panel and Remote Annunciator Shut Down Associated Fan Annunciate Supervisory At Fire Alarm Control Panel and Remote Annunciator Annunciate Trouble At Fire Alarm Control Panel and Remote Annunciator Transmit Event Offsite Manual Pull Station Activated X X 80" FACP X Smoke Detector Activated X X 42" ANN O X Duct Smoke Detector Activated MANUAL PULL ELEVATION X C— - 2 SILENT KNIGHT X Sprinkler Flow Switch Activated X X SILENT KNIGHT SD500-PS MANUAL PULL TATION X Sprinkler Tamper or Pressure Switch Activated 4 SILENT KNIGHT SD500-AIM MONITOR MODULE M Power Failure 2 by others — SPRINKLER WATERFLOW SWITCH OF X Wiring Fault by others -- SPRINKLER TAMPER SWITCH TS X X Panel Trouble -- SPRINKLER PRESSURE SWITCH PS 6 Notes: TYPICAL MOUNTING ELEVATIONS DEVICE LEGEND TITLE SYMBOL QTY. MFG. MODEL # DESCRIPTION MEZZANINE FLOOR PLAN 1 SILENT KNIGHT 5700 80" FACP 60" 1 SILENT KNIGHT 5860 42" ANN O TYPICAL WALL MOUNT HORN STROBE ELEVATION ANNUNCIATOR ELEVATION MANUAL PULL ELEVATION 1. DEVICE POLARITY MUST BE OBSERVED. 2. ALL INITIATING AND NOTIFICATION CIRCUIT WIRING MUST BE SUPERVISED. 3. ALL WIRING, INCLUDING SHIELDS, MUST BE DRY AND FREE OF SHORTS AND GROUNDS. 4. WIRE RUNS ON FLOOR PLANS ARE SHOWN DIAGRAMMATICALLY. EXACT LOCATIONS OF WIRE RUNS ARE TO BE DETERMINED IN THE FIELD. 5. WIRING SHALL BE POINT TO POINT. THERE SHALL BE NO T TAPPING. 6. INITIATING CIRCUIT WIRING SHALL BE (1) 18/2 FPLR. 7. NOTIFICATION CIRCUIT WIRING SHALL BE (1) 14/2 FPLR. 8. ANNUNCIATOR WIRING SHALL BE (2)16/2 FPLR. 9. DEDICATED 120V CIRCUIT(S) TO BE PROVIDED FOR FIRE ALARM PANELS. CONNECTIONS TO THE LIGHT AND POWER SERVICE SHALL BE ON A DEDICATED BRANCH CIRCUIT(S). THE CIRCUIT(S) AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED. CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT'. THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL PANEL. 10. 120V DUPLEX POWER OUTLET TO BE PROVIDED ABOVE OR ADJACENT TO FIRE ALARM CONTROL PANEL FOR USE BY RADIO COMMUNICATOR. Circuit Designations: NOTIFICATION APPLIANCE CIRCUITS (NAC) SHALL BE CLASS "B" SIGNALING LINE CIRCUITS (SLC) SHALL BE CLASS "B" INITIATING DEVICE CIRCUITS (IDC) SHALL BE CLASS "B" Scope of Work: FURNISH AN ADDRESSABLE FIRE ALARM SYSTEM FOR THE TUKWILA LIBRARY. Without Comments As Noted Rn4 Per The Attacjiet1 Letter Th se pians have been review u '1 n e Tukwila Fire Pre;erition Burma 'c.? tt:" co*1t'?rma.1cf ;.'ii current City srrrtdards. Acce2. ars subje;". to error:• oinissions which i r of r..hori iot,,rtc, ; of dopted :, a ±.;r.P,r!t =,,_,. The esc.) )r'r�l': f for the , CtGts, 1C' L, of d . t 1d.iY .r%ttb :ne i-vff ti0fl , rr; rhese :i! iiwings after . N+,s>re a rti� CIdCt 4 � - l i rest.thrhl t.a _ t Final acc pta _e riela test aria inspection by, The Tukwila Fir~ ,'t c, t bureau. Date:?' i- By: TUKWILA FIRE DEPARTMENT Nesse call 206-575-4407 and dive this Fire Permit No. I ~F ,. 0 70 Li_) I-17 and exact address for shut- down hutdown or restoron approval" TUKWILA FIRE DEPAPT -11T res ca!a 206-575 p: t 7 and t � o give ttila = eC i 1. clu.tb'n Nana completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and trffmination of the testing ndSt S144thSt S 146th St S 148th St - S150th St- --._.._ S152nd St .. PAID APR 11 2: TU ILA FIRE PAID 0`1I' JUL —7 2n16 TUKWILA FIRE SHEET SCHEDULE DEVICE LEGEND TITLE SYMBOL QTY. MFG. MODEL # DESCRIPTION MEZZANINE FLOOR PLAN 1 SILENT KNIGHT 5700 FIRE ALARM CONTROL PANEL FACP 1 SILENT KNIGHT 5860 REMOTE ANNUNCIATOR ANN O 1 SILENT KNIGHT SD505-APS SMOKE DETECTOR C— - 2 SILENT KNIGHT SD505-DUCT DUCT SMOKE DETECTOR 3 SILENT KNIGHT SD500-PS MANUAL PULL TATION F 4 SILENT KNIGHT SD500-AIM MONITOR MODULE M 2 by others — SPRINKLER WATERFLOW SWITCH OF 1 by others -- SPRINKLER TAMPER SWITCH TS 1 by others -- SPRINKLER PRESSURE SWITCH PS 6 SYSTEM P2R Series HORN STROBE - WALL MOUNT, MULTI CANDELA 'o' xxCD 1 SYSTEM SENSOR P2RK Series HORN STROBE - WALL MOUNT, MULTI CANDELA WEATHERPROOF WP •o, xxCD 9 SYSTEM SENSOR PC2R Series HORN STROBE - WALL MOUNT, MULTI CANDELA c 11. xxCD xxCD 5 SYSTEM SENSOR SR Series STROBE - WALL MOUNT, MULTI CANDELA TUKWILA FIRE DEPARTMENT Nesse call 206-575-4407 and dive this Fire Permit No. I ~F ,. 0 70 Li_) I-17 and exact address for shut- down hutdown or restoron approval" TUKWILA FIRE DEPAPT -11T res ca!a 206-575 p: t 7 and t � o give ttila = eC i 1. clu.tb'n Nana completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and trffmination of the testing ndSt S144thSt S 146th St S 148th St - S150th St- --._.._ S152nd St .. PAID APR 11 2: TU ILA FIRE PAID 0`1I' JUL —7 2n16 TUKWILA FIRE SHEET SCHEDULE SHEET NO. TITLE FA -1.0 PROJECT INFORMATION FA -2.1 LEVEL 01 FLOOR PLAN FA -2.2 MEZZANINE FLOOR PLAN FA -3.0 RISER DIAGRAM and SYSTEM CALCULATIONS FA -4.0 PANEL AND DEVICE DIAGRAMS .original drawing size - 24"x36" 19009 62nd Ave NE Arlington, WA 98223 (360) 652-1088 (Is gym° � o 4-4 (ti ozb •1.4 or) oz) Tukwi/a, WA 981 REVISIONS No. Description Date 0 Preliminary 09-08-15 Project Information FIRE ALARM SYSTEM Sheet Number FA -1.0 Scale: NONE SHEET: 1 of 5 CA) Tukwila Library original drawing size - 24"x36" 1 2 3 1-' , F • i-- • • • 1,• • • UP 75CD (NI -90 STAFF ANN: 117 UP TO FACP BREAK EC 116 N N1-9 15CD N1-82 TAF TOILET 114 15CD 15CD ANI l Olt 3A 15CD STAFF OFFICE 118 N • SHIP'S 117A 75CE 42) 4•11(5.-'s' 5 5; OL 'dd,05 6 1, UP WOMEN 115 �N-g) 15CD MEN 113 15CD - FEC _ 1 CHILDREN'S 112 110CD (N7-6) 75CD SELF - CHECK 101 READING PLATFORM 30CD 104 ASSISTANCE 103 UP TO FACP STUDY 110 NORTH 95C N2-1 0 LEVEL 01 COMMUNITY MOSAIC 105 TEEN LOUNGE 108 7 8 9 10 N2-6) 30CD SCALE: 1/8" = 1'-0" 0 .•, - WWII MIN 8 30CD CYBER BAR 108 COLLECTION - 16 24 feet WIRE LEGEND A SIGNALING LINE CIRCUIT (SLC) (1) 18/2 FPLR N NOTIFICATION CIRCUIT (NAC) (1) 14/2 FPLR ANN REMOTE ANNUNCIATOR CIRCUIT (2) 16/2 FPLR (SBUS) DEVICE ADDRESS LEGEND 1 SLC Device # Candela Rating 15CD fN1-1 / N End -of --Line Resistor Notification Circuit # Device # MEETING ROOM 106 30CD 30CD 30CD N2-4) FEC N2-5) KEYED SHEET NOTES Q RECESSED IN WOOD PANEL WALL. 0 FIELD COORDINATE EXACT LOCATION AND QUANTITIES OF SPRINKLER DEVICES. 0 AIR HANDLER SHUTDOWN BY OTHERS. KITCHENETTE ALCOVE 1085 STORAGE Inc STUDY 107 A B E F ' 19009 62nd Ave NE Arlington, WA 98223 (360) 652-1088 Th'kwi/a Library 14346 Tukwiia /nternafibnal Boule vard lZikwi/a, WA 98168 REVISIONS No. Description Date 0 Preliminary 09-08-15 Level 01 Floor Plan FIRE ALARM SYSTEM Sheet Number FA -2.1 J Scale: t /8" = 1'-0" SHEET: 2 of 5 ) Tukwila Library DEVICE LEGEND SYMBOL DESCRIPTION FACP FIRE ALARM CONTROL PANEL ANN REMOTE ANNUNCIATOR Q? SMOKE DETECTOR a.:-- DUCT SMOKE DETECTOR F MANUAL PULL STATION M MONITOR MODULE El SPRINKLER WATERFLOW SWITCH TS SPRINKLER TAMPER SWITCH PS SPRINKLER PRESSURE SWITCH po .°. xxCD HORN STROBE - WALL MOUNT, MULTI CANDELA WP A xxCD HORN STROBE - WALL MOUNT, MULTI CANDELA WEATHERPROOF C 0` xxCD HORN STROBE - CEILING MOUNT, MULTI CANDELA xxCD STROBE - WALL MOUNT, MULTI CANDELA ' 19009 62nd Ave NE Arlington, WA 98223 (360) 652-1088 Th'kwi/a Library 14346 Tukwiia /nternafibnal Boule vard lZikwi/a, WA 98168 REVISIONS No. Description Date 0 Preliminary 09-08-15 Level 01 Floor Plan FIRE ALARM SYSTEM Sheet Number FA -2.1 J Scale: t /8" = 1'-0" SHEET: 2 of 5 ) Tukwila Library original drawing size - 24"x36" 1 2 3 4 5 6 OPEN TO BELOW C8) _V_ A DOWN MECHANICAL 201 M W F M M PS TS M • F174] DOWN N ELECTRICAL A 2cz _ A • • 30CD IL _ 7 8 9 10 Nf-f NORTH O 1 MEZZANINE SCALE: 1/8" = 1'-0" 0 4 8 16 WIRE LEGEND A SIGNALING LINE CIRCUIT (SLC) (1) 18/2 FPLR N NOTIFICATION CIRCUIT (NAC) (1) 14/2 FPLR ANN REMOTE ANNUNCIATOR CIRCUIT (2) 16/2 FPLR (SBUS) DEVICE ADDRESS LEGEND SLC Device # Candela Rating 15CD N9-1 — End -of -Line Resistor Notification Circuit # Device # 24 feet KEYED SHEET NOTES 01 RECESSED IN WOOD PANEL WALL. ® FIELD COORDINATE EXACT LOCATION AND QUANTITIES OF SPRINKLER DEVICES. 03 AIR HANDLER SHUTDOWN BY OTHERS. A B E F DEVICE LEGEND SYMBOL DESCRIPTION FACP FIRE ALARM CONTROL PANEL ANN REMOTE ANNUNCIATOR 0 SMOKE DETECTOR Ct.:- DUCT SMOKE DETECTOR MANUAL PULL STATION F MONITOR MODULE M SPRINKLER WATERFLOW SWITCH M SPRINKLER TAMPER SWITCH TS SPRINKLER PRESSURE SWITCH PS 0- 'o' HORN STROBE - WALL MOUNT, MULTI CANDELA xxCD HORN STROBE - WALL MOUNT, MULTI CANDELA WEATHERPROOF 10. ,o, WP xxCD C ► '3' HORN STROBE - CEILING MOUNT, MULTI CANDELA xxCD xxCD STROBE - WALL MOUNT, MULTI CANDELA a4OLYMPIC )..E 19009 62nd Ave NE Arlington, WA 98223 (360) 652-1088 lZikw//a Library 74346 lZikw/Ia /nternatibnalBou/evard Tukw//a, WA 98168 REVISIONS No. Description Date 0 Preliminary 09-08-15 Mezzanine Floor Plan FIRE ALARM SYSTEM Sheet Number FA -2.2 Scale: 1 /8" = 1'-0" SHEET: 3 of 5 Tukwila Library BATTERY CALCULATION - FACP 'PROJECT: Tukwila Library PANEL: 5700 Fire Alarm Control Panel QTY. MODEL NUMBER DESCRIPTION STANDBY (in Amps) ALARM (In Amps) Control Panel Devices Current Total Current Current Total Current 1 5700 Fire Alarm Control Panel 0.1600 0.1600 0.3300 0.3300 1 5860 Remote Annunciator 0.0200 0.0200 0.0250 0.0250 Addressable SLC Devices, SD Protocol (127 max.) 1 SD505-APS Photoelectric Smoke Detector 3 SD500-PS Manual Pull Station 0.00055 , 0.00055 0.00055 0.00055 0.0006 0.00165 0.00055 0.0017 4 SD500-AIM Addressable Input Module 0.00055 0.00220 0.00055 0.0022 2 SD505-Duct Duct Smoke Detector 0.00055 0.00110 0.00050 0.0010 NOTIFICATION DEVICES Initiating Totals 0.1855 0.360 STANDBY (in Amps) ALARM (in Amps) QTY. MODEL NUMBER DESCRIPTION Current Total Current Current Total Current Horn Strobes, wall mount 4 1 1 6 2 1 P2R 'P2R P2R Hom Strobe, 15cd Hom Strobe, 75cd Hom Strobe, 110cd Horn Strobes, ceiling mount PC2R 'PC2R 'PC2R Hom Strobe, ceiling 30cd Hom Strobe, ceiling 75cd Hom Strobe, ceiling 95cd Hom Strobes, Weatherproof 1 jP2RK IHom Strobe, weatherproof 75 cd 0.079 0.176 0.212 0.107 0.176 0.194 0.316 0.176 0.000 0.642 0.352 0.194 0.176 1 0.176 Strobes, wall mount 3 2 21 SR 'SR Total Notification Devices Strobe, 15cd Strobe, 30cd Standb Amus Standby Load Current (Amps) 0.1855 Standby Time in Hours 24 Total Standby Load 4.452 Alarm Amps Initiating Alarm Load Current (Amps) 0.3604 Notification Alarm Load Current (Amps) 2.2420 Alarm (sub total) 2.6024 Alarm Time in Minutes / 60 (5 min. = .084) 0.0840 Total Alarm Load 0.2186 Total Standby + Total Alarm 4.671 Safety Margin +20%1 0.934 Total Amp. Hrs. Required Battery Size Provided =I 5.60 7Ahl 0.066 0.094 0.198 0.188 Notification Total 2.242 VOLTAGE VOLTAGE DROP CALCULATION 'PROJECT: Tukwila Library ANN PANEL: 5700 Fire Alarm Control Panel CIRCUIT #N 1 QYY. MODEL NUMBER (DESCRIPTION Alarm Current Horn Strobes, ceiling mount Horn Strobes, wall mount F 4 P2R Hom Strobe, 15cd 0.079 0.316 1 P2R Hom Strobe, 75cd 0.176 0.176 1 P2R Hom Strobe, 110cd 0.212 0.212 Horn Strobes, Weatherproof Horn Strobes, ceiling mount STROBE - WALL MOUNT, MULTI CANDELA 1 IPC2R (Hom Strobe, ceiling 75cd 1 0.176 1 0.176 9 Strobes, wall mount TOTAL CIRCUIT LOAD (Amps) 3 SR Strobe, 15cd 0.066 0.198 2 SR Strobe, 30cd 0.094 0.188 12 TOTAL DEVICES TOTAL CIRCUIT LOAD (Amps) 1.266 CIRCUIT DISTANCE (Feet) ADDITIONAL LENGTH (20' per device) TOTAL DISTANCE (Feet) RESISTANCE, 14AWG (Ohms/foot) TOTAL RESISTANCE POWER SUPPLY VOLTAGE VOLTS DROPPED 175 240 830 0.00307 2.548 20.4 3.2259 END OF LINE VOLTAGE 17.17 VOLTAGE DROP CALCULATION SIGNALING LINE CIRCUIT (SLC) (1) 18/2 FPLR PROJECT: Tukwila Library ANN REMOTE ANNUNCIATOR CIRCUIT (2) 16/2 FPLR (SBUS) PANEL: 5700 Fire Alarm Control Panel CIRCUIT #N 2 QTY. MODEL NUMBER IDESCRIPTION Alarm Current Horn Strobes, ceiling mount MANUAL PULL STATION F 6 PC2R Horn Strobe, ceiling 30cd 0.107 0.642 1 PC2R Horn Strobe, ceiling 75cd 0.176 0.176 1 PC2R Hom Strobe, ceiling 95cd 0.194 0.194 Horn Strobes, Weatherproof STROBE - WALL MOUNT, MULTI CANDELA 1 P2RK (Hom Strobe, weatherproof 75 cd 1 0.176 0.176 9 TOTAL DEVICES TOTAL CIRCUIT LOAD (Amps) 1.188 STROBE - WALL MOUNT, MULTI CANDELA CIRCUIT DISTANCE (Feet) ADDITIONAL LENGTH (20' per device) TOTAL DISTANCE (Feet) RESISTANCE, 14AWG (Ohms/foot) TOTAL RESISTANCE POWER SUPPLY VOLTAGE VOLTS DROPPED 310 180 980 0.00307 3.009 20.4 3.5742 END OF LINE VOLTAGE 16.83 Per NFPA 72 2010 Edition, Section 18.3.2: Under all operating conditions, the voltage on the NAC must be sufficient to operate all the notification appliances so that they deliver the proper signal intensity. Often, the worst-case operating condition is when the control unit's primary power supply has failed and the battery capacity is at its lowest point. ANSUUL 864, Standard for Control Units and.1ccessoriesfor Fire Signaling Systems, indicates a minimum value of 20.4 volts (end of useful battery life). This value then becomes the starting point for the voltage drop calculations. In the case of 24 volt appliances, when the voltage drop is being calculated, both the listed and the nameplate operating voltage ranges will be 16-33 volts. Therefore, 16 volts should be considered the minimum voltage that must be delivered to any appliance. original drawing size - 24"x36" RISER DIAGRAM AI WF M 6 7 AI WF M 5- AI Oz - 8 A PS M A TS M 3 A 2 A 1 A 10 ANN FACP 30CD f 15CD N1-1 120 VAG fg"0. N j 30CD N N1-2 A11-3 MEZZANINE ANN N1-4 N1 -s N1-6 N1-7 N1-13 N1 -g N 75CD c N9 -lo FIRST FLOOR NI 99 N1-12 VOLTAGE DROP FORMULAS.. Total Distance = (Distance) # (addition/per device) x(2) Total Resistance = (Tota/Distance) x(1re Resistance) Volts Dropped = (Tota/CircuitLoad) x (Total Resistance) End of Line Voltage = (Power Supply Voltage) - (Volts Dropped) NOTES: Lyre distance is doubled in the calculations for two wires (f and An addition/length per device is added to the distance to a//owfor drops from cel//ng. WIRE LEGEND A SIGNALING LINE CIRCUIT (SLC) (1) 18/2 FPLR N NOTIFICATION CIRCUIT (NAC) (1) 14/2 FPLR ANN REMOTE ANNUNCIATOR CIRCUIT (2) 16/2 FPLR (SBUS) DEVICE ADDRESS LEGEND 1 SLC Device # Candela Rating 15CD N1-1 N End -of -Line Resistor Notification Circuit # Device # DEVICE LEGEND SYMBOL DESCRIPTION FIRE ALARM CONTROL PANEL FACP REMOTE ANNUNCIATOR ANN ?O SMOKE DETECTOR a. - DUCT SMOKE DETECTOR MANUAL PULL STATION F MONITOR MODULE © SPRINKLER WATERFLOW SWITCH tri SPRINKLER TAMPER SWITCH TS SPRINKLER PRESSURE SWITCH PS STROBE - WALL MOUNT, MULTI CANDELA ► ;o; xxCDHORN HORN STROBE - WALL MOUNT, MULTI CANDELA WEATHERPROOF WP xxCD HORN STROBE - CEILING MOUNT, MULTI CANDELA C ► ,o, xxCD xxCD STROBE - WALL MOUNT, MULTI CANDELA 19009 62nd Ave NE Arlington, WA 98223 (360) 652-1088 REVISIONS No. Description Preliminary 09-08-15 Riser Diagram and System. Calculations FIRE ALARM SYSTEM Sheet Number FA -3.0 Scale: NONE SHEET: 4 of 5 J Tukwila Library 120 VAC wiring by others PREVIOUS REVIEW STATUS 1 2 3 4 Task to Perform €Ber<77 press then enter a code if prompted. Silence LED will light. Reset Alarms Press M then enter a code if prompted. Acknowledge Alarms and Troubles Press n then enter a code acknowledged an: will appear if prompted. When the Alarm or Trouble is in the annunciator display as shown Below. Acknowledge / Mark �F' T SMOKE x �4 X11 Mt?E 3rd P01#$T327F Ct3T3Cfl 1rt #'.fit,' `fl2Rt•�' � � 1:{�� View Alarms and Troubles Press the M or l! button to view Alarms and Troubles. Conduct a Fire Drill 0 Menu, then enter a code if prompted. System Tests. 2. Then press t; to select 3. Enter code if prompted, then 4. Press n to start the fire 0 drill. drill. 5. Press El to end the fire View a Points Status 1. Press ' a to access Main Menu, then enter a code if prompted. Point Functions. 2. Then press CD to select ALARM SUPERVISORY TROUBLE SILENCE 0 0 0 0 POWER 0 SD505-DUCT Duct Smoke Detector SILENT KNIGHT by Honeywell Model 5700 Basic Operating Instructions These Instructions must be framed and displayed next to the 5700 panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems. Test the system in accordance to NFPA 72. Refer to Installation Manual P/N 151295. Operation Task to Perform Silence Alarms and Troubles press then enter a code if prompted. Silence LED will light. Reset Alarms Press M then enter a code if prompted. Acknowledge Alarms and Troubles Press n then enter a code acknowledged an: will appear if prompted. When the Alarm or Trouble is in the annunciator display as shown Below. Acknowledge / Mark �F' T SMOKE x �4 X11 Mt?E 3rd P01#$T327F Ct3T3Cfl 1rt #'.fit,' `fl2Rt•�' � � 1:{�� View Alarms and Troubles Press the M or l! button to view Alarms and Troubles. Conduct a Fire Drill 1. Press ''° to access Main Menu, then enter a code if prompted. System Tests. 2. Then press t; to select 3. Enter code if prompted, then 4. Press n to start the fire press 0 to select Fire Drill. drill. drill. 5. Press El to end the fire View a Points Status 1. Press ' a to access Main Menu, then enter a code if prompted. Point Functions. 2. Then press CD to select 3. Enter code if prompted, then 4. Select the module the device 5. Enter the point number. press 0 to select Point Status. is located on by using the F7 or M. Then press ❑. Check Detector Sensitivity 1. Follow steps 1 through 5 for viewing a point status. sensitivity. 2. Press ( to view detector Set Time and Date 1. Press n to access Main Menu, then enter a code if prompted. Set Time & Date. Enter a code if prompted on the screen as necessary. keep the changes. time and date. 2. Then press 0 to select 3. Make changes in the fields 4. Press ❑ if you wish to 5. Press n to set the entered Enable / Disable a Point 1. Rotate the key or enter a code to access to access Main Menu. Point Functions. / Enable Point. Pt. through the list. Then press n to select the module to disable/enable is located number that you want to disable/enable. NORMAL (enable) or DISABLE. 2. Then press El to select 3. Press CDto select Disable 4. Press til to Disable / Enable 5. Use the [7] or 04 to move where the point you want 6. Enter the point or circuit 7. Press ® key to toggle between View Event History 1. Press ' to access Main Menu, then enter a code if prompted. History. events in the history buffer. 2. Press 0 to select Event 3. Press the Ei or IN to view ev. RESET To Next Device Z on SLC Loop S AC Nuetral Earth Ground To Next Device on SLC Loop NOTIFICATION DEVICE SD500-AIM Addressable Input Module 0 l TELCO 1 RING TIP PHONE 1 RING TIP TELCO 2 RING TIP PHONE 2 RING TIP TROUBLE NO COM NC SLC IN SLC OUT SLC PROG C21 To Next Device or EOLR EOL Resistor SBUS To Remote To Notification Annunciator Devices SD505-APS Smoke Detector 4.7K EOL Resistor Waterflow or Tamper Switch (F.B.O.) SLC Loop - To Next Device on SLC Loop BATTERY BATTERY SBUS From FACP 5860 Annunciator (Back wiew) . original drawing size - 24"x36" 5700 Fire Alarm Control Panel 5860 Remote Annunciator SD500-PS Manual Pull Station To Next Device on SLC Loop 19009 62nd Ave NE Arlington, WA 98223 (360) 652-1088 %* tit szb *4**, °°4°4% (XI Ct ki#44.4 '414t% v .(13 4tt. 1:1*4 t44k %(*b CiCa ,0*) lZikwiIa, WA 98768 REVISIONS No. Description Date 0 Preliminary 09-08-15 Panel and Device Diagrams FIRE ALARM SYSTEM Sheet Number FA -4.0 Scale: NONE SHEET: 5 of 5 Tukwila Library