HomeMy WebLinkAboutPP - 1091 ANDOVER PARK EAST - RYDER SYSTEMS / XEROX - PERMITS AND PLANS1091 ANDOVER PARK EAST
ASSOCIATED PERMITS
07-S-275 B95-0068
B95-0112
i
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy witFj.permit
MAR 1 1 2008
07-5°' 27 s"
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
444 Andover Park East, Tukwila, Wa. 98188 206-575-4407
Project: it ui d a,Q, etilif. 8ft rbc.
Type of Inspection:
Address: i 'fl A -AE
Suite #:
Contact Person:
Am,
Special Instructions:
Phone No.:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
Sprinklers:
Date:
d r0 % C. T'
U}M%
2_ jiour
Monitor:
ST♦ghGi" 170-4'G
Nso. PJ.r 224
Permits:
Occupancy Type:
ri cit
?,ir/e.
14 3A" pss- ,224
' 00
5„,...fek.,,..
A.,s4.I : /1 acid- ..47, hge ve. a.") jga 4,64 -
two #w egra- All 4r,i' n
/eZtr-1ir.d.5
ylrvnX.1on, A`.
F-rfc FN%- i c k
Il - )-1, - t (
Needs Shift Inspection:
Sprinklers:
Date:
Fire Alarm:/
Hood & Duct:
2_ jiour
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Inspector:
3v)6-1 6-
Date:
3%S70 x
Hrs.:
2_ jiour
$80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Word/Inspection Record Form.Doc 1/13/06
T.F.D. Form F.P. 113
SMITH FIRE SYSTEMS,
INC.
1106 54th Avenue East
Tacoma, Washington 98424
CONTR. REG. NO. SMITHFS1360T
BUS: (2531 926-1880 FAX: (253) 926-2350
THIS BUILDING IS PROTECTED BY A HYDRAULICALLY
AUTOMATIC SPRINKLER SYSTEM
DESIGNED
PROJECT TITLE
BLDG / AREA
ADDRESS
SFS JOB NO.
SYSTEM NO.
DESIGN CRITERIA
RYDER PALLET STORAGE T.I.
INCLUDES TENNANT IMPROVEMENT
1091 ANDOVER PARK E.
TI -7175
EXIST / WET
NO. OF SPKRS :
84 (NEW)
PER NFPA 13-2007
(12) ESFR K25 SPRINKLERS ((4) SPRINKLERS ON (3)
BRANCHLINES) FLOWING AT 15 PSI MINIMUM
IDLE WOOD PALLETS STORED IN RACKS WITHOUT SOLID
SHELVING TO A MAXIMUM OF 25'-0 W/ A 30'-0 ROOF.
FILE COPY
BASIS OF DESIGN
SYSTEM DEMAND
12 HDS
DENSITY
1204.95
HOSE ALLOWANCE INCLUDED :
VOLUME (IF DRY SYSTEM)
WATER SUPPLY :
130
20
GPM /
SQ. FT.
GPM
AT
15 PSI
AREA OF OPERATION
50.95
AT BASE OF RISER
0
NA
6723
SQ.
FT.
PSI
GALLONS
GALLONS
STATIC RESIDUAL FLOWING GPM
TEST DATA BY
SMITH FIRE SYSTEMS, INC.
1106 54th Avenue East • Tacoma, Washington 98424
(253) 926-1880 • FAX (253) 926-2350
CONTR. REG. NO. SMITHFS1360T
HYDRAULIC CALCULATION INFORMATION SHEET
PROJECT NAME
RYDER PALLET STORAGE T.I.
JOB NO. TI7175
1091 ANDOVER PARK E.
DATE
03/06/08
ADDRESS
TUKWILA, WA 98188
BY
JOHN RETHERFORD
SYSTEM DESIGNATION: ESFR SYSTEM
HAZARD DESCRIPTION: IDLE WOOD PALLET STORAGE TO 25' MAX W/ 30' MAX ROOF
HAZARD CLASS PER NFPA 13: 2007 EDITION
SPECIFIC RULING:
RULING MADE BY: OF
DENSITY: (12) SPRINKLER FLOWING AT 15 PSI MIN. (4) SPRINKLERS PER BRANCH LINE
ALLOWANCES INCLUDED IN CALCULATIONS:
INSIDE HOSE 0 GPM
OUTSIDE HOSE 250 GPM
IN -RACK SPRINKLER DEMAND
SYSTEM TYPE: WET
"C" FACTOR OVERHEAD : 120
GPM
ADDED AT:
NODE 3 (SITE MAIN)
TOTAL NUMBER OF SPRINKLERS THIS SYSTEM 84
"C° FACTOR UNDERGROUND : 140
MAXIMUM ACTUAL AREA OF COVERAGE PER SPRINKLER: 96
SPRINKLER MANUFACTURER: VIKING MODEL: VK510
K -FACTOR: K=25.2
SQUARE FEET
TEMPERATURE: 165° F
ORIFICE SIZE: 1"
WATER SUPPLY:
STATIC 130 PSI
RESIDUAL 20 PSI
FLOW 6,723 GPM
BASE OF RISER DEMAND(NODE 5)
1204.95 GPM REQUIRED AT 50.95 PSI
(INCLUDING 0 GPM FOR HOSE STREAMS)
SUMMARY
1454.95 GPM REQUIRED AT 61.69 PSI
AT CITY CONNECTION (NODE 0)
(INCLUDING 250 GPM FOR TOTAL HOSE STREAMS)
w
0
tia.
WATER SUPPLY DA
■ - ■ 16 .: ■ +..-- •■' ■■ ■■ L r
owl �� :i::■..:...0 ■ ■:. me ..Cu ......C.n...........
reign �C'':'. idellikilinillbElliPlimdmilmiliir•N•CCz _. II•l ■ C.■ M :■ :� ■CE;C■■ B..9I �C.�CC i �C ■C : ■.q C C.m::CE .�g.C�C..ppC
ui w irk, CCC ' 'C:::' C niC:'CC:':u::C: ■■ ■ .:
'°'w a, �■■..■.■:.■i Il■�:■l■t.■■■ ■L ■E n.na. /C.■...■'uii
SUBMITTAL SERIAL NO:2244HY1 03-06-2008 PAGE 1
TI7175 RYDER PALLET STORAGE T.I.
INDOOR STORAGE OF IDLE WOOD PALLETS
(12) K25 ESFR SPRINKLERS FLOWING AT 15 PSI MIN. 97.60 GPM
FILE = TI7175.SIG
FLOW TEST RESULTS
Water Supply
STATIC 130.00 PSI
RESIDUAL 20.00 PSI @ 6723.00 GPM
CITY PRESSURE AVAILABLE AT 1454.9 GPM 123.52 PSI
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K -FACTOR PRESSURE
101 105.25 97.60 25.20 17.44
102 100.74 97.60 25.20 15.98
103 98.58 97.60 25.20 15.30
104 97.97 97.60 25.20 15.11
105 1-04195 97760 250 1773
106 100.45 97.60 25.20 15.89
107 98.29 97.60 25.20 15.21
108 97.68 97.60 25.20 15.02
109 104.86 97.60 25.20 17.32
110 100.37 97.60 25.20 15.86
111 98.21 97.60 25.20 15.19
112 97.60 97.60 25.20 15.00
TOTAL WATER REQUIRED FOR SYSTEM
OUTFLOWS AT 3
TOTAL WATER REQUIREMENT
PRESSURE REQUIRED AT 0
MAXIMUM PRESSURE UNBALANCE IN LOOPS
MAXIMUM VELOCITY FROM 21 TO 31
1204.95 GPM
250.00 GPM
1454.95 GPM
61.69 PSI
0.00 PSI
22.11 FPS
SUBMITTAL SERIAL NO:2244HY1
TI7175 RYDER PALLET STORAGE T.I.
INDOOR STORAGE OF IDLE WOOD PALLETS
(12) K25 ESFR SPRINKLERS FLOWING AT 15 PSI MIN. 97.60 GPM
FILE = T27175.SIG
03-06-2008 PAGE 2
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
111 112 2.727 L 8.00 C=120 PT 15.00 (112)
Q 97.60 F=0 F 0.00 PE 0.00
FM T 8.00 0.0233 PF 0.19
110 111DQ 98.21 2.727 L 8.00 C=120 PT 15.19 (111)
Q 195.81 F=0 F 0.00 PE 0.00
FM T 8.00 0.0845 PF 0.68
109 110DQ 100.37 2.727 L 8.00 C=120 PT 15.87 (110)
Q 296.18 F=0 F 0.00 PE 0.00
FM T 8.00 0.1816 PF 1.45
3-3 10-9DQ . 104.8-6 _ __2_.727 L 12.1/--C=120 --PT-1:7:n_(10
Q 401.04 F=0 F 0.00 PE 0.00
FM T 12.17 0.3182 PF 3.87
23 33 2.727 L 2.00 C=120 PT 21.19 ( 33)
Q 401.04 F=T/T F 40.00 PE 0.87
FM T 42.00 0.3182 PF 13.36
22 23 6.357 L 10.50 C=120 PT 35.42 ( 23)
Q 401.04 F=0 F 0.00 PE 0.00
FM T 10.50 0.0052 PF 0.05
PT 35.47 ( 22)
107 108 2.727 L 8.00 C=120 PT 15.02 (108)
Q 97.68 F=0 F 0.00 PE 0.00
FM T 8.00 0.0233 PF 0.19
106 107DQ 98.29 2.727 L 8.00 C=120 PT 15.21 (107)
Q 195.97 F=0 F 0.00 PE 0.00
FM T 8.00 0.0846 PF 0.68
105 106DQ 100.45 2.727 L 8.00 C=120 PT 15.89 (106)
Q 296.42 F=0 F 0.00 PE 0.00
FM T 8.00 0.1819 PF 1.46
32 105DQ 104.95 2.727 L 12.17 C=120 PT 17.35 (105)
Q 401.36 F=0 F 0.00 PE 0.00
FM T 12.17 0.3187 PF 3.88
22 32 2.727 L 2.00 C=120 PT 21.23 ( 32)
Q 401.36 F=T/T F 40.00 PE 0.87
FM T 42.00 0.3187 PF 13.39
SUBMITTAL SERIAL NO:2244HY1 03-06-2008 PAGE 3
TI7175 RYDER PALLET STORAGE T.I.
INDOOR STORAGE OF IDLE WOOD PALLETS
(12) K25 ESFR SPRINKLERS FLOWING AT 15 PSI MIN. 97.60 GPM
FILE = TI7175.SIG
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
21 22DQ 401.04 6.357 L 10.50 C=120 PT 35.49 ( 22)
Q 802.40 F=0 F 0.00 PE 0.00
FM T 10.50 0.0186 PF 0.20
PT 35.69 ( 21)
103 104 2.727
Q 97.97
FM
102 103DQ 98.58 2.727
Q 196.55
FM
L 8.00 C=120 PT 15.11 (104)
F=0 F 0.00 PE 0.00
T 8.00 0.0235 PF 0.19
L 8.00 C=120 PT 15.30 (103)
F=0 F 0.00 PE 0.00
T 8.00 0.0851 PF 0.68
101 102DQ 100.74 2.727 L 8.00 C=120 PT 15.98 (102)
Q 297.29 F=0 F 0.00 PE 0.00
FM T 8.00 0.1829 PF 1.46
31 101DQ 105.25 2.727 L 12.17 C=120 PT 17.44 (101)
Q 402.54 F=0 F 0.00 PE 0.00
FM T 12.17 0.3205 PF 3.90
21 31 2.727 L 2.00 C=120 PT 21.34 ( 31)
Q 402.54 F=T/T F 40.00 PE 0.87
FM T 42.00 0.3205 PF 13.46
11 21DQ 802.40 6.357 L 110.00 C=120 PT 35.67 ( 21)
Q 1204.95 F=0 F 0.00 PE 0.00
FM T 110.00 0.0395 PF 4.35
10 11 8.249 L 36.00 C=120 PT 40.02 ( 11)
Q 1204.95 F=E/T F 59.00 PE 0.00
FM T 95.00 0.0111 PF 1.05
5 10 8.249 L 21.00 C=120 PT 41.07 ( 10)
Q 1204.95 F=GV,ALV/E F 49.60 PE 9.10
FR T 70.60 0.0111 PF 0.78
3 5 8.265 L 25.00 C=140 PT 50.95 ( 5)
Q 1204.95 F=T/E F 71.00 PE 2.17
UN T 96.00 0.0083 PF 0.80
2 3DQ 250.00 8.265 L 100.00 C=140 PT 53.92 ( 3)
Q 1454.95 F=E/2E F 57.00 PE 0.00
UN T 157.00 0.0117 PF 1.84
SUBMITTAL SERIAL NO:2244HY1
TI7175 RYDER PALLET STORAGE T.I.
INDOOR STORAGE OF IDLE WOOD PALLETS
(12) K25 ESFR SPRINKLERS FLOWING AT 15 PSI MIN. 97.60 GPM
FILE = TI7175.SIG
03-06-2008 PAGE 4
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
1 2 8.000 L 0.01 C=140 PT 55.76 ( 2)
Q 1454.95 F=DD1 F 0.00 PE 0.00
UN T 0.01 0.0137 PF 0.00
8" WILKINS MODEL 350DA DOUBLE DETECTOR ASSEMBLY 4.57
1
Q 1454.95
8.265 L 20.00 C=140 PT 60.33 ( 1)
F=T,GV/2E F 96.00 PE 0.00
UN T 116.00 0.0117 PF 1.36
PT 61.69 ( 0)
4". wr r ••6, ' • • • t•--,7*
City of Tukwila
Fire Department
MAY 5 1995
John W. Rants, Mayor
TUKWILA FIRE DEPARTMENT
FINAL APPROVAL FORM '
Thomas P. Keefe, Fire Chief
Permit No. L 006A>
Project Name E72 -DX .
Address /n9/ Adve, 144eZ Retain
-
Retain current inspection schedule
KNeeds shift inspection
Suite #
Approved without correction notice
Approved with correction notice issued
Sprinklers:
Fire Alarm:
Hood & Duct:
Halon:
Monitor:
Pre -Fire:
Permits:
Authorized Signature
Signature
Date
FINALAPP.FRM T.F.D. Form P.P. 85
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 575-4404 • Fax (206) 575-4439
>a.>4 r.` s'"'rT'4n'ry+r�.[?' rw'....r .....v,... --:"-r.--" ...` R �....,.i.-
( rr
City of Tukwila
Fire Department
T' n'c"<.'t' r
MAY 5 1998
John W. Rants, Mayor
TUKWILA FIRE DEPARTMENT
FINAL APPROVAL FORM
Project Name X - 0,(4-X
Address
Permit No.
Thomas P. Keefe, Fire Chief
/67/ 4444
Retain curr_4K
ent inspection schedule
Needs shift inspection
Suite #
.5C Approved withoutcorrection notice
Approved with correction notice issued
Sprinklers:
Fire Alarm:
Hood & Duct:
Halon:
Monitor:
Pre -Fire:
Permits:
Authorized Signature
9S -
Date
FINALAPP.FRM T.F.D. Form F.P. 85
Headquarters Station: 444 Andover Pant East • Tukwila, Washington 98188 • Phone: (206) 575-4404 • Fax (206) 575-4439